FOAM CHAMBER

Model: NF-FC Series

FEATURES
• Heavy duty welded construction with choice of
Carbon Steel or Stainless Steel material
• Frangible Glass Vapour Seal
• Controlled Air Flow proportional to liquid flow for
optimum foam quality and rupture of vapour seal
in narrow pressure tolerances for increased reliability
• Field replaceable orifice plate fitted with Foam Chamber

APPLICATION
Foam Chamber is used in one of the most common application
to protect vertical fixed roof (cone) liquid storage tanks, with
or without internal floating roof with the low expansion foam
system. The application of foam is on the basis that the risk
comprises the total surface area of the fuel. The foam system
design guidelines generally used are in accordance with
NFPA-11, standard.
Foam chambers are defined by NFPA-11 as Type II discharge
outlets for delivering the foam to the surface of a flammable
liquid. The Foam Chambers are widely used with the Inline
Foam Inductor, Balance Pressure Foam Proportioning system,
Bladder Tank Proportioner or Foam Tender.

SPECIFICATION
Foam Chamber is an air aspirating foam discharge device,
covering wide range of flow from 150 to 2400 litres per minute
at 2.8 to 7 kg/sq.cm. inlet pressure. The Foam Chamber
contains a vapour seal to prevent the entry of vapour into the
foam chamber and the foam solution pipe. Each foam chamber
is supplied with an orifice plate, designed for the required flow TECHNICAL DATA
and inlet pressure. The orifice is field replaceable in the event Model Refer Table
of change in design parameters.
Inlet Size 65, 80, 100, 150 NB
The foam is produced by introducing air into the foam solution Min. 2.8kg/cm² (40 PSI)
stream. The inlet of foam chamber is designed to create venturi Working Pressure Max. 7kg/cm² (100 PSI)
jet which draws air into the foam solution stream. The air is
Foam Proportioning 3% or 6% AFFF
drawn into the foam solution through the holes located on the
foam chamber covered with stainless steel screen to exclude Flange Connection ANSI B16.5 Class 150#
nesting birds and insects. The aerated foam is directed into the 65 NB - 34.5kg
Weight
deflector for the gentle application of the expanded foam. The 80 NB - 49.5kg
(Approx.)
100 NB - 72.0kg
deflectors are available in different models.
0.7 to 1.75 Kg/sq.cm.
On removal of cover plate from the top of the chamber allows Vapour Seal Rapture (10 PSI to 25 PSI)
the system to be tested and to draw a sample of the expanded Pressure Running water/ water foam solution
foam, without removing the vapour seal or disconnecting the pressure at inlet of Foam Chamber
foam chamber from the tank. Frangible glass bursting disc Maximum Permissable Back
0.07 Kg/sq.cm. (1.0 PSI)
(vapour seal) can be replaced by easily. Pressure On Vapour Seal
The vapour seal is designed to rupture within 0.7 to 1.75 Kg/ Vapour Seal Glass
sq.cm. (10 to 25 PSI) pressure at inlet flange of Foam Chamber, Deflector Solid or Split Deflector
as required by NFPA, UL & FM standard. The vapour seal will Finish Red RAL 3000
withstand maximum back pressure of 0.07 Kg/sq.cm. Bar (1.0
• Model & Size
PSI) or equal to 686mm of water column as specified by API
• Flow & Pressure at inlet of each
for welded storage tank. If the requirement exceeds 0.07 Kg/ Foam Chamber
sq.cm. Bar (1.0 PSI) as in case of nitrogen blanketing system, Ordering Information • Inlet, outlet flange specification
then this equipment may not be suitable. The vapour seal is • Type of Deflector
frangible glass. The vapour seal is supplied with holder and • Foam concentrate used
• Tank number / Tag number
for spares it can be with or without holder. The ‘O’ ring used
for seal are Nitride rubber and optional Viton for polar solvent. *NOTE: AFFF 6% Proportioning is FM Approved only.

In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice.

www.naffco.com 87
SYSTEM DESIGN REQUIREMENT
The NFPA-11, a standard for low expansion foam, provides The air screen is to be inspected periodically for the obstruction
the essential requirement of an appropriate designed foam of air inlet holes. If any obstruction is noticed, remove the
pouring system, which are identified and outlined as below: same and flush if necessary. It is recommended to have
The Foam Deflector is used with the Foam Chamber. regular maintenance programme to inspect the Vapour Seal
Chamber discharge area and deflector for possible deposit or
The aerated foam from the Foam Chamber is directed in to the
obstruction.
deflector for the gentle application of the expanded foam. The
deflector reduces the expanded foam velocity and allows the
foam to slide down the tank wall. CAUTION
Do not install Foam chambers on pressured storage tanks (Inert
(A) Number of Foam Chamber: gas blanketed tanks) and storage tanks containing product
The number of foam chambers required is determined which attack the foam chamber standard construction material.
by the tank diameter. Where two or more foam chambers Maximum permissible back pressure on vapour seal is 0.07 Kg/
are required, they shall be spaced equally around the tank sq.cm.2 (1.0 PSI)
periphery and each Foam Chamber shall be sized to deliver
foam at an approximately same rate. Please refer graph to
select the unit that will provide the required minimum foam
*NOTES:
solution application rate at the available operating pressure of
• A provision is to be made for pressure gauge mounting at inlet of foam
the Foam Chamber. chamber, which may be plugged after successful commissioning of
For minimum number of Foam Chamber requirement, kindly the system. This will help to analyse the system while commissioning.
• Refer to the individual foam listing for operating limitation with each
follow the recommendations as per NFPA OISD/TAC or as per foam concentrate and foam chamber.
the governmental codes or ordinances wherever applicable • Listings, Approvals and/or Certifications for NAFFCO foam concentrate
and/or equipment are valid only when used with other NAFFCO foam
(B) Minimum Foam Solution Application Rate: concentrates or equipment in a manner as outlined in the applicable
The minimum foam solution application rate is the rate at which Listing, Approval and/or Certification
the water and foam concentrate in correctly proportioned ratio
should be delivered to the surface of a storage tank under
protection to control and extinguish the fire.
For minimum application rate requirement, follow the
recommendations as per NFPA/OISD/ TAC or governmental
codes or ordinances wherever applicable.

TESTING & MAINTENANCE


Qualified and trained person must commission the system.
After few initial successful tests, an authorized person must
be trained to perform inspection and testing of the system. It
is recommended to carry out physical inspection of the system
regularly. The system must be fully tested at least once in a year
or in accordance with applicable NFPA/OISD/TAC standards or
in accordance with standards of the organization having local
jurisdiction.
Do not turn off the system or any valve to make repair or test
the system, without placing a roving Fire Patrol in the area
covered by the system. The Patrol should continue until the
system is put back in service. Also inform the local security
guard and control alarm station, so as to avoid false alarm.
Each system is to be flushed properly. The vapour seal must
be replaced if the system has been operated. Normal testing
of the chamber can be carried out by removing the cover plate
from the top of the chamber. This allows the system to draw
a sample of the expanded foam without removing the vapour
seal or disconnecting the Foam Chamber from the tank.

In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice.

88 www.naffco.com
FLOW RATE
FLOW RATE (LPM)
MODEL NO. AFFF3% AFFF3% AFFF6%
(as per UL) (as per FM) (as per FM)
NF-FC65 150 - 550 173-559 173-559
NF-FC80 300 - 1021 330-997 338-1022
NF-FC100 600 - 2400 658-1855 653-1839
NF-FCR150 ---* 2497-3975 2487-4047

*NOTES: 150 NB Foam Chamber not included in UL Listing.

DIMENSIONS
INLET SIZE (F1) OUTLET SIZE (F2) A B C
65 NB 100 NB 756 600 175
80 NB 150 NB 1793 908 225
100 NB 200 NB 1221 996 275
150 NB 250 NB 1241 1000 275

PARTLIST
MATERIAL SPECIFICATION
ITEM NO. DESCRIPTION
NF-FC/NF-FCR NF-FCSS
1 Orifice Assembly Stainless Steel Stainless Steel
2 Inlet Flange Steel Stainless Steel
3 Strainer Assembly Stainless Steel Stainless Steel
4 Foam Making Chamber Steel Pipe SS Pipe
5 Foam Chamber Steel Stainless Steel
6 Inspection Cover Steel Stainless Steel
7 Discharge Pipe Steel Pipe SS Pipe
8 Outlet Flange Steel Stainless Steel
9 Vapour Seal Assembly Glass Glass
*NOTES:
• Pipes used are ERW (Seamless Pipe are optional)
• Foam chambers are open to atmosphere & do not have internal shutoff device,hence no hydrotest is offered during inspection.
• Listings, Approvals and/or Certifications for NAFFCO foam concentrate and/or equipment are valid only when used with other NAFFCO foam
concentrates or equipment in a manner as outlined in the applicable Listing, Approval and/or Certification

In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice.

www.naffco.com 89
TYPICAL INSTALLATION OF FOAM CHAMBER WITH STUD FLANGED SPLIT DEFLECTOR

*NOTE: Stud Mounting Pad with gasket & split deflector are optional items.
To be ordered separately.

TANK CUTOUT FOR MOUNTING OF SPLIT DEFLECTOR

HOLE DIAMETER
MODEL NO RØ PCD NUMBER OF HOLES
Ø-D’
NF-FC65 / NF-FCSS65 114 191 19 4
NF-FC80 / NF-FCSS80 168 241 22 4
NF-FC100 / NF-FCSS100 219 298 22 8
NF-FCR150 276 362 25 12

In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice.

90 www.naffco.com
TYPICAL INSTALLATION OF FOAM CHAMBER WITH STUD FLANGED TANK NOZZLE
AND SOLID DEFLECTOR

GLASS VAPOUR SEAL


WITH HOLDER (STANDARD SUPPLY)

*NOTES:
• Above dimensions are general guidelines only. The system designer can adopt the dimensions as per NFPA/TAC/OISD or as per the governing rules
& ordinance having local jurdiction.
• Tank Nozzle nut bolts & gasket are optional to be ordered separately.
• Split deflector Model SD and solid deflector Model FD is standard supply in carbon steel material and optional in stainless steel.

In line with NAFFCO policy for continuous product development, NAFFCO has the right to change specifications without prior notice.

www.naffco.com 91