JAKARTA, 15 JULY 2020

SETTING AND CONFIGURATION REQ650


BREAKER FAILURE PROTECTION
ID PGGA POWER GRIDS

© Copyright 2020 ABB. All rights reserved. Document ID.: Rev.:


Operation Principle

July 15, 2020 Slide 2


Typical Feature

Ø 1 ph and/or 3 ph starting
Ø Re-trip (i.e in first time delay
Ø Back-up trip/Bus trip (i.e second time delay)
Ø Correctly trip only to associated CBs via disconnector replica available inside the busbar differential protection

July 15, 2020 Slide 3



CSPRBRF
Breaker Failure Protection Phase Segregated Activation and Output

Ø Breaker failure protection, phase segregated activation and output CSPRBRF ensure fast backup tripping of surrounding breakers in
case of own breaker fail to open.
Ø CSPRBRF can be current base, contact based, or adaptive combination between this two principles.
Ø CSPRBRF can be programmed to give single- or three- phase re-trip of own breaker
Ø The breaker failure protection is initiated from protection trip command, either from protection function within the IED or from
external protection device

July 15, 2020 Slide 4


RetripMode vs FunctionMode

Ø Depedencies between parameters retrip mode and the


function mode

July 15, 2020 Slide 5


Breaker Failure Time Setting

Ø Breaker failure protection act as backup of other protection


Ø The total fault clearance time shall less than given critical time

July 15, 2020 Slide 6


Setting Parameters

Ø IP>: Current level of breaker failure detection, set in % of Ibase


Ø T1: Time delay of retrip
Ø T2: Time delay of backup trip

July 15, 2020 Slide 7