ELEC3206 Lab 1 3-ph Transformer
ELEC3206 Lab 1 3-ph Transformer
ELEC3206 Lab 1 3-ph Transformer
1.1 Aim
To determine the parameters of the per-phase equivalent circuit of a three-phase transformer.
Verify the equivalent circuit model of the transformer by a load test
1.2 Theory
Transformer Models
Ignoring any phase shift from primary to secondary due to the way the transformer is connected
(which has no effect on the parameters measured in this experiment), the per phase equivalent circuit
of a three phase transformer is shown in Fig. 1.
The impedances Rc and X m are shown on the primary side. They could as easily be referred to the
secondary.
I1 R1 X1 X2 R2 I2
+ +
V1 Rc Xm V2
_ _
Ideal Transformer
Turns ratio = n
Fig. 1 Per phase equivalent circuit
I1 R X I2
+ +
V1 Rc Xm V2
_ _
Ideal Transformer
Turns ratio = n
Fig. 2 Equivalent circuit with impedances referred to primary
In Fig. 2, the secondary resistance and leakage reactance have been referred to the primary and added
to the primary resistance and leakage reactance.
R R1 n 2 R2 , X X 1 n 2 X 2
The turns ratio (primary turns /secondary turns) is n . The term ‘turns ratio’ can be a bit confusing in
the case of a three phase transformer - think of it as the turns ratio of the transformer in the per
phase equivalent circuit (or simply as the inverse of the ‘voltage gain ratio’).
Parameter Calculation
The parameters R c and X m can be calculated from the open circuit test measurements using the
circuit of Fig.3 (a). As Voc, Ioc and real power P are measured, the reactive power Q can be worked out
2
by Q VI sin S 2 P 2 , where the complex power S=VI. From P Voc and Q Voc the
2
Rc Xm
parameters in the magnetising branch can be worked out then.
I oc I sc R X
+ +
Voc Rc Xm Vsc
_ _
(a) (b)
R and X can be calculated using the circuit of Fig. 3 (b). Similarly work out the reactive power Q.
Based on the short-circuit equivalent circuit Fig. 3(b), the overall resistance and leakage reactance for
both primary and secondary side of the transformer can be calculated by P I sc 2 R and Q I sc 2 X .
The current flowing in the shunt branch can be ignored because of its very high impedance. Note the
formulae above are for single phase equivalent circuit calculations. Therefore the voltage should be
line-to –neutral and powers are for single phase as well.
What is the voltage you should apply to the secondary side of the transformer bank if the
primary side is open-circuited?
Which meters in the setup in Figure 4 should be monitored for the voltage?
+ com
A
a
I1
+
A
red
HV
Secondary LV
E1 E3
B
com
b
Primary
com
B
yellow
E2
+ +
C
com
c
I2
C
blue
3-phase Transformer
Variable 3-ph AC 0~415V Bank
2) Before starting to connect the circuit, check all the circuit breakers (located at the bottom of the
bench) are at the OFF position and the knob of 3-phase variac is turned back to ZERO position.
Then connect the open-circuit test system shown in Figure 4. Ask a tutor to check your
connections and turn on the power supply for you. Note: Incorrect connections on the positive
(red) and COM (black) of voltage and current meters will cause the wrong readings for power
measurements.
3) Slowly increase the 3-phase variac and watch the meter E1, E2 and E3. Stop increasing the variac
till reaching the rated voltage on either side of the transformer. Take 2~3 sets of readings for the
meters by clicking Record Data from the top bar menu in the Data Table. Export the data table to
Excel file for further process.
4) After save the readings, carefully turn the 3-phase variac back to ZERO and switch off the circuit
breaker for the 3-phase variable AC supply.
5) From these readings, calculate the parameters Rc and Xm in Fig.2. When doing these calculations,
assume that the voltage across the series impedance R+jX of Fig.2 is negligible. Note: you should
use single phase real and reactive power to do the calculation.
What are the rated currents of the transformer used in this test?
At what currents you should stop increasing the 3-phase variac?
Which meters in Fig.5 you should watch for these currents?
+ com
A
a
I1
+
A
red
HV
Secondary LV
E1 I3
B
com
Primary
com
B
yellow
E2
+ +
C
c
I2 com
C
blue
3-phase Transformer
Variable 3-ph AC 0~415V Bank
1) In Metering window of LVDAC-EMS, set meter E1 and E2 to measure the secondary line-line
voltage, I1 and I2 for line current, as well as a meter I3 for the primary side line current. The setup
of power meters remains the same as in O.C test. Clear the Data Table and update the meters in
the Table accordingly. Click the Continuous Refresh button to enable continuous refresh of the
measurements.
2) Before connecting the circuit, ensure all the circuit breakers are at OFF positions and the 3-phase
variac is turned back to ZERO. Each phase on the secondary side of the transformer (LV side) has
a 5A fuse in series (pre-connected) to protect an overcurrent. Connect the setup based on Fig.5.
Ask a tutor to check your connections, and turn on the power supply as well as increase the variac
for you.
3) In the case of S.C, the voltage to reach the rated currents is very low, just a fraction of rated
voltage (around 10% of rated voltage). In this part, when applying the voltage from the secondary
side and short-circuit the primary side, the voltage is only about 7-8 volts which means to turn
the variac a little bit. Hence increase the 3-phase variac steadily and slowly till the point where
the rated current of either side of the transformer is reached. Watch the meter I1, I2and I3 for
the currents when applying the variac. Note! the variac is must be ensured at the ZERO position
before the system is energised, as the voltage of the AC variable supply is controlled by the 3-
phase variac.
4) Once reach to the rated current, record the meter readings in the Data Table for a number of
times and export the Table to Excel.
5) Turn the variac back to zero and then switch off the circuit breaker.
6) Use the formula in section 1.2 to calculate R and X of Fig. 2. To simplify the calculation, the
current flowing through the magnetising branch can be ignored due to the large magnetising
impedance.
Complete the per phase equivalent circuit of the transformer and draw the circuit with all the
parameters calculated from the above O.C and S.C test. Note the parameters should be referred to the
LV side as the voltages are applied to LV side during the experiments.
In this part of exercise, you will measure the voltage regulation and efficiency when the load current
reaches to a part of the rated current (depending on the available load). Then verify the equivalent
circuit you work out from the above by comparing the calculations with measurements at a load
condition.
The connection diagram for load test is shown in Figure 6. The resistor bank module 8311 is used as a
three-phase load.
R1
+ com + com
A
a
I1 I3
+ +
A
red
HV
E3
S econdary LV
E1
R2
B
com com
b
Primary
com com
B
yellow E4
E2
+ + R3
+ + com
C
com
c
I2 I4
C
blue
3-phase Transformer
Variable 3-ph AC 0~415V Bank
1) In Metering window of LVDAC-EMS, set meter E1 and E2 to measure the secondary side line-
line voltage, I1 and I2 for secondary line current. On the primary side of the transformer, set
meter E3 and E4 to measure the line-line voltage, I3 and I4 for line current. The meters
PQS1(E1,I1), PQS2(E2,I2), PQS3(E3,I3), andPQS4(E4,I4) are set up for real power
measurements. Clear the Data Table and update the meters in the Table accordingly. Click the
Continuous Refresh button to enable continuous refresh of the values.
2) Check the bench 3-phase variable supply is OFF and the variac is at Zero position. Connect the
setup in Figure 6 and get a tutor to check the connections and switch on for you.
3) Make the three resistors (1200Ω, 2400Ω, 4800Ω) in the bank at position of O (means open). In
this case the transformer is open circuit. Slowly increase the variac till the secondary side
voltage E1 or E2 reaches to rated voltage. Click Record Data to take the measurements.
4) Then switch on the resistor 1200Ω for three phase, you should be the load voltage (primary
side) drops a bit and currents (from meter I1, I2, I3 and I4) increases. Click Record Data to take
the measurements.
5) Then switch on the three resistors for three phase (three resistors in parallel for each phase).
Click Record Data to take the measurements.
6) Calculate the voltage regulations and efficiency at these two load conditions.
7) Use the measured secondary side voltage and the equivalent circuit of the transformer to
calculate the current and power, as well as the efficiency. Compare the calculations with the
measurements at the load condition in the step 5). Comment on the discrepancy.