Hydraulic Calculations Fire Protection
Hydraulic Calculations Fire Protection
Hydraulic Calculations Fire Protection
Since the sprinkler requires 21.17 gpm to meet the 7 psi requirement and 20.74 gpm to meet the
density requirement, the flow at the end sprinkler will be 20.74 GPM
FLOW ADJUSTMENT
1 to 2 ACT 1.049 1
Qt 21.17
2 to T ACT 1.049 1 12
Qt 47.51
A to B ACT 2.469 1
Qt 82.09
From NFPA table 11.2.3.1.2 Hose stream allowallowand water supply FIRE PUMP REQUIREMENT:
750 GPM
@ Ordinary Hazard over combined inside & outside 210 psi TDH
667.83 GPM 150 HP
TOTAL = 667.83 GPM SYSTEM REQUIREMENT
TDH = 194.7 PSI SYSTEM REQUIREMENT
PIPE EQ. LENGTH PSI/FT REQ. PRESSURE K-FACTOR
C-FACTOR
m ft PSI
L Pt 20.74 5.6
F 120 HAZEN WILLIAMS fric. Loss Pf
tot Pe
TOT L 2.908 10 Pt 20.7
T 2.908 10 Pe 0.0
TOT L 3.916 13 Pt 22.1
T 3.916 25 Pe 0.0
TOT L 6 20 Pt 38.1
T 6 20 Pe 0.0
TOT L 0 Pt 194.7
120 5.6
0.00 F 0 0 Pf
T 0 0 Pe