Test Report For Grounding Resistance: Skyworth

The document is a test report for grounding resistance at a power room. It tests the grounding resistance of various equipment like transformers and low voltage panels. All equipment tested had a grounding resistance of 5 ohms or less, which is considered good. Photographs show the grounding points for the transformers and distribution boards. A wiring diagram illustrates the grounding setup.

Uploaded by

muhamad soleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
187 views

Test Report For Grounding Resistance: Skyworth

The document is a test report for grounding resistance at a power room. It tests the grounding resistance of various equipment like transformers and low voltage panels. All equipment tested had a grounding resistance of 5 ohms or less, which is considered good. Photographs show the grounding points for the transformers and distribution boards. A wiring diagram illustrates the grounding setup.

Uploaded by

muhamad soleh
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

SKYWORTH

Facility Maintenance Section


TEST REPORT FOR GROUNDING RESISTANCE

Project Maintenance Power Room


Location Power Room
Climate Sunny Rainy ✘ Cloudy

Classification Grounding Conductor Ground Good ≤ 5Ώ ( ohms )


No. Grounding Application and Name of Equipment to be grounded Resistance in
Ώ ( ohms )
( EA , EB or EC ) Copper Rod (Size and Type ) Yes No
GROUNDING BOX ( Power Room)

1 NEUTRAL TRANSFORMER-1 E2 NYA 95mm2 3.08 a

2 BODY LOW VOLTAGE PANEL / MDB 1 E1 & E3 NYA 95mm2 2.87 a

3 NEUTRAL TRANSFORMER-2 E5 NYA 95mm2 0.54 a

4 BODY LOW VOLTAGE PANEL E4 NYA 95mm2 0.55 a

Remarks :

Ground Resistance : ≤ 5 Ώ
Tested By : Checked By : Approved By :

Date: / / Date: / / Date: / Date:/ / /


PHOTOGRAPH REPORT

Date : 01 November 2020 Date : 01 November 2020


Location : Power room Location : Power room
Grounding Point : Grounding Neutral Trafo 1 Grounding Point : Grounding MDB 1

Date : 01 November 2020 Date : 01 November 2020


Location : Power room Location : Power room
Grounding Point : Grounding Neutral Trafo 2 Grounding Point : Grounding MDB 2

GROUNDING WIRING DIAGRAM