Manual Caudalímetro UTM10 IM
Manual Caudalímetro UTM10 IM
MI Issue 1
UTM10 Series
Ultrasonic Transit-time Flowmeters
Installation and Maintenance Instructions
5CHGV[KPHQTOCVKQP
)GPGTCNRTQFWEV
KPHQTOCVKQP
6TCPUOKVVGT
KPUVCNNCVKQP
6TCPUFWEGT
KPUVCNNCVKQP
+PRWVUCPFQWVRWVU
3WKEMUVCTV
QRGTCVKPIKPUVTWEVKQPU
5VCTVWRCPF
EQPſIWTCVKQP
5QHVYCTGWVKNKV[
#RRGPFKZ
6CDNGQHEQPVGPVU
1PVJGDCEMEQXGT
IM-P197-02
Printed in the MI
USAIssue 1 © Copyright 2011
1
Please note:
BELDEN is a registered trademark of Belden Technologies, Inc.
BACNET is a registered trademark of American Society of Heating,
CSA is a registered trademark of the Canadian Standards Association.
Refrigerating and Air-Conditioning Engineers (ASHRAE).
WINDOWS, VISTA and EXCELl are registered trademarks of Microsoft Corporation.
NATIONAL ELECTRICAL CODE is a registered trademark of the NFPA.
SONOTEMP is a registered trademark of Sonotemp, Inc.
ULTEM is a registered trademark of General Electric Company.
VESPEL is a registered trademark of E.I. DuPont Nemours and Company.
5CHGV[KPHQTOCVKQP
Safe operation of these units can only be guaranteed if they are properly installed,
commissioned and maintained by a qualified person in compliance with the
operating instructions. General installation and safety instructions for pipeline and
plant construction, as well as the proper use of tools and safety equipment must
also be complied with.
These products are designed and constructed to withstand the forces encountered
during normal use. Use of these products for any other purpose, or failure to install
these products in accordance with these Installation and Maintenance Instructions,
could cause damage to the products, will invalidate their markings, and may cause
injury or fatality to personnel.
Warning
These products comply with the requirements of the Electromagnetic Compatibility
Directive 89 / 336 / EEC by meeting the standards of: EN 61326: 1997 Electrical
equipment for measurement, control and laboratory use EMC requirements:
- Immunity to industrial locations annex A -Table A1.
- Emissions to domestic locations Table 4.
The following conditions should be avoided as they may create interference above
the limits specified in EN 61326: 1997 if:
- The product or its wiring is located near a radio transmitter.
- Cellular telephones and mobile radios may cause interference if used within
approximately 1 metre (39") of the product or its wiring. The actual separation
distance necessary will vary according to the surroundings of the installation and
the power of the transmitter. If this product is not used in the manner specified by
this IMI, then the protection provided may be impaired.
2 IM-P197-02 MI Issue 1
The symbols, used on the product and in this manual, mean:
1.2 Access
Ensure safe access and if necessary a safe working platform (suitably guarded)
before attempting to work on the product. Arrange suitable lifting gear if required.
1.3 Lighting
Ensure adequate lighting, particularly where detailed or intricate work is required.
IM-P197-02 MI Issue 1 3
1.7 Pressure systems
Ensure that any pressure is isolated and safely vented to atmospheric pressure.
Consider double isolation (double block and bleed) and the locking or labelling of
closed valves. Do not assume that the system has depressurized even when the
pressure gauge indicates zero.
1.8 Temperature
Allow time for temperature to normalize after isolation to avoid the danger of burns
and consider whether protective clothing (including safety glasses) is required.
1.12 Handling
Manual handling of large and /or heavy products may present a risk of injury. Lifting,
pushing, pulling, carrying or supporting a load by bodily force can cause injury
particularly to the back. You are advised to assess the risks taking into account the
task, the individual, the load and the working environment and use the appropriate
handling method depending on the circumstances of the work being done.
1.14 Freezing
Provision must be made to protect products which are not self-draining against
frost damage in environments where they may be exposed to temperatures below
freezing point.
1.15 Disposal
Unless otherwise stated in the Installation and Maintenance Instructions, this
product is recyclable and no ecological hazard is anticipated with its disposal
providing due care is taken.
4 IM-P197-02 MI Issue 1
+PVTQFWEVKQP
2.1 General
The UTM10 Series of ultrasonic flowmeters are designed to measure the fluid velocity of
liquid within a closed conduit. The transducers are a non-contacting, clamp-on type or
clamp-around, which will provide benefits of non-fouling operation and ease of installation.
The UTM10 Series of transit-time flowmeters utilize two transducers that function as both
ultrasonic transmitters and receivers. The transducers are clamped on the outside of a
closed pipe at a specific distance from each other. The transducers can be mounted in
V-mount where the sound transverses the pipe two times, W-mount where the sound
transverses the pipe four times, or in Z-mount where the transducers are mounted on
opposite sides of the pipe and the sound crosses the pipe once. The selection of mounting
method is based on pipe and liquid characteristics which both have an effect on how much
signal is generated. The flowmeter operates by alternately transmitting and receiving a
frequency modulated burst of sound energy between the two transducers and measuring
the time interval that it takes for sound to travel between the two transducers. The difference
in the time interval measured is directly related to the velocity of the liquid in the pipe.
IM-P197-02 MI Issue 1 5
2.3 CE compliance
The UTM10 transmitter can be installed in conformance to EN 55011 (CISPR 11) standards.
See the CE compliance drawings in the Appendix - Section 9.
6 IM-P197-02 MI Issue 1
6TCPUOKVVGTKPUVCNNCVKQP
3.1 General information
After unpacking the UTM10, it is recommended that its shipping carton and packing
materials be saved in case the instrument needs to be stored or re-shipped to a different
location. Inspect the equipment and carton for damage. If there is evidence of shipping
damage, notify the carrier immediately.
The enclosure should be mounted in an area that is convenient for servicing, calibration or
for observation of the LCD readout.
1) Locate the transmitter within the length of transducer cables supplied. If this is not
possible, it is recommended that the cable be exchanged for one that is of proper length.
If additional cable is added, utilize RG59 75 Ohm coaxial cable and BNC connections.
Transducer cables that are up to 300 metres (990 feet) can be accommodated.
2) Mount the UTM10 transmitter in a location:
- Where little vibration exists.
- That is protected from corrosive fluids.
- That is within the transmitters ambient temperature limits -40 to +85°C (-40 to +185°F).
- That is out of direct sunlight. Direct sunlight may increase transmitter temperature to
above the maximum limit.
3) Mounting - Refer to Figure 2 for enclosure and mounting dimension details. Ensure that
enough room is available to allow for door swing, maintenance and conduit entrances.
Secure the enclosure to a flat surface with two appropriate fasteners.
4) Conduit holes - Conduit holes should be used where cables enter the enclosure. Holes
not used for cable entry should be sealed with plugs.
An optional cable gland kit is available for inserting transducer and power cables. The part
number for this kit is D010-1100-000 and can be ordered directly from the manufacturer.
104.1 mm
(4.1")
152.1mm
(6")
109.7 mm
(4.32")
52.3mm
Fig. 2 UTM10 transmitter dimensions (2.06")
Note: Use IP65 (NEMA 4) rated fittings / plugs to maintain the watertight integrity of the
enclosure. Generally, the right conduit hole (viewed from front) is used for power, the left
conduit hole for transducer connections, and the center hole is utilized for I/O wiring.
IM-P197-02 MI Issue 1 7
3.2 Transducer connections
To access terminal strips for wiring, loosen the two screws in the enclosure door and open.
Guide the transducer terminations through the transmitter conduit hole located in the
bottom-left of the enclosure. Secure the transducer cable with the supplied conduit nut (if
flexible conduit was ordered with the transducer).
372
9(
'
1500mA250V
O
N
&86
5
W
$&1
$&/
Modbus A
Modbus B
Modbus Gnd
Reset Total
4-20 mA Out
Frequency Out
Control 2
Control 1
Signal Gnd.
'&2879$
$&,19$&+] $
95 - 264 VAC
&86
AC Neutral
(
3:&(
ZZZDVWURG\QHFRP
5
VWURG\QH
352'8&76(59,&(
789
+
Downstream
-
5R+6
-
5
Upstream
+
9R
Modbus
9R
TFX Rx
TFX Tx
To transducers
Caution: Any other wiring method may be unsafe or cause improper operation
of the instrument.
Note: This instrument requires clean electrical line power. Do not operate this unit on
circuits with noisy components (i.e., fluorescent lights, relays, compressors, or variable
frequency drives). The use of step down transformers from high voltage, high amperage
sources is also not recommended. Do not run signal wires with line power within the same
wiring tray or conduit.
8 IM-P197-02 MI Issue 1
3.3 Line voltage ac power connections
Connect 90 to 265 Vac, ac Neutral and Chassis Ground to the terminals referenced in
Figure 4. Do not operate without an earth (chassis) ground connection.
$&1 9R
VWURG\QH
ZZZDVWURG\QHFRP
1500mA250V
3:&(
372
W
9R
&86
$&,19$&+] $
9(
'
5
'&2879$
5
5
789 5R+6
&86
352'8&76(59,&(
$&/ (
95 - 264 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd Modbus
Modbus B TFX Rx
Modbus A TFX Tx
Downstream
Upstream
+
+
-
-
O
N
IM-P197-02 MI Issue 1 9
3.4 Low voltage ac power connections
Connect 20 to 28 Vac, ac Neutral and Chassis Ground to the terminals referenced in
Figure 5. Do not operate without an earth (chassis) ground connection.
The 24 Vac power supply option for the UTM10 is intended for a typical HVAC and Building
Control Systems (BCS) powered by a 24 Vac, nominal, power source. This power source
is provided by ac line power to 24 Vac drop down transformer and is installed by the
installation electricians.
Note: In electrically noisy applications, grounding the flowmeter to the pipe where the
transducers are mounted may provide additional noise suppression. This approach is
only effective with conductive metal pipes. The earth (chassis) ground derived from the
line voltage power supply should be removed at the flowmeter and a new earth ground
connected between the flowmeter and the pipe being measured.
Note: Wire gauges up to 2.08 mm 2 (14 AWG) can be accommodated in the UTM10 terminal
block.
Note: ac powered versions are protected by a field replaceable fuse, P.N. D005-1301-012.
This fuse is equivalent to Wickmann P.N. 3720500041 or 37405000410.
VWURG\QH
,19$&
1500mA250V
,1
287í
287
372
2879'&
&86
9(
'
$6'6
Chassis Gnd.
24 VAC
AC Neutral
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd Modbus
Modbus B TFX Rx
Modbus A TFX Tx
Downstream
Upstream
7HVW
3
+
+
-
-
O
N
24 Vac
Fig. 5 24 Vac power connections 24 VAC
Transformer
Transformer
10 IM-P197-02 MI Issue 1
3.5 dc power connections
The UTM10 may be operated from a 10 to 28 Vdc source, as long as the source is capable
of supplying a minimum of 5 Watts of power.
Connect the dc power to the 10 to 28 Vdc In, Power Ground, and Chassis Ground, as
in Figure 6.
Note: dc powered versions are protected by an automatically resetting fuse. This fuse
does not require replacement.
10 - 28 VDC
Power Gnd.
Signal Gnd.
Control 1
Control 2
Frequency Out
4-20 mA Out
Reset Total
Modbus Gnd Modbus
Modbus B TFX Rx 10 -28 VDC
Modbus A TFX Tx
Downstream
Power
Upstream
Ground
+
+
-
-
O
N
IM-P197-02 MI Issue 1 11
6TCPUFWEGTKPUVCNNCVKQP
4.1 General
The transducers that are utilized by the UTM10 contain piezoelectric crystals for transmitting
and receiving ultrasonic signals through walls of liquid piping systems. The UTT10-050S,
UTT10-050L, and UTT10-050H transducers are relatively simple and straightforward to
install, but spacing and alignment of the transducers is critical to the system's accuracy
and performance. Extra care should be taken to ensure that these instructions are carefully
executed. UTT10-015S to UTT10-040S, small pipe transducers, have integrated transmitter
and receiver elements that eliminate the requirement for spacing measurement and alignment.
Mounting of the UTT10-05S, UTT10-050L, and UTT10-050H clamp-on ultrasonic transit-time
transducers is comprised of three steps:
1) Selection of the optimum location on a piping system.
2) Entering the pipe and liquid parameters into either the software utility or keying the
parameters into the transmitter using the keypad. The software utility or the transmitters
firmware will calculate proper transducer spacing based on these entries.
3) Pipe preparation and transducer mounting.
The UTM10-E transmitter requires two RTDs to measure heat usage. The flowmeter utilizes
1000 Ohm, three-wire, platinum RTDs in two mounting styles. Surface mount RTDs are
available for use on well insulated pipes. If the area where the RTD will be located is not
insulated, inconsistent temperature readings will result and insertion (wetted) RTDs should
be utilized.
12 IM-P197-02 MI Issue 1
Table 1 Piping configuration and transducer positioning
The flowmeter system will provide repeatable measurements on piping systems that do
not meet these requirements, but accuracy of these readings may be influenced to various
degrees.
Flow 30 5
A B
Flow
15 5
A B
Flow
10 5
A B
Flow 10 5
A B
Flow 10 5
A B
Flow 30 5
A B
IM-P197-02 MI Issue 1 13
4.3 Step 2 - Transducer spacing
UTM10 transit-time flowmeters can be used with four different transducer types:
UTT10-050S, UTT10-050L, UTT10-050H and UTT10-015S to UTT10-040S. Flowmeters
that utilize the UTT10-05S, UTT10-050L, or UTT10-050H transducer sets consist of
two separate sensors that function as both ultrasonic transmitters and receivers.
UTT10-015S to UTT10-040S transducers integrate both the transmitter and receiver
into one assembly that fixes the separation of the piezoelectric crystals. UTT10-050S,
UTT10-050L and UTT10-050H transducers are clamped on the outside of a closed pipe at
a specific distance from each other.
The UTT10-050S, UTT10-050L and UTT10-050H transducers can be mounted in:
- W-mount where the sound traverses the pipe four times. This mounting method
produces the best relative travel time values but the weakest signal strength.
- V-mount where the sound traverses the pipe twice. V-mount is a compromise
between travel time and signal strength.
- Z-mount where the transducers are mounted on opposite sides of the pipe and
the sound crosses the pipe once. Z-mount will yield the best signal strength but the
smallest relative travel time.
Table 2
Transducer mounting modes —
UTT10-050S, UTT10-050L and UTT10-050H
Transducer
Pipe material Pipe size Liquid composition
mount mode
Plastic (all types)
Carbon steel 50 - 100 mm
Stainless steel (2" - 4")
W-mount
Copper
Ductile iron
Not recommended
Cast iron
Plastic (all types)
100 - 300 mm
Carbon steel
(4" - 12")
Stainless steel Low TSS
V-mount 100 - 750 mm (Total Suspended Solids);
Copper non-aerated
(4" - 30")
Ductile iron 50 - 300 mm
Cast iron (2" - 12")
Plastic (all types) >750 mm (>30")
Carbon steel
>300 mm (>12")
Stainless steel
Z-mount
Copper >750 mm (>30")
Ductile iron
>300 mm (>12")
Cast iron
14 IM-P197-02 MI Issue 1
For further details, reference Figure 7. The appropriate mounting configuration is based on
pipe and liquid characteristics. Selection of the proper transducer mounting method is not
entirely predictable and many times is an iterative process. Table 2 contains recommended
mounting configurations for common applications. These recommended configurations may
need to be modified for specific applications if such things as aeration, suspended solids,
out of round piping or poor piping conditions are present. Use of the UTM10 diagnostics in
determining the optimum transducer mounting is covered later in this Section.
Table 3
Transducer mounting modes — UTT10-015S to UTT10-040S
Size Frequency setting Transducer Mounting mode
UTT10-015SM
15 mm ½" 2 MHz UTT10-015SC
UTT10-015SP
UTT10-020SM
20 mm ¾" 2 MHz UTT10-020SC
UTT10-020P
UTT10-025SM
25 mm 1" 2 MHz UTT10-025SC V
UTT10-025P
UTT10-032SM
32 mm 1¼" 2 MHz UTT10-032SC
UTT10-032SP
UTT10-040SM
40 mm 1½" 2 MHz UTT10-040SC
UTT10-040SP
For pipe sizes of 600 mm (24") and larger the UTT10-050L transducer using a transmission
frequency of 500 KHz is recommended.
The UTT10-050L transducer may also be advantageous on pipes of between 100 - 600 mm
(4" - 24") if there are less quantifiable complicating aspects such as – sludge, tuberculation,
scale, rubber liners, plastic liners, thick mortar, gas bubbles, suspended solids, emulsions,
or pipes that are perhaps partially buried where a V-mount is required / desired, etc.
IM-P197-02 MI Issue 1 15
4.4 Step 3 - Entering pipe and liquid data
The UTM10 system calculates proper transducer spacing by utilizing piping and liquid
information entered by the user. This information can be entered via the keypad on a UTM10
or via the optional software utility.
The best accuracy is achieved when transducer spacing is exactly what the UTM10 calculates,
so the calculated spacing should be used if signal strength is satisfactory. If the pipe is not
round, the wall thickness not correct or the actual liquid being measured has a different
sound speed than the liquid programmed into the transmitter, the spacing can vary from the
calculated value. If that is the case, the transducers should be placed at the highest signal
level observed by moving the transducers slowly around the mount area.
Note: Transducer spacing is calculated on 'ideal' pipe. Ideal pipe is almost never found so
the transducer spacing distances may need to be altered. An effective way to maximize
signal strength is to configure the display to show signal strength, fix one transducer on
the pipe and then starting at the calculated spacing, move the remaining transducer small
distances forward and back to find the maximum signal strength point.
Important! Enter all of the data on this list, save the data and reset the UTM10 before
mounting transducers.
The following information is required before programming the instrument:
Pipe liner thickness (if present) Pipe liner material (if present)
Note: Much of the data relating to material sound speed, viscosity and specific gravity
is pre-programmed into the UTM10 flowmeter. This data only needs to be modified if it
is known that a particular application's data varies from the reference values. Refer to
Section 7 'Start-up and configuration' for instructions on entering configuration data into
the UTM10 flowmeter via the transmitter's keypad. Refer to Section 8 'Software utility' for
data entry via the software.
* Nominal values for these parameters are included within the UTM10 operating system. The
nominal values may be used as they appear or may be modified if exact system values are
known.
After entering the data listed above, the UTM10 will calculate proper transducer spacing
for the particular data set. This distance will be in millimetres if configured in metric units or
inches if the UTM10 is configured in imperial units.
16 IM-P197-02 MI Issue 1
4.5 Step 4 - Transducer mounting
Pipe preparation - After selecting an optimal mounting location (Step 1- Section 4.2)
and successfully determining the proper transducer spacing (Steps 2 and 3, Sections 4.3
and 4.4), the transducers may now be mounted onto the pipe - Which is covered in
Step 4, this Section).
Before a transducer is mounted onto the pipe surface, an area slightly larger than the flat
surface of each transducer must be cleaned of all rust, scale and moisture. For pipes with
rough surfaces, such as ductile iron pipe, it is recommended that the pipe surface be wire
brushed to a shiny finish. Paint and other coatings, if not flaked or bubbled, need not be
removed. Plastic pipes typically do not require surface preparation other than soap and
water cleaning.
The UTT10-050S, UTT10-050L and UTT10-050H transducers must be properly oriented
and spaced on the pipe to provide optimum reliability and performance. On horizontal pipes,
when Z-mount is required, the transducers should be mounted 180° from one another and
at least 45° from the top-dead-center and bottom-dead-center of the pipe - See Figure 8.
Also see Z-mount transducer installation (Section 4.8). On vertical pipes the orientation is
not critical.
TOP OF TOP OF
Top of pipe Top of pipe
PIPE PIPE
Flowmeter Flowmeter
mounting
FLOW orientation
METER mounting
FLOW orientation
METER
MOUNTINGUTT10-050L
UTT10-050S, ORIENTATION and MOUNTINGto
UTT10-015S ORIENTATION
UTT10-040S
UTT-050S, UTT-050L
UTT10-050H and UTT050H
transducers UTT-015S totransducers
UTT-040S TRANSDUCERS
TRANSDUCERS
Fig. 8 Transducer orientation — Horizontal pipes
The spacing between the transducers is measured between the two spacing marks on the
sides of the transducers. These marks are approximately 19 mm (0.75") back from the nose
of the UTT10-050S and UTT10-050H transducers, and 30 mm (1.2") back from the nose of
the UTT10-050L transducers - See Figure 9.
UTT10-015S to UTT10-040S transducers should be mounted with the cable exiting within
±45° of the side of a horizontal pipe. See Figure 8. On vertical pipes the orientation does
not apply.
Alignment
marks
IM-P197-02 MI Issue 1 17
4.6 V-mount and W-mount installation
4.6.1 Application of couplant
For UTT10-050S, UTT10-050L and UTT10-050H transducers, place a single bead of couplant,
approximately 12 mm (½") thick, on the flat face of the transducer. See Figure 10. Generally, a
silicone-based grease is used as an acoustic couplant, but any grease-like substance that is
rated not to 'flow' at the temperature that the pipe may operate at will be acceptable. For pipe
surface temperature over 55°C (130°F), Sonotemp® (P.N. D002-2011-010) is recommended.
12 mm (½") thick
18 IM-P197-02 MI Issue 1
4.6.2 Transducer positioning
1) Place the upstream transducer in position and secure with a mounting strap. Straps
should be placed in the arched groove on the end of the transducer. A screw is provided
to help hold the transducer onto the strap. Verify that the transducer is true to the pipe
and adjust as necessary. Tighten the transducer strap securely.
2) Place the downstream transducer on the pipe at the calculated transducer spacing
(Figure 11) - see Section 6 'Quick-start operating instructions'. By applying firm hand
pressure test to see if the signal strength is greater than 5 - If it is secure the transducer
at this location. If the signal strength is not 5 or greater, use firm hand pressure and
slowly move the transducer both towards and away from the upstream transducer while
observing signal strength.
Note: Signal strength readings
update only every few seconds, so it
is advisable to move the transducer
", wait, see if signal is increasing or
decreasing and then repeat until the
highest level is achieved.
Signal strength can be displayed on
the UTM10 display or on the main data
screen in the software utility - See
Section 8. Clamp the transducer at
the position where the highest signal
strength is observed. The factory
default signal strength setting is 5,
however there are many application
specific conditions that may prevent
the signal strength from attaining this
level. For the UTM10, signal levels
much less than 5 will probably not be
acceptable for reliable readings. Transducer
spacing
3) If after adjustment of the transducer
the signal strength does not rise
above 5, then an alternate transducer
mounting method should be selected.
If the mounting method was W-mount, Fig. 11 Transducer positioning
then re-configure the transmitter
for V-mount, move the downstream
transducer to the new spacing distance
and repeat Step 4 (Section 4.5).
IM-P197-02 MI Issue 1 19
4.7 UTT10 small pipe transducer installation
4.7.1 UTT10-015S to UTT10-040S
small pipe transducer installation
The small pipe transducers are designed for specific pipe outside diameters. Do not
attempt to mount a UTT10-015S to UTT10-040S transducer onto a pipe that is either too
large or too small for the transducer. Contact the manufacturer to arrange for a replacement
transducer that is the correct size.
UTT10-015S to UTT10-040S installation consists of the following steps:
1) Apply a thin coating of acoustic coupling grease to both halves of the transducer
housing where the housing will contact the pipe. See Figure 12.
2) On horizontal pipes, mount the transducer in an orientation such that the cable exits
at ±45° from the side of the pipe. Do not mount with the cable exiting on either
the top or bottom of the pipe. On vertical pipes the orientation does not matter -
See Figure 8, page 17.
3) Tighten the wing nuts so that the acoustic coupling grease begins to flow out from the
edges of the transducer or from the gap between the transducer halves. Do not over
tighten.
4) If signal strength is less than 5, remount the transducer at another location on the piping
system.
1⁄16”
1.5 (1.5
mm (mm)
")
Acoustic couplant
Acoustic grease
Couplant
Grease
Fig. 12 Application of acoustic couplant — UTT10-015S to UTT10-040S transducers
20 IM-P197-02 MI Issue 1
4.7.2 UTT10-015S to UTT10-040S
small pipe transducer configuration procedure
1) Establish communications with the transit-time flowmeter - See Section 8 'Software utility'.
2) From the Tool Bar select Calibration - See Figure 13.
3) On the pop-up screen, click Next button twice to get to Page 3 of 3 - See Figure 14.
4) Click Edit.
8OWUD/,1.'HYLFH$GGU
)LOH (GLW 9LHZ &RPPXQLFDWLRQV :LQGRZ +HOS
&RQILJXUDWLRQ 6WUDWHJ\ &DOLEUDWLRQ (UURUV
UUR 3ULQW 3ULQW3UHYLH
'HYLFH$GGU
7LPH 0LQ 6FDOH
)ORZ *DO0LQ
7RWDOL]HU1HW 2%
3RV 2%
1HJ 2%
6LJ6WUHQJWK
0DUJLQ
'HOWD7 QV
/DVW8SGDWH
3OHDVHHVWDEOLVKD
UHIHUHQFHIORZUDWH
)360360LQLPXP
(QWHUWKHUHIHUHQFHIORZ
UDWHEHORZ'RQRWHQWHU
:DLWIRUIORZWRVWDELOL]H
3UHVVWKH6HWEXWWRQ
*DO0
)ORZ
6HW
(GLW
'HOWD7LPH ([SRUW
IM-P197-02 MI Issue 1 21
5) If calibration point is displayed in Calibration Points Editor screen, record the information,
highlight and click Remove - See Figure 15.
6) Click ADD...
6HOHFWSRLQWVWRHGLWRUUHPRYH
QV*DO0LQ
$GG
(GLW
5HPRYH
6HOHFW$OO
6HOHFW1RQH
2. &DQFHO
2. &DQFHO
7) Enter Delta T, Uncalibrated Flow, and Calibrated Flow values from the UTT10-015S to
UTT10-040S calibration label, then click OK - See Figure 16.
8) Click OK in the Edit Calibration Points screen.
9) Process will return to Page 3 of 3. Click Finish - See Figure 14.
10) After 'Writing Configuration File' is complete, turn the power off. Turn the power back
on to activate the new settings.
22 IM-P197-02 MI Issue 1
4.8 Mounting transducers in Z-mount configuration
Installation on larger pipes requires careful measurement of the linear and radial placement
of the UTT10-050S, UTT10-050L and UTT10-050H transducers. Failure to properly orient
and place the transducers on the pipe may lead to weak signal strength and/or inaccurate
readings. This section details a method for properly locating the transducers on larger pipes.
This method requires a roll of paper such as freezer paper or wrapping paper, masking tape
and a marking device.
Fold
Pipe circumference
Transducer
Transducer spacing
Spacing
Crease
Crease(Center
(centre of pipe)
of Pipe)
IM-P197-02 MI Issue 1 23
3) Crease the paper at the fold line. Mark the crease. Place a mark on the pipe where one
of the transducers will be located. See Figure 19 for acceptable radial orientations. Wrap
the template back around the pipe, placing the beginning of the paper and one corner
in the location of the mark. Move to the other side of the pipe and mark the pipe at the
ends of the crease. Measure from the end of the crease (directly across the pipe from
the first transducer location) the dimension derived in Section 4.3, 'Step 2 - Transducer
spacing'. Mark this location on the pipe.
TOP OF TOP OF
Top of pipe Top of pipe
PIPE PIPE
Flowmeter Flowmeter
mounting
FLOW orientation
METER mounting
FLOW orientation
METER
MOUNTINGUTT10-050L
UTT10-050S, ORIENTATION and MOUNTINGto
UTT10-015S ORIENTATION
UTT10-040S
UTT-050S, UTT-050L
UTT10-050H and UTT050H
transducers UTT-015S totransducers
UTT-040S TRANSDUCERS
TRANSDUCERS
4) The two marks on the pipe are now properly aligned and measured.
If access to the bottom of the pipe prohibits the wrapping of the paper around the
circumference, cut a piece of paper ½ the circumference of the pipe and lay it over the
top of the pipe. The length of ½ the circumference can be found by:
½ Circumference = Pipe O.D. × 1.57
See Section 4.6.2 'Transducer positioning' for transducer spacing.
Mark opposite corners of the paper on the pipe. Apply transducers to these two marks.
5) For UTT10-050S, UTT10-050L and UTT10-050H transducers, place a single bead
of couplant, approximately 12 mm (½") thick, on the flat face of the transducer -
See Figure 20. Generally, a silicone-based grease is used as an acoustic couplant, but
any good quality grease-like substance that is rated to not 'flow' at the temperature that
the pipe may operate at will be acceptable.
12 mm (½") thick
24 IM-P197-02 MI Issue 1
6) Place the upstream transducer in position and secure with a stainless steel strap or
other fastening device. Straps should be placed in the arched groove on the end of the
transducer. A screw is provided to help hold the transducer onto the strap. Verify that
the transducer is true to the pipe, adjust as necessary. Tighten transducer strap securely.
Larger pipes may require more than one strap to reach the circumference of the pipe.
7) Place the downstream transducer on the pipe at the calculated transducer spacing - See
Figure 21. Using firm hand pressure, slowly move the transducer both towards and away
from the upstream transducer while observing signal strength. Clamp the transducer at
the position where the highest signal strength is observed. Signal strength of between
5 and 98 is acceptable. The factory default signal strength setting is 5, however there
are many application specific conditions that may prevent the signal strength from
attaining this level.
A minimum signal strength of 5 is acceptable as long as this signal level is maintained
under all flow conditions.
On certain pipes, a slight twist to the transducer may cause signal strength to rise to
acceptable levels.
Top view
of pipe
8) Certain pipe and liquid characteristics may cause signal strength to rise to greater than
98. The problem with operating a UTM10 with very high signal strength is that the signals
may saturate the input amplifiers and cause erratic readings. Strategies for lowering
signal strength would be changing the transducer mounting method to the next longest
transmission path. For example, if there is excessive signal strength and the transducers
are mounted in a Z-mount, try changing to V-mount or W-wount. Finally you can also
move one transducer slightly off line with the other transducer to lower signal strength.
9) Secure the transducer with a stainless steel strap or other fastener.
IM-P197-02 MI Issue 1 25
4.9 Mounting track installation:
1) A convenient transducer mounting track can be used for pipes that have outside diameters
between 50 and 250 mm (2" and 10"). If the pipe is outside of that range, select a V-mount
or Z-mount mounting method.
2) Install the single mounting rail on the side of the pipe with the stainless steel bands
provided. Do not mount it on the top or bottom of the pipe. Orientation on vertical pipe
is not critical. Ensure that the track is parallel to the pipe and that all four mounting feet
are touching the pipe.
3) Slide the two transducer clamp brackets towards the center mark on the mounting rail.
4) Place a single bead of couplant, approximately 12 mm (½") thick, on the flat face of the
transducer - See Figure 22.
12 mm (½") thick
5) Place the first transducer inbetween the mounting rails near the zero point on the scale.
Slide the clamp over the transducer. Adjust the clamp / transducer such that the notch
in the clamp aligns with zero on the scale - See Figure 23.
6) Secure with the thumb screw. Ensure that the screw rests in the counter bore on the
top of the transducer. (Excessive pressure is not required. Apply just enough pressure
so that the couplant fills the gap between the pipe and transducer.)
7) Place the second transducer inbetween the mounting rails near the dimension derived
in Section 4.3 'Step 2 - Transducer spacing'. Read the dimension on the mounting rail
scale. Slide the transducer clamp over the transducer and secure with the thumb screw.
26 IM-P197-02 MI Issue 1
+PRWVUCPF1WVRWVU
5.1 General
The UTM10 is available configured as follows:
1) There is the UTM10-S flow model that is equipped with a 4-20 mA output, two open
collector outputs, a rate frequency output, and RS485 communications using the Modbus
RTU command set.
2) The energy version of the UTM10-E has inputs for two 1000 Ohm RTD sensors in place
of the rate frequency and alarm outputs. This version allows the measurement of pipe
input and output temperatures so that energy usage calculations can be performed.
Operate in the shaded areas
Supply voltage (Vdc)
IM-P197-02 MI Issue 1 27
90-265 VAC
AC Neutral Signal ground
Signal Gnd.
Control 1
Loop Control 2
resistance
Frequency Out
4-20 mA Out
Reset Total
7 Vdc drop
Meter power
The 4-20 mA output signal is available between the 4-20 mA out and Signal Gnd. terminals
as shown in Figure 25.
Both control outputs are rated for a maximum of 100 mA and 10 to 28 Vdc. A pull-up resistor
can be added externally or an internal 10 K Ohm pull-up resistor can be selected using DIP
switches on the power supply board.
28 IM-P197-02 MI Issue 1
For the Rate Alarm and Signal Strength Alarm the on/off values are set using either the
keypad or the software utility.
Typical control connections are illustrated in Figure 27. Please note that only the Control
1 output is shown. Control 2 is identical except the pull-up resistor is governed by SW2.
VCC VCC
10K 10K
90-265 VAC
O
N
10 - 20 90-265 VAC
O
AC Neutral SW1/SW2
SW1/SW2
Vdc AC Neutral
N
SW1/SW2
SW1/SW2
Signal Gnd. Signal Gnd.
Control 1 Control 1
Control 2
Control 2
Frequency Out
Frequency Out
4-20 mA Out
Reset Total 100 mA maximum 4-20 mA Out
Reset Total
Minimum Maximum
Flow Flow
Minimum flow Maximum flow
Set OFF
Set ON
Set Set
OFF ON Output ON
Output ON
Output OFF
Output OFF
Deadband
Deadband
IM-P197-02 MI Issue 1 29
5.3.2 Batch / totalizer output
Totalizer mode configures the output to send a 33 millisecond pulse each time the display
totalizer increments divided by the TOT MULT. The TOT MULT value must be a whole, positive,
numerical value.
For example, if the totalizer exponent (TOTL E) is set to E0 (×1) and the totalizer multiplier
(TOT MULT) is set to 1, then the output will pulse each time the totalizer increments one
count, or each single, whole measurement unit totalized.
If the totalizer exponent (TOTL E) is set to E2 (×100) and the totalizer multiplier (TOT MULT)
is set to 1, then the control output will pulse each time the display totalizer increments or
once per 100 measurement units totalized.
If the totalizer exponent (TOTL E) is set to E0 (×1) and the totalizer multiplier (TOT MULT) is
set to 2, the control output will pulse once for every two counts that the totalizer increments.
Frequency Output
Fig. 29 Frequency output switch settings Frequency output
30 IM-P197-02 MI Issue 1
If, for example, the MAX RATE parameter was set to 1514 litres/minute (400 US gallons/
minute) then an output frequency of 500 Hz (half of the full-scale frequency of 1000 Hz)
would represent 757 litres/minute (200 US gallons/minute).
In addition to the control outputs, the frequency output can be used to provide total
information by use of a 'K-factor'. A K-factor simply relates the number of pulses from the
frequency output to the number of accumulated pulses that equates to a specific volume.
For the UTM10 this relationship is described by the following equation. The 60 000 relates
to measurement units in volume/min. Measurement units in seconds, hours or days would
require a different numerator.
60 000
Equation 1 K-factor calculation K - factor =
Full-scale units
A practical example would be if the MAX RATE for the application were 400 GPM (Gallons/
Minute), the K-factor (representing the number of pulses accumulated needed to equal
1 Gallon) would be:
60 000
K - factor = = 150 pulses per gallon
400 GPM
If the frequency output is to be used as a totalizing output, the UTM10 and the receiving
instrument must have identical K-factor values programmed into them to ensure that accurate
readings are being recorded by the receiving instrument. Unlike standard mechanical
flowmeters such as turbines, gear or nutating disk meters, the K-factor can be changed by
modifying the MAX RATE flowrate value.
Note: For a full treatment of K-factors please see the Section 9 'Appendix'.
There are two frequency output types available:
Turbine meter simulation - This option is utilized when a receiving instrument is capable
of interfacing directly with a turbine flowmeter's magnetic pickup. The output is a relatively
low voltage ac signal whose amplitude swings above and below the signal ground reference.
The minimum ac amplitude is approximately 500 mV peak-to-peak. To activate the turbine
output circuit, turn SW4 OFF.
P9
500 mV p-p
SS
9
IM-P197-02 MI Issue 1 31
5.5 RS485
The RS485 feature allows up to 126 UTM10 systems to be placed on a single three-wire
cable bus. All flowmeters are assigned a unique numeric address that allows all of the
flowmeters on the cable network to be independently accessed. A Modbus RTU command
protocol is used to interrogate the flowmeters. An explanation of the command structure
is detailed in Section 9 'Appendix'. Flowrate, total, signal strength and temperature (if so
equipped) can be monitored over the digital communications bus. Baud rates up to 9600
and cable lengths to 1500 m (5000 ft) are supported without repeaters or 'end of line'
resistors.
To interconnect flowmeters, utilize three-wire shielded cable such as Belden® 9939
or equal. In noisy environments the shield should be connected on one end to a good
earth ground connection. A USB to RS485 converter such as the B&B Electronics P/N
485USBTB-2W can be used to communicate with a PC running Windows 98, Windows
ME, Windows 2000, Windows NT, Windows XP, and Windows Vista®. For computers
with RS232C serial ports, an RS232C to RS485 converter, such as B&B Electronics P/N
485SD9TB (illustrated in Figure 33), is required to interconnect the RS485 network to a
communication port on a PC. If more than 126 flowmeters must be monitored, an additional
converter and communication port are required.
Note: When the USB programming cable is connected, the RS485 and frequency outputs
are disabled.
4-20 mA Out
Reset Total
A (-)
Modbus Gnd
B (+) Modbus B
Model 485USBTB-2W A (-)
B (+) Modbus A
GND
USB to RS485
USB to RS485
4-20 mA Out
Reset Total
TA (A) -
Modbus Gnd
TD (B) + Modbus B
GND
GND
Modbus A
+12V
RS-485
RS-485 Converter
To 12 Vdc
Model 485SD9TB
supply
RS-232
RS232 to RS485
Fig. 32 RS485 network connections
32 IM-P197-02 MI Issue 1
5.6 Energy flow UTM10-E only
The UTM10-E allows the integration of two 1000 Back of
%$&.2)
Ohm, platinum RTDs with the flowmeter, effectively connector
&211(&725
providing an instrument for measuring energy
consumed in liquid heating and cooling systems. If
RTDs were ordered with the UTM10 flowmeter, they
have been factory calibrated and are shipped with
the flowmeter.
Heat tape
IM-P197-02 MI Issue 1 33
Route the RTD cables back to the UTM10 flowmeter and secure the cable so that it will not
be pulled on or abraded inadvertently. Replace the insulation on the pipe, ensuring that the
RTDs are not exposed to air currents.
If the cables are not long enough to reach the UTM10, route the cables to an electrical
junction box and add additional cable from that point. Use three-wire shielded cable, such
as Belden® 9939 or equal, for this purpose.
Note: Adding cable adds to the resistance the flowmeter reads and may have an effect on
absolute accuracy. If cable is added, ensure that the same length is added to both RTDs to
minimize errors due to changes in cable resistance.
$&1 9R
VWURG\QH
ZZZDVWURG\QHFRP
1500mA250V
3:&(
372
9R
&86
$&,19$&+] $
9(
'
'&2879$
5
5
789 5R+6
&86
352'8&76(59,&(
$&/ (
RTD 1
RTD 2
95 - 264 VAC
AC Neutral Exc. Exc. Supply line
6833/</,1(
OCNIM
57'
Sig. Sig. RTD #1
Gnd. Gnd.
Shield Shield
RTD's
Return line
-40 to 200°C
5(7851/,1(
MINCO
0 to 100°C
TEMP. SET
57'
0 to 50°C
Upstream
+
+
-
-
34 IM-P197-02 MI Issue 1
5.6.3 Replacement RTDs
If it is necessary to replace RTDs, complete RTD kits including the energy flowmeters plug-in
connector and calibration values for the replacements are available from the manufacturer.
It is also possible to use other manufacturer's RTDs. The RTDs must be 1000 Ohm platinum
RTDs suitable for a three-wire connection. A connection adapter, P.N. D005-0350-300, is
available to facilitate connection to the UTM10 - See Figure 36.
White
:+,7(
5('
Red 57'
RTD2
Pin 8
3,1
%/$&.
Black
Pin 6
3,1 Pin 5
3,1
*5((1
Green
Pin 4
3,1 Pin 3
3,1
%52:1
Brown 57'
RTD1
Pin 2
3,1 Pin 1
3,1
%/8(
Blue
'5$,1
Drain
:+,7(
White Pin3,1
5
%/$&.
Black Pin3,1
3
5('
Red Pin3,1
1
'5$,1
Drain Pin3,1
8
Green
*5((1 Pin3,1
6
Blue
%/8( Pin3,1
4
Brown
%52:1 Pin3,1
2
Note: It will be necessary to calibrate third party RTDs to the UTM10 for proper operation
- See Section 9 'Appendix' for the calibration procedure.
IM-P197-02 MI Issue 1 35
3WKEMUVCTVQRGTCVKPIKPUVTWEVKQPU
This Section provides the basic instructions for operation. If specific instrument features
are to be used or if the installer is unfamiliar with this type of instrument, refer to the
appropriate Section in this document for complete details.
Warning: Before supplying power to the unit it is advised that Section 1 'Safety information'
be read by the person commissioning the unit into operation.
Please note: It will be necessary to supply power to the unit, at least temporarily, to obtain
set-up information that will be required in the following steps (Sections 6.1 to 6.4):
3) Enter the following data into the UTM10 transmitter via the integral keypad or the
software utility:
1. Transducer mounting method
2. Pipe O.D. (Outside Diameter)
3. Pipe wall thickness
4. Pipe material
5. Pipe sound speed*
6. Pipe relative roughness*
7. Pipe liner thickness
8. Pipe liner material
9. Fluid type
10. Fluid sound speed*
11. Fluid viscosity*
* Nominal values for these parameters are included within the UTM10 operating system.
The nominal values may be used as they appear or may be modified if the exact system
values are known.
4) Record the value calculated and displayed as Transducer Spacing (XDC SPAC).
36 IM-P197-02 MI Issue 1
6.2 Electrical connections
Transducer / power connections:
1) Route the transducer cables from the transducer mounting location back to the UTM10
enclosure. Connect the transducer wires to the terminal block in the UTM10 enclosure.
2) Verify that power supply is correct for the flowmeters power option:
- Line voltage ac units require 95 to 265 Vac 47 to 63 Hz @ 17 VA maximum.
- Low voltage ac units require 20 to 28 Vac 47 to 63 Hz @ 17 VA maximum.
- dc units require 10 to 28 Vdc @ 5 Watts maximum.
3) Connect the power to the UTM10 flowmeter.
Downstream+
Downstream-
Upstream-
Upstream+
IM-P197-02 MI Issue 1 37
6.3.2 UTT10-015S to UTT10-040S transducers:
1) Place the flowmeter in signal strength measuring mode. This value is available on the
UTM10 display (Service Menu) or in the data display of the software utility.
2) The pipe surface, where the transducer is to be mounted, must be clean and dry. Remove
any scale, rust or loose paint to ensure satisfactory acoustic conduction. Wire brushing
the rough surface of the pipe to a smooth bare metal may also be useful. Plastic pipes
do not require preparation other than cleaning.
3) Apply a single 12 mm (½") bead of acoustic couplant grease to the upstream transducer
and secure it to the pipe with a mounting strap.
4) Tighten the nuts so that the acoustic coupling grease begins to flow out from the edges
of the transducer and from the gap between the transducer and the pipe. Do not over
tighten.
6.4 Start-up
Initial settings and power up:
1) Apply power to the transmitter.
2) Verify that SIG STR is greater than 5.0.
3) Input proper units of measure and I/O data.
38 IM-P197-02 MI Issue 1
5VCTVWRCPF%QPHKIWTCVKQP
7.1 Before starting the instrument
Note: The UTM10 flowmeter system requires a full pipe of liquid before a successful
start-up can be completed. Do not attempt to make adjustments or change configurations
until a full pipe is verified.
Note: If Dow 732 RTV was utilized to couple the transducers to the pipe, the adhesive
must be fully cured before readings are attempted. Dow 732 requires 24 hours to cure
satisfactorily. If Sonotemp® acoustic coupling grease was utilized as a couplant, curing is
not required.
IM-P197-02 MI Issue 1 39
7.3 Keypad programming
The UTM10 units that have been ordered with a keypad can be configured through the
keypad interface or by using the Windows® compatible software utility - See Section
8 'Software utility'. Of the two methods of configurating the UTM10, the software utility
provides more advanced features and offers the ability to store and transfer flowmeter
configurations between UTM10 units. All entries are saved in non-volatile FLASH memory
and will be retained indefinitely in the event of power loss.
Note: When USB programming cable is connected, the RS485 and frequency outputs are
disabled.
The UTM10 keypad contains a four-key tactile feedback keypad interface that allows the
user to view and change configuration parameters used by the operating system.
Mode Keypad
indicators
1) The MENU key is pressed from RUN mode to enter PROGRAM mode. The MENU key is
pressed in PROGRAM mode to exit from configuration parameter selection and menus.
If changes to any configuration parameters are made, the user will be prompted with a
SAVE? when returning to RUN mode. If YES is chosen the new parameters will be saved
in program memory.
2) The arrow STkeys are used to scroll through menus and configuration parameters. The
arrow keys are also used to adjust parameter numerical values.
3) The ENTER key functions are:
- Pressed from the RUN mode to view the current software version operating in the
instrument.
- Used to access the configuration parameters in the various menus.
- Used to initiate changes in configuration parameters.
- Used to accept configuration parameter changes.
40 IM-P197-02 MI Issue 1
7.4 Menu structure
The UTM10 firmware uses a hierarchical menu structure. A map of the user interface is
included in Section 9 'Appendix'. The map provides a visual path to the configuration
parameters that users can access. This tool should be employed each time configuration
parameters are accessed or revised.
SENSOR - This menu is used to select the sensor type Section 7.8
SEN MENU
(i.e. STD 1 MHZ, etc.) page 56
Units selection:
- UNITS - Programming unit selection (choice)
- METRIC (Millimetres)
- IMPERIAL (Inches)
Installs a global measurement standard into the memory of the instrument. The choices are
either Metric or Imperial units.
Select METRIC if the flowmeter is to be configured in millimetres. Select IMPERIAL if all
configurations (pipe sizes, etc.) are to be made in inches.
The METRIC / IMPERIAL selection will also configure the UTM10 to display sound speeds in
pipe materials and liquids as either metres / second (MPS) or feet / second (FPS), respectively.
IM-P197-02 MI Issue 1 41
Important!: If the UNITS entered have been changed from METRIC to IMPERIAL or vice
versa the entry must be saved and the instrument reset (power cycled or System Reset SYS
RSET entered) in order for the UTM10 to initiate the change in operating units. Failure to
save and reset the instrument will lead to improper transducer spacing calculations and an
instrument that may not measure properly.
Address
ADDRESS - Modbus address (Value)
1-126
Note: This is for the RS485 connection only. The Modbus TCP / IP address is set via the
integrated HTML application in the Ethernet port.
Each UTM10 connected on the communications bus must have an unique address
number assigned.
Transducer mount
XDCR MNT - Transducer mounting method (Choice)
V
W
Z
Selects the mounting orientation for the transducers. The selection of an appropriate
mounting orientation is based on pipe and liquid characteristics - See Section 4
'Transducer installation'.
Flow direction
FLOW DIR - Transducer flow direction control (Choice)
FORWARD
REVERSE
Allows the flow direction to be changed from that which the flowmeter assumes to be
forward. This feature allows upstream and downstream transducers to be 'electronically'
reversed making upside down mounting of the display unnecessary when mounting a
UTM10 flowmeter with integral transducer.
Transducer frequency
XDCR HZ - Transducer transmission frequency (Choice)
500 KHZ (500 Kilohertz)
1 MHZ (1 Megahertz)
2 MHZ (2 Megahertz)
Transducer transmission frequencies are specific to the type of transducer and the
size of pipe. In general the UTT10-050L 500 KHz transducers are used for pipes
greater than 600 mm (24"). UTT10-050S and UTT10-050H, 1 MHz transducers, are for
intermediate sized pipes between 50 mm (2") and 600 mm (24"). The UTT10-015S to
UTT10-040S, 2 MHz transducers, are for pipe sizes between 15 mm (½") and 40 mm (1½").
42 IM-P197-02 MI Issue 1
Pipe outside diameter
PIPE OD - Pipe outside diameter entry (Value)
METRIC (Millimetres)
IMPERIAL (Inches)
Enter the pipe outside diameter in millimetres if METRIC was selected as your choice
of units.
Note: Charts listing popular pipe sizes have been included in Section 9 'Appendix'.
Correct entries for pipe O.D. and pipe wall thickness are critical to obtaining accurate
flow measurement readings.
Pipe material
PIPE MAT - Pipe material selection (Choice)
The following list is provided as an example. Additional pipe materials are added
periodically. Select the appropriate pipe material from the list or select OTHER if the
material is not listed.
IM-P197-02 MI Issue 1 43
Pipe sound speed
PIPE SS - Speed of sound in the pipe material (Value)
METRIC (metres per second)
IMPERIAL (feet per second)
Allows adjustments to be made to the speed of sound value, shear or transverse wave,
for the pipe wall. If METRIC was chosen as your choice of units, the entry will be in MPS
(metres / second).
If a pipe material was chosen from the PIPE MAT list, a nominal value for speed of
sound in that material will be automatically loaded. If the actual sound speed is known
for the application piping system and that value varies from the automatically loaded
value, the value can be revised.
If OTHER was chosen as PIPE MAT, then a PIPE SS must also be entered.
Pipe roughness
PIPE R - Pipe material relative roughness (Value)
Unitless value
The UTM10 provides flow profile compensation in its flow measurement calculation.
The ratio of average surface imperfection as it relates to the pipe internal diameter is
used in this compensation algorithm and is found by using the following formula:
If a pipe material was chosen from the PIPE MAT list, a nominal value for relative
roughness in that material will be automatically loaded. If the actual roughness is
known for the application piping system and that value varies from the automatically
loaded value, the value can be revised.
Liner thickness
LINER T - Pipe liner thickness (Value)
METRIC (Millimetres)
IMPERIAL (Inches)
If the pipe has a liner, enter the pipe liner thickness. If METRIC was chosen as your
choice of units, enter this value in millimetres.
44 IM-P197-02 MI Issue 1
Liner material
LINER MA - Pipe liner material (Choice)
Liner type - (If a LINER thickness was selected)
The following list is provided as an example. Additional materials are added periodically.
Select the appropriate material from the list or select OTHER if the liner material is not
listed.
If a liner was chosen from the LINER MA list, a nominal value for speed of sound in
that media will be automatically loaded. If the actual sound speed rate is known for the
pipe liner and that value varies from the automatically loaded value, the value can be
revised.
Liner roughness
LINER R - Liner material relative roughness (Value)
Unitless value
The UTM10 provides flow profile compensation in its flow measurement calculation.
The ratio of average surface imperfection as it relates to the pipe internal diameter is
used in this compensation and is found by using the following formula:
If a liner material was chosen from the LINER MA list, a nominal value for relative
roughness in that material will be automatically loaded. If the actual roughness is
known for the application liner and that value varies from the automatically loaded
value, the value can be revised.
IM-P197-02 MI Issue 1 45
Fluid type
FL TYPE - Fluid / media type (Choice)
The following list is provided as an example. Additional liquids are added periodically.
Select the appropriate liquid from the list or select OTHER if the liquid is not listed.
46 IM-P197-02 MI Issue 1
Fluid viscosity
FLUID VI - Absolute viscosity of the fluid (Value - cP)
Allows adjustments to be made to the absolute viscosity of the liquid in centipoise.
UTM10 flowmeters utilize pipe size, viscosity and specific gravity to calculate Reynolds
numbers. Since the Reynolds number influences flow profile, the UTM10 has to
compensate for the relatively high velocities at the pipe center during transitional or
laminar flow conditions. The entry of FLUID VI is utilized in the calculation of Reynolds
and the resultant compensation values.
If a fluid was chosen from the FL TYPE list, a nominal value for viscosity in that media
will be automatically loaded. If the actual viscosity is known for the application fluid and
that value varies from the automatically loaded value, the value can be revised.
If OTHER was chosen as FL TYPE, then a FLUID VI must also be entered. A list of
alternate fluids and their associated viscosities is located in Section 9 'Appendix'.
IM-P197-02 MI Issue 1 47
Fluid specific heat capacity
SP HEAT - Fluid specific heat capacity (Value)
BTU/lb
Allows adjustments to be made to the specific heat capacity of the liquid.
If a fluid was chosen from the FL TYPE list, a default specific heat will be automatically
loaded. This default value is displayed as SP HEAT in the BSC MENU. If the actual
specific heat of the liquid is known or it differs from the default value, the value can
be revised. See Tables 5, 6 and 7 for specific values. Enter a value that is the mean of
both pipes.
48 IM-P197-02 MI Issue 1
Transducer spacing
XDC SPAC - Transducer Spacing Calculation (Value)
METRIC (Millimetres)
IMPERIAL (Inches)
Note: This value is calculated by the firmware after all pipe parameters have
been entered. The spacing value only pertains to UTT10-050S, UTT10-050L and
UTT10-050H transducer sets.
This value represents the one-dimensional linear measurement between the transducers
(the upstream / downstream measurement that runs parallel to the pipe). If METRIC was
chosen as your choice of units, the entry will be in (millimetres). This measurement is
taken between the lines which are scribed into the side of the transducer blocks.
If the transducers are being mounted using the transducer track assembly, a measuring
scale is etched into the track. Place one transducer at 0 and the other at the appropriate
measurement.
Rate units
RATE UNT - Engineering units for flowrate (Choice)
Select a desired engineering unit for flowrate measurements.
Rate interval
RATE INT - Time interval for flowrate (Choice)
SEC Seconds
MIN Minutes
HOUR Hours
DAY Days
Select a desired engineering unit for flowrate measurements.
IM-P197-02 MI Issue 1 49
Totalizer units
TOTL UNT - Totalizer units
Select a desired engineering unit for flow accumulator (totalizer) measurements.
Totalizer exponent
TOTL E - Flow totalizer exponent value (Choice)
E(-1) to E6
Utilized for setting the flow totalizer exponent. This feature is useful for accommodating
a very large accumulated flow or to increase totalizer resolution when flows are small
(displaying fractions of whole barrels, gallons, etc.) The exponent is a × 10n multiplier,
where 'n' can be from –1 (× 0.1) to +6 (× 1,000,000). Table 8 should be referenced for
valid entries and their influence on the display. Selection of E-1 and E0 adjusts the
decimal point on the display. Selection of E1, E2 and E3 causes an icon of × 10, × 100
or × 1000 respectively to appear to the right of the total flow display value.
50 IM-P197-02 MI Issue 1
Minimum flowrate
MIN RATE - Minimum flowrate settings (Value)
A minimum rate setting is entered to establish filter software settings and the lowest
rate value that will be displayed. Volumetric entries will be in the Rate Units and Interval
selected on Page 49 of this manual. For unidirectional measurements, set MIN RATE to
zero. For bidirectional measurements, set MIN RATE to the highest negative (reverse)
flowrate expected in the piping system.
Note: The flowmeter will not display a flowrate at flows less than the MIN RATE value.
As a result, if the MIN RATE is set to a value greater than zero, the flowmeter will display
the MIN RATE value, even if the actual flow / energy rate is less than the MIN RATE.
For example, if the MIN RATE is set to 25 and actual rate is 0, the flowmeter display will
indicate 25. Another example, if the MIN RATE is set to -100 and the actual flow is -200,
the flowmeter will indicate -100. This can be a problem if the flowmeter MIN RATE is
set to a value greater than zero because at flows below the MIN RATE the rate display
will show zero flow, but the totalizer which is not affected by the MIN RATE setting will
keep totalizing.
Maximum flowrate
MAX RATE - Maximum flowrate settings (Value)
A maximum volumetric flowrate setting is entered to establish filter software settings.
Volumetric entries will be in the Rate Units and Interval selected on Page 49. For
unidirectional measurements, set MAX RATE to the highest (positive) flowrate expected
in the piping system. For bidirectional measurements, set MAX RATE to the highest
(positive) flowrate expected in the piping system.
Damping percentage
DAMP PER - System damping (Value)
0-100%
Flow filter damping establishes a maximum adaptive filter value. Under stable flow
conditions (flow varies less than 10% of reading), this adaptive filter will increase the
number of successive flow readings that are averaged together up to this maximum
value. If flow changes outside of the 10% window, the flow filter adapts by decreasing
the number of averaged readings which allows the flowmeter to react faster. Increasing
this value tends to provide smoother steady-state flow readings and outputs. If very
erratic flow conditions are present or expected, other filters are available for use in the
software utility - See Section 8 'Software utility'.
IM-P197-02 MI Issue 1 51
7.6 CH1 menu - Channel 1 menu
CH1 MENU - 4-20 mA output menu (Applies to all UTM10 Versions)
4-20 MA - 4-20 mA set-up options (Values)
FL 4MA Flow at 4 mA
FL 20MA Flow at 20 mA
CAL 4MA 4 mA calibration
CAL 20MA 20 mA calibration
4-20 TST 4-20 mA test
The CH1 menu controls how the 4-20 mA output is spanned for all the UTM10 flowmeters
and how the frequency output is spanned for the UTM10-S flow model.
The FL 4MA and FL 20MA settings are used to set the span for both the 4-20 mA output and
the 0 - 1000 Hz frequency output on the UTM10-S flowmeter versions.
The 4-20 mA output is internally powered (current sourcing) and can span negative
to positive flow / energy rates. This output interfaces with virtually all recording and
logging systems by transmitting an analog current that is proportional to system
flowrate. Independent 4 mA and 20 mA span settings are established in firmware using
the flow measuring range entries. These entries can be set anywhere in the -12 to
+12 metres/second (-40 to + 40 feet/second) range of the instrument. Resolution of the
output is 12-bits (4096 discrete points) and the can drive up to a 400 Ohm load when the
flowmeter is ac powered. When powered by a dc supply, the load is limited by the input
voltage supplied to the instrument - See Figure 24, page 27, for allowable loop loads.
FL 4MA - Flow at 4 mA
FL 20MA - Flow at 20 mA
The FL 4MA and FL 20MA entries are used to set the span of the 4-20 mA analog output
and the frequency output on UTM10-S flowmeter versions. These entries are volumetric
rate units that are equal to the volumetric units configured as RATE UNT and RATE INT
discussed on Page 49.
Example 1 - To span the 4-20 mA output from -100 to +100 litres / minute (LPM), with
12 mA being 0 litres / minute, set the FL 4MA and FL 20MA inputs as follows:
FL 4MA = -100.0
FL 20MA = 100.0
If the flowmeter were a UTM10-S, this setting would also set the span for the frequency
output. At -100 litres / minute (LPM), the output frequency would be 0 Hz. At the maximum
flow of 100 litres / minute, the output frequency would be 1000 Hz, and in this instance a
flow of zero would be represented by an output frequency of 500 Hz.
52 IM-P197-02 MI Issue 1
Example 2 - To span the 4-20 mA output from 0 litres / minute (LPM) to +100 litres / minute,
with 12 mA being 50 litres / minute, set the FL 4MA and FL 20MA inputs as follows:
FL 4MA = 0.0
FL 20MA = 100.0
For the UTM10-S flowmeter, in this instance zero flow would be represented by 0 Hz and
4 mA. The full-scale flow or 100 litres / minute (LPM) would be 1000 Hz and 20 mA, and a
midrange flow of 50 litres / minute would be expressed as 500 Hz and 12 mA.
The 4-20 mA output is factory calibrated and should not require adjustment. If small
adjustments to the DAC (Digital to Analog Converter) are needed, for instance if adjustment
due to the accumulation of line losses from long output cable lengths are required, the
CAL 4 mA and CAL 20 MA can be used.
CAL 4 MA - 4 mA DAC calibration entry (Value)
CAL 20 MA- 20 mA DAC calibration entry (Value)
The CAL 4MA and CAL 20 MA entries allow fine adjustments to be made to the 'zero' and
full-scale of the 4-20 mA output. To adjust the outputs, an ammeter or reliable reference
connection to the 4-20 mA output must be present.
Note: Calibration of the 20 mA setting is conducted much the same way as the 4 mA
adjustments.
Note: The CAL 4MA and CAL 20MA entries should not be used in an attempt to set the
4-20 mA range. Utilize FL 4MA and FL 20MA, detailed above, for this purpose.
4 mA calibration procedure:
1) Disconnect one side of the current loop and connect the ammeter in series (disconnect
either wire at the terminals labeled 4-20 mA Out or Signal Gnd).
2) Using the arrow keys, increase the numerical value to increase the current in the loop
to 4 mA. Decrease the value to decrease the current in the loop to 4 mA. Typical values
range between 40-80 counts.
3) Reconnect the 4-20 mA output circuitry as required.
20 mA calibration procedure:
1) Disconnect one side of the current loop and connect the ammeter in series (disconnect
either wire at the terminals labeled 4-20 mA Out or Signal Gnd).
2) Using the arrow keys, increase the numerical value to increase the current in the loop to
20 mA. Decrease the value to decrease the current in the loop to 20 mA. Typical values
range between 3700-3900 counts.
3) Reconnect the 4-20 mA output circuitry as required.
IM-P197-02 MI Issue 1 53
7.7 CH2 menu - Channel 2 menu
The CH2 menu is used to configure model specific I/O options. The UTM10-S flowmeter
presents a different set of parameters than the UTM10-E flowmeter.
Channel 2 options
CH2 Menu - Channel 2 I/O options (Choice)
RTD - Input values for UTM10-E floweters (Values)
CONTROL/HZ - Output options for UTM10-S flowmeters
UTM10-E options
RTD - Calibration values (Value)
RTD1 A Calibration value for RTD1 A
RTD1 B Calibration value for RTD1 B
RTD2 A Calibration value for RTD2 A
RTD2 B Calibration value for RTD2 B
Inputs from two 1 000 Ohm platinum RTD temperature sensors allow measurements of
heating or cooling usage.
The values used to calibrate the RTD temperature sensors are derived in the laboratory
and are specific to the RTD and to the electronic circuit it is connected to. The RTDs on
new units come with the calibration values already entered into the UTM10 and should not
need to be changed.
Field replacement of RTDs is possible through the use of the keypad or the software utility.
If the RTDs were ordered from the manufacturer, they will come with calibration values that
need to be loaded into the UTM10.
New, non-calibrated RTDs will need to be field calibrated using an ice bath and boiling
water to derive calibration values. This procedure is outlined in Section 9 'Appendix'.
Table 9 RTDs
Surface mount RTDs
Maximum temperature 200°C (392°F)
URTD-C-20 Set of two:
Cable length 6 m (20 ft)
Maximum temperature 200°C (392°F)
URTD-C-50 Set of two:
Cable length 15 m (50 ft)
Maximum temperature 200°C (392°F)
URTD-C-100 Set of two:
Cable length 30 m (100 ft)
54 IM-P197-02 MI Issue 1
UTM10-S options
Two independent open collector transistor outputs are included with the UTM10-S model.
Each output can be configured independently for one of the following:
ERRORS
Alarm outputs on any error condition. See Error Table in the Appendix of this manual.
NONE
Alarm outputs disabled.
Note: The set-up options for both CONTROL 1 and CONTROL 2 follow the same menu
path. For a complete view of the menu options, see the Menu Map in Section 9 'Appendix'.
IM-P197-02 MI Issue 1 55
7.8 SEN menu - Sensor menu
The SEN MENU allows access to the various types of transducers the UTM10 can work with.
Selecting the proper transducers in conjunction with the transducer mount (XDCR MNT)
and transducer frequency (XDCR HZ) is critical to accurate operation of the flowmeter.
56 IM-P197-02 MI Issue 1
7.9 SEC menu - Security menu
The SEC MENU menu allows access to flowmeter functions that may need to be protected
from changes.
IM-P197-02 MI Issue 1 57
7.10 SER menu - Service menu
The SER MENU menu allows access to flowmeter set-up values that may need revision due
to application specific conditions and information valuable in troubleshooting.
58 IM-P197-02 MI Issue 1
SIG STR - Signal strength (Reported by Firmware)
The SIG STR value is a relative indication of the amount of ultrasound making it from the
transmitting transducer to the receiving transducer. The signal strength is a blending of
esoteric transit time measurements distilled into a usable overall reference.
The measurement of signal strength assists service personnel in troubleshooting the
UTM10 system. In general, expect the signal strength readings to be greater than 5 on a
full pipe with the transducers properly mounted. Signal strength readings that are less than
5 indicate a need to choose an alternative mounting method for the transducers or that
an improper pipe size has been entered.
Signal strength below the Low Signal Cut-off (SIG C-OF) value will generate a 0010 error
(Low Signal Strength) and require either a change in the SIG C-OF value or transducer
mounting changes.
Note: If the unit is configured to display totalizer values, the display will alternate between
ERROR 0010 and the totalizer value.
Signal strength readings in excess of 98 may indicate that a mounting method with a
longer path length may be required. For example, if transducers mounted on a 75 mm (3")
PVC pipe in V-mount cause the measured signal strength value to exceed 98, change the
mounting method to W-mount for greater stability in readings.
Because signal strength is not an 'absolute' indication of how well a UTM10 flowmeter is
functioning, there is no real advantage to a signal strength of 50 over a signal strength of 10.
When RTD is selected from the CH2 menu and RTDs are connected to the UTM10-E energy
flowmeter, the firmware will display the temperature measured by RTD 1 in°C.
When RTD is selected from the CH2 menu and RTDs are connected to the UTM10-E energy
flowmeter, the firmware will display the temperature measured by RTD 2 in°C.
When RTD is selected from the CH2 menu and RTDs are connected to the UTM10-E energy
flowmeter, the firmware will display the difference in temperature measured between RTD 1
and RTD 2 in°C.
IM-P197-02 MI Issue 1 59
SIG C-OF - Low signal cut-off (Value)
0.0 - 100.0
The SIG C-OF is used to drive the flowmeter and its outputs to the SUB FLOW (Substitute
Flow described below) state if conditions occur that cause low signal strength. A signal
strength indication below 5 is generally inadequate for measuring flow reliably, so the
minimum setting for SIG C-OF is 5. A good practice is to set the SIG C-OF at approximately
60-70% of actual measured maximum signal strength.
Note: The factory default 'Signal strength cut-off' is 5.
If the measured signal strength is lower than the SIG C-OF setting, an error 0010 will be
displayed on the UTM10 display until the measured signal strength becomes greater than
the cut-off value.
A signal strength indication below 2 is considered to be no signal at all. Verify that the
pipe is full of liquid, the pipe size and liquid parameters are entered correctly, and that the
transducers have been mounted accurately. Highly aerated liquids will also cause low signal
strength conditions.
Substitute Flow (SUB FLOW) is a value that the analog outputs and the flowrate display will
indicate when an error condition in the flowmeter occurs. The typical setting for this entry
is a value that will make the instrument display zero flow during an error condition.
Substitute flow is set as a percentage between MIN RATE and MAX RATE. In a unidirectional
system, this value is typically set to zero to indicate zero flow while in an error condition.
In a bidirectional system, the percentage can be set such that zero is displayed in a error
condition. To calculate where to set the substitute flow value in a bidirectional system,
perform the following calculation:
Table 10 lists some typical settings to achieve 'Zero' with respect to MIN RATE and
MAX RATE settings.
60 IM-P197-02 MI Issue 1
SET ZERO - Set zero flow point (Choice)
NO
YES
Because every flowmeter installation is slightly different and sound waves can travel in slightly
different ways through these various installations, it is important to remove the zero offset
at zero flow to maintain the flowmeter's accuracy. A provision is made using this entry to
establish 'Zero' flow and eliminate the offset.
Procedure:
1) The pipe must be full of liquid.
2) Flow must be absolute zero - securely close any valves and allow time for any settling
to occur.
3) Press ENTER, use the arrow ST keys to make the display read YES.
4) Press ENTER.
IM-P197-02 MI Issue 1 61
7.11 DSP menu - Display menu
The DISPLAY menu parameters control what is shown on the display and the rate at which
displayed items alternate (dwell time).
62 IM-P197-02 MI Issue 1
5QHVYCTGWVKNKV[
8.1 Introduction
In addition to or as a replacement for the keypad entry programming, the UTM10 flowmeter
can be used with a software utility. The software utility is used for configuring, calibrating
and communicating with the UTM10 family of flowmeters. Additionally, it has numerous
troubleshooting tools to make diagnosing and correcting installation problems easier.
This software has been designed to provide the UTM10 user with a powerful and convenient
way to configure calibrate and troubleshoot all UTM10 family flowmeters. A PC can be hard-
wired to a UTM10 flowmeter through a standard USB connection found on most current
computers.
8.3 Installation
1) From the Windows 'Start' button, choose the Run command. From the 'Run' dialog box,
use the Browse button to navigate to the USP_Setup.exe file and double-click.
2) The USP Setup will automatically extract and install on the hard disk. The USP icon can
then be copied to the desktop, if desired.
Note: If a previous version of this software is installed, it must be un-installed before a new
version of the software can be installed. Newer versions will 'ask' to remove the old version
and perform the task automatically. Older versions must be removed using the Microsoft
Windows® Add / Remove Programs applet.
Note: Most PCs will require a restart after a successful installation.
8.4 Initialization
1) Connect the B end of the USB A /B communications cable to the UTM10 USB
communication port and the A end to a convenient USB port on the computer.
Note: It is advisable to have the UTM10 flowmeter powered up prior to running this
software.
Note: While the USB cable is connected, the RS485 and frequency outputs are
disabled.
2) Double-click on the USP icon. The first screen is the 'RUN' mode screen (see
Figure 42), which contains real-time information regarding flowrate, totals, signal
strength, communications status, and the flowmeter's serial number. The COMM
indicator in the lower right-hand corner indicates that the serial connection is active.
If the COMM box contains a red ERROR, click on the Communications button on the
Menu bar and select Initialize. Choose the appropriate COM port and the RS232 /
USB Com Port Type. Proper communication is verified when a green OK is indicated
in the lower right-hand corner of the PC display and the 'Last Update' indicator in the
text area on the left side of the screen changes from red to an active clock indication.
IM-P197-02 MI Issue 1 63
863'HYLFH$GGU
)LOH (GLW 9LHZ &RPPXQLFDWLRQV :LQGRZ $ERXW
+LVWRULFDO'DWD
Flow: 135 Gal/Min
Totalizer Net: 237 Gal
Pos: 237 Gal
Neg: 0 Gal
Sig. Strength: 15.6%
Margin: 100%
Delta T: 2.50 ns
Last Update: 12:17:20
Reset Totalizers
)ORZ5DWH
7LPHPPVV
64 IM-P197-02 MI Issue 1
8.5 Basic tab
General
The general heading allows users to select the measurement system for UTM10 set-up,
either Metric (mm) or Imperial (inches) and choose from a number of pre-programmed
small pipe configurations in the Standard Configurations drop-down. If pipe measurements
are to be entered in mm, select Metric. If the General entries are altered from those at
instrument start-up, then click on the Download button in the lower right-hand portion of
the screen and cycle power to the UTM10.
When using the Standard Configurations drop-down menu alternate, menu choices can be
made by using the following guidelines:
1) Select the transducer type and pipe size for the transducer to be used. The firmware
will automatically enter the appropriate values for that pipe size and type. Every entry
parameter except for Units, MODBUS Address, Standard Configurations, Frequency,
Flow Direction, and Specific Heat Capacity will be unavailable behind a 'grayed out'
entry box.
2) Go back to the Standard Configurations drop-down menu and select Custom. As soon
as Custom is chosen, the previously grayed out selections will become available for
editing.
3) Make any changes to the Basic configuration deemed necessary and press Download.
4) To ensure that the configuration changes take effect, turn the power off and then back
on again to the transmitter.
Also under the General heading is a field for entering a MODBUS Address. If the UTM10 is
to be used on a multi-drop RS485 network, it must be assigned a unique numerical address.
This box allows that unique address to be chosen.
Note: This address does not set the Modbus TCP / IP, EtherNet / IP™, BACnet® address.
That is set via the web page interface that is integrated into the Ethernet port.
Note: Do not confuse the MODBUS Address with the 'Device Address' as seen in the upper
left-hand corner of the display. The Device Addr is included for purposes of backward
compatibility of first generation UTM10 products. The Device Addr has no function and will
not change when used with a UTM10.
Transducer
Transducer Type selects the transducer that will be connected to the UTM10 flowmeter.
Select the appropriate transducer type from the drop-down list. This selection influences
transducer spacing and flowmeter performance, so it must be correct. If you are unsure
about the type of transducer to which the UTM10 will be connected, consult the shipment
packing list or call the manufacturer for assistance.
Note: A change of Transducer Type will cause a System Configuration Error (1002: Sys
Config Changed) to occur. This error will clear when the microprocessor is reset or power
is cycled on the flowmeter.
IM-P197-02 MI Issue 1 65
Transducer Mount selects the orientation of the transducers on the piping system - See
Section 4 'Transducer installation' and Table 2, page 14, for detailed information regarding
transducer mounting modes for particular pipe and liquid characteristics. Whenever
Transducer Mount is changed, a download command and subsequent microprocessor reset
or flowmeter power cycle must be conducted.
6\VWHP&RQILJXUDWLRQ
Basic Flow
Basic Flow Filtering Output Security Display
General
MODBUS Address:
Transducer
Mount: = Spacing: LQ
Type: 6WDQGDUG0+= Frequency: 0+] Flow Direction: )RUZDUG
Pipe
Sound Speed: FPS Roughness:
Liner
Sound Speed: FPS Roughness:
Material: 1RQH Thickness: in
Fluid
Sound Speed: FPS Abs. Viscosity: cp
Type: 2WKHU Spec. Gravity: Spec. Heat Capacity:
Transducer Frequency permits the UTM10 to select a transmission frequency for the various
types of transducers that can be utilized. In general, the larger the pipe the slower the
transmission frequency needs to be to attain a good signal.
66 IM-P197-02 MI Issue 1
Transducer spacings
Transducer spacing is a value calculated by the UTM10 firmware that takes into account pipe,
liquid, transducer and mounting information. This spacing will adapt as these parameters
are modified. If Metric was chosen as your choice of units the spacing will be given in
millimetres. This value is the lineal distance that must be between the transducer alignment
marks. Selection of the proper transducer mounting method is not entirely predictable and
many times is an iterative process.
Note: This setting only applies to UTT10-050S, UTT10-050L and UTT10-050H transducers.
Pipe material
Pipe material is selected from the pull-down list. If the pipe material utilized is not found in
the list, select Other and enter the actual pipe material Sound Speed and Roughness (much
of this information is available at web sites such as www.ondacorp.com/tecref_acoustictable.
html) for pipe relative roughness calculations.
Liner material
Liner material is selected from the pull-down list. If the pipe liner material utilized is not
included in the list, select Other and enter liner material Sound Speed and Roughness (much
of this information is available at web sites such as www.ondacorp.com/tecref_acoustictable.
html). See Page 44 for pipe liner relative roughness calculations.
Fluid type
Fluid type is selected from a pull-down list. If the liquid is not found in the list, select Other
and enter the liquid Sound Speed and Absolute Viscosity into the appropriate boxes.
The liquid's Specific Gravity is required if mass measurements are to be made, and the
Specific Heat Capacity is required for energy measurements.
Totalizer Units are selected from drop-down lists. Select an appropriate totalizer unit and
totalizer exponent. The totalizer exponents are in scientific notation and permit the eight
digit totalizer to accumulate very large values before the totalizer 'rolls over' and starts
again at zero. Table 8 illustrates the scientific notation values and their respective decimal
equivalents.
IM-P197-02 MI Issue 1 67
6\VWHP&RQILJXUDWLRQ
Min Flow is the minimum volumetric flowrate setting entered to establish filtering parameters.
Volumetric entries will be in the flowrate units. For unidirectional measurements, set Min
Flow to zero. For bidirectional measurements, set Min Flow to the highest negative (reverse)
flowrate expected in the piping system.
Max Flow is the maximum volumetric flowrate setting entered to establish filtering
parameters. Volumetric entries will be in the flowrate units. For unidirectional measurements,
set Max Flow to the highest (positive) flowrate expected in the piping system. For bidirectional
measurements, set Max Flow to the highest (positive) flowrate expected in the piping system.
Low Flow Cut-off is provided to allow very low flowrates (that can be present when pumps
are off and valves are closed) to be displayed as zero flow. Typical values that should be
entered are between 1.0% and 5.0% of the flow range between Min Flow and Max Flow.
Low Signal Cut-off is used to drive the flowmeter and its outputs to the value specified
in the Substitute Flow field when conditions occur that cause low signal strength. A signal
strength indication below 5 is generally inadequate for measuring flow reliably, so generally
the minimum setting for Low Signal Cut-off is 5. A good practice is to set the Low Signal
Cut-off at approximately 60-70% of actual measured maximum signal strength.
68 IM-P197-02 MI Issue 1
If the measured signal strength is lower than the Low Signal Cut-off setting, a 'Signal Strength
too Low' highlighted in red will become visible in the text area to the left in the Data Display
screen until the measured signal strength becomes greater than the cut-off value.
Signal strength indication below 2 is considered to be no signal at all. Verify that the pipe
is full of liquid, the pipe size and liquid parameters are entered correctly, and that the
transducers have been mounted accurately. Highly aerated liquids will also cause low signal
strength conditions.
Substitute Flow is a value that the analog outputs and the flowrate display will indicate when
an error condition in the flowmeter occurs. The typical setting for this entry is a value that
will make the instrument display zero flow during an error condition.
Substitute Flow is set as a percentage between Min Flow and Max Flow. In a unidirectional
system, this value is typically set to zero to indicate zero flow while in an error condition.
In a bidirectional system, the percentage can be set such that zero is displayed in an error
condition. To calculate where to set the Substitute Flow value in a bidirectional system,
perform the following operation:
Entry of data in the Basic and Flow tabs is all that is required to provide flow measurement
functions to the flowmeter. If the user is not going to utilize input / output functions, click
on the Download button to transfer the configuration to the UTM10 instrument. When the
configuration has been completely downloaded, turn the power to the flowmeter off and
then on again to guarantee the changes take effect.
IM-P197-02 MI Issue 1 69
8.7 Filtering tab
The Filtering tab contains several filter settings for the UTM10 flowmeter. These filters can
be adjusted to match response times and data 'smoothing' performance to a particular
application.
6\VWHP&RQILJXUDWLRQ
Time Domain Filter (range 1-256) adjusts the number of raw data sets (the wave forms viewed
on the software Diagnostics Screen) that are averaged together. Increasing this value will
provide greater damping of the data and slow the response time of the flowmeter. Conversely,
lowering this value will decrease the response time of the meter to changes in flow / energy
rate. This filter is not adaptive, it is operational to the value set at all times.
Note: The UTM10 completes a measurement in approximately 350 - 400 milliseconds. The
exact time is pipe size dependent.
Short Pulse Duration is a function used on pipes larger than 200 mm (8"). The Short Pulse is
utilized by the UTM10 to measure course transmit-time delays on larger pipes, which permits
the flowmeter to operate without having the DSP chip run an excess of fine transmit delay
correlations. The result is that the flowmeter's processing time is used more efficiently. If
the flowmeter did not operate with a course transmit-time delay, the flowmeter would be
forced to run unnecessary cross correlation calculations and the data throughput per second
would be radically reduced. Without the Short Pulse feature the potential for peak-hopping
would also be greatly increased.
70 IM-P197-02 MI Issue 1
A shorter pulse than the standard pulse loaded through the Strategy window determined
by the Short Pulse setting or calculated automatically is transmitted periodically during the
measurement cycle. This pulse is suitable for measuring course transit-time, but does not
have enough resolution to display flow. When the pipe is small, the potential for peak-hopping
is reduced to zero, because difference time never gets to be greater than 180° of phase
shift or 2 MHz (250 ns) or 1 MHz (500 ns), so course transit-time delays are not required.
The Short Pulse function does not operate until the combination of fluid velocity, transducer
mounting method and pipe size warrant, and this is typically if a delta T time in excess of
1 MHz (500 ns) is anticipated. (The software determines this possibility from the pipe size
and flowrates that are entered by the user.)
Note: There are some very, very rare occasions that the Short Pulse value would need to
be manipulated, but generally just changing the transmitted wave forms through the use of
'Strategies' works better than altering the Short Pulse numbers.
Flow Filter (Damping) establishes a maximum adaptive filter value. Under stable flow
conditions (flow that varies less than the Flow Filter Hysteresis entry), this adaptive filter
will increase the number of successive flow readings that are averaged together up to this
maximum value. If flow changes outside of the Flow Filter Hysteresis window, the filter adapts
by decreasing the number of averaged readings and allows the flowmeter to react faster.
The damping value is increased to increase stability of the flowrate readings. Damping values
are decreased to allow the flowmeter to react faster to changing flowrates. The factory
settings are suitable for most installations. Increasing this value tends to provide smoother
steady-state flow readings and outputs.
Flow Filter Hysteresis creates a window around the average flow measurement reading
allowing small variations in flow without changing the damping value. If the flow varies within
that hysteresis window, greater display damping will occur up to the maximum values set
by the Flow Filter (Damping) entry. The filter also establishes a flowrate window where
measurements outside of the window are examined by the Bad Data Rejection filter. The
value is entered as a percentage of actual flowrate.
For example, if the average flowrate is 100 litres / minute (LPM) and the Flow Filter Hysteresis
is set to 5%, a filter window of 95 - 105 litres / minute (LPM) is established. Successive
flow measurements that are measured within that window are recorded and averaged in
accordance with the Flow Filter Damping setting. Flow readings outside of the window are
held up in accordance with the Bad Data Rejection filter.
Flow Filter MinHysteresis sets a minimum hysteresis window that is invoked at sub
0.08 metres/second 'MPS' (0.25 feet/second 'FPS') flowrates, where the 'of rate' Flow Filter
Hysteresis is very small and ineffective. This value is entered in pico-seconds ( sec) and is
differential time. If very small fluid velocities are to be measured, increasing the Flow Filter
MinHysteresis value can increase reading stability.
Flow Filter Sensitivity allows configuration of how fast the Flow Filter Damping will
adapt in the positive direction. Increasing this value allows greater damping to occur faster
than lower values. Adaptation in the negative direction is not user adjustable.
IM-P197-02 MI Issue 1 71
Bad Data Rejection is a value related to the number of successive readings that must be
measured outside of the Flow Filter Hysteresis or Flow Filter MinHysteresis windows before
the flowmeter will use that flow value. Larger values are entered into Bad Data Rejection when
measuring liquids that contain gas bubbles, as the gas bubbles tend to disturb the ultrasonic
signals and cause more extraneous flow readings to occur. Larger Bad Data Rejection values
tend to make the flow meter more sluggish to rapid changes in actual flowrate.
6\VWHP&RQILJXUDWLRQ
Control 1
Flow at 4mA / 0Hz: Gal/M
Mode: )ORZ
Flow at 20mA / 1KHz: Gal/M
Off < Gal/M
Test
7HVW
72 IM-P197-02 MI Issue 1
8.9 Channel 1 - 4-20 mA configuration
Note: The 4-20 mA Output Menu applies to all UTM10 versions and is the only output
choice for Channel 1.
The Channel 1 menu controls how the 4-20 mA output is spanned for all UTM10 models and
how the frequency output is spanned for the UTM10-S flow model.
The Flow at 4 mA / 0 Hz and Flow at 20 mA / 1000 Hz settings are used to set the span for
both the 4-20 mA output and the 0 - 1000 Hz frequency output on the UTM10-S flowmeter
versions.
The 4-20 mA output is internally powered (current sourcing) and can span negative to
positive flow/energy rates. This output interfaces with virtually all recording and logging
systems by transmitting an analog current that is proportional to system flowrate.
Independent 4 mA and 20 mA span settings are established in firmware using the flow
measuring range entries. These entries can be set anywhere in the -12 to +12 metres/
second 'MPS' (-40 to +40 feet/second 'FPS') range of the instrument. Resolution of the
output is 12-bits (4096 discrete points) and can drive up to a 400 Ohm load when the
flowmeter is ac powered. When powered by a dc supply, the load is limited by the input
voltage supplied to the instrument. See Figure 24, page 27, for allowable loop loads.
Flow at 4 mA / 0 Hz
Flow at 20 mA / 1000 Hz
The Flow at 4 mA / 0 Hz and Flow at 20 mA / 1000 Hz entries are used to set the span of the
4-20 mA analog output and the frequency output on UTM10-S flowmeter versions. These
entries are volumetric rate units that are equal to the volumetric units configured as rate
units and rate interval discussed on Page 49.
Example 1 - To span the 4-20 mA output from -100 litres / minute 'GPM' to +100 litres / minute
'LPM' with 12 mA being 0 litres / minute 'LPM', set the Flow at 4 mA / 0 Hz and Flow at
20 mA / 1000 Hz inputs as follows:
Flow at 4 mA / 0 Hz = -100.0
Flow at 20 mA / 1 000 Hz = 100.0
If the flowmeter were a UTM10-S, this setting would also set the span for the frequency
output. At -100 litres / minute 'LPM', the output frequency would be 0 Hz. At the maximum
flow of 100 litres / minute 'LPM', the output frequency would be 1000 Hz, and in this instance
a flow of zero would be represented by an output frequency of 500 Hz.
Example 2 - To span the 4-20 mA output from 0 litres / minute 'LPM' to +100 litres / minute
'LPM' with 12 mA being 50 litres / minute 'LPM', set the Flow at 4 mA / 0 Hz and Flow at
20 mA / 1000 Hz inputs as follows:
Flow at 4 mA / 0 Hz = 0.0
Flow at 20 mA / 1 000 Hz = 100.0
For the UTM10-S flowmeter, in this instance, zero flow would be represented by 0 Hz and
4 mA.
The full-scale flow or 100 litres / minute 'LPM' would be 1000 Hz and 20 mA and a midrange
flow of 50 litres / minute 'LPM' would be expressed as 500 Hz and 12 mA
IM-P197-02 MI Issue 1 73
The 4-20 mA output is factory calibrated and should not require adjustment. If small
adjustments to the DAC (Digital to Analog Converter) are needed, for instance if adjustments
due to the accumulation of line losses from long output cable lengths are required, the
Calibration 4 mA and Calibration 20 mA can be used.
Calibration 4 mA - 4 mA DAC calibration entry (Value)
Calibration 20 mA- 20 mA DAC calibration entry (Value)
The Calibration 4 mA and Calibration 20 mA entries allows fine adjustments to be made to
the 'zero' and full-scale of the 4-20 mA output. To adjust the outputs, an ammeter or reliable
reference connection to the 4-20 mA output must be present.
Note: Calibration of the 20 mA setting is conducted much the same way as the 4 mA
adjustments.
Note: The Calibration 4 mA and Calibration 20 mA entries should not be used in an attempt
to set the 4 - 20 mA range. Utilize Flow at 4 mA / 0 Hz and Flow at 20 mA / 1 000 Hz detailed
above for this purpose.
4 mA calibration procedure:
1) Disconnect one side of the current loop and connect the ammeter in series (disconnect
either wire at the terminals labeled 4-20 mA Out or Signal Gnd).
2) Using the arrow keys, increase the numerical value to increase the current in the loop
to 4 mA. Decrease the value to decrease the current in the loop to 4 mA. Typical values
range between 40 - 80 counts.
3) Reconnect the 4 - 20 mA output circuitry as required.
20 mA calibration procedure:
1) Disconnect one side of the current loop and connect the ammeter in series (disconnect
either wire at the terminals labeled 4 - 20 mA Out or Signal Gnd).
2) Using the arrow keys, increase the numerical value to increase the current in the loop to
20 mA. Decrease the value to decrease the current in the loop to 20 mA. Typical values
range between 3700 - 3900 counts.
3) Reconnect the 4 - 20 mA output circuitry as required.
4 - 20 Test - 4 - 20 mA output test (Value)
Allows a simulated flow value to be sent from the 4-20 mA output. By incrementing this
value, the 4-20 mA output will transmit the indicated current value.
74 IM-P197-02 MI Issue 1
Inputs from two 1 000 Ohm platinum RTD temperature sensors allow the measurement of
energy delivered in liquid heating and cooling systems.
The values used to calibrate the RTD temperature sensors are derived in the laboratory
and are specific to a specific RTD. The RTDs on new units come with the calibration values
already entered into the UTM10 and should not need to be changed.
Field replacement of RTDs is possible through the use of the keypad or the software. If the
RTDs were ordered from the manufacturer, they will come with calibration values that need
to be loaded into the UTM10.
6\VWHP&RQILJXUDWLRQ
Calibration/Test
Calibration
P$ RTD #2:
P$
A: B: &DOLEUDWH
Test
7HVW
New, non-calibrated RTDs will need to be field calibrated using an ice bath and boiling
water to derive calibration values. This procedure is outlined in Section 9 'Appendix'.
IM-P197-02 MI Issue 1 75
8.11 Channel 2 - Control output configuration UTM10-S only
Two independent open collector transistor outputs are included with the UTM10-S
flowmeter. Each output can be configured independently to 'Alarm' for one of the following.
See Alarm Output in Section 5.
None
Batch / Total
Flow
Signal Strength
Errors
6\VWHP&RQILJXUDWLRQ
Control 1
Flow at 4mA / 0Hz: Gal/M
Mode: )ORZ
Flow at 20mA / 1KHz: Gal/M
%DWFK7RWDO
Off <
)ORZ Gal/M
6LJ6WUHQJWK
Calibration/Test (UURUV
On> Gal/M
Calibration
P$ Control 2
None
All alarm outputs are disabled.
Batch / Total
Multiplier (Value)
This is the value to which the totalizer will accumulate before resetting to zero and
repeating the accumulation. This value includes any exponents that were entered in
the BSC MENU as TOTAL E - See Alarm Output in Section 5.
Control 1
Mode: %DWFK7RWDO
Multiplier:
76 IM-P197-02 MI Issue 1
Flow
ON (Value)
Sets value at which the alarm output will switch from OFF to ON.
OFF (Value)
Sets value at which the alarm output will switch from ON to OFF.
Control 1
Mode: )ORZ
Signal strength
ON (Value)
Sets value at which the alarm output will turn ON.
OFF (Value)
Sets value at which the alarm output will turn OFF.
Control 1
Mode: 6LJ6WUHQJWK
Off <
On>
Errors
Alarm outputs on any error condition - See the Error Table in Section 9 'Appendix'.
IM-P197-02 MI Issue 1 77
8.12 Setting zero and calibration
The software utility contains a powerful multi-point calibration routine
that can be used to calibrate the UTM10 flowmeter to a primary
&DOLEUDWLRQ
measuring standard in a particular installation. To initialize the three-
step calibration routine, click on the Calibration button located on the
top of the Data Screen. The display shown in Figure 47 will appear.
0DNHVXUHIORZLVDW]HUR
:DLWIRUIORZWRVWDELOL]H
3UHVV6HW!WRFDOLEUDWHWKH]HURRIIVHW
Step 1 - The first screen (Page 1 of 3), establishes a baseline zero flowrate measurement
for the instrument.
Because every flowmeter installation is slightly different and sound waves can travel in
slightly different ways through these various installations, it is important to remove the zero
offset at zero flow to maintain the flowmeters accuracy. A provision is made using this entry
to establish 'Zero' flow and eliminate the offset.
To zero the flowmeter:
1) Establish zero flow in the pipe (ensure that the pipe is full of fluid, turn off all pumps, and
close a dead-heading valve). Wait until the delta-time interval shown in 'Current Delta T'
is stable (and typically very close to zero).
2) Click the Set button.
3) Click the Next button when prompted, then click the Finish button on the calibration
screen.
The zeroing process is essential in systems using the UTM10-015S to UTM10-040S
transducer sets to ensure the best accuracy.
78 IM-P197-02 MI Issue 1
Step 2 - (Page 2 of 3) in the calibration process is the selection of the engineering units
with which the calibration will be performed. Select the Flowrate Units and click the Next
button at the bottom of the window.
,WLVDGYLVDEOHWR)LOH6DYHWKHH[LVWLQJFDOLEUDWLRQEHIRUHPRGLI\LQJLW,IWKH)ORZ5DWH8QLWVVHOHFWHGRQWKLVSDJHGRQRW
PDWFKWKH)ORZ5DWH8QLWVXWLOL]HGIRUWKHH[LVWLQJGDWDSRLQWVFROOHFWHGRQ3DJHRIIORZPHDVXUHPHQWHUURUVFDQRFFXU
7RYLHZPHDVXUHPHQWXQLWVJRWR3DJHRIDQGSUHVV(GLW7KH&DOLEUDWLRQ3RLQWV(GLWRUZLOOVKRZZKDWXQLWV
ZHUHXVHGGXULQJWKHH[LVWLQJFDOLEUDWLRQ
,IQRGDWDH[LVWVLQWKHHGLWRUVHOHFWLRQRI)ORZ5DWH8QLWVZLOOQRWLQIOXHQFHPHDVXUHPHQWV
,IQHZFDOLEUDWLRQSRLQWVDUHWREHHQWHUHGRQ3DJHRILWLVDGYLVDEOHWRUHPRYHWKHH[LVWLQJFDOLEUDWLRQ
SRLQWVXVLQJWKH&DOLEUDWLRQ3RLQWV(GLWRU
IM-P197-02 MI Issue 1 79
Step 3 - (Page 3 of 3) as shown in Figure 49 allows multiple actual flowrates to be
recorded by the UTM10. To calibrate a point, establish a stable, known flowrate (verified
by a real-time primary flow instrument), enter the actual flowrate in the cell as shown in
Figure 49 and click the Set button. Repeat for as many points as desired.
Note: If only two points are to be used (zero and span), it is preferable to use the highest
flowrate anticipated in normal operation as the calibration point. If an erroneous data point
is collected, the point can be removed by pressing the Edit button, selecting the bad point
and then selecting Remove.
3OHDVHHVWDEOLVKD
UHIHUHQFHIORZUDWH
)360360LQLPXP
(QWHUWKHUHIHUHQFHIORZUDWH
EHORZ'RQRWHQWHU
:DLWIRUIORZWRVWDEOL]H
Gal/MIN
3UHVVWKH6HWEXWWRQ
)ORZ
(GLW
Zero values are not valid for linearization entries. Flowmeter zero is entered on Page 1 of 3.
If a zero calibration point is attempted, the following error message will be shown:
863
9DOXHFDQQRWEH
! 7KLVYDOXHZDVDOUHDG\VHWLQDSUHYLRXVVFUHHQ3DJHRI
2.
Press the Finish button when all points have been entered.
80 IM-P197-02 MI Issue 1
8.13 Target Dbg data screen - Definitions
1) Calc count - The number of flow calculations 7DUJHW'EJ'DWD
performed by the flowmeter beginning at the
'HYLFH7\SH
time the power to the flowmeter was last turned
off and then on again. &DOF&RXQW 1 &36 2
5DZ'HOWD7QV 3 4
2) Sample count - The number of samples
currently being taken in one second. *DLQ 5 6
7['HOD\ 7
3) Raw delta T ( s) - The actual amount of time it
takes for an ultrasonic pulse to cross the pipe. )ORZ)LOWHU 8
660LQ0D[ 9 2. 10
4) Course delta T
6RXQG6SHHG 11
5) Gain - The amount of signal amplification
applied to the reflected ultrasound pulse 5H\QROGV 12 13
to make it readable by the digital signal
processor.
Fig. 50 5HVHW
6) Gain setting / waveform power - The first
number is the gain setting on the digital pot
(automatically controlled by the AGC circuit). Valid numbers are from 1 to 100. The second
number is the power factor of the current waveform being used. For example, '8' indicates
that a 1/8 power wave form is being used.
7) Tx delay - The amount of time the transmitting transducer waits for the receiving
transducer to recognize an ultrasound signal before the transmitter initiates another
measurement cycle.
8) Flow filter - The current value of the adaptive filter.
9) SS (Min/Max) - The minimum and maximum signal strength levels encountered by the
flowmeter beginning at the time the power to the flowmeter was last turned off and then on
again.
10) Signal strength state - Indicates if the present signal strength minimum and maximum
are within a pre-programed signal strength window.
11) Sound speed - The actual sound speed being measured by the transducers at that moment.
12) Reynolds - A number indicating how turbulent a fluid is. Reynolds numbers between
0 and 2000 are considered laminar flow. Numbers between 2000 and 4000 are in transition
between laminar and turbulent flows and numbers greater than 4000 indicate turbulent flow.
13) Reynolds factor - The value applied to the flow calculation to correct for variations in
Reynolds numbers.
IM-P197-02 MI Issue 1 81
82
9.1.1 System
Liquid types Most clean liquids or liquids containing small amounts of suspended solids or gas bubbles.
Velocity range Bidirectional to greater than 12 metres / second (40 feet / second)
Option 1:
0 to +50°C (+32 to +122°F); Absolute 0.12°C (0.22°F) Difference 0.05°C (0.09°F).
Option 2:
#RRGPFKZ
Temperature accuracy 0 to +100°C (+32 to +212°F); Absolute 0.25°C (0.45°F) Difference 0.10°C (0.18°F).
(Energy flowmeters only) Option 3:
-40 to +177°C (-40 to +350°F); Absolute 0.60°C (1.10°F) Difference 0.25°C (0.45°F).
Option 4:
-20 to +30°C (-4 to to +86°F); Absolute 0.12°C (0.22°F) Difference 0.05°C (0.09°F).
Option 1: Option 2:
0.012°C (0.03°F). 0.025°C (0.05°F).
Temperature sensitivity
Option 3: Option 4:
0.06°C (0.1°F). 0.012°C (0.03°F).
IM-P197-02 MI Issue 1
9.1.2 Transducers
Liquid types Most non-aerated, clean liquids.
Cable length Up to 300 meters (990 ft) Standard lengths 6, 15, 30 meters (20, 50, 100 ft).
UTT10-050S and UTT10-050H: 50 mm (2") and larger
Pipe sizes UTT10-050L: 600 mm (24") and larger.
UTT10-015S to UTT10-040S: (Small pipe) 15 mm to 40 mm (½" to 1½") (ASME pipe, copper tube, tube).
IM-P197-02 MI Issue 1
Environment IP 67.
Pipe surface UTT10-050S, UTT10-050L and UTT10-015S to UTT10-040S: -40°C to +121°C (-40°F to +250°F).
temperature UTT10-050H: -40°C to +177°C (-40°F to +350°F).
Ambient
-40°C to +85°C (-40°F to +185°F), 0 to 95% relative humidity (non-condensing).
conditions
UTT10-050S, UTT10-050L and UTT10-015S to UTT10-040S: CPVC, Ultem®, and nylon cord grip, PVC cable
Housing
jacket.
material
UTT10-050H: PTFE, Vespel®, and nickel-plated brass cord grip, PFA cable jacket.
Standard: None.
Optional - UTT10-050S only: CSA Class ,, Div 1, Groups C & D; Requires intrinsically safe transducer kit
with barrier.
UL 1604: Electrical Equipment for Use in Class , and ,,, Division 2, and Class III Hazardous (Classified)
Approvals Locations.
CSA C22.2 No. 213: Non-Incendive Electrical Equipment for Use in Class ,, Division 2 Hazardous Locations.
EN 60079-0: Electrical Apparatus for Explosive Gas Atmospheres Part 0: General Requirements.
EN60079-15: Electrical Apparatus for Explosive Gas Atmospheres Part 15: Electrical Apparatus with Type of
Protection 'n'.
83
84
9.1.4 Transmitter
ac: 95-264 Vac 47-63 Hz at 17 VA Maximum.
20-28 Vac 47-63 Hz at 17 VA Maximum.
dc: 10-28 VDC at 5.0 W.
Power requirements
Protection: Reverse polarity and transient suppression.
ac: Field replaceable fuse.
dc: Auto resettable fuse.
General Safety: UL 61010-1, CSA C22.2 No. 61010-1 and EN 61010-1.
Hazardous Location: Class , Division 2 Groups C,D; Class ,, and ,,,, Division 2, Groups C, D, F,
Installation compliance and G for US/CAN; Class I, Zone 2, AEx nA IIB T6; ATEX II 2 G EEx nA II T6: UL 1604, CSA 22.2
No. 213, EN 60079-0 and EN 60079-15.
CE: EN61326-1:2006 on integral flow transducers or remote transducers with conduit.
2 line LCD, LED backlight.
Top Row: 7 segment, 18 mm (0.7") high, numeric.
Display Bottom Row: 14 segment, 9 mm (0.35") high alpha-numeric.
Flowrate Indication: 8 digit positive, 7 digit negative max.; auto decimal, lead zero blanking.
Flow totalizer: 8 digit positive, 7 digit negative. Reset via software, keypad, contact closure.
Gal, Litres, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquor barrels (31.5 gal), ft, m, lb, kg.
Rate
Additional units for Energy version BTU, MBTU, MMBTU, Ton.
Gal, Litres, million gal, ft³, m³, acre-ft, oil barrels (42 gal), liquor barrels (31.5 gal), lb, kg.
Totalizer
Additional units for Energy version BTU, MBTU, MMBTU, Ton.
Input / output
All modules optically isolated from earth and system ground.
(all transmitters)
4-20 mA 12-bit resolution, internal power (current source). Can span negative to positive flow/energy rates.
IM-P197-02 MI Issue 1
9.1.4 Transmitter (continued)
USB 2.0 for connection of a PC. (Requires USB A/B interface cable).
10/100 Base-T RJ45 communications via Modbus TCP / IP, Ethernet™ and BACnet® / IP.
IM-P197-02 MI Issue 1
Rate Pulse: Open collector, 0 to 1 000 Hz maximum; 12 bit resolution,1.0 A max. Can span
negative to positive rates. Square-wave or simulated turbine output.
Input / output
[UTM10-S transmitter]
Alarm Outputs (2): Open collector, configure as Error alarm, Rate alarm, Signal Strength alarm, or
Total / Batch pulse.
Ambient conditions -40°C to +85°C (-40°F to +185°F), 0 to 95% relative humidity (non-condensing).
Type:
Wall: Nickel-plated steel mounting brackets.
Integral transducer: Clamped around pipe.
Transmitter mounting
Conduit holes:
2 holes x ½" NPT Female
1 hole x ¾" NPT Female
Response time (Flow) 0.3 to 30 seconds, user configured, for 10% to 90% step change in flow.
85
9.2 Menu map
Primary Secondary Tertiary Quaternary
Page 91
BASIC MENU
86 IM-P197-02 MI Issue 1
Page 88
IM-P197-02 MI Issue 1 87
Primary Secondary Tertiary Quaternary
Page 87
CHANNEL 1 MENU
FL 4MA RTD
FL 20MA CONTROL/HZ
CAL 4MA
CAL 20MA
4-20 TST
ON (Value) .K
OFF (Value) .%%
88 IM-P197-02 MI Issue 1
Page 90
The Channel 2 menu allows the conguration of meter specific I/O parameters RTD values
are specific to a particular RTD.
The menu structure and programming are identical for both Control 1 and Control 2, but
the choice of function for a specific control output is independent of the other.
RTD1 A 13#
RTD1 B 13#!
RTD2 A 13#!
RTD2 B 13#!
CONTROL 1 ".-31.+
CONTROL 2 ".-31.+
Signal strength
ON (Value) .K
OFF (Value) .%%
IM-P197-02 MI Issue 1 89
Page 89
SENSOR MENU SECURITY MENU
90 IM-P197-02 MI Issue 1
Page 86
SERVICE MENU DISPLAY MENU
Temperature 1 QBJM
Temperature 2 QBJM
Temperature difference QBJMAFCC
Totalising mode
Low signal cut-off PFD@- LC
Substitute flow PR?CILT Net -BQ
Set zero PBQWBOL Positive MLP
Default zero A- CIQL Negative KBD
Correction factor @LOCQO Batch ?>Q@E
Batch multiplier
BTCH MUL (1-32,000)
IM-P197-02 MI Issue 1 91
9.3 Communications protocols
9.3.1 UTM10 MODBUS
Each Modbus Holding Register represents a 16-bit integer value (2 bytes). The official
Modbus standard defines Modbus as a 'big-endian' protocol where the most significant
byte of a 16-bit value is sent before the least significant byte. For example, the 16-bit hex
value of '1234' is transferred as '12' '34'.
Beyond 16-bit values, the protocol itself does not specify how 32-bit (or larger) numbers
that span over multiple registers should be handled. It is very common to transfer 32-bit
values as pairs of two consecutive 16-bit registers in little-endian word order. For example,
the 32-bit hex value of '12345678' is transferred as '56' '78' '12' '34'. Notice the Register
Bytes are still sent in big-endian order per the Modbus protocol, but the Registers are sent
in little-endian order.
Other manufacturers, store and transfer the Modbus Registers in big-endian word order.
For example, the 32-bit hex value of '12345678' is transferred as '12' '34' '56' '78'. It doesn't
matter which order the words are sent, as long as the receiving device knows which way
to expect it. Since it's a common problem between devices regarding word order, many
Modbus master devices have a configuration setting for interpreting data (over multiple
registers) as 'little-endian' or 'big-endian' word order. This is also referred to as swapped
or word swapped values and allows the master device to work with slave devices from
different manufacturers.
If, however, the endianness is not a configurable option within the Modbus master device,
it's important to make sure it matches the slave endianess for proper data interpretation.
The UTM10 actually provides two Modbus Register maps to accommodate both formats.
This is useful in applications where the Modbus Master cannot be configured for endianness.
Communication settings
Baud rate 9600
Parity None
Data bits 8
Stop bits 1
Handshaking None
92 IM-P197-02 MI Issue 1
Table 14 UTM10 Modbus register map
for 'Little-endian' word order master devices
For reference: If the UTM10 Net Totalizer = 12345678 hex
Register 40102 would contain 5678 hex (word low)
Register 40103 would contain 1234 hex (word high)
MODBUS registers
Data Long integer Floating point Available
component format Single Double units
name precision Precision
format format
Signal strength 40100 - 40101 40200 - 40201 40300 - 40303
Flowrate 40102 - 40103 40202 - 40203 40304 - 40307 Gallons, Litres,
Net totalizer 40104 - 40105 40204 - 40205 40308 - 40311 MGallons, Cubic
Positive totalizer 40106 - 40107 40206 - 40207 40312 - 40315 Feet, Cubic
Metres, Acre
Feet, Oil Barrel,
Liquid Barrel,
Negative Feet, Metres, Lb,
40108 - 40109 40208 - 40209 40316 - 40319 Kg, BTU, MBTU,
totalizer
MMBTU, TON Per
Second, Minute,
Hour, Day
Temperature 1 40110 - 40111 40210 - 40211 40320 - 40323 ºC
Temperature 2 40112 - 40113 40212 - 40213 40324 - 40327 ºC
IM-P197-02 MI Issue 1 93
Table 16 Modbus coil map
Modbus coil
Modbus coil Notes
description
Forcing this coil on will reset all totalizers.
Reset totalizers 1 After reset, the coil automatically returns
to the off state.
Writing an (1)
active state
to this object
Reset totalizers BO1 will reset all
totalizers. The
Object will then
automatically
return to the (0)
inactive state.
94 IM-P197-02 MI Issue 1
9.3.3 Network settings: 9.3.4 Diagnostics web page
IP address, IP subnet, IP gateway, and The Diagnostics web page refreshes itself
Device Description are configured through every 5 seconds and provides real time data
the web interface. IP address and subnet from the flowmeter.
defaults to 192.168.0.100 and 255.255.255.0.
Connection to the web interface requires Diagnostics
an Ethernet crossover cable, power to the Main page
flowmeter, and a PC with a web browser.
Typing http://192.168.0.100 in the address
bar will allow connection to the flowmeter's Device values
web interface for editing. Signal strength 22.8
Note: Changing the IP address will require Flowrate 100.4
use of the new number when trying to Net totalizer 1659.1
access the web page. Each meter must be
setup with a unique IP address when trying Positive totalizer 1659.1
to network multiple units. Negative totalizer 0.0
Temp 1 26.5
UTM10 flowmeter
Ultrasonic f lowmeter Temp 2 48.7
DEVICE NAME
/RFDWLRQ 5HVHW7RWDOL]HUV
(QWHUORFDWLRQLQIRUPDWLRQKHUH
Main page
(GLW
1HWZRUN6HWWLQJV
,3$GGUHVV
6XEQHW0DVN
*DWHZD\,3$GGUHVV
(GLW
1HWZRUN6WDWXV
0$&$GGUHVV '
6RIWZDUH5HYLVLRQ
/LQN'XSOH[ )8//
/LQN6SHHG 0%36
3DVVZRUGV
8VHU1DPH $FFHVV/HYHO
9LHZHU $FFHVVWR'HYLFH9DOXHV
$FFHVVWR'HYLFH9DOXHVDQG
8VHU
5HVHWWLQJ7RWDOL]HUV
$FFHVVWR'HYLFH9DOXHV
$GPLQ 5HVHWWLQJ7RWDOL]HUVDQG
&RQILJXUDWLRQ
(GLW
%DFNWR0DLQ3DJH
IM-P197-02 MI Issue 1 95
9.3.5 BACnet® Object Support
Nine BACnet standard objects are supported, a Device object (DEx), a Binary Output object
(BO1), and seven Analog Input objects (AI1 through AI7). The BACnet/IP UDP port defaults
to 0xBAC0. The Object Identifier (BACnet Device ID) and Location can both be modified
through the web page interface.
96 IM-P197-02 MI Issue 1
9.3.6 BACnet® protocol implementation conformance statement
BACnet standardized
device profile (Annex L): BACnet Application Specific Controller (B-ASC)
BACnet interoperability building
blocks supported (Annex K): DS-RP-B, DS-WP-B, DS-WPM-B,
DM-DDB-B, DM-DOB-B and DM-DCC-B
IM-P197-02 MI Issue 1 97
9.4 Heating and cooling measurement
The UTM10-E energy flowmeter is designed to measure the rate and quantity of heat
delivered to a given building, area or heat exchanger. The instrument measures the
volumetric flowrate of the heat exchanger liquid (water, water / glycol mixture, brine, etc.),
the temperature at the inlet pipe and the temperature at the outlet pipe. Heat delivery is
calculated by the following equation:
Where:
Q = volumetric flow rate
Tin = temperature at the inlet
Tout = temperature at the outlet
Cp = specific heat of the liquid
The RTD temperature measurement circuit in the UTM10 flowmeter measures the differential
temperature of two 1000 Ohm, three-wire platinum RTDs. The three-wire configuration
allows the temperature sensors to be located several hundred feet away from the flowmeter
without influencing system accuracy or stability.
The UTM10-E energy flowmeter allows
Platinum RTD
integration of two 1000 Ohm platinum
RTDs with the UTM10 flowmeter, effectively Type 1 000 Ohm
providing an instrument for measuring ±0.3°C
energy delivered in liquid cooling and Accuracy
0.0385 curve
heating systems. If RTDs were ordered
with the UTM10 flowmeter, they have Temperature Positive temperature
been factory calibrated and are shipped response coefficient
connected to the module as they were
calibrated.
Field replacement of RTDs is possible through the use of the keypad or the software
utility. If the RTDs were ordered from the manufacturer of the UTM10, they will come with
calibration values that need to be loaded into the UTM10.
New, non-calibrated RTDs will need to be field calibrated using an ice bath and boiling
water to derive calibration values. This procedure is outlined below.
Equipment required:
Ice bath
Boiling water bath 100°C
Laboratory grade thermometer
(accurate to 0.1°C) 0 °C
Software utility
98 IM-P197-02 MI Issue 1
9.4.2 Replacing or re-calibrating RTDs
This procedure works with pairs of surface mount RTDs or pairs of insertion RTDs supplied
by the manufacturer of the UTM10 flowmeter.
6\VWHP&RQILJXUDWLRQ
Calibration/Test
Calibration
P$ RTD #2:
P$
A: B: &DOLEUDWH
Test
7HVW
IM-P197-02 MI Issue 1 99
6) Click on the 'Calibrate' button and the following screen should now be visible.
Make sure that the 'Calibrate Both RTDs at same temperature' box is checked and then
enter the temperature to the nearest 0.1°C in the box labeled 'Reference Temp (deg C)'.
7) Press 'Next'.
The procedure for Step 2 of 2 is similar to Step 1 except the second water bath is used.
57'&DOLEUDWLRQ6WHSRI
&DOLEUDWH57'RUVHOHFWWKHFKHFNER[EHORZWRFDOLEUDWHERWK57'VDWWKHVDPH
WHPSHUDWXUH0DNHVXUHWKDWWKH57'LVDWDNQRZQWHPSHUDWXUHDQGHQWHUWKLV
WHPSHUDWXUHEHORZ
)LUVW&DO3RLQW
5HIHUHQFH7HPSGHJ&
57' 57'
'$&9DOXH
&DOLEUDWH%RWK57'VDWVDPHWHPSHUDWXUH
2. &DQFHO
8) Insert both RTD temperature sensors and the laboratory grade thermometer into the
second water bath and allow about 20 minutes for the sensors to come up to the same
temperature.
9) Make sure that the 'Both RTDs at same temperature' box is checked and then enter the
temperature to the nearest 0.1°C in the box labeled 'Temp (deg C)'.
10) Press 'OK'.
11) Press 'Download' on the 'System configuration' screen to save the calibration values to
the flowmeter. After the download is complete, turn the power off and then on again to
the flowmeter to make the newly downloaded values take effect.
&DOLEUDWH57'RUVHOHFWWKHFKHFNER[EHORZWRFDOLEUDWHERWK57'VDWWKHVDPH
WHPSHUDWXUH0DNHVXUHWKDWWKH57'LVDWDNQRZQWHPSHUDWXUHDQGHQWHUWKLV
WHPSHUDWXUHEHORZ
6HFRQG&DO3RLQW
5HIHUHQFH7HPSGHJ&
57' 57'
'$&9DOXH
&DOLEUDWH%RWK57'VDWVDPHWHPSHUDWXUH
2. &DQFHO
If the calibration points are not separated by at least 40°C or if either one or both of the
RTDs are open, the following error message will be displayed:
863
! &DOLEUDWLRQSRLQWVDUHWRRFORVH&DOLEUDWLRQQRWXVDEOH
2.
Check the RTDs resistance values with an ohmmeter to make sure they are not 'open' or
'shorted'. See Table A-4.2 for typical RTD resistance values. Next check to ensure that
incorrect 'Cal Point' values were not entered inadvertently.
Class C errors
Initiate a flowmeter RESET by cycling power or
1001 System tables have changed
by selecting SYSTEM RESET in the SEC MENU.
System configuration has Initiate a flowmeter RESET by cycling power or
1002
changed by selecting SYSTEM RESET in the SEC MENU.
Class B errors
Invalid hardware
3001 Upload corrected file.
configuration
3002 Invalid system configuration Upload corrected file.
1. Refer to transmitter's installation manual for transducer location and mounting instructions.
G 2. Warning - to prevent ignition of flammable atmospheres, disconnect power before servicing.
3. Warning: substitution of components may impair intrinsic safety.
4. No revision to drawing without prior CSA-international approval.
5. Associated apparatus manufacturer's installation drawing must be followed when installing this
equipment.
6. Installation in Canada should be in accordance with the canadian electrical code, CSA C22.1,
Part 1, Appendix F.
F 7. Installation shall be in accordance with the national electrical code (ASME (ANSI) / NFPA 70)
Sections 504 and 505 and the ASME (ANSI) / ISA RP12.6 installation of intrinsically safe
systems for hazardous (classified) locations.
8. The maximum non-hazardous location voltage is 250 Vac / Vdc.
3. RADII TO BE .005/.010
2. FINISH TO BE 63
1. REMOVE ALL BURRS AND BREAK SHARP EDGES .005/.010
NOTES: UNLESS OTHERWISE SPECIFIED
12 11 10 9 8 7
Non-hazardous location
Maximum ambient temperature: -40°C to +50°C
installation manual
Black Red
02'(/,6%DUULHU8OWUDVRQLFV
'
3.60
&86
(MTG. holes)
6.26
(MTG. holes)
C
I.S module
I.S wiring part no. D070-1010-001
D091-1053-005
B
PART NUMBER:
6 5 4 3 2 1
H
Hazardous (classified) location
Class I division 1 groups C and D
Maximum ambient temperature: -40°C to +85°C
1. Refer to transmitter's installation manual for transducer location and mounting instructions.
G 2. Warning - to prevent ignition of flammable atmospheres, disconnect power before servicing.
3. Warning: substitution of components may impair intrinsic safety.
4. No revision to drawing without prior CSA-international approval.
5. Associated apparatus manufacturer's installation drawing must be followed when installing this
equipment.
6. Installation in Canada should be in accordance with the canadian electrical code, CSA C22.1,
Part 1, Appendix F.
F 7. Installation shall be in accordance with the national electrical code (ASME (ANSI) / NFPA 70)
Sections 504 and 505 and the ASME (ANSI) / ISA RP12.6 installation of intrinsically safe
systems for hazardous (classified) locations.
8. The maximum non-hazardous location voltage is 250 Vac / Vdc.
Tee fitting
E
Flexible armored
conduit suitable
for incidental
and temporary
D submersion
3. RADII TO BE .005/.010
2. FINISH TO BE 63
1. REMOVE ALL BURRS AND BREAK SHARP EDGES .005/.010
NOTES: UNLESS OTHERWISE SPECIFIED
12 11 10 9 8 7
H
Non-hazardous location
Maximum ambient temperature: -40°C to +50°C
installation manual
Black Red
3.60
(MTG. holes)
D
6.26
(MTG. holes)
C
I.S module
I.S wiring part no. D070-1010-001
B
PART NUMBER:
6 5 4 3 2 1
Flowmeter
Inputs Vmax Imax Ci Li
ac power 265 Vac 500 mA
0.0 uF 0.0 uH
Total reset 28 Vdc 25 mA
Earth Gnd.
90 - 265 Vac In
Outputs V Isc Ca La AC Neutral
Control 1 Signal Gnd.
Control 2 Control 1 Out
28 Vdc 2.8 mA 3.3 uF 100 mH
Frequency Control 2 Out
Total pulse Freq. Out
4-20 mA 28 Vdc 22 mA 3.3 uF 100 mH 4 - 20 mA Out
Reset Total In
Modbus Gnd.
Modbus Interface must meet wiring
requirements to comply with NEC Article 500 Modbus B
and the CEC Sections 18 and 18J. Modbus A
By others
ac power source
Associated apparatus
Other device
By others
PART NUMBER:
Flowmeter
Inputs Vmax Imax Ci Li
dc power 500 mA 40 uF 22 uH
28 Vdc
Total reset 25 mA 0.0 uF 0.0 uH
Earth Gnd.
10 - 28 Vdc In
Outputs V Isc Ca La AC Neutral
Control 1 Signal Gnd.
Control 2 Control 1 Out
28 Vdc 2.8 mA 3.3 uF 100 mH
Frequency Control 2 Out
Total pulse Freq. Out
4-20 mA 28 Vdc 22 mA 3.3 uF 100 mH 4 - 20 mA Out
Reset Total In
Modbus Gnd.
Modbus Interface must meet wiring
requirements to comply with NEC Article 500 Modbus B
and the CEC Sections 18 and 18J. Modbus A
By others
Associated apparatus
Other device
By others
PART NUMBER:
OFF ON
95 - 264 Vac
ac neutral
To:
Rate pulse, tot, al pulse,
4-20 mA, total reset or
Disconnect RS485 I/O if used
(Note 2, 3)
User equipment
NAME: ac POWERED
HAZARDOUS AREA INSTALLATION
PART NUMBER:
OFF ON
10 - 28 Vdc
Ø Vdc
To:
Rate pulse, tot, al pulse,
4-20 mA, total reset or
Disconnect RS485 I/O if used
(Note 2, 3)
User equipment
NAME: dc POWERED
HAZARDOUS AREA INSTALLATION
PART NUMBER:
An example might be a K-factor of 250 (pulses per litre). This means that if you were counting
pulses, when the count total reached 250, you would have accumulated 1 litre of liquid. Using
the same reasoning each individual pulse represents an accumulation of 1/250 of a litre. This
relationship is independent of the time it takes to accumulate the counts.
The frequency aspect of K-factors is a little more confusing because it also involves the
flowrate. The same K-factor number, with a time frame added, can be converted into a
flowrate. If you accumulated 1000 counts (four litres) in one minute, then your flowrate
would be 4 Litres/minute (4 LPM). The output frequency, in Hz, is found simply by dividing
the number of counts (1000) by the number of seconds (60) to get the output frequency.
1000 ÷ 60 = 16.6666... Hz. If you were looking at the pulse output on a frequency counter, an
output frequency of 16.666...Hz would be equal to 4 Litres / minute (4 LPM). If the frequency
counter registered 33.333...Hz (2 × 16.666...Hz), then the flowrate would 8 Litres / minute
(8 LPM).
Finally, if the flowrate is 8 Litres/minute (8 LPM), then the accumulation of 1000 counts would
take place in 30 seconds because the flowrate, and hence the speed that the 1000 counts
is achieved would be twice as fast.
The most basic K-factor calculation requires that an accurate flowrate and the output
frequency associated with that flowrate be known.
Example 1:
Known values are:
Frequency = 700 Hz
Flowrate = 218.21 Litres / minute 'LPM' (48 gallons / minute 'GPM')
Full-scale flowrate = 386.42 Litres / minute 'LPM' (85 gallons / minute 'GPM')
Full-scale output frequency = 650 Hz
The calculation is a little more complex if velocity is used because you first must convert
the velocity into a volumetric flowrate to be able to compute a K-factor.
To convert a velocity into a volumetric flow, the velocity measurement and an accurate
measurement of the inside diameter of the pipe must be known. If using Imperial units,
1 US gallon is equal to 231 cubic inches.
Example 3:
Known values are:
Velocity: = 1.31 m / s (4.3 ft / s)
Inside diameter of pipe = 0.077 9 m (3.068")
Frequency = 700 Hz
§ 0.0779 · 2
Area = S x r 2 = S x ¨ ¸ = 0.004 77m2 (7.39"2 )
© 2 ¹
frequency 700
K - factor = = = 112 179.49 pulses per m3
Volumetric flow 0.006 24
= 112.18 pulses /litre (423.9 pulses/gallon )
CAUTION:
Refer to accompanying documents.
WARNING:
Explosion hazard - Substitution of components may impair suitability
for Class ,, Division 2.
WARNING:
Do not connect or disconnect either power or outputs unless the area is
known to be non-hazardous.
IMPORTANT NOTE:
Not following instructions properly may impair safety of equipment and/
or personnel.
IMPORTANT NOTE:
Must be operated by a Class ,, supply suitable for the location.
IMPORTANT NOTE:
Do not connect the interface cable between a TFX Ultra flow meter and
a personal computer unless the area is known to be non-hazardous.
Electrical symbols
Direct Alternating Earth Protective Chassis
Function
current current (Ground) ground ground
Symbol
dc ac
4" 4.500 4.334 0.083 4.260 0.120 4.026 0.237 4.026 0.237
5" 5.563 5.345 0.109 5.295 0.134 5.047 0.258 5.047 0.258
6" 6.625 6.407 0.109 6.357 0.134 6.065 0.280 6.065 0.280
8" 8.625 8.407 0.109 8.329 0.148 8.125 0.250 8.071 0.277 7.981 0.322 7.981 0.322
10" 10.75 10.482 0.134 10.42 0.165 10.25 0.250 10.13 0.310 10.02 0.365 10.02 0.365
12" 12.75 12.42 0.165 12.39 0.180 12.25 0.250 12.09 0.330 12.00 0.375 11.938 0.406
14" 14.00 13.50 0.250 13.37 0.315 13.25 0.375 13.25 0.375 13.124 0.438
16" 16.00 15.50 0.250 15.37 0.315 15.25 0.375 15.25 0.375 15.000 0.500
18" 18.00 17.50 0.250 17.37 0.315 17.12 0.440 17.25 0.375 16.876 0.562
20" 20.00 19.50 0.250 19.25 0.375 19.25 0.375 19.25 0.375 18.814 0.593
24" 24.00 23.50 0.250 23.25 0.375 23.25 0.375 23.25 0.375 22.626 0.687
30" 30.00 29.37 0.315 29.00 0.500 29.00 0.500 29.25 0.375 29.25 0.375
36" 36.00 35.37 0.315 35.00 0.500 35.00 0.500 35.25 0.375 35.25 0.375
42" 42.00 41.25 0.375 41.25 0.375
48" 48.00 47.25 0.375 47.25 0.375
IM-P197-02 MI Issue 1
"Steel, stainless steel, P.V.C. pipe"
Standard classes
Nominal SCH 10
Outside SCH 5 SCH 20 SCH 30 STD SCH 40
pipe size (Lt wall)
diameter
inches
ID Wall ID Wall ID Wall ID Wall ID Wall ID Wall
1"
IM-P197-02 MI Issue 1
1.315 0.957 0.179 0.957 0.179 0.815 0.250
1.25" 1.660 1.278 0.191 1.278 0.191 1.160 0.250
1.5" 1.900 1.500 0.200 1.500 0.200 1.338 0.281
2" 2.375 1.939 0.218 1.939 0.218 1.687 0.344
2.5" 2.875 2.323 0.276 2.323 0.276 2.125 0.375
3" 3.500 2.900 0.300 2.900 0.300 2.624 0.438
3.5" 4.000 3.364 0.318 3.364 0.318
9.10 Table 24 - ASME pipe data
4" 4.500 3.826 0.337 3.826 0.337 3.624 0.438 3.438 0.531
5" 5.563 4.813 0.375 4.813 0.375 4.563 0.500 4.313 0.625
6" 6.625 5.761 0.432 5.761 0.432 5.501 0.562 5.187 0.719
8" 8.625 7.813 0.406 7.625 0.500 7.625 0.500 7.437 0.594 7.178 0.719 6.183 1.221
10" 10.75 9.750 0.500 9.75 0.500 9.562 0.594 9.312 0.719 9.062 0.844 8.500 1.125
12" 12.75 11.626 0.562 11.75 0.500 11.37 0.690 11.06 0.845 10.75 1.000 10.12 1.315
14" 14.00 12.814 0.593 13.00 0.500 12.50 0.750 12.31 0.845 11.81 1.095 11.18 1.410
16" 16.00 14.688 0.656 15.00 0.500 14.31 0.845 13.93 1.035 13.56 1.220 12.81 1.595
18" 18.00 16.564 0.718 17.00 0.500 16.12 0.940 15.68 1.160 15.25 1.375 14.43 1.785
20" 20.00 18.376 0.812 19.00 0.500 17.93 1.035 17.43 1.285 17.00 1.500 16.06 1.970
24" 24.00 22.126 0.937 23.00 0.500 21.56 1.220 20.93 1.535 20.93 1.535 19.31 2.345
30" 30.00 29.00 0.500
36" 36.00 35.00 0.500
42" 42.00 41.00 0.500
48" 48.00 47.00 0.500
123
124
Copper tubing Copper Copper tubing Copper
Nominal Nominal
& brass Aluminium & brass Aluminium
diameter Type diameter Type
pipe pipe
K L M K L M
O. D. 0.625 0.625 0.625 0.840 O. D. 3.625 3.625 3.625 4.000
½" Wall 0.049 0.040 0.028 0.108 3½ " Wall 0.120 0.100 0.083 0.250
I.D. 0.527 0.545 0.569 0.625 I.D. 3.385 3.425 3.459 3.500
IM-P197-02 MI Issue 1
Ductile Iron Pipe (Standard Classes)
Size Class Mortar Size Class Mortar
(Inches) 50 51 52 53 54 55 56 lining (Inches) 50 51 52 53 54 55 56 lining
O.D. 3.96 3.96 3.96 3.96 3.96 3.96 O.D. 19.50 19.50 19.50 19.50 19.50 19.50 19.50
Std. 0.123 Std . 0.1875
3" Wall 0.25 0.28 0.31 0.34 0.37 0.41 18" Wall 0.35 0.38 0.41 0.44 0.47 0.50 0.53
Dbl. 0.250 Dbl. 0.375
I.D. 3.46 3.40 3.34 3.28 3.22 3.14 I.D. 18.80 18.74 18.68 18.62 18.56 18.50 18.44
IM-P197-02 MI Issue 1
O.D. 4.80 4.80 4.80 4.80 4.80 4.80 O.D. 21.60 21.60 21.60 21.60 21.60 21.60 21.60
Std. 0.123 Std . 0.1875
4" Wall 0.26 0.29 0.32 0.35 0.38 0.42 20" Wall 0.36 0.39 0.42 0.45 0.48 0.51 0.54 Dbl. 0.375
Dbl. 0.250
I.D. 4.28 4.22 4.16 4.10 4.04 3.93 I.D. 20.88 20.82 20.76 20.70 20.64 20.58 20.52
O.D. 6.90 6.90 6.90 6.90 6.90 6.90 6.90 O.D. 25.80 25.80 25.80 25.80 25.80 25.80 25.80
Std. 0.123 Std . 0.1875
6" Wall 0.25 0.28 0.31 0.34 0.37 0.40 0.43 24" Wall 0.38 0.41 0.44 0.47 0.50 0.53 0.56
Dbl. 0.250 Dbl. 0.375
I.D. 6.40 6.34 6.28 6.22 6.16 6.10 6.04 I.D. 25.04 24.98 24.92 24.86 24.80 24.74 24.68
O.D. 9.05 9.05 9.05 9.05 9.05 9.05 9.05 O. D. 32.00 32.00 32.00 32.00 32.00 32.00 32.00
Std. 0.123 Std. 0.250
8" Wall 0.27 0.30 0.33 0.36 0.39 0.42 0.45 30" Wall 0.39 0.43 0.47 0.51 0.55 0.59 0.63
Dbl. 0.250 Dbl. 0.500
I.D. 8.51 8.45 8.39 8.33 8.27 8.21 8.15 I.D. 31.22 31.14 31.06 30.98 30.90 30.82 30.74
9.10 Table 26 - Ductile iron pipe data
O.D. 11.10 11.10 11.10 11.10 11.10 11.10 11.10 O.D. 38.30 38.30 38.30 38.30 38.30 38.30 38.30
Std. 0.123 Std. 0.250
10" Wail 0.39 0.32 0.35 0.38 0.41 0.44 0.47 36" Wall 0.43 0.48 0.62 0.58 0.45 0.68 0.73
Dbl. 0.250 Dbl. 0.500
I.D. 10.32 10.46 10.40 10.34 10.28 10.22 10.16 I.D. 37.44 37.34 37.06 37.14 37.40 36.94 36.48
O.D. 13.20 13.20 13.20 13.20 13.20 13.20 13.20 O.D. 44.50 44.50 44.50 44.50 44.50 44.50 44.50
Std. 0.123 Std. 0.250
12" Wall 0.31 0.34 0.37 0.40 0.43 0.46 0.49 42" Wall 0.47 0.53 0.59 0.65 0.71 0.77 0.83
Dbl. 0.250 Dbl. 0.500
I.D. 12.58 12.52 12.46 12.40 12.34 12.28 12.22 I.D. 43.56 43.44 43.32 43.20 43.08 42.96 42.84
O.D. 15.30 15.30 15.30 15.30 15.30 15.30 15.30 O.D. 50.80 50.80 50.80 50.80 50.80 50.80 50.80
Std . 0.1875 Std. 0.250
14" Wall 0.33 0.36 0.39 0.42 0.45 0.48 0.51 48" Wall 0.51 0.58 0.65 0.72 0.79 0.86 0.93
Dbl. 0.375 Dbl. 0.500
I.D. 14.64 14.58 14.52 14.46 14.40 14.34 14.28 I.D. 49.78 49.64 49.50 49.36 49.22 49.08 48.94
O.D. 17.40 17.40 17.40 17.40 17.40 17.40 17.40 O.D. 57.10 57.10 57.10 57.10 57.10 57.10 57.10
Std . 0.1875 Std. 0.250
16" Wall 0.34 0.37 0.40 0.43 0.46 0.49 0.52 54" Wall 0.57 0.65 0.73 0.81 0.89 0.97 1.05
Dbl. 0.375 Dbl. 0.500
I.D. 16.72 16.66 16.60 16.54 16.48 16.42 16.36 I.D. 55.96 55.80 55.64 55.48 55.32 55.16 55.00
125
Cast iron pipe (Standard classes)
126
Size Class Size Class
(Inches) A B C D E F G H (Inches) A B C D E F G H
O.D. 3.80 3.96 3.96 3.96 O.D. 25.80 25.80 26.32 26.32 26.90 26.90 27.76 27.76
3" Wall 0.39 0.42 0.45 0.48 24" Wall 0.76 0.98 1.05 1.16 1.31 1.45 1.75 1.88
I.D. 3.02 3.12 3.06 3.00 I.D. 24.28 24.02 24.22 24.00 24.28 24.00 24.26 24.00
O.D. 4.80 5.00 5.00 5.00 O. D. 31.74 32.00 32.40 32.74 33.10 33.46
4" Wall 0.42 0.45 0.48 0.52 30" Wall 0.88 1.03 1.20 1.37 1.55 1.73
I.D. 3.96 4.10 4.04 3.96 I.D. 29.98 29.94 30.00 30.00 30.00 30.00
O.D. 6.90 7.10 7.10 7.10 7.22 7.22 7.38 7.38 O.D. 37.96 38.30 38.70 39.16 39.60 40.04
6" Wall 0.44 0.48 0.51 0.55 0.58 0.61 0.65 0.69 36" Wall 0.99 1.15 1.36 1.58 1.80 2.02
I.D. 6.02 6.14 6.08 6.00 6.06 6.00 6.08 6.00 I.D. 35.98 36.00 35.98 36.00 36.00 36.00
O.D. 9.05 9.05 9.30 9.30 9.42 9.42 9.60 9.60 O.D. 44.20 44.50 45.10 45.58
8" Wall 0.46 0.51 0.56 0.60 0.66 0.66 0.75 0.80 42" Wall 1.10 1.28 1.54 1.78
I.D. 8.13 8.03 8.18 8.10 8.10 8.10 8.10 8.00 I.D. 42.00 41.94 42.02 42.02
O.D. 11.10 11.10 11.40 11.40 11.60 11.60 11.84 11.84 O.D. 50.55 50.80 51.40 51.98
10" Wail 0.50 0.57 0.62 0.68 0.74 0.80 0.86 0.92 48" Wall 1.26 1.42 1.71 1.99
I.D. 10.10 9.96 10.16 10.04 10.12 10.00 10.12 10.00 I.D. 47.98 47.96 47.98 48.00
9.10 Table 27 - Cast iron pipe data
O.D. 13.20 13.20 13.50 13.50 13.78 13.78 14.08 14.08 O.D. 56.66 57.10 57.80 58.40
12" Wall 0.54 0.62 0.68 0.75 0.82 0.89 0.97 1.04 54" Wall 1.35 1.55 1.90 2.23
I.D. 12.12 11.96 12.14 12.00 12.14 12.00 12.14 12.00 I.D. 53.96 54.00 54.00 53.94
O.D. 15.30 15.30 15.65 15.65 15.98 15.98 16.32 16.32 O.D. 62.80 63.40 64.20 64.28
14" Wall 0.57 0.66 0.74 0.82 0.90 0.99 1.07 1.16 60" Wall 1.39 1.67 2.00 2.38
I.D. 14.16 13.98 14.17 14.01 14.18 14.00 14.18 14.00 I.D. 60.02 60.06 60.20 60.06
O.D. 17.40 17.40 17.80 17.80 18.16 18.16 18.54 18.54 O.D. 75.34 76.00 76.88
16" Wall 0.60 0.70 0.80 0.89 0.98 1.08 1.18 1.27 72" Wall 1.62 1.95 2.39
I.D. 16.20 16.00 16.20 16.02 16.20 16.00 16.18 16.00 I.D. 72.10 72.10 72.10
O.D. 19.50 19.50 19.92 19.92 20.34 20.34 20.78 20.78 O.D. 87.54 88.54
18" Wall 0.64 0.75 0.87 0.96 1.07 1.17 1.28 1.39 84" Wall 1.72 2.22
I.D. 18.22 18.00 18.18 18.00 18.20 18.00 18.22 18.00 I.D. 84.10 84.10
IM-P197-02 MI Issue 1
9.11 CE compliance drawings
Armoured conduit
Anaconda ½" UA gray * Ferrite bead
Steward P/N: 28B1020-100 *
* or equivalent
Fig. 65 CE compliance drawing for dc powered flowmeters