ION9000 Manual
ION9000 Manual
User manual
7EN02-0390-04
11/2020
www.se.com
Legal Information
The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
PowerLogic™ ION9000 series
Safety information
Important information
Read these instructions carefully and look at the equipment to become familiar
with the device before trying to install, operate, service, or maintain it. The
following special messages may appear throughout this manual or on the
equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
This is the safety alert symbol. It is used to alert you to potential personal injury
hazards. Obey all safety messages that accompany this symbol to avoid possible
injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICE
NOTICE is used to address practices not related to physical injury.
Please note
Electrical equipment should be installed, operated, serviced and maintained only
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material. A qualified person is one who
has skills and knowledge related to the construction, installation, and operation of
electrical equipment and has received safety training to recognize and avoid the
hazards involved.
7EN02-0390-04 3
PowerLogic™ ION9000 series
Notices
FCC
This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to part 15 of the FCC rules. These limits are designed to
provide reasonable protection against harmful interference in a residential
installation. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instructions, may
cause harmful interference to radio communications. However, there is no
guarantee that the interference will not occur in a particular installation. If this
equipment does cause harmful interference to radio or television reception, which
can be determined by turning the equipment off and on, the user is encouraged to
try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment to an outlet on a circuit different from that to which the
receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
The user is cautioned that any changes or modifications not expressly approved
by Schneider Electric could void the user’s authority to operate the equipment.
This digital apparatus complies with CAN ICES-3 (B) /NMB-3(B).
4 7EN02-0390-04
PowerLogic™ ION9000 series
Related documents
Document Number
ION9000 online document portal https://www.productinfo.schneider-electric.
com/portals/ui/ion9000/
7EN02-0390-04 5
PowerLogic™ ION9000 series
Table of Contents
Safety precautions ....................................................................................15
Meter overview ..........................................................................................17
ION9000 series ........................................................................................17
Your meter in an energy management system ............................................18
Communications ......................................................................................19
Supported protocols ............................................................................19
Meter configuration ...................................................................................20
ION Setup device configuration tool......................................................20
Switching ION Setup to Advanced mode...............................................20
Data display .............................................................................................20
Built-in webpages and web server feature.............................................20
Localization ........................................................................................20
Display...............................................................................................20
Notification...............................................................................................21
Active and historical alarms .................................................................21
Email messaging feature .....................................................................21
Meter models and accessories ..................................................................21
Terminal covers ........................................................................................22
Installation and commissioning ...............................................................23
Installation ...............................................................................................23
Power system wiring ...........................................................................24
Residual current measurement ............................................................24
Functional ground ...............................................................................24
LVCS overview ...................................................................................25
LPCT configuration .............................................................................25
LPCT compensation............................................................................28
Removing the display from back-to-back mounting adapter....................28
Removing the meter from back-to-back mounting adapter......................30
Option modules ..................................................................................31
Maximum number of option modules ....................................................32
Commissioning ........................................................................................32
Factory default settings .......................................................................32
Commissioning using ION Setup..........................................................32
Configure basic metering parameters ...................................................33
Using the phasor viewer ......................................................................34
Basic setup using the webpages or display .................................................34
Communications .......................................................................................35
Communications overview ........................................................................35
Ethernet communications..........................................................................35
Ethernet communications connections .................................................35
Protocols, ports and connections..........................................................36
Self-discovery over Ethernet ................................................................37
Ethernet configuration .........................................................................38
DHCP ................................................................................................45
Meter domain name ...........................................................................46
Network protocol control ......................................................................46
Serial communications ..............................................................................48
7EN02-0390-04 7
PowerLogic™ ION9000 series
RS-485 wiring.....................................................................................48
RS-485 configuration ..........................................................................49
Disabling serial communications ports ..................................................52
ION .........................................................................................................53
Modbus ...................................................................................................53
Modbus best practices for Ethernet ......................................................54
Modbus best practices for serial ...........................................................54
Your meter as a Modbus master...........................................................54
Your meter as a Modbus slave .............................................................56
Supported Modbus features.................................................................58
Modbus implementation ......................................................................59
Modbus map ......................................................................................61
Ethernet gateway .....................................................................................62
EtherGate ..........................................................................................63
Modbus Ethernet gateway ...................................................................65
Creating an Ethernet gateway site using ION Setup...............................66
HTTPS ....................................................................................................67
Changing web protocol settings ...........................................................67
Secure website indicator .....................................................................67
Default SSL certificate and webpages security ......................................67
Uploading a custom SSL certificate ......................................................68
Generating a new self-signed SSL certificate ........................................68
Deleting a custom SSL certificate .........................................................68
SFTP.......................................................................................................68
Transferring files using SFTP...............................................................68
Freeing up flash memory .....................................................................69
SFTP folders and file permissions ........................................................69
SFTP filename requirements ...............................................................69
Simple Network Management Protocol (SNMP) ..........................................69
The meter in an SNMP system.............................................................70
SNMP trapping ...................................................................................70
SNMP implementation.........................................................................72
Default SNMP mapping .......................................................................73
IEC 61850................................................................................................74
Mapping additional data to IEC 61850 ..................................................74
Enabling IEC 61850 functionality..........................................................75
Configuring digital outputs for IEC 61850 control ...................................76
Deleting an IEC 61850 configuration file ...............................................76
DNP ........................................................................................................77
DNP supported features and default implementation .............................77
DLMS/COSEM .........................................................................................77
Inputs / outputs ..........................................................................................78
I/O overview .............................................................................................78
Input/output ION modules .........................................................................78
Input/output ION modules, ports and labels ................................................79
I/O option modules ...................................................................................80
I/O option module data viewing ............................................................80
Option I/O modules configuration .........................................................80
Analog inputs ...........................................................................................81
Analog input applications.....................................................................81
Analog input voltage and current mode.................................................81
8 7EN02-0390-04
PowerLogic™ ION9000 series
7EN02-0390-04 9
PowerLogic™ ION9000 series
12 7EN02-0390-04
PowerLogic™ ION9000 series
7EN02-0390-04 13
PowerLogic™ ION9000 series
Display............................................................................................. 250
Option modules ................................................................................ 252
Other ............................................................................................... 252
Open source software components ..................................................... 253
14 7EN02-0390-04
Safety precautions PowerLogic™ ION9000 series
Safety precautions
Installation, wiring, testing and service must be performed in accordance with all
local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate Personal Protective Equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, CSA Z462 or other local
standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on or in the equipment.
• Follow guidelines in the Wiring section of the related Installation Sheet.
• Assume communications and I/O wiring are hazardous live until determined
otherwise.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Do not use the data from the meter to confirm power is off.
• Do not exceed the maximum ratings of this device.
• Do not short secondary terminals of Voltage Transformer (VT).
• Do not open secondary terminals of Current Transformer (CT).
• Ground secondary circuit of CTs.
• Use only Low Power Current Transformers (LPCTs) that are approved for
use with this device.
• Do not connect CT secondary signals to meter low voltage LPCT terminals.
• Do not install CTs or LPCTs in equipment where they exceed 75% of the
wiring space of any cross-sectional area in the equipment.
• Do not install CTs or LPCTs in areas where ventilation openings may be
blocked or in areas of breaker arc venting.
• Do not install CTs or LPCTs using Class 2 wiring methods or connect to
Class 2 equipment. See NFPA 70.
• Secure CT or LPCT secondary conductors to ensure they do not contact live
circuits.
• Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
NOTE: See IEC 60950-1 for more information on communications and I/O
wiring connected to multiple devices.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
7EN02-0390-04 15
PowerLogic™ ION9000 series Safety precautions
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords/passcodes to help prevent unauthorized access
to device settings and information.
• Disable unused ports/services and default accounts, where possible, to
minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example: least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
16 7EN02-0390-04
Meter overview PowerLogic™ ION9000 series
Meter overview
ION9000 series
The ION9000 series advanced energy and power quality meter helps meet the
needs of your energy management, power management, and cost management
applications within your EcoStruxure™ Power architecture.
ION9000 series revenue-accurate meters comply to international metering
standards. The meters feature flexible ION programmability that enhances
functionality through customization by loading specialized frameworks. You can
add optional modules and incorporate mounting accessories into the physical
installation to meet a variety of installation and application needs.
Measurement accuracy
Third-party international standards-certified:
• Class 0,1S for energy
• Power Quality Instrument – Class A (PQI-A) for all normative IEC 61000-4-30
power quality metrics
• IEC 62053-22, -23, -24 and ANSI C12.20
Power quality
Third-party international standards-certified:
• IEC 62586-1, IEC 62586-2, and IEC 61000-4-30
• EN 50160, including flicker monitoring
• IEEE 519
Cybersecurity
• Meter security with multiple users and access levels
• Total control for each communications port and protocol, including protocol
lockout
• Secure webpages (HTTPS)
• Support for meter event logging to a remote server (syslog)
Account management
If your meter’s user access information is lost, you must return the meter to the
factory, where your meter is reset to its factory defaults and all logged data is lost.
7EN02-0390-04 17
PowerLogic™ ION9000 series Meter overview
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
18 7EN02-0390-04
Meter overview PowerLogic™ ION9000 series
Power quality
monitoring
Understand
Easy access
to information
Act
Time of use
Cost allocation/tenant billing Energy
efficiency
Perform basic setup using ION Setup, meter webpages Configure meter to help protect against unauthorized
or the display. configuration of your meter and access to your meter’s data.
Use the onboard or expansion I/O for non-critical control, Log data in a number of onboard default logs, or customize
WAGES and input metering, energy pulsing and system your meter to log other parameters, and access that
monitoring, for example, breaker status. information using software or webpages.
Receive notifications of predefined meter and system events Time of use and perform cost allocation/tenant billing.
or create custom alarms.
Track the trends for power system values over time to Easily access information after basic configuration using:
understand: energy usage patterns, optimize network capacity
and forecast future usage. • a variety of industry-standard protocols.
• the touch-screen display.
• Monitor compliance to a variety of power quality standards • EcoStruxure™ Power Monitoring Expert and
using the meter’s highly accurate metering. PowerSCADA Operation software.
• Use the meter’s setpoint learning feature to learn your • meter webpages that can be customized to suit your needs.
power system’s normal operating values. • the meter’s gateway feature to access downstream devices.
• Locate disturbances using disturbance direction detection.
Communications
Supported protocols
Your meter’s fundamental protocol and architecture is ION.
You can integrate the meter into various industry-standard networks. Data that the
meter measures can be made available to other devices using Modbus, DNP 3.0,
DLMS and SNMP, as well as the MV-90 billing software. You can configure the
meter to import data from other devices on these networks. Your meter supports
the IEC 61850 protocol and COMTRADE waveform data format.
Your meter also supports IPv6, DPWS and RSTP Ethernet protocols.
7EN02-0390-04 19
PowerLogic™ ION9000 series Meter overview
Meter configuration
ION Setup device configuration tool
ION Setup is a free configuration tool for your meter that allows you to remotely
configure your meter’s features over Ethernet or serial communications.
• Use the setup screens to guide you through the process of configuring your
meter.
• Use the real-time data screens to verify your meter’s configuration.
• Use the data screens to view your meter’s recorded data.
• Use the charting function to view your meter’s recorded waveforms.
• Use ION Setup in Advanced mode to work directly with modules.
Download ION Setup from www.se.com.
Data display
Built-in webpages and web server feature
Your meter’s onboard internal web server and built-in web pages provide quick
and easy access to real-time energy, basic power quality information and meter
configuration without having to use specialized software.
Localization
The meter can be customized to use different regional settings.
Localization settings determine:
• The language used for the display and webpages
• Time, date and digit formats
• Displayed phase labels (123/ABC)
• IEEE (Institute of Electrical and Electronics Engineers) or IEC (International
Electrotechnical Commission) conventions for power, power factor and
energy
You can configure your meter’s localization settings using ION Setup, or the
display.
Display
Use the meter’s display to view real-time and historical power quality data, access
monitoring tools, receive and acknowledge alarms, and perform basic device
configuration.
The touch-screen color display has multiple mounting options to suit your
environment and an eight-language interface with external LED indicators for
power, alarms, and energy pulsing applications.
20 7EN02-0390-04
Meter overview PowerLogic™ ION9000 series
Notification
Active and historical alarms
The meter’s display shows an alarm icon and the alarm LED flashes if your meter
detects an active alarm condition.
Depending on the priority of the alarm, the display also flashes. You can view and
acknowledge active alarms and historic alarms and events through the display
and software webpages. An active alarm becomes a historic alarm when the
alarm condition no longer exists.
METSEION92830
METSEION92040 ION9000 series meter with RD192 remote display
METSEION92840
METSEION92043 ION9000 series – Measurement Canada Approved meter
METSERD192 RD192 192 x 192 mm remote display with ION9000 series back-to-
back mounting adapter and 1/4 DIN (92 x 92 mm) panel cutout
mounting adapter
Refer to your meter’s catalog pages, available from www.se.com, for updated
information on meter types and accessories.
7EN02-0390-04 21
PowerLogic™ ION9000 series Meter overview
Terminal covers
The voltage and current terminal covers help prevent tampering with the meter’s
voltage and current measurement inputs.
The terminal covers enclose the terminals, the conductor fixing screws and a
length of the external conductors and their insulation. The terminal covers are
secured by tamper-resistant meter seals.
These covers are included for meter models where sealable voltage and current
covers are required to comply with revenue or regulatory standards.
The meter terminal covers must be installed by a qualified installer.
Refer to your meter's installation guide or the instructions that came with your
terminal covers for instructions on installing the terminal covers.
22 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
Installation
Installation, wiring, testing and service must be performed in accordance with all
local and national electrical codes.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate Personal Protective Equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, CSA Z462 or other local
standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on or in the equipment.
• Assume communications and I/O wiring are hazardous live until determined
otherwise.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Do not use the data from the meter to confirm power is off.
• Do not exceed the maximum ratings of this device.
• Do not short secondary terminals of Voltage Transformer (VT).
• Do not open secondary terminals of Current Transformer (CT).
• Ground secondary circuit of CTs.
• Use only Low Power Current Transformers (LPCTs) that are approved for
use with this device.
• Do not connect CT secondary signals to meter low voltage LPCT terminals.
• Do not install CTs or LPCTs in equipment where they exceed 75% of the
wiring space of any cross-sectional area in the equipment.
• Do not install CTs or LPCTs in areas where ventilation openings may be
blocked or in areas of breaker arc venting.
• Do not install CTs or LPCTs using Class 2 wiring methods or connect to
Class 2 equipment. See NFPA 70.
• Secure CT or LPCT secondary conductors to ensure they do not contact live
circuits.
• Replace all devices, doors and covers before turning on power to this
equipment.
Failure to follow these instructions will result in death or serious injury.
7EN02-0390-04 23
PowerLogic™ ION9000 series Installation and commissioning
3 CT wiring
For a 3-phase 3-wire system, the meter calculates residual current For a 3-phase 3-wire system, the meter measures the residual
for Ground. current for Ground at I4.
For a 3-phase 4-wire system, the meter calculates residual current For a 3-phase 4-wire system, the meter measures the residual
for Neutral. current for Neutral at I4.
I1 I2 I3 I4 I5 I1 I2 I3 I4 I5
L1 L1
L2 L2
L3 L3
N
4 CT wiring
For a 3-phase 4-wire system, the meter calculates residual current For a 3-phase 4-wire system, the meter measures the residual
for Ground. current for Ground at I5.
I1 I2 I3 I4 I5 I1 I2 I3 I4 I5
L1 L1
L2 L2
L3 L3
N N
Functional ground
The meter’s functional ground terminal must be wired for optimal performance.
Use the supplied ferrite when terminating the functional ground terminal to earth
ground. Make sure the ground wire is looped through, around and back through
the ferrite as shown.
24 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
LVCS overview
The Low Voltage Current Sensor (LVCS) hardware option is used with external
low voltage current transformers to sense current in each phase of a power feed.
Use the LVCS option to:
• Measure and monitor individual phases.
• Help reduce installation costs for new or retrofitted installations.
• Provide non-intrusive load monitoring.
LVCS only works with voltage output Low-Power Current Transformers (LPCTs)
and is intended for use with listed Energy-Monitoring current transformers rated
for the application. To use LVCS, an ION9000 LVCS meter (METSEION93030,
METSEION93040) is required.
LPCT configuration
This section assumes your meter and LPCTs are already installed. For more
information related to installation, refer to the ION9000 series – LVCS installation
guide at www.se.com.
This section illustrates two common LPCT configuration scenarios and how they
are configured using ION Setup. You can also configure LPCTs using the meter
webpages or display.
7EN02-0390-04 25
PowerLogic™ ION9000 series Installation and commissioning
Example:
Set the meter CT ratio to 10:1 to match the transformation ratio of the LPCT and report the
conductor primary current.
CT ratio:
= LPCT ratio x Meter ratio
= 10:1 x 1:1
= 10:1
The CT Prim and CT Sec values are stored to the device register.
I4, I5
Configure these settings in Metering Setup > Advanced tab.
26 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
Example:
The total transformation ratio is the product of all component transformation ratios. Set the meter CT
ratio to match the total transformation ratio and measure the primary current at CT1.
CT ratio:
= CT1 ratio x LPCT ratio x Meter ratio
= 500:5 x 10:1 x 1:1
= 5000:5 (or 1000:1)
7EN02-0390-04 27
PowerLogic™ ION9000 series Installation and commissioning
The calculated CT Prim and CT Sec values are stored to the device register.
I4, I5
Configure these settings in Metering Setup > Advanced tab.
LPCT compensation
Minor phase and magnitude compensation can be made using the Instrument
Transformer Correction (ITC) module. For more information about the ITC
module, refer to the ION Reference document at www.se.com.
28 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
1. Holding the display, turn the tightening wheel with a flat-head screwdriver until
it disengages from the display.
+
–
2. Carefully pull the display away, far enough to access the cable connector on
the display.
7EN02-0390-04 29
PowerLogic™ ION9000 series Installation and commissioning
30 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
2. Holding the meter firmly, swing it outwards and pull slightly upwards to detach
it from the top retaining hooks.
Option modules
Option modules are ordered separately from your meter, and can be connected to
your meter without specialized equipment.
Option modules are identified based on how they are physically connected to the
meter’s external I/O bus.
The first connected module, attached directly to the meter, is Module A. The
second module, attached to Module A, is Module B. The meter supports up to four
external modules:
Module A
Module B
Module C Meter
Module D
7EN02-0390-04 31
PowerLogic™ ION9000 series Installation and commissioning
Option modules are monitored and controlled by the meter’s ION modules.
External I/O modules are mapped to the corresponding ION modules:
Commissioning
Factory default settings
Use these default values the first time you connect to your meter.
IP address1 169.254.0.10
Subnet mask 255.255.0.0
Gateway 0.0.0.0
32 7EN02-0390-04
Installation and commissioning PowerLogic™ ION9000 series
2. Click the Assistant tab and clear the Configuration Checklist check box.
NOTE: ION Setup also performs a configuration test and displays results
when configuring certain features such as the Sag/Swell or Transient Logging
wizard in the Power Quality setup assistant.
Basic tab
Advanced tab
Scale Rev Param ON, OFF Specifies whether revenue readings are
presented as primary or secondary side
values (ON = primary side, OFF =
secondary side)
1. Demo mode is for demonstration only, and does not use the meter input terminals to display values.
7EN02-0390-04 33
PowerLogic™ ION9000 series Installation and commissioning
34 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Communications
Communications overview
Communications is the transfer of data to and from the meter and is controlled by
a combination of hardware and software components in the meter.
For each connected communications port, the meter uses the applicable
communications protocol to establish communications with other devices or
software. The protocol manages the communications session and defines the set
of rules, commands and packet structure of the transmitted data. You can also
control which protocols are enabled or disabled on the meter.
NOTE: To maximize the performance of your power management system, it is
recommended that devices be connected directly to an Ethernet network.
Other means of controlling communications, such as who can access certain
types of meter data, are discussed in the security topics for the meter.
Your meter’s default protocol settings meet the needs of most systems with only
basic configuration. You can customize these settings to meet your specific needs.
These are advanced procedures that require an understanding of your meter’s
architecture, supported protocols, and the communications network and power
system that your meter is connected to.
Ethernet communications
Your Ethernet connection source should be installed in a location that helps
minimize the overall Ethernet cable routing length and complexity of your network.
The meter supports a single IP address for both physical Ethernet connections.
Your device’s second Ethernet port acts as an Ethernet switch to help simplify
network connections and reduce installation time and costs, by having shorter
Ethernet cable runs between devices without needing additional Ethernet routers
or repeaters. You cannot connect your meter to two different Ethernet networks.
The two Ethernet ports do not split the signal, so connecting both of the ports
should not impact your communications speed.
The meter uses dual-stack IPv4/IPv6 routing technology to manage network
communications and allow network hosts to communicate with the meter using
either IPv4 or IPv6.
7EN02-0390-04 35
PowerLogic™ ION9000 series Communications
DHCP 67 (68) 1
SFTP 22 2
Webserver (HTTPS)4 443 10
NTP 123 1
IEC 61850 102 5
By enabling or disabling TCP/IP protocols, you can control whether or not your
meter accepts new socket connection requests. Changing settings for one port
does not impact the other existing connections. Depending on the protocol, you
can also change the port number.
2. These 8 simultaneous connections are shared by ION, Modbus TCP, Modbus RTU over Ethernet, DLMS and DNP. You can have a
maximum of 3 DNP connections. You can have a maximum of 1 DLMS connection.
3. These protocols must be enabled for Modbus gateway functionality.
4. These are used for the meter’s webpages.
36 7EN02-0390-04
Communications PowerLogic™ ION9000 series
B LAN / WAN (Local Area Network / Wide Area Network), common subnet, no routers
7EN02-0390-04 37
PowerLogic™ ION9000 series Communications
Ethernet configuration
In order to use Ethernet communications, you must configure your device’s IP
settings.
You need to enter network information for any Ethernet servers used by the device
(for example, a DNS or email server). Contact your network system administrator
for your IP address and other Ethernet network configuration values.
NOTE: For meters that do not have a display, you must connect your meter
directly to your computer to set a unique IP address for each device or
configure the meter to use a DHCP server to acquire IP addresses.
It is recommended that you test your communications with the meter after
changing any communications-related settings (for example, communicating with
the meter using the fully-qualified domain name if using DNS or with assigned
addresses after these are provided by the DHCP server). In addition, make sure
that any software or other devices communicating with the meter are using the
new settings.
Protocol Format
IPv4 0.0.0.0 to 255.255.255.255
IPv6 :: to FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:FFFF:
FFFF
All meters ship from the factory with the IPv6 global address and IPv6 gateway
undefined (set to “::”). To communicate with the meter using IPv6 outside the local
network, you must configure these settings manually or use DHCP to assign the
addresses to the meter. Within the local network, you can use the meter’s IPv6
Link Local address.
38 7EN02-0390-04
Communications PowerLogic™ ION9000 series
IPv4 address W W W
IPv4 Subnet mask W W W
IPv4 Default gateway W W W
IPv4 Assignment W W W
Mode (DHCP/Stored)
IPv6 Assignment W W W
Mode (DHCP/Stored)
IPv6 gateway R W W
Ethernet Rx timeout — W W
Modbus TCP timeout — W W
Modbus gateway — W —
MAC address R R R
Ethernet primary DNS R W W
Ethernet secondary R W W
DNS
7EN02-0390-04 39
PowerLogic™ ION9000 series Communications
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
Contact your network system administrator for your IP addresses and other
Ethernet network configuration values.
1. Start ION Setup.
2. Open the Setup Assistant for your device.
3. Select Communications > Basic Ethernet and click the IPv4 or IPv6 tab.
4. Select the IP address then click Edit.
5. Select your IP address assignment mode.
IPv4
Use DHCP to obtain an DHCP The meter acquires its IP addresses from
IPv4 address your network’s DHCP server. The Device
Name and Domain Name fields are used to
define the meter’s fully-qualified domain
name (FQDN).
Use the following IPv4 Stored The meter uses the IP addresses that you
address manually enter for IPv4 (address, subnet
mask and gateway).
For IPv6, select the IPv6 Enabled check box to enable IPv6 communications
or clear it to disable IPv6 communications.
NOTE: The IPv6 Link Local address itself is factory set and is read-only.
IPv6
Use DHCP to obtain an DHCPv6 The meter acquires its IP addresses from
IPv6 address your network’s DHCPv6 server. The Device
Name and Domain Name fields are used to
define the meter’s fully-qualified domain
name (FQDN).
Use the following IPv6 Stored The meter uses the IP addresses that you
address manually enter for IPv6 (global address and
default gateway).
You can have different assignment modes for IPv4 and for IPv6.
6. Configure the settings for the selected mode then click OK.
The changes are saved to the meter. If ION Setup detects that the connection
information is already in use, you are prompted to confirm the change.
7. Click Yes to confirm the change or No to cancel.
An example of an instance where you might want to confirm the change is if
you are programming the meter to replace another meter already in service.
40 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Device name Contact your local network The Ethernet device name is
administrator for parameter used by DPWS for self-
values. discovery over Ethernet and as
the hostname to uniquely
identify your meter for DHCP
and DNS.
Domain name Contact your local network The Ethernet domain name for
administrator for parameter the network that the meter
values. resides on.
Global Address Contact your local network The Internet protocol address
administrator for parameter of your device.
values.
Default Gateway Contact your local network The address the meter uses to
administrator for parameter route communications to a
values. different network or subnet.
7EN02-0390-04 41
PowerLogic™ ION9000 series Communications
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
Contact your network system administrator for your IP addresses and other
Ethernet network configuration values.
42 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Domain name Contact your local network The Ethernet domain name for
administrator for parameter the network that the meter
values. resides on.
Primary DNS Contact your local network The IP address of your
administrator for parameter network’s primary DNS server,
values. if your network uses DNS.
7EN02-0390-04 43
PowerLogic™ ION9000 series Communications
Stored IPv6 Global Address Contact your local network The Internet protocol address
administrator for parameter of your device.
values.
Stored IPv6 Gateway Contact your local network The address the meter uses to
administrator for parameter route communications to a
values. different network or subnet. If
you do not set this or the
address is incorrect, you may
see slow communications or
communications errors.
The webpage also displays the acquired IPv6 settings if the Assignment mode is set to DHCP.
NOTE: To disable communications over IPv6, set Enable IPv6 in Advanced Settings to No.
NOTE: You must enclose an IPv6 address in square brackets when typing it in a web browser,
for example: “http://[fe80::260:78ff:fe04:5943]”.
Option Description
Stored The meter uses the IP addresses that you manually enter for IPv4
(address, subnet mask and gateway) and IPv6 (Global address,
gateway address).
DHCP/DHCPv6 The meter acquires its IP addresses from your network’s DHCP
server.
You can have different assignment modes for IPv4 and for IPv6.
If you set the IPv4 Assignment Mode to Stored, continue with the remaining
steps to configure stored IPv4 addresses. If you are using addresses
acquired from a DHCP server, press the down arrow to view the assigned
addresses.
4. Go to the Stored IPv4 Address Setup screen and press the Edit icon.
44 7EN02-0390-04
Communications PowerLogic™ ION9000 series
IP Address Contact your local Sets the IP address for the meter
network administrator for
parameter values. Your meter’s default IP address is
169.254.0.10
Subnet Mask Contact your local Used if subnetting applies to your network
network administrator for
parameter values. Your meter’s default subnet address is
255.255.0.0
Gateway Contact your local Used in networks with multiple segments
network administrator for
parameter values. Your meter’s default gateway address is
0.0.0.0
MAC Address Read-only Your meter’s media access control (MAC)
address
DHCP
The meter can function as a DHCP (Dynamic Host Configuration Protocol) client,
allowing a DHCP server to assign IP addresses to the meter.
The meter supports assignment of the following addresses by a DHCP server
when the Assignment Mode is set to DHCP:
• IPv4 IP Address
• IPv4 Subnet mask
• IPv4 Gateway
• IPv6 Global Address
• IPv6 Gateway
7EN02-0390-04 45
PowerLogic™ ION9000 series Communications
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
46 7EN02-0390-04
Communications PowerLogic™ ION9000 series
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
1. Open a web browser and enter your meter’s IP address in the address bar.
The webpage login is displayed.
2. Enter your login credentials.
3. Navigate to Setup > Ethernet.
4. Click Advanced Settings at the bottom of the screen.
5. Select YES or NO to enable or disable each configurable protocol.
6. Enter the port number for each configurable protocol.
7. Click Apply to send these settings to your meter.
7EN02-0390-04 47
PowerLogic™ ION9000 series Communications
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
NOTE: You cannot change the Ethernet port number assignments through the
display.
1. Press the Home button on the display.
2. Navigate to Setup Menu > Ethernet Port Enable Setup.
3. Press Edit. Enter your meter’s password, if prompted.
4. Press the up or down icons to navigate available Ethernet protocols. A gray
bar appears behind the active selection.
5. Press Enable/Disable.
6. Press Select to accept the change.
7. Press Select to confirm.
Serial communications
The meter supports serial communications through its onboard RS-485 ports.
RS-485
In an RS-485 network, there is one master device, typically an Ethernet to RS-485
gateway. It provides the means for RS-485 communications with multiple slave
devices (for example, meters). For applications that require only one dedicated
computer to communicate with the slave devices, a USB to RS-485 converter can
be used to connect to the master device.
Up to 32 devices can be connected on a single RS-485 bus.
RS-485 wiring
Connect the devices on the RS-485 bus in a point-to-point configuration, with the
(+) and (-) terminals from one device connected to the corresponding (+) and (-)
terminals on the next device.
RS-485 cable
Use a shielded 2 twisted pair or 1.5 twisted pair RS-485 cable to wire the devices.
Use one twisted pair to connect the (+) and (-) terminals, and use the other
insulated wire to connect the C terminals.
The total distance for devices connected on an RS-485 bus should not exceed
1200 m (4000 ft).
RS-485 terminals
C Common. This provides the voltage reference (zero volts) for the data plus and data minus
signals
Shield. Connect the bare wire to this terminal to help suppress signal noise that may be
present. Ground the shield wiring at one end only (either at the master or the last slave
device, but not both).
48 7EN02-0390-04
Communications PowerLogic™ ION9000 series
NOTE: If some devices in your RS-485 network do not have the C terminal,
use the bare wire in the RS-485 cable to connect the C terminal from the
meter to the shield terminal on the devices that do not have the C terminal.
RS-485 configuration
Before connecting your device to the RS-485 bus, use ION Setup, the meter
webpages or the display to configure your meter’s default RS-485 settings.
Your meter has two RS-485 connections.
Each RS-485 connection must have a unique unit identifier (Unit ID) and have the
following settings match the rest of the devices on the RS-485 bus:
• Protocol
• Baud rate
• Parity and stop bits
You can configure the following settings to help optimize communications
performance:
• RTS delay
• RS-485 bias
You can use a communications converter (USB to RS-485 or RS-232 to RS-485)
or an Ethernet gateway device to connect to your meter.
RS-485 Bias
You can use the RS-485 bias setting to fine tune communications.
Set the RS-485 bias to ON when the meter is acting as a master over RS-485
communications, and set the RS-485 bias to OFF when the meter is acting as a
slave. You can configure RS-485 biasing through ION Setup, the meter webpages
or the display.
• ION • EtherGate
• Modbus RTU • GPS: Truetime/Datum 1
• Modbus Master • GPS: Arbiter 1
• DNP 3.0 • GPS: Arbiter-Vorne 1
• DLMS • None 2
1 These protocol settings are used for connecting to a GPS receiver communicating in serial ASCII
format.
2 This protocol setting stops communications using this port.
7EN02-0390-04 49
PowerLogic™ ION9000 series Communications
Protocol ION, Modbus RTU, Sets the communications protocol for your
Modbus Master, DNP meter’s RS-485 port
v3.00, DLMS, EtherGate,
NOTE: the NONE setting stops
GPS: Truetime/Datum, communications using this port.
GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Baud Rate 2400, 4800, 9600, 19200, Sets the data rate, in bits per second
38400, 57600, 115200
50 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Protocol ION, Modbus RTU, Sets the communications protocol for your
Modbus Master, DNP meter’s RS-485 port
v3.00, DLMS, EtherGate,
NOTE: the NONE setting stops
GPS: Truetime/Datum, communications using this port.
GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Baud Rate 2400, 4800, 9600, 19200, Sets the data rate, in bits per second
38400, 57600, 115200
Serial Port 8N1, 8N2, 8E1, 8E2, 8O1, Sets the parity and stop bits for the port
8O2
RS485 Bias OFF, ON Turns on biasing when mastering devices
over the RS-485 port
1 Only applies to a subset of protocols.
7EN02-0390-04 51
PowerLogic™ ION9000 series Communications
Protocol ION, Modbus RTU, Sets the communications protocol for your
Modbus Master, DNP meter’s RS-485 port
v3.00, DLMS, EtherGate, NOTE: the NONE setting stops
GPS: Truetime/Datum, communications using this port.
GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Baud Rate 2400, 4800, 9600, 19200, Sets the data rate, in bits per second
38400, 57600, 115200
52 7EN02-0390-04
Communications PowerLogic™ ION9000 series
ION
ION is the native protocol and architecture of your meter.
The basic building blocks of ION architecture are the ION modules, each of which
is specialized to perform a specific task and contains data and instructions on how
to manage that data. ION modules are combined (linked) together to create the
meter’s functions and features. ION modules that are linked together to perform a
specialized task are called a framework, such as the Power Quality framework.
These different functional frameworks are then grouped together to define the
entire meter, and are collectively referred to as the device template.
Your meter ships with a default device template which provides extensive
capabilities. You can also configure your meter’s template to modify your meter’s
existing functions or to create new functions.
See the ION Reference, available from www.se.com for further information about
ION architecture and a detailed description of the different ION modules. See the
ION Device Template Reference, available from www.se.com, for details on the
modules and their configuration in your meter’s default template.
Modbus
Modbus is a master/slave communications protocol where the master initiates
transactions and the slave(s) responds with the requested information or action.
Your device can function as a Modbus slave or Modbus master, depending on
how it is configured. Your device comes with Modbus slave functionality
configured and ready to use. You can add custom Modbus information to the
default Modbus slave data provided by your device.
Key terms
Term Definition
Modbus gateway A communications method that lets you communicate through an
Ethernet gateway device to a Modbus serial network connected to
that device.
Modbus master A device that issues commands and receives responses from
Modbus slave devices. Serial Modbus networks can only have one
Modbus master per network.
7EN02-0390-04 53
PowerLogic™ ION9000 series Communications
Term Definition
Modbus RTU Serial Modbus protocol format; Modbus RTU transmits data using
binary. Master and slave devices must use the same format.
Modbus register/address Identifies the data to read/write. Modbus register maps are available
for Modbus slave devices and detail the information available from
the slave device. More than one register may be used to store a
single value.
Modbus slave A device that responds to Modbus commands and performs actions
or provides information back to the Modbus master. Most Modbus
networks contain multiple slave devices.
You can download your device’s Modbus map from www.se.com and get
additional information about the Modbus protocol from www.modbus.org.
Prerequisite Description
Port All devices must be communicating over Ethernet port 502 for Modbus TCP.
Prerequisite Description
The Modbus slave devices must have communications wiring to the Modbus
master.
Protocol Slave: for your meter to be a serial Modbus slave, the meter’s protocol must be
set to Modbus RTU. Master and slave devices must use the same format.
Master: for your meter to be a serial Modbus master, the meter’s protocol must
be set to Modbus Master.
Baud rate The baud rate must be the same for all devices on the serial Modbus network.
Stop bits and The communication stop bits and parity (for example, 8N1) must be the same
parity for all devices on the serial Modbus network.
Unit ID Each device on the serial Modbus network must have a unique unit ID (also
called the device address).
54 7EN02-0390-04
Communications PowerLogic™ ION9000 series
A. Ethernet
B. Your meter
C. Modbus slaves
For Modbus mastering, you must add the Modbus slave devices using ION Setup.
A. Ethernet
B. Your meter
C. RS-485 Modbus RTU
D. Modbus slaves
For Modbus mastering, you must add the Modbus slave devices using ION Setup.
Prerequisite Description
Modbus slave All Modbus slave devices must be communicating and appropriately
devices configured.
Protocol • Modbus mastering serial devices: the master’s serial port protocol must
be set to Modbus master.
• Modbus mastering Ethernet devices: the master must be communicating
to the slave devices over Ethernet port 502.
NOTE: Having more than one Modbus master on a serial Modbus network
may cause communication conflicts.
Mastered The Modbus master device must have the slave device information entered for
devices mastering.
7EN02-0390-04 55
PowerLogic™ ION9000 series Communications
If the meter is a Modbus master over TCP/IP, the Modbus TCP/IP and Modbus
RTU protocols must be enabled.
NOTE: Devices supporting multiple simultaneous Modbus TCP connections
can have communications delays. Adjust your network timeout settings to
accommodate this.
The meter as a Modbus master over TCP/IP attempts to communicate with a
slave device for up to 100 seconds (as per the RFC 1122 standard) before moving
on to the next slave device.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Communications > 3rd Party Protocols and click on the
Modbus Master tab.
4. Click Add to add a Modbus slave device.
The Modbus Device dialog appears.
5. Enter the Modbus slave information:
– Enter the Modbus slave device’s name and a label suffix (if applicable).
– Select the device type of the slave device from the Device Type drop-
down list box.
– Enter the unit ID of the Modbus slave device into the Slave ID text box.
– Select the serial or TCP connection from the Connected via drop-down
list box. This is the connection from the Modbus master to the slave
device.
6. Click Connections. The Modbus Master Connections dialog appears.
7. Select the tab that corresponds to the connection you are configuring (for
example, if you selected TCP Connection 1 from the Connected via drop-
down list box, select the TCP 1 tab) and configure it based on the connection
type.
Serial connection Select the serial communications port that is connected to the
Modbus slave devices from the Assigned Port list.
TCP connection Enter the IP address of the Modbus slave device, making sure that
the IP port is set to 502.
Make sure that the Modbus RTU and Modbus TCP/IP protocols are
enabled.
A. Modbus master
B. Ethernet Modbus TCP
C. Your meter
56 7EN02-0390-04
Communications PowerLogic™ ION9000 series
A. Modbus master
B. RS-485 Modbus RTU
C. Your meter
D. Modbus slaves
Your meter’s serial connection must be wired and configured correctly. The same
mode of serial communication must be used for all devices on the network.
Parameter Setting
See your device’s Modbus map, available from www.se.com for Modbus register
information.
Parameter Setting
7EN02-0390-04 57
PowerLogic™ ION9000 series Communications
See your device’s Modbus map, available from www.se.com for Modbus register
information.
Parameter Setting
See your device’s Modbus map, available from www.se.com for Modbus register
information.
58 7EN02-0390-04
Communications PowerLogic™ ION9000 series
16-bit data (one word) is transmitted with most-significant byte first and least-
significant byte second.
32-bit data (two words) is transmitted with the most-significant word first and the
least-significant word second.
Modbus commands
A Modbus master command to unit ID 0 is broadcast (sent to) all Modbus slave
devices. The only supported broadcast command is preset multiple registers.
For serial Modbus networks with only one slave device, the master can send
commands using the single connection, one-to-one address of unit ID 248,
regardless of the slave device’s actual unit ID.
Modbus implementation
Your meter's Modbus implementation includes exception codes, invalid register
responses, fixed and configurable register maps, and security.
7EN02-0390-04 59
PowerLogic™ ION9000 series Communications
Float32 0xFFC00000
Modbus security
Your meter’s onboard security options include Modbus-specific settings. These
security settings may need to be configured in order to write Modbus data to the
meter.
60 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Modbus map
Your meter’s default Modbus register information (map) is available for download
from www.se.com.
The Modbus register information includes:
• registers and mapped values
• formats and scaling
• additional details where applicable
NOTE: Your meter’s Modbus registers are specified differently than previous
devices using ION architecture. If you are configuring Modbus slave
information on your meter, confirm you are using the appropriate Modbus
register addressing. Refer to your meter’s Modbus map for more information.
Your meter has a fixed (static) register map which contains the most common
metering values. This map is defined by a series of Data Mapping modules, which
also determine the values shown on the meter webpages or the display. The Data
Mapping modules are named based on the type of information they map to
Modbus:
Data Mapping Dmd Modules Maps kW, kVA and kVAR demand data such as
kW sd del (sliding demand kilowatts delivered)
as well as current demand such as I a sd (sliding
demand phase A current).
Data Mapping Egy Modules Maps kWh, kVAh and kVARh delivered and
received data, including conditional, quadrant
and incremental energies.
Data Mapping EN Prev Modules Maps previous interval EN50160 power quality
compliance data.
Data Mapping I/O Modules Maps input metering data, alarms, resets and
reset counts.
Data Mapping Meas Modules Maps measured data from the standard and
high-speed Power Meter module.
Data Mapping Stats Modules Maps statistical low, mean and high data values,
such as I a mean (phase A current average
value).
Data Mapping TOU Modules Maps time-of-use (TOU) data, such as seasons,
rates, and per-season demand such as kW sd
rec A (sliding demand kilowatts received in
season A).
You can add extra Modbus information or duplicate information that is already in
the fixed map to different Modbus registers using Modbus Slave modules.
See the ION Reference available from www.se.com for detailed information about
Data Mapping modules and Modbus Slave modules.
7EN02-0390-04 61
PowerLogic™ ION9000 series Communications
Option Description
Default Sets your meter to use the default Modbus map. Any custom Modbus
slave data is removed.
NOTE: You can download your meter’s Modbus map information
from www.se.com.
Modified Add Modbus information in addition to the meter’s default Modbus
map.
Custom Removes the meter’s default Modbus map so that all registers are
available, and you can create a completely custom Modbus map.
NOTE: Use this option if you want to make your meter’s Modbus
map identical to a device that it is replacing, for example in a
retrofit application.
Disabled Removes your meter’s Modbus data map. Modbus functions are
unaffected, but no meter Modbus data is available.
6. In the Modbus Slave Map Setup screen, you can modify parameters by
clicking Edit, or add parameters by clicking Add.
The Modbus Register screen is displayed.
7. Configure the Modbus register information and click OK to return to the
Modbus Slave Map Setup screen.
a. Source: click Select and chose a source from the Parameter Selection
screen. Select Show all available registers to see a complete list of the
parameters available on your meter. Click OK.
b. Address: enter the Modbus address that will hold the Source data.
NOTE: If you hover your mouse over the Address field, a tooltip
indicates the Modbus function code and start address to send for
retrieving the data.
c. Format: select the Modbus data format from the list.
d. Scaling: select the scaling value from the list, or select Custom and click
Scales to configure custom scaling.
8. In the Modbus Slave Map Setup screen you can click Delete to remove a
Modbus register, Set Name to create a new name for the set of additional
data mapped to Modbus, or Save As to save the additional data you have
mapped to Modbus as a separate file.
9. Click Finish to complete your meter’s Modbus slave configuration and return
to the Setup Assistant.
Ethernet gateway
Ethernet gateway is a communications method that allows you to communicate
through a gateway device to a serial network.
62 7EN02-0390-04
Communications PowerLogic™ ION9000 series
RS-485
120 Ω
A. LAN/WAN
B. Ethernet gateway meter
C. Serial RS-485 network of devices
D. Terminating resistor
There are two types of Ethernet gateways that you can configure on your meter:
• EtherGate: a single TCP connection communicates through the gateway
meter to a serial network of devices.
• Modbus gateway: up to a maximum of 32 Modbus master TCP connections
communicate through the gateway meter to a serial network of Modbus
devices.
EtherGate
The meter can function as an Ethernet gateway (EtherGate).
EtherGate is a protocol-agnostic communications method that lets you
communicate through a gateway meter to a serial network of devices letting ION
or other RTU over TCP data pass through the gateway meter to other networks,
including third party systems. When a meter installed on the Ethernet network has
EtherGate enabled, a master device (such as an energy management system)
can communicate through the gateway meter to a serial network of devices wired
to the gateway meter’s COM port. You must create an additional communications
connection to the gateway meter in order to read its information.
NOTE: EtherGate supports only one master device.
Before proceeding, make sure you have completed the following tasks:
• Confirm the serial network of devices are wired to the gateway meter’s serial
communication port.
• Confirm all serial devices are configured to have the same baud rate, serial
port settings (for example, 8N1), and protocol (ION).
• Confirm each serial device has a unique unit identifier (unit ID/address).
• Confirm your gateway meter is communicating over Ethernet.
7EN02-0390-04 63
PowerLogic™ ION9000 series Communications
Parameter Setting
Protocol EtherGate
Baud Rate
Serial port settings must match the settings for all connected
Serial Port serial devices
Parameter Setting
Protocol EtherGate
Baud Rate
Serial port settings must match the settings for all connected
Serial Port serial devices
You can use ION Setup to create an Ethernet gateway site and access the serial
network of devices connected through the EtherGate meter.
Parameter Setting
Protocol EtherGate
Baud Rate
Serial port settings must match the settings for all connected
Serial Port serial devices
You can use ION Setup to create an Ethernet gateway site and access the serial
network of devices connected through the EtherGate meter.
64 7EN02-0390-04
Communications PowerLogic™ ION9000 series
7EN02-0390-04 65
PowerLogic™ ION9000 series Communications
66 7EN02-0390-04
Communications PowerLogic™ ION9000 series
HTTPS
HTTPS (Hypertext Transfer Protocol Secure) is an extension of HTTP and is used
by a web browser to establish communication between a client computer and the
meter’s web server hosting webpages.
HTTPS uses Transport Layer Security (TLS) encryption to secure the
communications channel and protect exchanged data between the client and the
server. When configured to use HTTPS, the meter uses the self-signed certificate
installed on its web server.
You can view the meter’s webpages by entering the meter’s IP address on a web
browser.
The meter uses port 443 for HTTPS by default.
HTTPS With HTTP Redirect Redirects all HTTP requests to use HTTPS.
1. Open ION Setup > select the meter > Setup Assistant.
2. Communications > Advanced Ethernet > Protocols tab.
3. Select the Web protocol and click Edit.
4. Select a web protocol setting.
5. Change the default Assigned Port Numbers for HTTPS With HTTP Redirect
and HTTPS. This requires appending the changed port number for HTTPS
access to the meter’s webpages, for example: <meter IP address>:<changed
https port number>.
7EN02-0390-04 67
PowerLogic™ ION9000 series Communications
SFTP
Your meter has an internal SSH server that can be accessed using an encrypted
connection with SFTP (Secure File Transfer Protocol) client software. The SSH
server hosts an internal SFTP site and stores files in the meter’s flash memory,
such as webpages, COMTRADE records and firmware files.
68 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Key terms
Term Definition
Agent Software resident on the managed device which interfaces between the
device and the NMS.
Managed device Your meter in the SNMP network.
Community name/ A text string that helps authenticate requests between the managed
string device and the NMS.
7EN02-0390-04 69
PowerLogic™ ION9000 series Communications
Term Definition
OID An object identifier that uniquely identifies and labels a managed object in
the MIB.
Trap receiver An NMS that is configured to receive traps and whose IP address is an
SNMP trap destination.
A. Trap receiver(s)
B. SNMP agent (meter)
C. NMS with SNMP manager software and MIB file installed
SNMP trapping
SNMP trapping allows your meter’s agent to notify the NMS of events with an
unsolicited SNMP message (a “trap” of the meter’s alarm event).
You can enter up to four IP addresses for SNMP trap notification for generic and
enterprise-specific traps. For enterprise traps, you must also define the number of
events or maximum time delay before SNMP traps are sent to the NMS.
SNMP trapping is only supported on SNMP v2.
70 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Parameter Description
Trap Rcvr1 Addr to Enter up to four trap receiver IP addresses where trap messages will
Trap Rcvr4 Addr be sent.
Read only Enter the community string used for SNMP get (read-only) requests.
community
Read write Enter the community string used for SNMP set (read/write) requests.
community
NOTE: You can use the read/write community string for SNMP
get (read-only) requests.
SNMP Port Number 161 (default) Enter your meter’s SNMP port number.
Read-only Community Name - Enter the community string used for SNMP get (read-only) requests.
Read-write Community Name - Enter the community string used for SNMP set (read/write) requests.
NOTE: You can use the read/write community string for SNMP get (read-
only) requests.
Enable SNMP Traps Enable/disable Enables or disables SNMP trapping on your meter.
Enable High Priority Alarms Yes/no Enables trapping of events that create high priority alarms.
Enable Med Priority Alarms Yes/no Enables trapping of events that create medium priority alarms.
Enable Low Priority Alarms Yes/no Enables trapping of events that create low priority alarms.
Report Buffer Size 1–30 Enter the maximum number of trap messages to be stored before the trap
messages are sent. Traps are sent when the number of trap messages is
equal to or greater than this value.
Report Hold Time 1–300 seconds Enter the maximum duration for trap messages to be held. Trap
messages are sent when the time after a trap event has occurred is equal
to or greater than this value.
Trap Rcvr1 Addr to - Enter up to four trap receiver IP addresses, where trap messages will be
Trap Rcvr4 Addr sent.
7EN02-0390-04 71
PowerLogic™ ION9000 series Communications
SNMP implementation
MIB files
Your meter is compliant with MIB-II as defined by the standard MIB file RFC 1213.
SNMP requires that you load your meter’s ION MIB file (available for download
from www.se.com) into the NMS.
You must install RFC 1213, which is required to read basic network information for
the meter (for example, TCP/IP traffic or number of packets received), if it is not
included with your SNMP manager software.
Community strings
A community string is a text string which acts to help authenticate requests from
the NMS to your meter.
There are two community strings on your meter:
• Read Only Community: this community string is used by SNMP get (read-
only) requests. The read only community string’s initial factory-set value is
public.
• Read Write Community: this community string is used by SNMP set (read/
write) requests. The read write community string’s initial factory-set value is
private.
NOTE: You can also use the read write community string for SNMP get (read-
only) requests.
If your meter receives an incorrect community string, it generates an
AuthenticationFailure trap.
System strings
A system string is a text string which can be configured to provide information
about your meter.
There are three system strings on your meter:
• System contact: enter the name of the SNMP system administrator.
• System name: enter a descriptive name for your meter.
• System location: enter a description of your meter’s location.
Low 64–127
Medium 128–191
High 192–255
72 7EN02-0390-04
Communications PowerLogic™ ION9000 series
NOTE: The number of events or maximum time delay settings only apply to
enterprise SNMP traps.
See the ION Reference, available from www.se.com, for detailed information on
the SNMP Mapping, SNMP Options and Alarm Options modules.
If you change your meter’s default values, you must modify the custom MIB file to
reflect the new values.
Changing your meter’s default SNMP configuration assumes that you have an
advanced understanding of ION architecture, SNMP, and the communications
network and power system that your meter is connected to.
See the ION Reference, available from www.se.com, for detailed information on
the SNMP Mapping module.
7EN02-0390-04 73
PowerLogic™ ION9000 series Communications
3. Save your meter’s MIB file. Keep the original file extension of .MIB.
This example shows an original and an updated OID entry in an MIB file, where
the default meter value of voltage line-to-neutral phase A is modified in the meter’s
SNMP Mapping module and is now connected to voltage line-to-neutral phase C.
Vln_a OBJECT-TYPE
ACCESS read-only
STATUS mandatory
DESCRIPTION “Host Meter Voltage Line A to Neutral Units = V (Volts)” ::= { Schneider Electric 34 }
You must update the variable name and description to match the meter values
connected to the SNMP Mapping module:
The SNMP client software reads the original and updated file as follows:
Original Updated
Description: “SNM1 Input 1 - Voltage (line-to- Description: “SNM1 Input 1 - Voltage (line-to-
neutral) phase A” neutral) phase C”
IEC 61850
IEC 61850 is an Ethernet-based communications protocol designed for electrical
substations.
Your meter can be integrated into an IEC 61850 system as an Intelligent
Electronic Device (IED) or server that supports concurrent IEC 61850 client
connections and an SFTP connection.
Go to the IEC International Electrotechnical Commission website at www.iec.ch
for more information on the IEC 61850 protocol.
Refer to the IEC 61850 and ION technology protocol document at www.se.com for
information about setup and configuration.
74 7EN02-0390-04
Communications PowerLogic™ ION9000 series
Watch the video on How to Enable IEC 61850 Functionality on Your Meter
7EN02-0390-04 75
PowerLogic™ ION9000 series Communications
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1. Open SFTP client software. See “SFTP”, page 68 for information connecting
with SFTP client software.
2. Connect to the meter using the meter’s IP address and SFTP port number.
See “Protocols, ports and connections”, page 36 for information on port
numbers
3. Open the IEC61850 folder in SFTP file directory and delete the CID file.
4. Close SFTP client software.
76 7EN02-0390-04
Communications PowerLogic™ ION9000 series
DNP
Your meter can be integrated into a DNP network as a DNP slave.
The Distributed Network Protocol Version 3.0 (DNP 3.0) is an open protocol used
in the electric utility industry for communications and interoperability among
substation computers, Remote Terminal Units (RTUs), Intelligent Electronic
Devices (IEDs, e.g. meters), and master stations.
DLMS/COSEM
The Device Language Message Specification (DLMS) is described by the
international standard IEC 62056. It defines structured modeling and meter data
exchange for an interoperable environment.
DLMS supports applications such as remote meter reading, remote control, and
value-added services for metering different kinds of energy, such as electricity,
water, gas or heat.
COSEM stands for Companion Specification for Energy Metering. It is an interface
model for communicating with energy metering equipment, providing a view of the
functionality available through the communications interfaces. The model uses an
object-oriented approach.
The COSEM model allows for a manufacturer-independent and controlled method
to identify, retrieve and interpret the information held in any meter.
See the DLMS/COSEM and ION technology technote for more information about
how DLMS is implemented on your meter.
7EN02-0390-04 77
PowerLogic™ ION9000 series Inputs / outputs
Inputs / outputs
I/O overview
Your meter has onboard digital I/O which can be increased by adding optional
digital and analog I/O modules to expand your meter’s I/O capabilities.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
78 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
Internally/
Digital Input Port S1–S8 S1–S8 Port S1–S8 externally excited
Digital Input Port A/B/C/D S1– S1–S6 Port A S1–S6 Option module
S6 digital inputs
Port B S1–S6
Port C S1–S6
Port D S1–S6
Digital Output Port A/B/C/D D1– Relay 1–Relay 2 Port A D1–D2 Option module
D2 digital output
Port B D1–D2
Port C D1–D2
Port D D1–D2
Analog Input Port A/B/C/D A1– A1–A4 Port A A1–A4 Option module
A4 analog input
Port B A1–A4
Port C A1–A4
Port D A1–A4
Analog Output Port A/B/C/D Q1–Q2 Port A Q1–Q2 Option module
Q1–Q2 analog output
Port B Q1–Q2
Port C Q1–Q2
Port D Q1–Q2
NOTE: When configuring your meter, the configuration interface may show all
of the possible ports, regardless of what is physically available on your meter.
See the ION Reference, available from www.se.com for more information about
ION modules.
7EN02-0390-04 79
PowerLogic™ ION9000 series Inputs / outputs
80 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
Analog inputs
Analog input applications
You can use an analog input to monitor an analog signal, for example a flowmeter,
to monitor how much water flows through a pipe.
For analog input operation, your meter takes an analog input signal and provides
the resulting scaled value.
Your meter’s analog I/O option modules can measure either low voltage or current
using standard analog transducers such as 4–20 mA current transducers.
NOTICE
EQUIPMENT DAMAGE
• Ensure the analog input is configured for the correct voltage or current mode
before connecting or activating the current transducer.
• Do not exceed the device’s ratings for maximum limits.
Failure to follow these instructions will result in equipment damage.
7EN02-0390-04 81
PowerLogic™ ION9000 series Inputs / outputs
Analog sensor Meter’s analog input signal Analog input register values
0–50 psi represented by a 4–20 mA analog input range Full scale = 50 (psi)
0–50 psi represented by a 0–20 mA analog input range5 Full scale = 50 (psi)
If the sensor’s output range does not match your meter’s hardware limits, you
must calculate the full scale and/or zero scale values by analyzing the system.
See the ION Reference, available from www.se.com, for detailed information
about the Analog Input module and full scale and zero scale calculations.
Zero scale 0 to ±109 The minimum source value that matches the minimum
analog input signal.
Full scale 0 to ±109 The maximum source value that matches the
maximum analog input signal.
Update Rate One Second/ Defines how frequently the input is updated.
High Speed
Analog outputs
Analog output applications
You can use an analog output to send a signal to an external analog input, for
example an analog-controlled valve, to modify a water pipe’s valve position in
order to change the flow rate.
5. Analog I/O option module must have firmware version v1.2 or later.
82 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
For analog output operation, your meter takes an input value and scales it to the
appropriate signal value to send out the physical analog output port.
Your meter’s analog I/O option modules can output either low voltage or current
using standard analog transducers such as 4–20 mA current transducers.
Normalized: 0.83
0–120 kW range Full scale = 120 (kW) 0–20 mA range6
Normalized: 0.83
If your meter’s analog output range does not match the range of the connected
analog sensor, you must calculate the full scale and zero scale values by
analyzing the system.
See the ION Reference, available from www.se.com for detailed information about
the Analog Output module and full scale and zero scale calculations.
6. Analog I/O option module must have firmware version v1.2 or later.
7EN02-0390-04 83
PowerLogic™ ION9000 series Inputs / outputs
3. Navigate to Expansion Modules > Option I/O Modules and select the
module tab that corresponds to the option module with the analog output you
want to configure.
4. Select the analog output channel and click Edit. Enter the meter password if
prompted. The setup screen for that analog output is displayed.
5. Configure the analog output by selecting the parameter and clicking Edit.
Zero scale 0 to ±109 The minimum source value that matches the minimum
analog output signal.
Full scale 0 to ±109 The maximum source value that matches the
maximum analog output signal.
Digital inputs
Digital input applications
Digital inputs are typically used for monitoring the status of switches or contacts,
such as status contacts on circuit breakers.
They can also be used for pulse counting or input metering applications, such as
WAGES (water, air, gas, electricity, steam) monitoring, or conditional energy
applications, or IRIG-B time synchronization.
Pulse mode
If you set Input Mode to PULSE, a pulse is generated at the Trigger output when
the State output changes from OFF-to-ON. No pulse is generated when State
changes from ON-to-OFF.
ON
Digital input signal OFF
ON
State output
OFF
Trigger output
(Input Mode = PULSE)
KYZ mode
If you set Input Mode to KYZ, a pulse is generated at the Trigger output for each
change of state transition, i.e. from OFF-to-ON and from ON-to-OFF transitions.
ON
Digital input signal OFF
ON
State output
OFF
Trigger output
(Input Mode = KYZ)
84 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
A/C mode
If you set Input Mode to A/C, the digital input port is configured to detect the
presence of a low voltage AC signal. The next illustration shows how a digital input
can be used to monitor the operation of a low voltage AC fan controller.
7EN02-0390-04 85
PowerLogic™ ION9000 series Inputs / outputs
5. Once the parameter has been configured, click OK to save the setting to the
meter.
Input Mode Pulse, KYZ, A/C, Specifies how the meter processes the
signal:
IRIG-B1
• Pulse: the meter counts an entire pulse
(from off-on to on-off) as one input.
• KYZ: the meter counts a transition
(from off-on or from on-off) as one input.
• A/C: the meter detects analog signals
where the ON condition is based on the
presence of an AC signal.
• IRIG-B1: the meter detects an IRIG-B
time synchronization signal.
Assigned Port Defined by your meter’s Your meter’s physical digital input port.
hardware
EventLog Mode Log Off/Log On Specifies if events generate log entries.
86 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
6. Once the parameter has been configured, click OK to save the setting to the
meter.
Input Mode Pulse, KYZ, Specifies how the meter processes the signal:
A/C, IRIG-B1
• Pulse: the meter counts an entire pulse (from off-
on to on-off) as one input.
• KYZ: the meter counts a transition (from off-on or
from on-off) as one input.
• A/C: the meter detects analog signals where the
ON condition is based on the presence of an AC
signal.
• IRIG-B1: the meter detects an IRIG-B time
synchronization signal.
Polarity Inverting/Non- Specifies if the signal from the digital port is inverted or
Inverting not inverted.
Debounce 0.000–1.000 Specifies how long (in seconds) the signal must remain
in a state to be considered a valid state change.
WAGES monitoring
WAGES monitoring allows you to record and analyze all energy sources and
utilities usage.
Your system may use several different types of energy. For example, you may
consume steam or compressed air for industrial processes, electricity for lights
and computers, water for cooling and natural gas for heating. WAGES monitoring
collects the usage information from all these different energy sources to enable a
more complete energy analysis.
WAGES information can help you:
• Identify losses or inefficiencies.
• Modify demand to reduce costs.
• Optimize energy source usage.
WAGES example
This example shows WAGES monitoring for a water flow meter.
You can connect your meter’s digital input to a transducer that sends a pulse for
every 15 kiloliters (4000 US Gal) of water. After configuring an input metering
channel and assigning it to the digital input, the meter is able to detect and record
the incoming pulses. An energy management system can then use the information
from the meter to perform WAGES analysis.
7EN02-0390-04 87
PowerLogic™ ION9000 series Inputs / outputs
30
Input metering
Your meter’s digital inputs can be used to count pulses from transducers and
convert the pulses to energy measurements.
Your meter’s input metering channels count pulses received from the digital inputs
assigned to that channel. The incoming pulses are used in calculating and
measuring consumption data (e.g., BTU, kWh, L, kg). Each channel must have the
following values configured to match the pulse data:
• Pulse Weight: the pulses per unit value.
• Unit Code: the unit of measure associated with the monitored value.
• Demand Code: for time-based values (such as kWh), this provides the
associated demand units (kW) for demand calculations; for other values
(such as kg), this can be configured to provide rate information (kg/h or kg/s).
• Mode: whether a pulse is based on a complete pulse or a transition.
For example, if each complete pulse represents 125 Wh, you can configure for Wh
pulsing as follows:
• Pulse Weight = pulses/Wh = 1/125 = 0.008
• Unit Code = Wh
• Demand Code = kW (this is automatically set)
• Mode = pulse
If you want to configure for kWh pulsing, you must adjust the pulse weight
calculation and unit code as follows:
• Pulse Weight = pulses/kWh = 1/0.125 = 8
• Unit Code = kWh
See “Meter resets”, page 219 for details about performing a meter reset.
88 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
Parameter Description
Demand Period Enter the frequency in minutes that input metering data is calculated in
your energy management system.
Source ID Enter a data identifier. This value is added to the input metering channel’s
output register labels to uniquely identify the data within your energy
management system.
NOTE: You must select a Unit for this field to appear.
7EN02-0390-04 89
PowerLogic™ ION9000 series Inputs / outputs
10. Configure your meter to log the input metering data if required.
Parameter Description
Demand Period Enter the frequency in minutes that input metering data is calculated in
your energy management system.
Scaling Select the scaling value based on the relationship between Units and Rate.
Time Base Select the value and units to match the Rate.
Digital outputs
Digital output applications
Digital outputs are typically used in switching applications, for example, to provide
on/off control signals for switching capacitor banks, generators, and other external
devices and equipment.
The digital output can also be used in demand synchronization applications,
where the meter provides pulse signals to the input of another meter to control its
demand period. The digital output can also be used in energy pulsing applications,
where a receiving device determines energy usage by counting the kWh pulses
coming from the meter’s digital output port.
90 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
4. Configure the digital output by selecting the parameter and clicking Edit.
Enter the meter password if prompted.
Source Digital/Boolean Link this input to the value that drives the
state of the digital output.
Force ON Pulse Link this input to a pulse that forces the digital
output on for the PulseWidth duration,
regardless of the Source input.
Force OFF1 Pulse Link this input to a pulse that forces the digital
output off.
Normal1 Pulse Pulsing this input will switch the driver of the
digital output from Force ON to Source.
7EN02-0390-04 91
PowerLogic™ ION9000 series Inputs / outputs
5. Configure the digital output by selecting the parameter and clicking Edit.
Source Digital/Boolean Link this input to the value that drives the state of the
digital output.
Force ON Pulse Link this input to a pulse that forces the digital output
on for the PulseWidth duration, regardless of the
Source input.
Force OFF1 Pulse Link this input to a pulse that forces the digital output
off.
Normal1 Pulse Pulsing this input will switch the driver of the digital
output from Force ON to Source.
Energy pulsing
You can configure the meter’s energy pulsing LEDs or onboard digital outputs for
energy pulsing applications.
When an LED or output is set to energy pulsing, the meter sends a readable pulse
or signal based on the measured energy source value. This pulse can be used for
accuracy verification or as an input to another energy monitoring system.
NOTE: The energy pulsing LEDs are configured in pairs. For example,
changing the energy source value will change it for both the regular and
infrared LEDs.
NOTE: To modify your default energy source value, go into the advanced
mode of ION Setup and modify the associated Calibration Pulser module. This
is an advanced procedure that should only be performed if you have advanced
knowledge of ION and the power system your meter is connected to.
See the ION Reference, available from www.se.com, for more information.
See “Alarm and status LED indicators”, page 108 for information about other
LED indicators.
92 7EN02-0390-04
Inputs / outputs PowerLogic™ ION9000 series
Parameter Description
Source Link this input to the value that you want to pulse on the LED.
Enable Configuring this setting should only be performed by users with advanced
knowledge of ION, the device template and the power system the device is
connected to.
Int Mode Specifies the integration mode for the LED (forward, reverse, absolute or
net).
Pulse Width The minimum time in seconds between LED pulse transitions.
Pulser Mode Select when the energy pulsing LEDs will pulse:
• Always: the energy pulsing LEDs are always pulsing based on their
energy source value.
Pulse ovrld Pulsing normally indicates that the energy pulsing LED should be
operating normally.
Pulsing suspended indicates that the energy pulsing LED is not able to
pulse quickly enough. Modify the Kt value to decrease the number of
energy pulses or decrease the pulse width, if supported by the device
collecting pulses.
7EN02-0390-04 93
PowerLogic™ ION9000 series Inputs / outputs
Parameter Description
Kt The amount of energy source required to trigger the digital output. For
example, in the Wh Del tab, the Kt value would be amount of real energy
delivered (Wh Del) per pulse.
Port Select an output port from the list. Only available output ports are shown
(ports that are not associated with another function).
(energy source) Pulsing normally indicates that the output port should be operating
ovrld normally.
Pulsing suspended indicates that the output port is not able to pulse
quickly enough. Modify the Kt value to decrease the number of energy
pulses.
94 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
Webpages
Webpage interface
Your meter comes with default webpages that contain typical elements.
B Username
C Main menu
D Webpage menu
E Webpage content
NOTE: This graphic is representative only, and your meter’s webpages may
appear differently than shown.
Monitoring
Trending & Forecasting Select the target and interval for trending and forecasting and view the results.
Waveforms View waveforms from your meter, using the meter’s COMTRADE files
Control
Resets Perform resets, and view when previous resets were performed.
7EN02-0390-04 95
PowerLogic™ ION9000 series Webpages
Diagnostics
Statistics • Communications
• Ethernet
• Serial Port
• Meter - Basic
• Meter - Advanced
Phasor Diagram View the phasor diagram and numeric values.
Setup
Date & Time Configure your meter’s time and time synchronization.
Maintenance
By default the Maintenance menu is empty, and the menu is not displayed until information is
added to it.
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate to and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
96 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
1. Open a web browser and enter your meter’s IP address in the address box.
The webpage login prompt is displayed.
If the browser cannot connect to the webserver, check the web protocol
setting.
2. Enter a valid username and password.
3. Select your desired Language from the drop-down list, and click Log In.
Your meter’s webpages are displayed. The default page is the Monitoring
webpage, showing real-time data.
4. Select the main menu tab that corresponds to the category of information you
want to view, and select the webpage menu from the list on the left.
The webpage content is displayed.
5. Click the webpage content headings to expand and view the meter’s data.
6. Select Setup to view and edit your meter’s configuration.
7EN02-0390-04 97
PowerLogic™ ION9000 series Webpages
Your custom webpage is available from the webpage menu under the Monitoring
(data viewing) or Setup (configuration) tab.
Watch the video on how to create custom webpages: How to Create Custom
Webpages for Your Meter
98 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
2. Navigate to the location on your local machine where you saved the webpage
.zip file.
NOTE: Extract the contents of the upgrade file.
3. Drag the resources and examples folders into the web folder. Confirm to
overwrite existing files when prompted.
The files are immediately transferred to the meter.
A HTML filename
B Content pane title
C Row heading
D Units
E Column heading
7EN02-0390-04 99
PowerLogic™ ION9000 series Webpages
1 SampleMonitorPane.html
2 <div class="content-fit">
3 <div class="accordion">
5 <div id="sample-readings">
6 <table class="datatable">
7 <tr>
8 <th> </th>
9 <th>$%localizedString(Minimum)#$</th>
10 <th>$%localizedString(Present)#$</th>
11 <th>$%localizedString(Maximum)#$</th>
12 </tr>
13 <tr class="minor">
18 </tr>
19 <tr class="minor">
24 </tr>
25 </table>
26 </div>
28 <div id="sample-energy">
29 <table class="datatable">
30 <tr>
31 <th> </th>
32 <th>$%localizedString(Present)#$</th>
33 </tr>
34 <tr>
37 </tr>
38 <tr>
41 </tr>
42 </table>
43 </div>
100 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
44 </div>
45
46
47 <script type="text/javascript">
48
49 instantaneousReadings.initInstantaneousReadings('sample-readings');
50
51 </script>
52 </div>
Line # Description
1 SampleMonitorPane.html
The HTML filename, including the HTML extension (.html). This filename must comply with SFTP filename requirements (no
spaces or special characters). The filename (without the HTML extension) is the name shown on the webpage menu.
4 <h3 target="sample-readings">
This creates the first webpage content pane. “sample-readings” is the name of the webpage content. This name must be
unique.
$%localizedString(Basic Readings)#$</h3>
Basic Readings is the title of the webpage content pane. This title is translated if possible.
5 <div id="sample-readings">
This must match the name of the webpage content in line 4.
9 <th>$%localizedString(Minimum)#$</th>
Minimum is the heading for the first column. This heading is translated if possible.
10 <th>$%localizedString(Present)#$</th>
Present is the heading for the second column. This heading is translated if possible.
11 <th>$%localizedString(Maximum)#$</th>
Maximum is the heading for the last column. This heading is translated if possible.
14 <td>$%localizedString(I a)#$
I a is the row heading. This heading is translated if possible.
<span unitsreg="I a"></span></td>
This displays the units that the meter has defined for the named register I a.
20 <td>$%localizedString(I b)#$
I b is the second row heading. This heading is translated if possible.
<span unitsreg="I b"></span></td>
This displays the units that the meter has defined for the named register I b.
27 <h3 target="sample-energy">
This creates the second webpage content pane. Sample-energy is the name of the webpage content. This name must be
unique.
$%localizedString(Energy Readings)#$</h3>
Energy Readings is the title of the webpage content pane. This title is translated if possible.
7EN02-0390-04 101
PowerLogic™ ION9000 series Webpages
Line # Description
28 <div id="sample-energy">
This must match the name of the webpage content in line 27.
32 <th>$%localizedString(Present)#$</th>
Present is the heading for the last column. This heading is translated if possible.
35 <td>$%localizedString(Active Energy)#$
Active Energy is the row heading. This heading is translated if possible.
<span unitsreg="kWh del-rec"></span></td>
This displays the units that the meter has defined for the named register kWh del-rec.
39 <td>$%localizedString(Reactive Energy)#$
Reactive Energy is the row heading. This heading is translated if possible.
<span unitsreg="kVARh del-rec"></span></td>
This displays the units that the meter has defined for the named register kVARh del-rec.
49 instantaneousReadings.initInstantaneousReadings('sample-readings');
Sample-readings is the unique name of the first webpage content name. This HTML code updates all of the webpage’s
values.
1Named registers are listed in the Modbus registers map. You can also reference a value by its ION handle using the following format: <td
regname=”_0x####”></td>.
102 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
A HTML filename
B Content pane title
C Sub-heading
D Row heading
1 SampleSetupPane.html
2
3 <div class="content-fit">
4 <form id="formSampleSettings">
5
6 <div class="accordion">
8 <div id="sample-basic">
9 <table class="formtable">
10 <tr>
11 <th> </th>
12 <th> </th>
13 </tr>
14 <tr>
15 <td>$%localizedString(Ethernet)#$</td>
16 <td> </td>
17 </tr>
18 <tr class="minor">
19 <td>$%localizedString(MAC Address)#$</td>
21 </tr>
22 <tr class="minor">
7EN02-0390-04 103
PowerLogic™ ION9000 series Webpages
25 </tr>
26 <tr class="minor">
27 <td>$%localizedString(IP Address)#$</td>
29 </tr>
30 </table>
31
32 </div>
33
34 <h3 target="sample-advanced">$%localizedString(Advanced Settings)#$</h3>
35 <div id="sample-advanced">
37 <tr>
38 <th> </th>
39 <th> </th>
40 </tr>
41 <tr>
43 <td><input type="text" name="TCP Keep Alive Minutes" class="small" /> <span unitsreg="TCP Keep
Alive Minutes"></span></td>
44 </tr>
45 <tr>
48 </tr>
49 </table>
50
51 </div>
52 </div>
53
54 <input type="submit" class="apply" value='$%localizedString(Apply)#$' />
55
56 </form>
57
58
59 <script type="text/javascript">
60
61 SetupPane.init('formSampleSettings');
62 formChangeDetection.initFormChangeDetection('#formSampleSettings', '#dialogFormChanges');
63
64 </script>
65 </div>
104 7EN02-0390-04
Webpages PowerLogic™ ION9000 series
Line # Description
1 SampleSetupPane.html
The HTML filename, including the HTML extension (.html). This filename must comply with SFTP filename requirements
(no spaces or special characters). The filename (without the HTML extension) is the name shown on the webpage menu.
4 <form id="formSampleSettings">
“formSampleSettings” is the name of the webpage content. This name must be unique
7 <h3 target="sample-basic">
This creates the first webpage content pane. “sample-basic” is the name of the webpage content. This name must be
unique.
$%localizedString(Basic Settings)#$</h3>
Basic Settings is the title of the webpage content pane. This title is translated if possible.
8 <div id="sample-basic">
15 <td>$%localizedString(Ethernet)#$</td>
19 <td>$%localizedString(MAC Address)#$</td>
This displays the value of the read-only named register MAC Address.
Ethernet Device Name is the row heading. This heading is translated if possible.
This displays the instantaneous value of the configurable named register Ethernet Device Name in a text-edit field.
The type must match the named register type, in this case, an alphanumeric string.
27 <td>$%localizedString(IP Address)#$</td>
This displays the instantaneous value of the configurable named register IP Address in a text-edit field.
The type must match the named register type, in this case, an alphanumeric string.
34 <h3 target="sample-advanced">
This creates the second webpage content pane. Sample-advanced is the name of the webpage content. This name must
be unique.
$%localizedString(Advanced Settings)#$</h3>
Advanced Settings is the title of the webpage content pane. This title is translated if possible.
35 <div id="sample-advanced">
This must match the name of the webpage content in line 34.
TCP Keep Alive Minutes is the row heading. This heading is translated if possible.
This displays the instantaneous value of the configurable named register TCP Keep Alive Minutes in a text-edit field.
The type must match the named register type, in this case, an alphanumeric string.
This displays the units that the meter has defined for the named register TCP Keep Alive Minutes.
NOTE: There are no defined units for TCP Keep Alive Minutes, so no units are displayed.
7EN02-0390-04 105
PowerLogic™ ION9000 series Webpages
Line # Description
Enable Web Server is the row heading. This heading is translated if possible.
Enable Web Server is the named register that is displayed. Named registers are listed in the meter’s registers map.
The type must match the named register type, in this case, an enumerated value that is displayed as a drop-down list.
61 SetupPane.init('formSampleSettings');
62 formChangeDetection.initFormChangeDetection('#formSampleSettings', '#dialogFormChanges');
This must match the webpage content name from line 4. This HTML code updates all of the webpage’s values.
106 7EN02-0390-04
Display PowerLogic™ ION9000 series
Display
Display overview
The display allows you to view meter data and perform basic configuration.
NOTE: The display backlight dims after a defined period of inactivity. When
the meter detects an unacknowledged active high priority alarm, the display
flashes until the alarm is acknowledged.
Display
A Display port
K Home button
L Power/status LED, green or red
Mode indicator
The display mode indicator identifies whether the meter is in normal (NORM),
alternate display (ALT) or test (TEST) mode.
Home button
Press the Home button to access display menus or return to the active menu.
Press the Home button twice to access the last data screen displayed or the
Summary screen, if in ALT mode.
The function of the home button varies:
• NORM mode: Displays Energy and Demand screens.
• ALT mode: Displays ALT mode display and setup menus. Select Normal
Display Mode from the ALT display menu to exit the ALT display mode.
7EN02-0390-04 107
PowerLogic™ ION9000 series Display
Alarm icon
The alarm icon indicates the highest level and state of alarms detected by your
meter.
For example, if the meter detects a low priority and a high priority active alarm, the
alarm icon indicates a high priority active alarm.
NOTE: Alarms can only be viewed and acknowledged through the display.
Icon Description
The alarm indicator changes to the historic alarm indicator of the appropriate
level when the alarm state is no longer detected by the meter.
NOTE: The display backlight flashes for unacknowledged high priority
active alarms.
Unacknowledged historic alarm indicator:
• Red: unacknowledged high priority historic alarm
• Yellow: unacknowledged medium priority historic alarm
NOTE: Low priority historical alarms are not indicated.
The active alarm indicator changes to the historic alarm indicator of the
appropriate level when the alarm state is no longer detected by the meter.
LED Description
108 7EN02-0390-04
Display PowerLogic™ ION9000 series
Display icons
Icons are displayed on the bottom of the screen.
NOTE: If the icon is gray, the function is not available.
Icon Description
Tap Left arrow to select item to the left or to return to the previous screen.
Overrange indication
If any value measured by the meter is too large to fit on the display, the meter
initially reduces the size of the text to try and make the value fit.
If the value is still too large to be displayed, the meter truncates the value starting
with the least significant digit, and encloses the truncated value in a red box.
7EN02-0390-04 109
PowerLogic™ ION9000 series Display
Auto-scaling feature
Measurement units on the meter display and webpages automatically scale,
depending on the value of PT Primary and CT Primary.
Voltage units are scaled based on the PT Primary value:
< 1000 V
1000–999,999 kV
< 1000 A
1000–999,999 kA
Power units are scaled according to the value of (CT Primary x PT Primary x 3):
Display screens
Display modes
Your meter has three display modes and provides access to your meter’s setup
screens:
• Normal Mode Screens (NORM). In Norm mode, your meter automatically
scrolls through a series of customizable display screens. You can add or
remove Norm mode display screens. If there are no Norm mode display
screens, the meter displays a message stating that there are no available
screens. To exit Norm mode, press the home button to access the display
modes selection screen.
• Alt Display Mode (ALT): In Alt mode, you can navigate to view the different
alternate screens. You cannot modify the default Alt mode display screens,
but you can add custom screens. To exit Alt display mode, select Normal
Display Mode to access the display modes selection screen.
• Test Mode (TEST): In Test mode, you can manually scroll through a series of
default screens. To exit Test mode, press the home button and select Exit
Test Mode.
110 7EN02-0390-04
Display PowerLogic™ ION9000 series
7EN02-0390-04 111
PowerLogic™ ION9000 series Display
Summary Summary
Basic Readings Voltage Volts L-L Volts ll Average Volts ll Min Volts ll Max
Volts Unbalanced
Current Current I Average I Min (Ia Ib Ic) I Min (I4) I Max (Ia Ib Ic) I Max (I4)
Frequency Frequency
Power Power Summary Power Total Power Total Min Power Total Max
Power Phase A
Power Phase B
Power Phase C
Power Factor Power Factor Power Factor Total Min Power Factor Total Max
Energy Received
Normal Display
Normal Mode Screens
Mode
Test Mode
Setup Menu
Alarms Active alarms, Active and historical alarms can be viewed and
historical alarms acknowledged.
112 7EN02-0390-04
Display PowerLogic™ ION9000 series
Setup menu
Meter configuration can be performed through the display.
Configure your meter’s security settings to allow front panel (display)
programming in order to set up the meter using the display.
NOTE: Your display may appear differently than shown, depending on your
meter’s power system, configuration and display settings.
NOTE: Some setup parameters cannot be configured when revenue security
is enabled.
7EN02-0390-04 113
PowerLogic™ ION9000 series Display
Setup Menu
Meter Setup Volts Mode Volts Mode PhaseOrder
PT/CT Setup PT Primary PT Secondary CT Primary CT Secondary I4 Primary I4 Secondary
Voltage Polarity Setup Va Polarity Vb Polarity Vc Polarity
Current Polarity Setup Ia Polarity Ib Polarity Ic Polarity I4 Polarity
Nominal Nominal Nominal
Nominal Values
Voltage Current Frequency
Ethernet Port Ethernet Port Enable
Enable/Disable
Enable Setup Setup
Communications IPv4 Assignment Mode
Setup Setup
Stored IPv4 Address Stored IPv4 Stored IPv4 Stored IPv4
MAC Address
Setup Address Subnet Mask Gateway
IPv6 Link Local Address
IPv6 Assignment Mode
Setup
Acquired IPv6 Global
Address
Ethernet Device Name
DNS Setup
COM1 Setup Protocol Baud Rate RX Timeout Unit ID Serial Port RS485 Bias
COM4 Setup Protocol Baud Rate RX Timeout Unit ID Serial Port RS485 Bias
NTP Address
SMTP Address
Backlight
Display Setup Screen Setup
Timeout
Measurement PF
Label & Symbol Setup Phase Label
Symbols Convention
Voltage Current Power
Numeric Format Setup Digit Grouping
Resolution Resolution Resolution
Date/Time/Clock Timezone
Date & Time Setup Time Format Date Format DST Offset
Setup Offset
Time Sync Time Sync
Clock Setup Clock Source
Source Type
114 7EN02-0390-04
Display PowerLogic™ ION9000 series
Press to display the Setup Menu. The Setup Menu lists the setup
selections on your meter.
Meter Setup and press to select the meter setup screens. The Volts
Mode setup screen is displayed.
3. Press to highlight Volts Mode. Press to edit the volts mode. The
Enter Password screen is displayed.
the next digit. Press to enter your password using the onscreen
keyboard. The Volts Mode configuration screen is displayed.
5. Press or to highlight the desired volts mode from the list, in this case,
7EN02-0390-04 115
PowerLogic™ ION9000 series Display
6. Press to confirm, and the new setting is applied to your meter. Press
to cancel and maintain your meter’s original setting.
the next digit. Press to enter the new value. When the confirmation
Display setup
You can configure basic display parameters using the display.
Screen setup
Phase Lbls ABC, 123 Sets the voltage and current phase labels
116 7EN02-0390-04
Display PowerLogic™ ION9000 series
Digit Grouping 1000.0, 1,000.0, 1 000,0 Specifies how digits are grouped for display
Volts Resolution 1., 1.X, 1.XX, 1.XXX, 1. Specifies the number of decimal places
XXXX displayed for voltages
Power 1., 1.X, 1.XX, 1.XXX, 1. Specifies the number of decimal places
Resolution XXXX displayed for power and energy measurements
Language setup
Select the language to be shown on the display.
By default, your meter has the following languages:
• English • Italian
• Spanish • Portuguese
• French • Russian
• German • Chinese (simplified)
7EN02-0390-04 117
PowerLogic™ ION9000 series Display
Display scaling
You can customize the units for metered values shown on the display and
webpages.
You can configure the units for voltage, current, power and energy values shown
on the display and webpages from their default units, and you can set the
resolution for the display. To identify which values will have the modified units,
refer to the display and web units information in your meter’s Modbus map,
available from www.se.com.
Icon Description
118 7EN02-0390-04
Display PowerLogic™ ION9000 series
Icon Description
7EN02-0390-04 119
PowerLogic™ ION9000 series Cybersecurity
Cybersecurity
Cybersecurity overview
This chapter contains up-to-date information about your product’s cybersecurity.
Network administrators, system integrators and personnel that commission,
maintain or dispose of a device should:
• Apply and maintain the device’s security capabilities. See “Device security
capabilities”, page 120 for details.
• Review assumptions about protected environments. See "Protected
environment assumptions", page 122 for details.
• Address potential risks and mitigation strategies. See “Potential Risks and
compensating controls”, page 123 for details.
• Follow recommendations to optimize cybersecurity.
Your device has security capabilities that:
• Allow it to be part of a NERC CIP compliant facility. Go to the North American
Electric Reliability Corporation website for information on NERC Reliability
Standards.
• Align with cybersecurity standards in the IEC 62443 international standard for
business IT systems and Industrial Automation and Control Systems (IACS)
products. Go to the International Electrotechnical Commission website for
information about the IEC62443 international standard.
To communicate a security topic affecting a Schneider Electric product or solution,
go to www.schneider-electric.com/en/work/support/cybersecurity/vulnerability-
policy.jsp.
WARNING
POTENTIAL COMPROMISE OF SYSTEM AVAILABILITY, INTEGRITY, AND
CONFIDENTIALITY
• Change default passwords to help prevent unauthorized access to device
settings and information.
• Disable unused ports/services and default accounts, where possible, to
minimize pathways for malicious attacks.
• Place networked devices behind multiple layers of cyber defenses (such as
firewalls, network segmentation, and network intrusion detection and
protection).
• Use cybersecurity best practices (for example: least privilege, separation of
duties) to help prevent unauthorized exposure, loss, modification of data and
logs, interruption of services, or unintended operation.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Product defense-in-depth
Use a layered network approach with multiple security and defense controls in
your IT and control system to minimize data protection gaps, reduce single-points-
of-failure and create a strong cybersecurity posture. The more layers of security in
your network, the harder it is to breach defenses, take digital assets or cause
disruption.
120 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
7EN02-0390-04 121
PowerLogic™ ION9000 series Cybersecurity
122 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
• Zone boundary protection – the control system provides the capability to:
◦ Manage connections through managed interfaces consisting of
appropriate boundary protection devices, such as: proxies, gateways,
routers, firewalls and encrypted tunnels.
◦ Use an effective architecture, for example, firewalls protecting application
gateways residing in a DMZ.
◦ Control system boundary protections at any designated alternate
processing sites should provide the same levels of protection as that of the
primary site, for example, data centers.
• No public internet connectivity – access from the control system to the
internet is not recommended. If a remote site connection is needed, for
example, encrypt protocol transmissions.
• Resource availability and redundancy – ability to break the connections
between different network segments or use duplicate devices in response to
an incident.
• Manage communication loads – the control system provides the capability to
manage communication loads to mitigate the effects of information flooding
types of DoS (Denial of Service) events.
• Control system backup – available and up-to-date backups for recovery from
a control system failure.
User Default account If you do not Change the default password of 0 (zero)
accounts settings are change the to help reduce unauthorized access. See
often the source default “Passwords”, page 130.
of unauthorized password,
access by unauthorized
malicious users. access can
occur.
Secure ION, Modbus, If a malicious For transmitting data over an internal
protocols DNP, DLMS, IEC user gained network, physically or logically segment
61850 and some access to your the network.
IT protocols are network, they
unsecure. could intercept For transmitting data over an external
communications. network, encrypt protocol transmissions
The device does over all external connections using an
not have the encrypted tunnel, TLS wrapper or a
capability to similar solution.
transmit data
encrypted using See “Protected environment
these protocols. assumptions”, page 122.
Cybersecurity configuration
Security configuration settings selected in ION Setup are applied to the meter and
can be saved as a Security Configuration File (.scf). The security log file
(SECURITY.LOG) contains the history of Security Configuration Files saved from
ION Setup.
The security log and Security Configuration Files are saved to the C:
\ProgramData\Schneider Electric\ION Setup\Security folder.
NOTE: The security log file can be changed by anyone with access to the
ProgramData folder.
Recommendations to optimize cybersecurity in a protected environment:
• Use Advanced Security mode.
• Store your meter’s Security Configuration File (.scf) in a protected location.
7EN02-0390-04 123
PowerLogic™ ION9000 series Cybersecurity
It is recommended to enable
Advanced security mode.
See:
• “Legacy security
support”, page 223 for
details on Legacy
security support.
• “Setting up Advanced
security”, page 223 for
information on enabling
Advanced security mode.
See “Harden the device”, page 133 for information about changing default security
settings.
User credentials and Use a single account to access the meter with a numeric
password robustness password for login.
User account lockouts and Define user account lockout criteria after unsuccessful login
timeouts attempts and define session timeout length.
User privileges User accounts with variable permissions to read access, test
mode or configuration privileges.
Webpages Disable or enable webpages for viewing meter data online using a
web browser (Web Server).
124 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
Cybersecurity event logs and Set-up cybersecurity event logs and alarms using event priorities.
reports
7EN02-0390-04 125
PowerLogic™ ION9000 series Cybersecurity
126 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
1. Open ION Setup > select the meter > Setup Assistant.
2. Security > Security Mode > Send. The Open Security Configuration file
dialog box opens.
3. Select the Security Configuration File (.scf) that contains the current meter
settings you want and click Open. The Security Options dialog box opens.
NOTE: Open the security log file to determine the .scf file you want. See
“Cybersecurity configuration”, page 123 for more information.
4. Click Exit.
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
1. Open ION Setup > select the meter > Setup Assistant.
2. Security > Security Mode > Edit. The Open Security Configuration file
dialog box opens.
3. Select the standard.scf and click Open. If prompted, click No to use Legacy
security support.
4. Click Next to navigate to the Define individual users/passwords screen.
5. Click Finish. The Confirmation message box opens.
7EN02-0390-04 127
PowerLogic™ ION9000 series Cybersecurity
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
1. Open ION Setup > select the meter > Setup Assistant.
2. Security > Security Mode > Edit. The Open Security Configuration file
dialog box opens.
3. Select the Security Configuration File (.scf) that contains the current meter
settings and click Open. The Security Options dialog box opens.
NOTE: Open the security log file to determine the .scf file you want. See
“Cybersecurity configuration”, page 123 for more information.
4. Click Next to navigate to the Define individual users/passwords screen.
128 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
Time Sync Access Set the meter’s time and time synchronization
parameters.
Test Mode Access Switch the meter to test mode, if available with your
meter type.
7EN02-0390-04 129
PowerLogic™ ION9000 series Cybersecurity
5. Select each protocol and click Edit to change lockout and session timeout
values for:
– Protocol lockout after unsuccessful login attempts.
– Session timeout for ION protocol only. This is configurable because there
is no login and logout action for ION protocol sessions.
6. Enter a value for the Lockout duration for user lockout occurrences.
7. Click Finish. A Confirmation message box opens.
8. Click Yes. The Save As dialog box opens.
9. Save the Security Configuration File (.scf) with a unique file name to avoid
overwriting default Security Configuration Files.
Passwords
Recommendations to optimize cybersecurity in a protected environment:
• Document and store passwords and usernames in a protected location.
• Change the default password of 0 (zero) to help reduce unauthorized access.
Default account settings are often the source of unauthorized access by
malicious users.
• View the Device Configuration Checklist to quickly determine if the default
password is used:
130 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
See “Legacy security support”, page 223 for information on Legacy security
support default passwords and usernames.
Changing a password
Required for this procedure:
• Meter connection using ION Setup.
• Login credentials.
• Security configuration access privileges.
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
1. Open ION Setup > select the meter > Setup Assistant.
2. Security > Security Mode > Edit. The Open Security Configuration file
dialog box opens.
7EN02-0390-04 131
PowerLogic™ ION9000 series Cybersecurity
3. Select the Security Configuration File (.scf) that contains the current meter
settings and click Open. The Security Options dialog box opens.
NOTE: Open the security log file to determine the .scf file you want. See
“Cybersecurity configuration”, page 123 for more information.
4. Select a user.
5. Click Next to navigate to the Define individual users/passwords screen.
Select each user and assign passwords.
NOTE: Select the Show password check box to display the user
password after it’s been changed.
6. Click Finish. A Confirmation message box opens.
7. Click Yes. The Save As dialog box opens.
8. Save the Security Configuration File (.scf) with a unique file name to avoid
overwriting default Security Configuration Files.
You can also change the password using ION Setup Diagnostics tool, Security
Options Module using ION Setup Advanced Mode, Power SCADA Operation and
Power Monitoring Expert.
NOTICE
DATA LOSS
Record your device's user and password information in a secure location.
Failure to follow these instructions can result in equipment damage.
132 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
13. Save the file with a unique file name to a protected location. An ION Setup
message box opens
14. Click OK.
15. Click Exit.
16. Click Close.
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
1. Open ION Setup > select the meter > Setup Assistant.
2. Communications > Advanced Ethernet > Protocols.
3. Change the default port number.
4. Enable or disable the protocol.
5. Click OK.
6. Click Exit.
7EN02-0390-04 133
PowerLogic™ ION9000 series Cybersecurity
134 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
2. Security > Security Mode > Edit. The Open Security Configuration file
dialog box opens.
3. Select the Security Configuration File (.scf) that contains the current meter
settings and click Open. The Security Options dialog box opens.
NOTE: Open the security log file to determine the .scf file you want. See
“Cybersecurity configuration”, page 123 for more information.
4. On the Security Options dialog box:
– Select or clear Allow Web Server to enable or disable webpages for
viewing meter data online using a web browser.
– Select or clear Allow Broadcasting Time Synchronization to enable or
disable the ability to modify the meter’s time synchronization source.
5. Click Next to go through Setup Assistant screens.
6. Click Finish. The Confirmation message box opens.
7. Click Yes. The Save As dialog box opens.
8. Save the Security Configuration File (.scf) with a unique file name to avoid
overwriting default Security Configuration Files.
9. Click Exit.
See “Configuring time information using ION Setup”, page 208 for detailed steps
on setting up the time source.
Threat intelligence
Event logs and alarms can assist with monitoring suspicious activity and
identifying the cause of cybersecurity breaches that could lead to a cybersecurity
incident.
7EN02-0390-04 135
PowerLogic™ ION9000 series Cybersecurity
6. Leave default values or enter values for each event priority according to your
reporting requirements:
Info Only Recorded in the event log. Event log cut-off range. Will not 1–5
appear in Event Log reports or syslog records.
Low Recorded in the event log. Produces alarm low alarm. 64–127
High Recorded in the event log. Produces alarm low alarm. 192–255
Recorded in syslog records.
7. Click OK.
8. Click Next.
9. Click Finish. A Confirmation message box opens.
10. Click Yes. The Save As dialog box opens.
11. Save the Security Configuration File (.scf) with a unique file name to avoid
overwriting default Security Configuration files.
12. Click Exit. The Device Configuration Checklist message box opens.
13. Click Exit.
136 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
You can also change event priorities for cybersecurity events using ION Setup
Advanced Mode. Refer to the ION Reference document atwww.se.com for
information about working with modules.
7EN02-0390-04 137
PowerLogic™ ION9000 series Cybersecurity
NOTICE
DATA LOSS
Ensure all important data from the device has been saved before performing a
reset.
Failure to follow these instructions can result in data loss.
NOTICE
LOSS OF ACCESS
Ensure you maintain sufficient access to communicate with and configure your
device.
Failure to follow these instructions can result in loss of access to the
device.
138 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
1. Overwrite the meter template file. This overwrites the meter template with the
default factory template. See “Overwriting the Meter template file”, page 139
for detailed steps.
2. Delete files in the documents folder in SFTP file directory using SFTP client
software. See “SFTP”, page 68 for more information.
3. Delete the custom SSL certificate. See “Deleting a custom SSL certificate”,
page 68 for more information.
4. Delete webpages. See “Deleting custom webpages”, page 98 for more
information.
5. Delete the IEC 61850 configuration file. This deactivates functions related to
the IEC 61850 protocol. See “Deleting an IEC 61850 configuration file”, page
76 for more information.
6. Restore default security configuration. See “Restoring default security
configuration”, page 127 for more information.
7. Overwrite factory module registers. This deletes values for:
– Device owner.
– Device tag.
– Device location.
– Device name.
See “Overwriting factory module registers”, page 140 for more information.
8. Perform a master reset. This deletes values for:
– Event log, data and waveform records.
– Power quality event (COMTRADE) files.
– Energy, metering, min./max., revenue and test mode, and peak demand
values.
– Disturbance (sag/swell event) counter, EN50160 parameters and
statistics.
9. Overwrite communications module registers. This deletes values for network
infrastructure details. See “Overwriting communications module registers”,
page 140 for more information.
1. Go to www.se.com and search for the meter template for your device.
2. Download the ZIP file and extract files.
3. Open ION Setup.
4. Click the meter to select it > Setup Assistant.
5. Template > Send to Meter tab.
6. Click Send.
7. Navigate to the extracted files and select the DCF file.
NOTE: FWN file type is also an option.
8. Click Open.
9. Click Proceed. The Template Paste Options dialog box opens.
10. Clear all check boxes and click OK.
11. Click Yes. The overwriting process could take a few minutes.
12. Click OK.
13. Click Exit and then OK.
7EN02-0390-04 139
PowerLogic™ ION9000 series Cybersecurity
140 7EN02-0390-04
Cybersecurity PowerLogic™ ION9000 series
NOTICE
UNAUTHORIZED OR UNINTENDED ACCESS TO CONFIDENTIAL DATA
• Store devices that are not in service in an access-controlled or monitored
location.
• Physically destroy devices that are decommissioned.
Failure to follow these instructions can result in unauthorized or
unintended access to sensitive or secure customer data.
Device disposal
It is recommended that the entire device is physically destroyed. Destroying the
device helps prevent potential disclosure of data contained in the device that was
not removed.
Device reuse
Store the device in a location that is access controlled or monitored if there is
potential for reuse.
Device recycling
Go to www.se.com and search for the Product Environmental Profile for your
meter type to get instructions on managing e-waste.
7EN02-0390-04 141
PowerLogic™ ION9000 series Alarms and alerts
Alarm types
Your meter has five types of alarms.
Type Description
Setpoint Setpoint alarms compare the actual value of a parameter to a specified limit or
(standard) range of values. These include measured voltage and current values and
calculated power quality values.
Unary Unary alarms are not configurable and generate an alarm based on the meter’s
state, for example, the meter powering up.
Standard alarm
Standard alarms have a detection rate of once every one second.
142 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
High-speed alarm
High-speed alarms have a detection rate of once every half-cycle.
3-phase alarms
Alarms on 3-phase systems are evaluated per phase and reported for each
phase.
Some alarms, such as the sag/swell alarm, are evaluated per phase, but reported
as a single alarm: Each of the three phases are evaluated for the setpoint
condition individually, but there is only one alarm generated. The alarm pickup
occurs when the first phase exceeds the alarm pickup magnitude for the pickup
time delay. The alarm is active as long as any phase remains in an alarm state.
The alarm dropout occurs when the last phase drops below the dropout
magnitude for the dropout time delay.
Over setpoint
When the value rises above the pickup setpoint setting and remains there long
enough to satisfy the pickup time delay period (ΔT1), the alarm condition is set to
ON. When the value falls below the dropout setpoint setting and remains there
long enough to satisfy the dropout time delay period (ΔT2), the alarm condition is
set to OFF.
A Pickup setpoint
B Dropout setpoint
Max2
Max1 ΔT1 Pickup time delay period (in seconds)
∆T3
EV2 End of alarm condition
ΔT3 Alarm duration (in seconds)
EV1 EV2
Max1 Maximum value recorded during pickup period
The meter records the date and time when the alarm event starts (EV1) and when
it ends (EV2). The meter also performs any task assigned to the event, such as
operating a digital output. The meter also records maximum values (Max1, Max2)
before, during or after the alarm period.
Under setpoint
When the value falls below the pickup setpoint setting and remains there long
enough to satisfy the pickup time delay period (ΔT1), the alarm condition is set to
ON. When the value rises above the dropout setpoint setting and remains there
long enough to satisfy the dropout time delay period (ΔT2), the alarm condition is
set to OFF.
7EN02-0390-04 143
PowerLogic™ ION9000 series Alarms and alerts
A Pickup setpoint
∆T3 B Dropout setpoint
The meter records the date and time when the alarm event starts (EV1) and when
it ends (EV2). The meter also performs any task assigned to the event, such as
operating a digital output. The meter also records minimum values (Min1, Min2)
before, during or after the alarm period.
Relative setpoint
The meter’s Relative Setpoint modules behave similarly to the Setpoint modules,
except the pickup and dropout levels are set relative to the Nominal input source.
For more information on Relative Setpoint modules, download ION Reference at
www.se.com.
Sag/swell alarms
Your meter monitors your power system’s voltage and current for sags and swells
(INCITS (CBEMA) Type 2 and Type 3 disturbances); it then reports the
disturbance’s magnitude and duration.
You must configure nominal voltage and current for these alarms to function.
You can manually enter the limits (criteria) used by the meter to identify a sag or
swell, or you can have your meter learn sag/swell limits by monitoring your power
system.
For more information on the Sag/Swell and Disturbance Analyzer modules,
download ION Reference at www.se.com.
Digital alarms
These alarms are triggered when the associated digital input changes state.
You can configure the alarm to be active when the digital input is on or off,
depending on the alarm’s purpose.
For example, if you used a digital input to monitor a breaker that is always
supposed to be on, you would set the alarm to be active when the breaker has
tripped.
NOTE: To stop a digital alarm from being displayed, set the alarm priority to
Info Only. Disabling the digital alarm (setting it to Force Off) will disable all
alarming functions of the associated digital input.
See the ION Reference, available from www.se.com, for more information about
the Digital Input module.
144 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
Transient alarms
These alarms are triggered by voltage transient activity (i.e., ITI CBEMA Type 1
disturbances).
You must configure nominal voltage for these alarms to function.
The Threshold setup register in the Transient module defines what voltage
disturbance magnitude should be considered as transient activity. Threshold is
interpreted as a percentage of the nominal system voltage, plus 100. For example,
if you want transients recorded when voltage deviates from nominal by 20%, enter
120 into the Threshold setup register.
See “Transient overview”, page 159 for an overview about transients.
For more information on the Transient module, download the ION Reference at
www.se.com.
Alarm indicators
Your meter’s display has an alarm indicator to show you what alarm levels have
been detected (active or historic) and whether they have been acknowledged.
For active high priority alarms, the display will also flash until the alarm is
acknowledged. There is also an alarm LED to indicate the meter’s alarm
condition.
7EN02-0390-04 145
PowerLogic™ ION9000 series Alarms and alerts
Active high Red solid bell Flash if not • Flash if not Flash if not
acknowledged acknowledged acknowledged
• Steady if
acknowledged
Active medium Yellow solid bell Flash if not • Flash if not No flash
acknowledged acknowledged
• Steady if
acknowledged
Active low Blue solid bell Flash if not • Flash if not No flash
acknowledged acknowledged
• Steady if
acknowledged
Historic high Red outline bell Flash if not • Flash if not No flash
acknowledged acknowledged
• Steady if
acknowledged
Historic medium Yellow outline bell Flash if not • Flash if not No flash
acknowledged acknowledged
• Steady if
acknowledged
If there are multiple active alarms, the alarm condition associated with the most
important active alarm is displayed. If there are multiple unacknowledged historic
alarms, the meter displays the alarm condition associated with the most important
unacknowledged historic alarm.
NOTE: To stop an alarm from being displayed without impacting other
metering features, set the alarm priority to Info Only.
Default alarms
Your meter comes with default alarms. Some alarms are enabled by default.
NOTE: Some alarms require configuration in order to operate.
Current Sag Ph1 - 3 High Current sag alarms for phase 1, 2, 3 Disabled
Current Swell Ph1 - 3 High Current swell alarms for phase 1, 2, 3 Disabled
Over THD V1 - 3 Medium Over total harmonic distortion (THD) voltage alarms Enabled
4-30 Volt Intrp Ph1 - 3 Low 4-30 voltage interruption power quality alarms Enabled
146 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
Alarm information
You can view information about an alarm from your meter’s display.
Only alarms with a priority of low, medium or high are displayed.
Parameter Description
Alarm The name of the alarm (for example, Over THD V1).
Ack The date and time when the alarm was acknowledged (only applies to
acknowledged alarms).
Value Active alarm: The minimum or maximum value detected when the alarm was
triggered.
Historic alarm: The minimum or maximum value detected during the duration of
the alarm.
Alarm configuration
Alarm setup using the display
You can enable and disable alarms through the display.
7EN02-0390-04 147
PowerLogic™ ION9000 series Alarms and alerts
WARNING
INACCURATE DATA RESULTS
• Do not use data displayed on the display or in software as a substitute for
proper workplace practices or equipment maintenance.
• Confirm your alarm is properly configured.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Parameter7 Description
4-30 Volt Intrp Ph1 4-30 voltage interruption power quality alarm for phase 1
4-30 Volt Intrp Ph2 4-30 voltage interruption power quality alarm for phase 2
4-30 Volt Intrp Ph3 4-30 voltage interruption power quality alarm for phase 3
7. Any Setpoint or Relative Setpoint module with an event priority greater than or equal to the Low alarm event priority is also displayed on
this screen.
8. Enabling or disabling one phase for each alarm type will enable or disable all phases for that type.
148 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
By Percentage By Percentage/By Value When available, specifies if the Pickup and Dropoff entries are by percentage or
by value. If the option is not available, pickup and dropoff entries are by value.
Force Off Checked/Unchecked Forcing the alarm off disables all functions of the associated input.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
Label String value When available, lets you modify the default label so it more clearly identifies the
alarm. Letters, numbers, and underscores are permitted.
Pickup Numeric value Use this setting to provide a value for when the alarm turns on.
Pickup Delay Numeric value This specifies the number of seconds the input must be over the alarm pickup
value before the alarm turns on.
Dropout Numeric value Use this setting to provide a value for when the alarm turns off.
Dropout Delay Numeric value This specifies the number of seconds the input must be below the alarm dropoff
value before the alarm turns off.
Alarm Priority None, Info Only, Low, Specifies the priority level of the standard alarm. When priority is set to Info Only,
Medium or High the alarm does not appear on the display.
Custom Priority 0–255 Select custom priority to view and configure the event priority of the event
associated with the alarm. The event log cutoff value is displayed for reference;
priorities above the cutoff are stored in the meter’s event log.
7EN02-0390-04 149
PowerLogic™ ION9000 series Alarms and alerts
Sag/swell overview
Your meter monitors your power system’s voltage and current for sags and swells
(INCITS (CBEMA) Type 2 and Type 3 disturbances); it then reports the
disturbance’s magnitude and duration.
You can manually enter the limits (criteria) used by the meter to identify a sag or
swell, or you can have your meter learn sag/swell limits by monitoring your power
system.
Nominal 1–999,999 Specifies the nominal voltage value used for sag/swell detection.
Swell Limit Percentage of nominal Specifies the swell limit expressed as a percentage of the nominal voltage.
Sag Limit Percentage of nominal Specifies the sag limit expressed as a percentage of the nominal voltage.
Hysteresis Percentage – see Specifies the difference in magnitude between the sag or swell limit and the
description threshold for the power quality event to be considered over.
For example, if the meter has the sag limit set to 90% of nominal and the
hysteresis is set to 2%, this means that in a sag event, the voltage needs to return
to 92% of nominal for the sag event to be considered over
Alarm priority See description Select the alarm priority you want to associate with Sag/Swell alarms.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
Nominal 1–999,999 Specifies the nominal current value used for current sag or current swell detection.
Pickup Percentage of nominal Specifies the percentage the current must deviate from the nominal current in
order to be classified as a sag or a swell.
Dropout Percentage of nominal Specifies the percentage of nominal the current must recover to in order to signal
the end of the sag or the swell.
Hysteresis N/A Displays the difference in magnitude between the sag or swell Pickup and
Dropout values.
Alarm priority See description Select the alarm priority you want to associate with Sag/Swell alarms.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
150 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
Nominal 1–999,999 Specifies the nominal voltage value used for transient detection.
Threshold Percentage of nominal Specifies the threshold expressed as a percentage of the nominal voltage, plus
100.
For example, if you want transients recorded when voltage deviates from nominal
by 20%, enter 120.
Alarm priority See description Select the alarm priority you want to associate with Transient alarms.
To stop an alarm from being displayed without affecting other meter features, set
the alarm priority to Info Only.
Force Off Checked/Unchecked Forcing the alarm off disables all functions of the associated input.
To stop an alarm from being displayed without affecting digital input features, set
the alarm priority to Info Only.
Label String value When available, lets you modify the default label so it more clearly identifies the
alarm. Letters, numbers, and underscores are permitted.
Alarm Priority None, Info Only, Low, Specifies the priority level of the digital input alarm. To disable the alarm, set
Medium or High priority to Info Only.
Custom Priority 0–255 Select custom priority to view and configure the event priority of the event
associated with the alarm. The event log cutoff value is displayed for reference;
event priorities above the cutoff are stored in the meter’s event log.
7EN02-0390-04 151
PowerLogic™ ION9000 series Alarms and alerts
Alerting
An alert is an external notification from the meter to indicate changes, for example,
a change of state for a digital input, or a power quality event such as a sag or
swell.
When an alert condition occurs, a pulse or trigger is sent and generates the alert.
You can configure alerts to send notification emails or messages to your energy
management system through your meter’s existing Ethernet communications
connections. You can configure alert messages as a simple text string or you can
also include device information. You can configure the alert’s priority so that alerts
are also recorded in the meter’s event log.
You can configure multiple alerts on a single meter, each having different
activation triggers, messages and/or transmission types. For instance, you can
have two alerts, one generating an email, the other sending a message to your
energy management system, but using the same trigger conditions; or you can
have two alerts with different conditions that send two unique emails to two
different email addresses. You can also generate alerts based on triggers from
devices connected to your meter.
Creating alerts is an advanced feature that requires familiarity with ION
architecture and your power system and communications network. To create an
alert, you must configure the Alert module using a configuration tool. You must
also configure your device’s communications as needed to send the alerts, such
as configuring your meter’s SMTP settings and connecting it via Ethernet to an
SMTP mail server in order to send an alert by email.
Go to www.se.com to see the ION meter alerts technical note for detailed
information on creating and configuring alerts, and the ION Reference for detailed
information about the Alert module and its operation.
Feature Values
Setpoints (Alarms) High limit
Low limit
Sustain until ON
Transient Threshold
152 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
115%
Learned swell limit = 110%
Percentage of nominal
110%
105%
100%
95%
85%
110%
Percentage of nominal
105%
100%
95%
85%
See the ION Reference, available from www.se.com, for more information on Sag/
Swell, Setpoint and Relative Setpoint modules.
7EN02-0390-04 153
PowerLogic™ ION9000 series Alarms and alerts
7. Configure the learning parameters for each setpoint and click Save.
8. Click Start All to begin setpoint learning for all setpoints. Click Yes to confirm
or No to cancel.
– Learning status and time remaining are indicated in the Learning Status
box.
– Click Abort to stop learning for a specific setpoint. To stop all setpoint
learning, repeat for each setpoint tab.
9. Apply the learned setpoint values:
– Automatic: the setpoint values are automatically applied unless the
learning process has issues or the learned values are invalid.
– Manual: navigate to Alarming > Setpoints and click Learn. On each
setpoint tab, click Install to apply the learned values to that setpoint.
NOTE: If you click Install while learning is in progress (in either manual or
automatic installation mode), it stops the learning process and prompts
you for confirmation that you want to stop learning and install the learned
values. Once you confirm, the learned values are automatically installed
or prepared for manual installation.
154 7EN02-0390-04
Alarms and alerts PowerLogic™ ION9000 series
7EN02-0390-04 155
PowerLogic™ ION9000 series Alarms and alerts
156 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
Power quality
Power quality overview
Your meter measures voltage and current harmonics, and calculates several
harmonic distortion values, including K-factor and crest factor.
Configure your meter with the power system’s nominal values for voltage, current
and frequency in order for the meter to perform power quality calculations.
NOTICE
DATA LOSS
Ensure that all important data and waveforms have been recorded before
configuring the data and waveform recorders.
Failure to follow these instructions can result in data loss.
7EN02-0390-04 157
PowerLogic™ ION9000 series Power quality
Parameter Description
Enable Burst Data Select or clear this check box to turn burst data logging on or off.
Logging
Total # of recordings2 Specifies how many burst data log sets to save in long-term memory
(NVRAM). The actual number of records is configured in the high-
speed Sag/Swell data recorder’s Depth setup register = (Total # of
recordings) x (Pre-trigger Records + Post-trigger Records + 1). See
“Data recorder burst data”, page 171 for an example of how a data log
set is calculated.
1 If system frequency is changed, the recording duration for Pre-trigger recording and Post-
trigger recording automatically adjusts to reflect the new frequency setting.
2 When burst data logging is enabled, the equivalent number of records for 2 burst data log
sets is allocated in short-term memory (RAM). The actual number of records set in the high-
speed Sag/Swell data recorder’s Buffer Depth setup register = 2 x (Pre-trigger Records +
Post-trigger Records + 1).
8. Click Next.
158 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
9. The Waveform Log Setup screen allows you to configure the waveform
recorder for Standard or Delayed waveform capture.
NOTE: The Sag/Swell Logging Wizard does not support Extended
waveform capture. See “Waveform capture”, page 172 for details on
Standard, Delayed and Extended waveform capture.
Parameter Description
Waveform Depth Specifies the maximum number of waveform records stored on the
meter.
Waveform Format Specifies the number of samples per cycle and the number of cycles
that are stored in a waveform record.
Trigger Position Specifies the number of cycles to capture before the waveform versus
after the waveform. Trigger position can be set using the pre-cycle
arrows or the slider bar.
Transient overview
Your meter monitors your power system’s voltage and detects ITI (CBEMA) type
disturbances related to transients.
When voltage transient limits are defined and alarming is enabled, the meter
reports the disturbance’s magnitude and duration, and logs data and waveform
records associated with the disturbance.
7EN02-0390-04 159
PowerLogic™ ION9000 series Power quality
4. Select the data log and click Edit. Enter the meter password if prompted.
The Transient Logging Wizard appears.
5. The Device setting verification screen displays the results of meter
configuration check for potential errors related to transient monitoring and
reporting. Click Fix to view details, or click Next to ignore the results and
proceed to the next screen.
6. The Transient Logging Setup screen displays Transient data recorder’s Log
Depth setting. You can change the maximum number of records to store in
the Transient data log. Click Next to proceed to the next screen.
7. The Waveform Log Setup screen allows you to configure the waveform
recorder for Standard or Delayed waveform capture.
NOTE: The Transient Logging Wizard does not support Extended
waveform capture. See “Waveform capture”, page 172 for details on
Standard, Delayed and Extended waveform capture.
Parameter Description
Waveform Specifies the maximum number of waveform records stored on the meter.
Depth
Waveform Specifies the number of samples per cycle and the number of cycles that
Format are stored in a waveform record.
Trigger Position Specifies the number of cycles to capture before the waveform versus after
the waveform. Trigger position can be set using the pre-cycle arrows or the
slider bar.
Configuring Advanced PQ
Use ION Setup to configure your meter’s power quality (PQ) monitoring and
logging settings for IEC 61000-4-30, EN 50160, IEEE 519 and Rapid Voltage
Change (RVC).
The meter’s PQ frameworks are designed with logical dependencies. IEC 61000-
4-30 must be enabled first if you want to monitor and record PQ parameters for
EN 50160 or IEEE 519. In addition, the Sag/Swell feature must be enabled in
order to monitor and detect disturbances such as RVC.
160 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
NOTICE
DATA LOSS
• Enable IEC 61000-4-30 before enabling other power quality monitoring and
recording features.
• Enable Sag/Swell before configuring power quality disturbance related
features.
Failure to follow these instructions can result in data loss.
Parameter Description
Hysteresis Specifies the percentage above the Threshold that defines the end of
the disturbance. For example, if you set this to 2%, the end of the
disturbance occurs when the voltage rises to (10% + 2%) of nominal,
or 14.4 V and above.
Log 4-30 3s Select if you want to enable IEC 61000-4-30 3-second interval data
measurements logging.
Log 4-30 10s Select if you want to enable IEC 61000-4-30 10-second interval data
measurements logging.
Parameter Description
Nominal Voltage Specifies the nominal voltage value used for EN 50160.
7EN02-0390-04 161
PowerLogic™ ION9000 series Power quality
Parameter Description
Nominal Voltage Displays the nominal voltage value used for IEEE 519.
NOTE: If you change the Nominal Voltage, you must return to
this setup screen and manually update the IEEE 519
configuration.
<Bus voltage Select the bus voltage at the point of common coupling.
options> Select Disabled if you do not want to log IEEE 519 related data.
13. After specifying the bus voltage, click Next to configure the IEEE 519 current
parameters.
Parameter Description
Maximum short Enter the maximum short-circuit current at the point of common
circuit current coupling.
Maximum demand Enter the maximum demand load current at the point of common
load current coupling.
14. Click Next to view the screen that displays the voltage and current distortion
limits for the harmonic content.
Harmonics 2 to 50 and THD/TDD are displayed, with the corresponding set
limits for Voltage Distortion % and Current Distortion %.
15. Click Finish to save your changes.
The Advanced PQ Logging screen shows the new configuration.
16. Select RVC Enable and click Edit to configure your meter’s RVC (Rapid
Voltage Change) feature.
NOTE: You must enable the Sag/Swell module before the meter can start
monitoring and detecting RVC.
17. Configure the settings as required:
Parameter Description
Enabled • Disabled means ION Setup has detected that the Sag/Swell module
is disabled. Go to Alarming > Sag/Swell and enable Sag/Swell first,
in order for the meter to detect RVC.
• Yes means RVC monitoring is on. Make sure the Sag/Swell module
is enabled, otherwise RVC will not be detected.
• No means RVC monitoring is off.
Threshold Specifies, as a percentage, the RMS voltage limit that must be exceeded
for an RVC event to occur.
Hysteresis Specifies, as a percentage, the difference in magnitude between the start
and end thresholds for an RVC event.
162 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
Harmonics overview
Harmonics are integer multiples of the fundamental frequency of the power
system.
Harmonics information is valuable for power quality analysis, determining properly
rated transformers, maintenance and troubleshooting. Evaluation of harmonics is
required for compliance to system power quality standards such as EN50160 and
meter power quality standards such as IEC 61000-4-30.
Harmonics measurements include per-phase magnitudes and angles (relative to
the fundamental frequency of the phase A voltage) for the fundamental and higher
order harmonics relative to the fundamental frequency. The meter’s power system
setting defines which phases are present and determines how line-to-line or line-
to-neutral voltage harmonics and current harmonics are calculated.
Harmonics are used to identify whether the supplied system power meets required
power quality standards, or if non-linear loads are affecting your power system.
Power system harmonics can cause current flow on the neutral conductor, and
damage to equipment such as increased heating in electric motors. Power
conditioners or harmonic filters can be used to minimize unwanted harmonics.
7EN02-0390-04 163
PowerLogic™ ION9000 series Power quality
C = Crest factor
Vpeak
C= Vpeak = Voltage peak
VRMS
VRMS = Voltage RMS
C = Crest factor
I peak
C = ------------- Ipeak = Current peak
I RMS
IRMS = Current RMS
K-factor
K-factor relates the heating effect of a distorted current in a transformer to a
sinusoidal current with the same RMS magnitude — it describes a transformer’s
ability to serve non-linear loads without exceeding rated temperature rise limits.
The K-factor is equal to the sum of the squares of the harmonic currents multiplied
by the squares of the harmonic order. The meter uses the following equation to
calculate K-factor:
h
2 2
∑ (Ih x h )
n=1
K=
h 2
∑ Ih
n=1
Where K is the K-factor, h is the harmonic order and Ih is the true RMS current of
harmonic order h.
THD% calculations
THD% is a quick measure of the total distortion present in a waveform and is the
ratio of harmonic content (HC) to the fundamental harmonic (H1).
By default, the meter uses the following equation to calculate THD%:
HC
THD = -------
- x 100%
H1
164 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
Phasors
Phasors are used to represent the voltage and current magnitude and angles.
The length of the lines in the phasor diagram represent the relative magnitude of
the voltages with respect to the other phase voltages, and the currents with
respect to the other phase currents. All angles are measured with respect to the
Va/V1 phase. The Va/V1 phasor is fixed to the right-hand horizontal axis (positive
x-axis). Positive angles are measured counterclockwise.
Measured values are provided for the magnitude and relative angle for each
voltage and current phase.
Delta vector diagrams can be configured to display two different ways:
• Instrument (voltage vectors appear 60 degrees apart - showing the actual
voltage and current values that the meter is measuring).
• System (voltage vectors appear 120 degrees apart - showing true system
operation including any calculated values).
Phasor information can be used to troubleshoot incorrect connections on the
meter’s voltage and current inputs (for example, switched phase wiring or polarity
errors), if you know how the phasors should be oriented for your power system.
Phasor information can be viewed using ION Setup, meter webpages, or the
display.
I Indoor application
7EN02-0390-04 165
PowerLogic™ ION9000 series Power quality
IEC 61000-4-30
IEC 61000-4-30 power quality standard compliance is provided by ION modules
including: Power Quality Aggregator, Harmonics Measurement, Disturbance
Analyzer, Symmetrical Components, Mains Signaling Evaluation, and Sag/Swell.
See the IEC 61000-4-30 compliance and ION meters technical note for details.
EN 50160
The EN 50160 framework includes ION modules, such as: Flicker, Mains
Signaling Evaluation, Harmonics Evaluation and Voltage Harmonics.
Your meter’s framework is pre-configured for a low voltage system.
NOTE: Connect your meter to a UPS to avoid losing EN 50160 data in the
event of a power outage.
See the Power quality: ION meters and EN 50160:2010 technical note for details.
IEEE 519
The IEEE 519 framework includes ION modules, such as: Harmonics Evaluation,
Harmonics Measurement and Counter.
166 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
A. Disturbance location
B. Meter (B) reports downstream
disturbance
C. Meter (C) reports upstream
disturbance
D. Meters (D) report upstream
disturbance
E. Meter (E) reports downstream
disturbance
The arrows show the direction the meters have determined for the disturbance.
With this information, you can determine that the disturbance occurred between
meter (B) and meter (C), and can focus on that section of your system to find the
cause of the disturbance.
See the ION Reference, available from www.se.com, for more detailed information
about the Disturbance Direction Detection module.
COMTRADE
Your meter can generate COMTRADE files and store them on the meter’s internal
SFTP site.
COMTRADE stands for COMmon format for TRAnsient Data Exchange defined
by IEC 60255-24, and defines a common format for power quality event
(disturbance) data in order to simplify retrieval, analysis and exchange of
disturbance data between multiple sources and vendors.
The format of your meter’s COMTRADE files is as defined by IEC 60255-24.
COMTRADE can be used in conjunction with IEC 61850.
7EN02-0390-04 167
PowerLogic™ ION9000 series Power quality
See the COMTRADE and ION technology technical note, available from
www.se.com, for detailed information about COMTRADE file formats and
implementation.
168 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
1. Enable waveform capture on 2. A waveform is captured when 3. View the waveform on the
your meter a power quality event occurs meter’s webpages
Set the meter’s nominal voltage using ION A COMTRADE record is generated and Go to the waveform viewer (Monitoring >
Setup or meter webpages. saved to your meter’s internal SFTP site. Waveforms) to explore the waveform data.
The waveform viewer uses the meter’s COMTRADE files to display the
waveforms. If the events you want to capture are not included in the default
framework, you can customize the meter’s waveform recording framework.
7EN02-0390-04 169
PowerLogic™ ION9000 series Power quality
170 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
depending on the ION modules connected to the inputs of the Data Recorder
module.
NOTE: To maximize the performance of your power management system, it is
recommended that devices be connected directly to an Ethernet network.
1 record triggered
Buffer Depth
6 x 16
= 96
Data Log register
(trigger record) Depth
Input 1 value 16 x 16
Input 2 value = 256
Input 3 value . . .
7EN02-0390-04 171
PowerLogic™ ION9000 series Power quality
You can use the Power Quality setup assistant in ION Setup to specify how many
seconds of pre-trigger and post-trigger data you want to capture. ION Setup
automatically calculates the required number of records based on your input.
Waveform capture
The meter’s Waveform Recorder modules capture waveform data.
The Waveform Recorder module captures one waveform record every time its
Record input is triggered. A waveform record is defined by the module’s Format
setup register, expressed as (number of samples per cycle) x (number of cycles
per waveform record). For example, if Format is set to 256x7, that means one
waveform record is made up of 7 cycles of waveform data at 256 samples per
cycle resolution.
172 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
C Delay period (number of cycles specified in Record Delay Cycles setup register)
7EN02-0390-04 173
PowerLogic™ ION9000 series Power quality
The waveform log set for each triggered recording is equal to the sum of Pre-
trigger Records + Post-trigger Records + 1 (where 1 is the actual record when the
Waveform Recorder module’s Record input was triggered).
For example, if Pre-trigger Records is set to 2 and Post-trigger Records is set to 6,
the number of records for each waveform log set is 9:
174 7EN02-0390-04
Power quality PowerLogic™ ION9000 series
1 record triggered
Buffer Depth
4x9
= 36
The waveform log set for the extended waveform capture = [pre-trigger records] +
[actual trigger record] + [post-trigger records]. The total waveform records
captured in this example is 2 + 1 + 6 = 9.
When extended waveform capture is enabled, both Buffer Depth and Depth setup
registers must be set to a positive integer multiple of the waveform log set.
NOTE: The COMTRADE module does not support extended waveform
capture. The COMTRADE files saved are only for the trigger waveform record.
7EN02-0390-04 175
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
Prerequisites
To use the HSTC feature, you need the following:
• ION9000T meter.
• ION9000T frameworks files (v2.2.x or later).
• ION Setup (v3.2.x or later).
The HSTC feature is not supported on other ION9000 series meters.
1. Open ION Setup and select the Setup Assistant for your meter.
2. Click Template > Save to PC > FAC1 Feature Set.
176 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
1. Open a web browser and enter the IP address for your meter. Enter your login
credentials when prompted.
2. Click Diagnostics > Statistics > Meter - Basic > Feature Set.
Commission HSTC
This section supplements the meter installation guides and provides guidance on
commissioning your meter to enable the HSTC feature.
See your device installation guide for information related to installation.
System voltage
Potential transformer (PT) scaling is not applied in high-speed transient capture.
High-speed transient measurements are performed on voltage levels present at
the meter’s voltage terminals.
Voltage reference
Set the voltage reference, Ve or Vn, according to your system configuration.
High-speed transient voltage measurements are calculated between V1–V4 and
neutral (Vn), or between V1–V4 and earth (Ve) depending on this setting.
Communications
Ethernet communication is recommended. HSTC waveform viewing is not
supported over serial connections.
Set up HSTC
HSTC alarms are disabled by default. The HSTC feature is enabled when HSTC
alarms are enabled.
7EN02-0390-04 177
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
HSTC related settings, such as magnitude and duration thresholds, are pre-
configured at the factory. Use the default settings or make changes based on your
system needs.
Review and configure the settings for the following functions before enabling the
HSTC feature:
• HSTC alarms.
• HSTC logging.
HSTC alarms
Use HSTC alarms to notify you when a specific condition is met, such as a voltage
transient that exceeds a defined magnitude threshold.
HSTC alarms are included in the ION9000 series alarm system and are shown in
the meter’s Historical Alarm screen(s).
NOTICE
DATA LOSS
Ensure that all important data has been recorded before configuring HSTC
alarms.
Failure to follow these instructions can result in data loss.
178 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
1. Open ION Setup and select the Setup Assistant for your meter.
2. Click Alarming > Transient.
3. Select High Speed Transient and click Edit. The High Speed Transient
Setup window is displayed.
4. View or modify parameters:
5. Click Save. ION Setup performs a configuration check and displays a
message if the Magnitude Threshold setting is below the configured nominal
voltage.
Alarm Priority None, Info Only, Low, Medium, Select the alarm priority you
High want to associate with the HS
transient alarms. To stop an
alarm from being displayed
without affecting other meter
features, set the alarm priority
to Info Only.
See “Disabling and enabling alarms using the display”, page 149 for instructions.
7EN02-0390-04 179
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
Log HSTC
HSTC logging
The HSTC logging function is enabled with HSTC alarms. When defined transient
thresholds are exceeded the meter performs the following:
• HSTC data set logging.
• HSTC waveform logging.
The meter performs a set of calculations and stores separate records for each
voltage phase. Records are captured for V1–V4 regardless of which phase the
transient occurred on.
See “Configuring HSTC logging using ION Setup”, page 182 for information about
these settings.
180 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
NOTICE
DATA LOSS
Ensure that all important data and waveforms have been recorded before
configuring the data and waveform recorders.
Failure to follow these instructions can result in data loss.
7EN02-0390-04 181
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
View HSTC
The ION9000T continuously monitors incoming voltage signals. When HSTC is
enabled and defined transient thresholds are met the meter performs the following
functions:
• HSTC alarms
• HSTC logging
◦ Data set logging
◦ HSTC waveform logging
182 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
3. Go to the High Speed Transient Capture folder, then select the HSTC Data
Set log.
The HSTC Data Set Recorder log displays.
1. Open a web browser and enter your meter’s IP address in the address box.
The webpage login displays.
2. Enter your login credentials.
3. Select Monitoring > Power Quality Summary > HSTC.
The High-Speed Transient Summary screen displays.
7EN02-0390-04 183
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
3. Go to the High Speed Transient Capture folder, then select the HSTC
Waveform log.
The HSTC Waveform log displays. A progress bar at the bottom of the
screen indicates when all waveform logs have been retrieved from the meter.
NOTE: Records are sorted by Start Date/Time, with the newest entries
appearing at the top.
184 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
A Active window This window displays a portion of the overall captured disturbance.
B HSTC V1–V4 phase selector Click to select a single voltage phase V1 through V4.
C Slider control (top and bottom) Click and drag to focus on an event in the Active window. The
values shown in the information panel at the bottom of the screen
will update to reflect the new slider positions.
G Active histogram window This window functions as a coarse zoom. Select and drag the
window to any point in the histogram to focus on a specific set of
waveform samples. The waveform samples contained within this
histogram window are displayed in the active window above.
NOTE: The waveform samples in the active window reflect the
selected HSTC phase.
Right click in the histogram to set the number of active bins and
their corresponding thresholds.
NOTE: The updated threshold settings are used for
informational purposes only. They do not change the
conditions set to detect transients, nor are they retained when
the HSTC waveform viewer is closed.
I Trigger timestamp Timestamp representing the point in time that the transient condition
was detected.
7EN02-0390-04 185
PowerLogic™ ION9000 series High-Speed Transient Capture (HSTC)
J Active window zoom This window functions as a fine zoom. Click, hold and drag your
cursor across any waveform portion in the active window.
NOTE: The waveform samples in the active window zoom
reflect the selected HSTC phase.
K Spectral analysis Right click within the histogram window to view the spectral analysis
of the selected samples.
NOTE: The spectral analysis window reflects the selected
HSTC phase.
HSTC events
HSTC events are logged the same as other meter events:
• External events such as the detection of a high-speed transient
• Configuration changes such as editing the HSTC magnitude threshold
• Other meter events
See the “Event log overview”, page 197 for more information about logging meter
events.
HSTC resets
There are two HSTC reset methods, depending on what information you want to
clear:
Use the meter’s Master reset to clear HSTC Data set and Waveform logs.
Use the meter’s HSTC reset to clear HSTC event accumulations and statistics.
NOTICE
DATA LOSS
Ensure that all important data has been recorded before performing a reset.
Failure to follow these instructions can result in data loss.
Master reset
Perform a Master reset using ION Setup.
Alternatively, you can use the meter webpages or meter display.
See “Resets”, page 219 for more information about meter resets.
HSTC reset
Perform an HSTC reset using ION Setup.
186 7EN02-0390-04
High-Speed Transient Capture (HSTC) PowerLogic™ ION9000 series
3. Go to the High Speed Transient Capture folder, then select the HSTC
Summary log.
The HSTC Summary log displays
4. Click the HSTC Reset icon.
5. Click Yes to confirm HSTC reset.
7EN02-0390-04 187
PowerLogic™ ION9000 series Logging
Logging
Logging overview
The meter’s logging frameworks include factory-configured data recorders,
waveform recorders and event logs.
The logging frameworks store data related to:
• Power quality and compliance
• Energy and demand
• Revenue metering
• Trending and forecasting
• Meter events
When your system’s nominal parameters are programmed into the meter, power
quality events such as sags, swells and transients are automatically detected, and
associated voltage and current data and waveforms are logged. Meter data is
stored in non-volatile memory, so data is retained even if the meter loses power. If
your system nominal values fluctuate, you can configure the meter’s setpoint
learning feature to learn your power system’s normal operating values, then use
that information to help identify voltage sags and swells.
The meter’s logging framework also supports burst data logging for sag/swell
events. When burst data logging is enabled, additional data records immediately
before and immediately after the sag/swell event are captured. Energy
management systems can then retrieve this information for use in applications
such as power event analysis.
NOTE: To maximize the performance of your power management system, it is
recommended that devices be connected directly to an Ethernet network.
You can also configure the meter to email data from the logging frameworks.
Download the Internal email client feature technical note at www.se.com for
instructions on how to configure your meter to email logged data.
Meter events are recorded in the meter’s onboard event log. You can also
configure the meter to record events to an external SysLog (systems log) server.
Revenue log
The Revenue Log (Data Rec 1) is configured for use with UTS MV-90 billing
software. Factory settings for this data recorder:
• Log depth = 3360 records (35 days)
• Interval = 900 seconds (15 minutes)
By default, it logs the following values:
188 7EN02-0390-04
Logging PowerLogic™ ION9000 series
Parameter Description
Loss log
The Loss Log (Data Rec 9) is configured to record loss values. Factory settings for
this data recorder:
• Log depth = 3360 records (35 days)
• Interval = 900 seconds (15 minutes)
By default, it logs the following values:
Parameter Description
7EN02-0390-04 189
PowerLogic™ ION9000 series Logging
Parameter Description
Harmonics logs
Two harmonics logs record various harmonics data, including K-factor and Total
Harmonic Distortion (THD). These recorders are labeled Harm Mean Log and
Harm High Log. Factory settings for these data recorders:
• Log depth = 840 records (35 days)
• Interval = 3600 seconds (1 hour)
By default, they log the following values:
Parameter Description
190 7EN02-0390-04
Logging PowerLogic™ ION9000 series
Parameter Description
Sag/swell log
The Sag/swell Log (Data Rec 5) provides details of power quality events. Factory
settings for this data recorder:
• Log depth = 100 records
• Interval = Triggered on demand
By default, it logs the following values:
SS1 DistV3Engy SS1 DistNominal SS1 Swell Lim SS1 Sag Lim
Sg/Sw HS log
The Sg/Sw HS Log (Data Rec 6) captures high-speed (half-cycle) voltage and
current data that includes pre-event and post-event records related to the sag/
swell event. This data recorder is disabled by default.
If enabled, it logs the following by default:
HS Vln c HS Vll ca HS I c
Transient log
The Transient Log (Data Rec 15) provides details of power quality events. Factory
settings for this data recorder: Factory settings for this data recorder:
• Log depth = 100 records
• Interval = Triggered on demand
By default, it logs the following values:
7EN02-0390-04 191
PowerLogic™ ION9000 series Logging
EN50160 Frq/Mg (Data Rec 17) Power frequency and supply magnitude
The meter logs EN50160 counter data for present and previous observation
periods as well as EN50160 events.
Download the EN50160 2010 compliance and ION meters technical note at
www.se.com for more information about your meter’s EN50160 compliance.
V1 3s I2 3s V2 UnderDev 3s
V2 3s I3 3s V2 OverDev 3s
V3 3s V1 UnderDev 3s V3 UnderDev 3s
192 7EN02-0390-04
Logging PowerLogic™ ION9000 series
Download the IEC 61000-4-30 Compliance and ION Meters technical note at
www.se.com for more information about your meter’s IEC 61000-4-30 compliance.
7EN02-0390-04 193
PowerLogic™ ION9000 series Logging
V/I Hrm 49-50 (Data Rec 59) V1, V2, V3, I1, I2, I3 harmonics
NOTICE
DATA LOSS
Ensure that all important data has been recorded before configuring data
recording.
Failure to follow these instructions can result in data loss.
Parameter Description
Log Memory Information only. This is automatically calculated, and displays how
much memory the log uses based on the Log Interval and Log
Depth
Log Storage Information only. This is automatically calculated, and displays how
much total memory is left after subtracting the Log Memory usage
194 7EN02-0390-04
Logging PowerLogic™ ION9000 series
Key terms
Term Definition
Nominal The normal or usual parameter value. For example, the nominal voltage for
many power systems is 120 V.
Sag A power event where the voltage or current drops below the nominal value.
Swell A power event where the voltage or current rises above the nominal value.
Transient A power event where a short duration surge of electrical energy is detected.
See the ION Reference, available from www.se.com, for more information on the
Waveform Recorder module and its settings.
7EN02-0390-04 195
PowerLogic™ ION9000 series Logging
Wfm Rc V1-Sg/Sw (Wform Rec 1) V1 voltage waveforms recorded during a defined sag or
swell event.
Wfm Rc V2-Sg/Sw (Wform Rec 2) V2 voltage waveforms recorded during a defined sag or
swell event.
Wfm Rc V3-Sg/Sw (Wform Rec 3) V3 voltage waveforms recorded during a defined sag or
swell event.
Wfm Rc I1-Sg/Sw (Wform Rec 5) I1 current waveforms recorded during a defined sag or
swell event.
Wfm Rc I2-Sg/Sw (Wform Rec 6) I2 current waveforms recorded during a defined sag or
swell event.
Wfm Rc I3-Sg/Sw (Wform Rec 7) I3 current waveforms recorded during a defined sag or
swell event.
Vfm Rc V1-Trnst (Wform Rec 9) V1 voltage waveforms recorded during a defined transient
event.
Vfm Rc V2-Trnst (Wform Rec 10) V2 voltage waveforms recorded during a defined transient
event.
Vfm Rc V3-Trnst (Wform Rec 11) V3 voltage waveforms recorded during a defined transient
event.
Vfm Rc I1-Trnst (Wform Rec 13) I1 current waveforms recorded during a defined transient
event.
Vfm Rc I2-Trnst (Wform Rec 14) I2 current waveforms recorded during a defined transient
event.
Vfm Rc I3-Trnst (Wform Rec 15) I3 current waveforms recorded during a defined transient
event.
COMTRADE modules
The factory-default COMTRADE modules are preconfigured with their inputs
linked to the Trigger outputs of the waveform recorders for sag/swell and transient
monitoring.
196 7EN02-0390-04
Logging PowerLogic™ ION9000 series
NOTE: This example is representative only, and your meter’s event log may
appear different than shown.
See the ION Reference, available from www.se.com, for more information about
the Event Log Controller module and other ION modules.
7EN02-0390-04 197
PowerLogic™ ION9000 series Logging
See the ION Reference, available from www.se.com, for more information about
the Event Log Controller module and event priorities for specific ION modules.
Syslog overview
Syslog uses the User Datagram Protocol (UDP) to transport event log information
from the meter directly to a centralized syslog server.
The syslog server can receive logs from multiple devices, including meters, then
store and filter the log information as needed. You can use ION Setup to modify
the syslog network settings for your device. Syslog is a useful feature to help
maintain meter log information for extended periods of time.
NOTE: Ethernet is required to use the syslog feature.
198 7EN02-0390-04
Logging PowerLogic™ ION9000 series
Syslog is an open standard allowing you to use any one of a number of syslog
server applications currently available. The decision regarding which syslog
server solution to use can be based on budget and your technical requirements.
See the individual syslog server’s documentation for more information.
Syslog severity ION event priority name ION event priority range
7EN02-0390-04 199
PowerLogic™ ION9000 series Logging
This information can help you understand your log usage and how to optimize
your logging configuration for your situation.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to the Logging > Memory screen.
The Status tab:
• lists the default logs, their interval (Duration) and depth (Records), if
applicable, and the percentage of available memory used by the log.
• provides information on how much of the meter’s memory is used for
system tasks in the System Resources list item.
• displays the total meter memory and the percentage of memory in use
versus memory available.
NOTICE
DATA LOSS
Use an uninterruptible power supply (UPS) if you program your meter for heavy
logging.
Failure to follow these instructions can result in data loss.
200 7EN02-0390-04
Logging PowerLogic™ ION9000 series
x
A. Circular (FIFO) logging mode: when the log is full, a new record overwrites the oldest record
B. Stop-when-full logging mode: when the log is full, any new records are not logged
7EN02-0390-04 201
PowerLogic™ ION9000 series Logging
ensure that the buffer does not run out before all the records are replicated to the
long-term memory (e.g., in the case of high-speed recording).
You may want to use this configuration for logs with intervals greater than 60
seconds or with less critical data. Because the records are partially replicated, this
configuration uses less of the meter’s short-term memory, or RAM, in a log that is
otherwise configured the same. This allows you to make more RAM available for
other logs with a higher logging frequency or more critical data.
However, depending on your configuration, there may be instances where the log
buffer fills up faster than it can replicate records to long-term memory. In this case,
you may lose records and see gaps in your data.
NOTE: The Insert Outage Records functionality does not work if the data
recorder is configured as partially buffered. In order to use this functionality,
you must configure the data recorder to be fully buffered. See the Data
Recorder module description in the ION Reference, available for download
from www.se.com, for more information on Insert Outage Records
functionality.
A. Log buffer
B. Long-term memory
C. Total available space
8:45:30.000 8:45:30.000 in the log buffer (for
8:46:30.000 8:46:30.000 example, 20 records)
8:47:30.000 8:47:30.000
9:02:30.000 9:02:30.000
9:03:30.000 9:03:30.000
9:04:30.000 9:04:30.000
In this example, the log buffer equals the log depth and all the records are
replicated in both the short-term memory and the long-term memory.
A. Log buffer
B. Long-term memory
C. Total available space
in the log buffer (for
example, 20 records)
In this example, the buffer depth equals 20. The first record has already replicated
to the long-term memory, making room in the log buffer for the new records
(including the newest record, in gray).
202 7EN02-0390-04
Logging PowerLogic™ ION9000 series
A. Log buffer
B. Long-term memory
C. Record that cannot be logged because log buffer is full (this record is lost)
D. Record moving from short-term memory to long-term memory
E. New record at next interval
In the graphic on the left, the log buffer (A) is full, and the oldest record has not
replicated to the long-term memory yet. This means that the new record (C) is not
logged, and is permanently lost. In the graphic on the right, the oldest record (D)
has been replicated to long-term memory, making space in the buffer. The new
record at the next interval (E) is logged but there is a gap in the data for the lost
record (C).
NOTICE
DATA LOSS
Ensure that all important data has been recorded before configuring a log.
Failure to follow these instructions can result in data loss.
The default log settings are designed to meet the needs of most users.
This procedure provides the steps for configuring settings for a subset of data logs
using the ION Setup Assistant. Configuring these settings for custom logs, and
logs not listed in the Logging > Memory screen, is an advanced procedure; see
the ION Setup help for more information.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to the Logging > Memory screen.
4. Select the log you want to edit and click Edit.
7EN02-0390-04 203
PowerLogic™ ION9000 series Logging
5. Set the log depth and log interval as required for your logging needs.
• Log Interval: you can change the interval units to seconds, minutes,
hours or days.
• Log Depth: You can set the depth in time (seconds, hours, days, etc.) or
the number of records.
NOTE: For some log types, you only set the log depth (for example,
waveform recorders).
Log Memory shows the estimated impact of the changes on the total size of
the log and Log Storage displays the estimated available log memory on the
meter.
NOTE: If you receive a message stating that there is not enough memory
when you change a log’s configuration, check the configuration of your
meter’s other logs. You may not have enough RAM, or short-term
memory, to allow for the new configuration. You may need to use ION
Setup Advanced mode to check the detailed configuration of your logs.
6. Click Finish.
In some case, you may see a Next button instead of Finish. In this case, the
next screen allows you to configure the buffer depth for the log. The screen
displays the overall log depth and a field for setting the log buffer depth. It
also shows the impact of the Buffer Depth setting to your meter’s short-term
memory (RAM).
204 7EN02-0390-04
Time and timekeeping PowerLogic™ ION9000 series
Time synchronization
Your meter’s clock controls the timing of metering parameters, such as demand
intervals or power quality measurement aggregation over time intervals.
Adjustments to the clock are made by synchronizing the meter’s time with another
time source, determined by the Time Sync Source. Time synchronization
messages can be automatically generated and sent to your meter from your
energy management system software or other time sources such as an SNTP/
NTP server, PTP Master or GPS receiver. You can also manually trigger a time
synchronization message from your energy management system or configuration
software.
NOTE: To help maintain data integrity, some energy management systems
impose a blackout rule where time synchronization messages near energy
interval boundaries are ignored.
7EN02-0390-04 205
PowerLogic™ ION9000 series Time and timekeeping
Simple Network Time Protocol (SNTP) SNTP can synchronize the time of your meter
up to ± 1 second of other meters on an Ethernet
network. For SNTP time synchronization, your
meter must be connected to an Ethernet
network that has an active SNTP server and be
configured with the server’s information.
Network Time Protocol (NTP) NTP can typically synchronize the time of a
meter to ± 10 to 100 ms, depending on network
configuration. To implement NTP time
synchronization, your meter must be connected
to an Ethernet network that has an active NTP
server and be configured with the server’s
information.
Precision Time Protocol (PTP)2 PTP can synchronize the meter time to ± 1 ms
of other devices connected to a local area
network. To implement PTP time
synchronization, your meter must have PTP
selected as the time sync source and be
connected to an Ethernet network that has a
valid PTP Master (Grandmaster Clock).
1Use the digital inputs located on the meter base for IRIG-B time synchronization
and other high-accuracy applications.
2This clock precision assumes your meter is installed in a Star network topology
only.
Clock source
The Clock Source setup register defines the meter’s representation of a one
second period, and can be set to:
LINE FREQUENCY
The meter monitors the ISO Grid Operation line frequency, and adjusts the one
second period based on the measured line frequency. All devices connected to
the grid network are synchronized to maintain a consistent time base. If a power
outage occurs, the clock automatically synchronizes with the meter’s internal
crystal until power is restored. Once power is restored, the clock resynchronizes
with the line frequency.
NOTE: Do not use LINE FREQUENCY when your meter is synchronized to an
external time sync source.
INTERNAL
The meter clock is synchronized to the meter’s internal crystal.
206 7EN02-0390-04
Time and timekeeping PowerLogic™ ION9000 series
COMM
The meter clock is synchronized to an external time sync source. Use this for the
Clock Source if:
• The Time Sync Source setup register is set to a serial communications port to
receive GPS time synchronization signals.
• The Time Sync Source setup register is set to ETHERNET-PTP and your meter is
installed in a trusted PTP network.
• The Time Sync Source setup register is set to IRIG-B.
PTP device type End to End transparent clock A transparent clock that
supports the use of the end-to-
end delay measurement
mechanism between slave
clocks and the master clock.
Peer delay mechanism 2 step A clock that provides time
information using the
combination of an event
message and a subsequent
general message.
7EN02-0390-04 207
PowerLogic™ ION9000 series Time and timekeeping
208 7EN02-0390-04
Time and timekeeping PowerLogic™ ION9000 series
6. Select the parameter that you want to configure and click Edit. Enter the
password if prompted.
TimeZone – Sets the timezone based on the timezones available from the computer’s
operating system.
NOTE: This is also where you can synchronize your meter’s DST settings
with the computer’s.
Time Sync Type UTC or LOCAL Specifies the time format of the time sync message.
UTC (Coordinated Universal time) is equivalent to Greenwich Mean Time (GMT).
LOCAL is the local time with DST and time zone information applied.
• For SNTP/NTP and PTP time synchronization, set the Time Sync Type to
UTC.
Time Sync Source COM1, COM4, Sets which device port accepts time synchronization messages.
ETHERNET, Time synchronization messages on other ports are ignored.
ETHERNET - ION, • For GPS time synchronization, set the Time Sync Source to COM1 (or
ETHERNET - DNP,
COM4).
ETHERNET - PTP, IRIG-
B • For SNTP/NTP time synchronization, set the Time Sync Source to
ETHERNET.
• For ION time synchronization, set the Time Sync Source to ETHERNET-
ION.
• For DNP time synchronization, set the Time Sync Source to ETHERNET-
DNP.
• For PTP time synchronization, set the Time Sync Source to ETHERNET-
PTP.
• For IRIG-B time synchronization, set the Time Sync Source to IRIG-B.
Clock Source Internal, Line Freq, Sets the source for the clock:
COMM
• Internal: the meter’s internal clock.
• Line Freq: the measured line frequency of the power system is the clock
source.
• COMM: the meter’s communication port (used by the IRIG-B, GPS or
ETHERNET-PTP time sync source).
DST Offset Numeric Bounded Specifies the amount of time the displayed local time is moved forward when
Format/Elapsed Interval entering Daylight Savings. A value of zero disables this feature and local time is
Format not adjusted for DST.
Start of the Week Monday - Sunday Specifies the start day of the week used for Trending and Forecasting.
NOTE: Changing the start day of the week clears all trending and forecasting
data.
Enable NTP Time Sync NTP, SNTP, No NTP: specifies NTP time synchronization.
SNTP: specifies SNTP time synchronization.
NOTE: SNTP is recommended for revenue-related applications.
No: neither NTP nor SNTP time synchronization are used.
NTP Time Sync Interval Numeric value or Specifies how often the meter synchronizes over SNTP.
elapsed interval value
NOTE: This parameter is not used for NTP.
Event Logging Threshold 0.000001 to 1.000000 Specifies the minimum time difference (in seconds) for a time synchronization to
(NTP and PTP only) be logged as an event.
This parameter can be configured to help prevent the meter’s event log from being
flooded with time synchronization events.
NTP Server Server IP address or Specifies the IP address (or fully qualified domain name if DNS is active) of the
domain name SNTP or NTP server.
7EN02-0390-04 209
PowerLogic™ ION9000 series Time and timekeeping
8. If using serial GPS time synchronization, enter the following information under
Communications > Serial settings:
Parameter Description
Protocol Select the GPS setting that matches your GPS receiver.
Baud rate The recommended baud rate for GPS time synchronization is 9600 bps.
Serial port The recommended stop bits/parity for GPS time synchronization is 8N1.
Clock setup
Clock Source Internal, Line Freq, Specifies the time synchronization source.
COMM
Time Sync COM1, COM4, Specifies the port to receive time
Source ETHERNET, synchronization signals.
ETHERNET - ION,
ETHERNET - DNP,
ETHERNET - PTP, IRIG-
B
Time Sync Type UTC, Local Specifies whether time synchronization
signals are received in local time or UTC.
210 7EN02-0390-04
Measurements PowerLogic™ ION9000 series
Measurements
Energy
Your meter provides bi-directional, 4-quadrant, revenue accurate energy metering:
• kWh, kVARh, kVAh delivered and received
• kWh, kVARh, kVAh net (delivered minus received)
• kWh, kVARh, kVAh total (delivered plus received)
• Volt-squared-hours and amp-squared-hours
• Integration of any instantaneous measurement
Energy parameters can be logged automatically on a programmed schedule.
All energy values represent the total for all three phases.
Demand
Your meter supports several demand calculation methods, including block, rolling
block, synchronized and predicted demand.
It can measure demand on any instantaneous value and record peak (maximum)
demand with time and date information.
• kW, kVAR, kVA demand
• kW, kVAR, kVA peak demand
• Amps, Volts demand
Instantaneous measurements
Your meter provides one second and half-cycle true RMS readings.
Instantaneous readings include:
• 3-phase voltages (line-to-line, line-to-neutral): per phase and average
• Line-to-earth voltages per phase and V4, neutral-to-earth voltage
• 3-phase currents: per phase and average
• I4 and I5 currents, measured
• Residual current, calculated (I calc res)
• Active (kW), reactive (kVAR) and apparent (kVA) power: per phase and total
• Power factor per phase and total
• System frequency
• Voltage and current unbalance
• Phase reversal
Harmonics
Your meter provides harmonic distortion metering, recording and real-time values
for all voltage and current inputs.
• Individual harmonics (including magnitude, phase angle phase and inter-
harmonics) up to the 63rd harmonic
• Total even harmonic distortion (TEHD), total odd harmonic distortion (TOHD)
• Total harmonic distortion (THD), total demand distortion (TDD)
7EN02-0390-04 211
PowerLogic™ ION9000 series Measurements
Min/max recording
Your meter records new minimum and maximum data every recording interval for
a variety of values.
• Voltage and current
• kW, kVAR and kVA
• Power factor
• Frequency
• Voltage unbalance
Power quality
Your meter monitors the voltage channels, detects and records power quality
events.
The meter measures and records:
• Sag/swells: ITIC/CBEMA and SEMI curves
• Transients: 20 microseconds or longer in duration on any voltage channel
Power quality standards compliance:
• EN50160, including Flicker
• IEC 61000-4-30 Class A
• IEEE 519
The meter supports advanced power quality features:
• Disturbance Direction Detection: the meter can capture sag/swell and
transient disturbances, analyze the information and determine the direction of
the disturbance relative to the meter. Determining the source of a disturbance
more quickly and accurately helps prevent repeat occurrences and minimize
facility downtime.
• COMTRADE: the meter can save waveform data in COMmon format for
TRAnsient Data Exchange (COMTRADE) format, which is available for
download using an SFTP client application. This is intended for use in
conjunction with IEC 61850.
• Setpoint learning: You can configure your meter to learn certain disturbance-
related values, such as what constitutes a sag, swell, transient, or high or low
setpoint.
212 7EN02-0390-04
Measurements PowerLogic™ ION9000 series
P
PF = —
S
A purely resistive load has no reactive components, so its power factor is 1 (PF =
1, or unity power factor). Inductive or capacitive loads introduce a reactive power
(Q) component to the circuit which causes the PF to become closer to zero.
Imported/delivered
A)
Ap
(V
par
er
en
w
tp
po
ow
nt
re
er
pa
(V
Ap
A)
Exported/received Imported/delivered
Exported/received
Exported/received
A)
Ap
(V
pa
er
re
w
nt
po
po
nt
w
re
er
pa
(V
Ap
A)
Quadrant 3 Quadrant 4
PF lagging PF leading
Power factor sign convention: Power factor sign convention:
IEEE = − IEEE = +
IEC = − IEC = +
270°
-Q
(-kVAR, -kVARh)
The units for power are watts (W or kW) for real power P, vars (VAR or kVAR) for
reactive power Q, and volt-amps (VA or kVA) for apparent power S.
Positive real power P(+) flows from source to load, and negative real power P(-)
flows from the load to the power source.
7EN02-0390-04 213
PowerLogic™ ION9000 series Measurements
The following diagrams show how voltage and current waveforms shift based on
load type under ideal (laboratory) conditions.
Current and voltage in phase (resistive) Current leads voltage (capacitive) Current lags voltage (inductive)
Power demand
Power demand is a measure of average power consumption over a fixed time
interval.
NOTE: If not specified, references to demand are assumed to mean power
demand.
The meter measures instantaneous consumption and can calculate demand using
various methods.
Peak demand
Peak (or maximum) demand is the highest demand level recorded over the billing
period.
Power utilities generally bill commercial customers based on their peak usage
levels, called peak demand (in kW) and energy consumption (in kWh). Peak (or
maximum) demand is the highest demand level recorded over the billing period.
You can view peak demand values on your meter’s display.
Your meter calculates the average current demand and kW, kVAR and kVA
demand using sliding window demand methods. It supports coincident demand
values when a peak demand is detected.
Your meter’s default configuration is suitable for most applications, or you can
customize it for your specific application. You can configure the minimum time
between consecutive demand resets.
NOTE: If not specified, references to demand are assumed to mean power
demand.
214 7EN02-0390-04
Measurements PowerLogic™ ION9000 series
Demand value is
the average for the
Calculation updates at
last completed
the end of the interval
interval
Time
(min)
15 30 45
Time
(min)
15 20 25 30 35 40 45
Incremental energy
Incremental energy allows you to define a start time, end time, and the time
interval (increments) for incremental energy accumulation.
At the end of each interval, the energy accumulated during that period is stored.
By default, the meter only records the previous interval’s incremental energy and
the instantaneous energy accumulations in the active interval.
The first interval of incremental energy accumulation begins at the specified start
time. Incremental energy ends at the specified end time, which may result in a
truncated interval if the interval duration does not divide evenly into the overall
incremental energy duration. For example, an interval duration of three hours with
an overall duration of five hours truncates the last interval duration to two hours.
The latest value for the specified end time is midnight (24:00).
7EN02-0390-04 215
PowerLogic™ ION9000 series Measurements
Your start time must be before the end time and after midnight, and the period
over which incremental energy is accumulated cannot include midnight. This is
because your meter’s start and end times are defined relative to midnight.
Start: 6AM, End: Incremental energy accumulates from 6AM to midnight in intervals of 3
12AM, interval: 3 hrs hours.
Start: 6AM, End: Incremental energy will not function. End time must be after start time and
2AM, interval: 3 hrs before or equal to midnight.
Incremental energy helps provide information for analyzing energy and power
usage against present or future utility rates, and is useful for measuring energy
consumption by shift or for a specific process.
When configuring incremental energy, shorter incremental energy periods provide
more granular data which can make the data easier to use for comparison
purposes.
The first incremental energy interval is from 8AM (start time) to 3PM, and is 7
hours long. The second incremental energy interval is from 3PM to 10PM, and is
also 7 hours long. The third interval is from 10PM to 12AM, and is only 2 hours
long because 12AM is the specified end time. These intervals repeat every 24
hours until the configuration is changed or incremental energy feature is disabled.
216 7EN02-0390-04
Measurements PowerLogic™ ION9000 series
Start time 12:00 am to The incremental energy first interval’s start time. The
11:59 pm start time must be prior to the end time for energy
accumulation.
End time 12:01 am to The end time for incremental energy.
12:00 am
The end time must be after the start time and be less
than or equal to 12AM (midnight).
Interval duration Configurable The increment period for the incremental energy
duration.
Conditional energy
Conditional energy allows you to define an accumulation period for real and
reactive energy using one of your meter’s digital inputs.
You can use conditional energy to track four-quadrant accumulated energy during
a specific period. For example, you can track accumulated energy values during a
particular process that is controlled by a programmable logic controller (PLC).
Conditional energy is accumulated until it is reset. The conditional energy reset
date and time information is stored in the meter’s event log.
7EN02-0390-04 217
PowerLogic™ ION9000 series Measurements
Trending and forecasting data is a useful tool to help analyze changes in load and
power quality and forecasting values such as demand. For your meter’s trending
and forecasting feature to work, you only need to give the meter time to
accumulate data.
Vll ab I a mean
Vll bc I b mean
Vll ca I c mean
Vll avg I avg mean
You can configure the start day of the week for trending and forecasting using the
Clock setup assistant in ION Setup.
218 7EN02-0390-04
Resets PowerLogic™ ION9000 series
Resets
Meter resets
Resets allow you to clear various accumulated parameters stored on your meter,
reinitialize the meter or reinitialize meter accessories.
Meter resets clear your meter’s onboard data logs and other related information.
Resets are typically performed after you make changes to the meter’s basic setup
parameters to clear invalid or obsolete data to prepare the meter for active
service.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
You can reset your meter’s option module bus using ION Setup or through the
display. This power cycles all the modules attached to your meter. If you have
queued firmware updates for option modules on your meter’s internal SFTP site,
the firmware updates are performed.
By default, your meter is configured to automatically perform an option module
bus reset to help keep the option modules operating normally. Contact Technical
Support for instructions on changing this default configuration.
Available resets
You can perform various meter resets using ION Setup, the meter webpages or
through the display.
Reset Description
• Clears all cumulative and derived quantities from the meter, including: demand, peak demand,
energy, revenue and test mode parameters.
Master Reset • Clears meter event and waveform logs.
• Clears COMTRADE waveform records stored in the meter’s internal SFTP site.
• Clears meter data logs.
Harmonics Min/Max Reset Clears all accumulated maximum and minimum harmonics values stored in the meter.
Disturbance Count Reset Clears the sag/swell event counter. The sag/swell event counter counts the number of sag/swells that
have occurred since power-up or the last reset to provide power quality information to energy
management systems.
7EN02-0390-04 219
PowerLogic™ ION9000 series Resets
Reset Description
EN50160 Reset Clears all EN50160 parameters and statistics accumulated in the meter.
Option Modules Reset Resets communications to expansion modules connected to the meter.
Conditional (Cnd) Energy Reset Clears the conditional energy values stored in the meter.
Input Metering Reset Clears the input metering values stored in the meter.
NOTICE
DATA LOSS
Ensure all important data from the device has been retrieved before performing
a reset.
Failure to follow these instructions can result in data loss.
Master Reset
Volts, Amps and Power Master Reset
Master Reset
Input Metering IM(n) Reset
NOTE: n is the input metering number, for example IM1.
6. Click the appropriate button to perform the reset. For some resets, the meter
indicates that the reset is in progress.
Do not configure or power down your meter until it indicates that the reset is
complete or some parameters may not be completely reset.
220 7EN02-0390-04
Resets PowerLogic™ ION9000 series
NOTICE
DATA LOSS
Ensure all important data from the device has been retrieved before performing
a reset.
Failure to follow these instructions can result in data loss.
Parameter Description
Master Reset • Clears all cumulative and derived quantities from the meter,
including: demand, peak demand, energy, revenue and test
mode parameters.
• Clears meter event and waveform logs.
• Clears COMTRADE waveform records stored in the
meter’s internal SFTP site.
• Clears meter data logs.
EN50160 Reset Clears all EN50160 parameters and statistics accumulated in the
meter.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury or
equipment damage.
Meter resets clear the meter’s onboard data logs and related information.
7EN02-0390-04 221
PowerLogic™ ION9000 series Resets
NOTICE
DATA LOSS
Ensure all important data from the device has been retrieved before performing
a reset.
Failure to follow these instructions can result in data loss.
Reset Description
EN50160 Reset Clears all EN50160 parameters and statistics accumulated in the
meter.
Option Modules Resets communications to expansion modules connected to the
Reset meter.
6. Press Enable/Disable.
7. Press Select to accept the change.
When you select Master Reset, the message ALL RECORDED DATA WILL BE LOST.
RESET SELECTED PARAMETERS? is displayed.
222 7EN02-0390-04
Firmware upgrades PowerLogic™ ION9000 series
Firmware upgrades
Upgrade overview
It is recommended to upgrade PowerLogic™ advanced power quality meters to the
latest firmware version.
Before upgrading to the latest version, firmware version 2.1.0 must have been
previously installed. Go to www.se.com and search for Upgrading Meter Firmware
to v2.1.0 document for information on that upgrade. Firmware version can be
identified using ION Setup, meter webpages, or the display.
Meter firmware includes a digital signature which helps ensure authenticity.
Upgrade information
Meter firmware
A meter that has been upgraded to firmware version 3.0.0 or later cannot be
downgraded to an earlier firmware version.
NOTICE
LOSS OF DOWNGRADE CAPABILITY
Do not upgrade to firmware version 3.0.0 or later if you need to downgrade the
meter in the future.
Failure to follow these instructions can result in loss of firmware
downgrade functionality.
Upgrade agent
After upgrading the meter firmware to v2.2.1 or later, the previous upgrade agent
cannot be re-applied.
Restart requirement
Meter restart is required.
7EN02-0390-04 223
PowerLogic™ ION9000 series Firmware upgrades
Switch ION Setup into Advanced mode to setup multiple user accounts for meters
using Legacy security support: Open ION Setup > Ctrl + click on the meter to
select it.
NOTICE
LOSS OF CUSTOM WEBPAGES
Back up custom webpages before upgrading the meter firmware. The
webpages upgrade process overwrites all existing meter webpages.
Failure to follow these instructions can result in loss of custom webpage
functionality.
To back up meter webpages, copy the web folder to a local folder on the computer
using an SFTP client application.
NOTICE
LOSS OF CUSTOM FRAMEWORKS
Back up custom frameworks before upgrading the meter firmware. The upgrade
process overwrites existing meter frameworks.
Failure to follow these instructions can result in loss of custom framework
functionality.
224 7EN02-0390-04
Firmware upgrades PowerLogic™ ION9000 series
Connection requirements
• Use a direct Ethernet TCP connection to prevent delays and upgrade failure
risks associated with slower communications connection methods. You
cannot perform certain firmware updates over serial or Ethernet gateway.
• The display, webpages and option module firmware updates require an SFTP
over Ethernet connection.
• Use a computer connected to the same Ethernet network as the meter
(physically or through a remote desktop connection).
• To upgrade option module firmware, the option module(s) must be connected
to the meter.
NOTICE
UPGRADE FAILURE
Do not interrupt the upgrade process or disconnect the meter or any connected
components while ION Setup is performing the firmware upgrades.
Failure to follow these instructions can result in loss of meter
functionality.
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
Loading firmware or template onto your meter clears the meter’s recorded data.
7EN02-0390-04 225
PowerLogic™ ION9000 series Firmware upgrades
NOTICE
DATA LOSS
Ensure that all important data has been recorded before uploading firmware or
a template to your device.
Failure to follow these instructions can result in data loss.
226 7EN02-0390-04
Firmware upgrades PowerLogic™ ION9000 series
7. Click OK.
8. Click Proceed to start the upgrade process. Do not interrupt the process until
all the selected components have been upgraded.
9. Confirm upgrade status is complete and upload webpages to the meter. See
“Status”, page 227 for details.
NOTICE
LOST SETTINGS
Always select a template file when upgrading the meter firmware.
Failure to follow these instructions can result in loss of meter
settings.
2. Confirm upgrade status is complete and upload webpages to the meter. See
“Status”, page 227 for details.
Status
After all required meter firmware updates are complete, ION Setup continues to
perform the remaining updates.
• If you selected to upgrade the template, ION Setup will paste the template
into the meter.
7EN02-0390-04 227
PowerLogic™ ION9000 series Firmware upgrades
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTE: If your meter’s option module loses power during firmware upload, the
option module will revert to its original firmware and you will have to reload the
firmware file.
1. Connect to your meter’s internal SFTP site. Open the option module upgrade
(optionModuleUpg) folder.
2. Drag the option module firmware file into the option module upgrade folder.
The file is immediately transferred to the option module, and is not stored on
the meter.
228 7EN02-0390-04
Firmware upgrades PowerLogic™ ION9000 series
3. Review the option module firmware upgrade details stored in the meter’s
event log to confirm that the upload was successful. The upgrade folder must
match the position of the option module (A through D).
WARNING
UNINTENDED OPERATION
Do not use this device for critical control or protection of persons, animals,
property or equipment.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
NOTE: If your meter’s option module loses power during firmware upload, the
option module will revert to its original firmware and you will have to reload the
firmware file.
1. Obtain the Option Module firmware files (.S19) that you want to load onto
your option module(s). Save the files where they can be accessed by the
computer running ION Setup.
2. Start ION Setup.
3. Open the Setup Assistant for your meter.
4. Select the Template screen.
5. Click the Upgrade tab, then click Upgrade. Enter your meter’s password if
prompted and click OK.
6. Navigate to where you have stored the option module firmware. Select the
Option Module firmware file (*.S19) as the file type.
7. Select the option module firmware file and click Open.
An ION Setup window will open. Click Yes to confirm the firmware upgrade.
8. The Option Card Upgrade window opens. Select the Slot that corresponds to
the Option Module type. You can select multiple slots for the same option
module type.
9. Click Start.
A dialog box describes the firmware upgrade progress, verifies the firmware,
and finishes with an overview stating whether the firmware was successfully
uploaded.
7EN02-0390-04 229
PowerLogic™ ION9000 series Maintenance
Maintenance
Maintenance overview
The meter does not contain any user-serviceable parts. If the meter requires
service, contact your local Schneider Electric Technical Support representative.
NOTICE
METER DAMAGE
• Do not open the meter case.
• Do not attempt to repair any components of the meter.
Failure to follow these instructions can result in equipment damage.
Do not open the meter. Opening the meter voids the warranty.
Test mode
Test mode is typically used for verifying meter functions.
The meter is usually reading data from a test power supply while function
verification is performed.
The values shown in the test mode display screens represent different
accumulators than those shown in norm or alt mode (although they perform some
of the same basic measurements). The test mode display values are for accuracy
checking purposes; they only accumulate while the meter is in test mode.
You can create custom test mode screens and modify the existing test mode
screens.
NOTE: You cannot place revenue-locked meters into test mode.
Several things to note about test mode:
230 7EN02-0390-04
Maintenance PowerLogic™ ION9000 series
• All of the billing quantities that are recorded when the meter is in Normal
mode stop accumulating when the meter is switched to test mode – the data
is sent to special test mode registers instead.
• The values accumulated in these test registers are displayed on the test
mode displays and in ION Setup.
• The regular normal mode billing registers are unaffected while the meter is in
test mode; accumulation of this data continues as soon as you exit test mode.
• All test registers are reset to zero when you exit test mode.
Screen Description
Demand test This screen shows test mode kW delivered and received values. Both
quantities are produced from a sliding window (rolling block) demand
calculation.
Reactive energy This screen shows test mode kVARh delivered and received values.
test
Active energy This screen shows test mode kWh delivered and received values.
test
7EN02-0390-04 231
PowerLogic™ ION9000 series Maintenance
Device-specific information
Manufacturing-related information about the meter is available from the Factory
module or through Modbus commands.
The meter’s Factory module stores meter details such as device type, serial
number and vendor name. You can use ION Setup in advanced mode to view the
contents of the Factory module’s setup registers. Similarly, you can use Modbus
commands to read the Modbus registers mapped to the corresponding Factory
module’s registers.
NOTE: Not all ION device setup registers are mapped to Modbus registers by
default.
Other device-specific details, such as Product Code, are not stored in the Factory
module. Product Code (also known as Modbus Product ID) is a number that the
manufacturer assigned to a product to uniquely identify it, for use by systems that
specifically require this information. You can use the device’s Modbus map and
Modbus commands to read the Modbus Product ID.
The ION Reference describes the Factory module in detail. You can download the
ION Reference and your device’s Modbus map from www.se.com.
232 7EN02-0390-04
Revenue PowerLogic™ ION9000 series
Revenue
Revenue metering overview
A revenue meter provides, over a defined range of operating conditions,
measurements that are within international and national defined standards and
industry-accepted accuracy limits.
It also provides protection against unauthorized alteration of these measured
quantities. National and utility-based standards regulate protection against
unauthorized alteration of measured quantities.
Revenue locking
Revenue locking may be required to help meet government regulations and utility
security requirements.
Revenue locking your meter helps:
• Prevent changes to revenue-related features, settings and meter data.
• Prevent tampering with your meter’s voltage and current connections.
• Ensure the validity of revenue data.
Download the ION Device Template Reference, available from www.se.com to
view a complete listing of revenue-locked features, settings and meter data.
7EN02-0390-04 233
PowerLogic™ ION9000 series Revenue
See the meter’s catalog pages, available from www.se.com, or consult your local
Schneider Electric representative for information about your device, its options
and accessories.
Revenue-locking summary
You must configure and revenue lock your meter before installing it.
• Unlock your revenue meter if it is locked.
• Configure the required revenue settings specific for installation.
NOTE: If you are using ION Setup to configure your meter, allow for any
communication delays before removing power to your meter.
• Verify the revenue settings have been implemented.
• Clear all accumulated meter data.
• Revenue lock your meter.
• Verify the meter is revenue-locked.
• Install the meter and install the terminal covers according to your meter’s
installation guide.
234 7EN02-0390-04
Revenue PowerLogic™ ION9000 series
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Apply appropriate Personal Protective Equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, CSA Z462 or other local
standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on or in the equipment.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
Failure to follow these instructions will result in death or serious injury.
1. Turn off all power supplying this device and the equipment in which it is
installed before working on or in the equipment.
2. Always use a properly rated voltage sensing device to confirm that all power
is off.
3. Open the revenue lock switch cover.
4. Locate the revenue lock switch.
5. Toggle revenue lock switch on or off.
6. Close the revenue lock switch cover and make sure it is firmly in place.
7. Seal the revenue lock switch cover if required.
Anti-tamper sealing
The meter has several anti-tamper sealing points which can be sealed by a wire
seal or lock.
In certain countries, the meter is no longer revenue certified if the anti-tamper
seals are broken.
See your meter’s installation guide for sealing point locations.
NOTICE
LOSS OF COMPLIANCE
Ensure that you re-certify your meter with the appropriate revenue metering
authorities if you remove the anti-tamper seals.
Failure to follow these instructions may render your device non-compliant
for billing purposes.
7EN02-0390-04 235
PowerLogic™ ION9000 series Revenue
PT/CT correction
Potential transformer/current transformer correction (PT/CT correction), also
called instrument transformer correction, can help reduce the need to replace
transformers in installations where high accuracy is required.
The primary application for PT/CT correction is to apply correction factors for ratio
errors and phase angle errors to instrument transformers. PT/CT correction is
done for each current and voltage input to the meter and only affects 1-second
power meter data and values derived from it, such as energy or demand. No high-
speed, harmonics or waveform values are affected by the correction.
NOTE: For those familiar with ION architecture, the relevant 1-second Power
Meter module outputs are compensated using the Instr Xformer (ITC)
Correction module. All other modules that use the 1-second Power Meter
module’s data are also compensated.
See the ION Setup online help, available from www.se.com, for instructions on
how to configure PT/CT correction on your device.
See the ION Reference, available from www.se.com, for detailed information
about the Instr Xformer Correction (ITC) module and how it applies PT/ CT
correction to your device.
236 7EN02-0390-04
Revenue PowerLogic™ ION9000 series
low-voltage side of power transformers but the ownership change occurs on the
high-side of the transformer. Meters are usually installed on the low-voltage side of
a transformer because it is more cost-effective
NOTE: Due to the variation in installations, advanced knowledge of power
systems and connection methods is required before transformer loss
compensation can be properly implemented. Data parameters should only be
programmed by qualified personnel that have appropriate training and
experience with Transformer Loss Compensation calculations.
There are cases where the change of ownership occurs halfway along a
transmission line, where it is impractical to install a meter. In this case, power
metering must be compensated using line loss calculations.
See the Transformer / line loss calculations technical note available from
www.se.com.
Time of use
Time of Use (TOU) is often used when a utility has set up schedules with different
rates based on time of day, type of day and date when energy is consumed.
You can view the TOU active rates and seasons using the display.
See the ION Setup online help, available from www.se.com, for instructions on
how to configure TOU on your meter.
See the ION Reference, available from www.se.com, for a description of the Time
of use module and its settings.
7EN02-0390-04 237
PowerLogic™ ION9000 series Verifying accuracy
Verifying accuracy
Overview of meter accuracy
All meters are tested and verified at the factory in accordance with International
Electrotechnical Commission (IEC) and American National Standards Institute
(ANSI) standards.
Your digital power meter typically does not require re-calibration. However, in
some installations a final accuracy verification of the meters is required, especially
if the meters will be used for revenue or billing applications.
For a list of accuracy standards that your meter complies to, contact your local
Schneider Electric representative or download the meter brochure from
www.se.com.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Verify the device’s power source meets the specifications for your device’s
power supply.
Failure to follow these instructions will result in death or serious injury.
Control equipment
Control equipment is required for counting and timing the energy pulse outputs
from a visible LED, infrared LED or onboard digital output.
• Most standard test benches have an arm equipped with optical sensors to
detect LED pulses (the photodiode circuitry converts detected light into a
voltage signal).
• The reference device or energy standard typically has digital inputs that can
detect and count pulses coming from an external source (i.e., the meter’s
onboard digital output).
NOTE: The optical sensors on the test bench can be disrupted by strong
sources of ambient light (such as camera flashes, florescent tubes, sunlight
reflections, floodlights, etc.). This can cause test errors. Use a hood, if
necessary, to block out ambient light.
238 7EN02-0390-04
Verifying accuracy PowerLogic™ ION9000 series
Environment
The meter should be tested at the same temperature as the testing equipment.
The ideal temperature is about 23 ºC (73 ºF). Make sure the meter is warmed up
sufficiently before testing.
A warm-up time of 30 minutes is recommended before beginning energy accuracy
verification testing. At the factory, the meters are warmed up to their typical
operating temperature before calibration to help ensure that the meters will reach
their optimal accuracy at operating temperature.
Most high precision electronic equipment requires a warm up time before it
reaches its specified performance levels. Energy meter standards allow the
manufacturers to specify meter accuracy derating due to ambient temperature
changes and self-heating.
Your meter complies with and meets the requirements of these energy metering
standards.
For a list of accuracy standards that your meter complies to, contact your local
Schneider Electric representative or download the meter brochure from
www.se.com.
Energy pulsing
Energy pulsing LEDs and digital outputs can be used for energy pulsing.
Your meter is equipped with two types of energy pulsing LEDs: visible light and
infrared. These LEDs emit pulses that are then used to determine the accuracy of
the meter’s energy measurements. The pulses of light indicate accumulated
energy; the meter’s accumulations are compared with the reference/standard’s
accumulated energy in order to help determine the meter’s accuracy.
The meter’s digital output can also be used for energy pulsing. A closing (low
impedance) and then opening (high impedance) of the digital output represents a
pulse. If the accuracy testing equipment has a voltage requirement, a current-
limited wetting supply voltage must be provided.
NOTE: Digital outputs on option modules should not be used for meter
accuracy testing.
7EN02-0390-04 239
PowerLogic™ ION9000 series Verifying accuracy
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate Personal Protective Equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, CSA Z462 or other local
standards.
• Turn off all power supplying this device and the equipment in which it is
installed before working on or in the equipment.
• Always use a properly rated voltage sensing device to confirm that all power
is off.
• Do not exceed the maximum ratings of this device.
• Verify the device’s power source meets the specifications for your device’s
power supply.
Failure to follow these instructions will result in death or serious injury.
1. Turn off all power supplying this device and the equipment in which it is
installed before working on the device or equipment.
2. Use a properly rated voltage sensing device to confirm that all power is off.
3. Connect the test voltage and current source to the reference device or energy
standard. Ensure all voltage inputs to the meter under test are connected in
parallel and all current inputs are connected in series.
240 7EN02-0390-04
Verifying accuracy PowerLogic™ ION9000 series
4. Connect the control equipment used for counting the standard output pulses
using one of these methods:
Option Description
Energy pulsing LED Align the red light sensor on the standard test bench armature over
the energy pulsing LED.
Onboard Digital Connect the meter’s onboard digital output to the standard test bench
output pulse counting connections.
PF Power factor
Kt Pulse constant programmed in the meter under test in Wh/pulse
Round up the result of the calculation to the nearest integer number of pulses.
7EN02-0390-04 241
PowerLogic™ ION9000 series Verifying accuracy
242 7EN02-0390-04
Verifying accuracy PowerLogic™ ION9000 series
Full load 100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at unity power factor or one (1).
Light load 10% of the nominal current, 100% of the nominal voltage and nominal
frequency at unity power factor or one (1).
Inductive load (lagging 100% of the nominal current, 100% of the nominal voltage and nominal
power factor) frequency at 0.50 lagging power factor (current lagging voltage by 60°
phase angle).
Full load 100% to 200% of the nominal current, 100% of the nominal voltage and
nominal frequency at zero power factor (current lagging voltage by 90°
phase angle).
Light load 10% of the nominal current, 100% of the nominal voltage and nominal
frequency at zero power factor (current lagging voltage by 90° phase
angle).
Inductive load (lagging 100% of the nominal current, 100% of the nominal voltage and nominal
power factor) frequency at 0.87 lagging power factor (current lagging voltage by 30°
phase angle).
7EN02-0390-04 243
PowerLogic™ ION9000 series Troubleshooting
Troubleshooting
Setting up Advanced security troubleshooting
Some users could experience software access issues after enabling Advanced
Security mode. Resolve software access issues using these troubleshooting
steps:
244 7EN02-0390-04
Troubleshooting PowerLogic™ ION9000 series
Events related to option module initialization and operation are stored in your
meter’s onboard event log. Perform an option bus reset to restart the option bus
and re-initialize the option modules attached to your meter.
Information about your option module’s type, serial number, firmware version and
present status is available in the Factory and Diagnostics modules.
See the ION Reference, available from www.se.com, for more information about
the Factory and Diagnostics modules.
Technical assistance
Go to www.se.com and search for support to get assistance with troubleshooting.
Have the meter model, serial number and firmware version information ready. See
“Device-specific information”, page 232 for details about obtaining this
information.
You may be asked by a customer care agent to enable factory access to the
device for troubleshooting. Factory access is gained after a unique diagnostic
access code is used to login to the device over a secure protocol.
Factory access is:
• Disabled by default.
• Temporarily enabled for a duration defined in the Factory Access minutes
register.
• Requires adequate user privileges to enable.
• Provides read and write permissions.
7EN02-0390-04 245
PowerLogic™ ION9000 series ION9000 Specifications
ION9000 Specifications
Specifications overview
This section provides additional specifications for your meter and accessories.
The information contained in this section is subject to change without notice. You
can download updated documentation from www.se.com or contact your local
Schneider Electric representative for the latest updates.
See your device’s installation guide for specifications related to installation, such
as measured current and voltage ranges, inputs/outputs and control power
information.
Mechanical characteristics
ION9000 series meter
Mounting options DIN rail: IEC 60715 (DIN EN 60715), TH 35–7.5 or TH 35–15
Mechanical compliance
IEC 60068-2-57
Shock IEC 60068-2-27
Electrical characteristics
True RMS 4–quadrant metering up to the 63rd harmonic on three-phase systems,
1024 samples per cycle.
Measurement accuracy
NOTE: Reactive energy and demand values, by default, are based only on the
fundamental frequency, and do not include higher harmonics. Active and
apparent energy and demand values are measured using the entire signal
including harmonics. Contact Technical Support for more information.
246 7EN02-0390-04
ION9000 Specifications PowerLogic™ ION9000 series
Power quality
IEC 61000-4-15 Class F1 (Udin = 230 V/50 Hz, 120 V/60 Hz)
Voltage inputs
Specified accuracy range 57–400 V L-N/100–690 V L-L (Wye) or 100–600 V L-L (Delta or Wye with unearthed neutral)
Current inputs
Starting current 1 mA
Minimum signal 1 mV
Withstand 30 V pk continuous
Control power
AC control power
7EN02-0390-04 247
PowerLogic™ ION9000 series ION9000 Specifications
DC control power
Number 4
Type Form A solid-state
Reference voltage 40 V
Pulse frequency ≤ 25 Hz
Number 2
Type Form C mechanical relay
5 A @ 24 V DC
Digital inputs
Number 8
Type Externally excited, 24 V DC whetting voltage available from the meter
Reference voltage 40 V
Pulse frequency ≤ 25 Hz
OFF: ≤ 0.5 mA
Voltage ON state 4–30 V AC/4–60 V DC
248 7EN02-0390-04
ION9000 Specifications PowerLogic™ ION9000 series
Output voltage 24 V DC
Output current 20 mA
Environmental characteristics
Operating temperature –25 ºC to Max temp (–13 ºF to Max temp)
NOTE:
Maximum operating temperature could change based on the quantity and type of attached
option modules. See “Maximum operating temperature with option modules”, page 249.
Pollution degree 2
70 ºC (158 ºF) 0 2
LEDs
Energy pulsing LEDs (visible and infrared)
7EN02-0390-04 249
PowerLogic™ ION9000 series ION9000 Specifications
Conducted and radiated emissions EN 55011 and EN 55032 Class B, FCC part 15 Class B, ICES-003 Class B
Safety
Ethernet communications
Number of ports 2 (switched mode)
RS-485 communications
Number of ports 2
Real-time clock
Clock drift (time error) Meter Powered ON: 5 ppm max
Display
METSERD192 display
Display
Display type Capacitive touchscreen, WVGA color graphic TFT LCD 800 x 480 resolution
250 7EN02-0390-04
ION9000 Specifications PowerLogic™ ION9000 series
Communications ports
Control power
Power over Ethernet (PoE) power PD Type 1 Class 3 per IEEE 802.3af, 10W max.
Use UL listed or UL recognized NEC class 2 (or equivalent SELV or PELV) power source
Communication connection
Cable type CAT5 (or higher). Use with unshielded RJ45 modular connector
Environment
Operating temperature –20 ºC to 60 ºC (–4 ºF to 140 ºF)
Pollution degree 2
METSEPM89RD96 display
Display
Display type 1/4 VGA color graphic TFT LCD 320 x 240 resolution
Keypad 5 button
Communication connection
Cable type CAT5 (or higher). Use with unshielded RJ45 modular connector
Environment
IP degree of protection Front: IP54
Rear: IP30
7EN02-0390-04 251
PowerLogic™ ION9000 series ION9000 Specifications
Option modules
See your option module’s installation sheet for additional option module
specifications.
Other
Parameter Description
30 seconds: Communications
252 7EN02-0390-04
Open source software components PowerLogic™ ION9000 series
7EN02-0390-04 253
PowerLogic™ ION9000 series Open source software components
254 7EN02-0390-04
Open source software components PowerLogic™ ION9000 series
distribution of the Work otherwise complies with the conditions stated in this
License.
5. Submission of Contributions. Unless You explicitly state otherwise, any
Contribution intentionally submitted for inclusion in the Work by You to the
Licensor shall be under the terms and conditions of this License, without any
additional terms or conditions. Notwithstanding the above, nothing herein shall
supersede or modify the terms of any separate license agreement you may have
executed with Licensor regarding such Contributions.
6. Trademarks. This License does not grant permission to use the trade names,
trademarks, service marks, or product names of the Licensor, except as required
for reasonable and customary use in describing the origin of the Work and
reproducing the content of the NOTICE file.
7. Disclaimer of Warranty. Unless required by applicable law or agreed to in
writing, Licensor provides the Work (and each Contributor provides its
Contributions) on an "AS IS" BASIS, WITHOUT WARRANTIES OR CONDITIONS
OF ANY KIND, either express or implied, including, without limitation, any
warranties or conditions of TITLE, NON-INFRINGEMENT, MERCHANTABILITY,
or FITNESS FOR A PARTICULAR PURPOSE. You are solely responsible for
determining the appropriateness of using or redistributing the Work and assume
any risks associated with Your exercise of permissions under this License.
8. Limitation of Liability. In no event and under no legal theory, whether in tort
(including negligence), contract, or otherwise, unless required by applicable law
(such as deliberate and grossly negligent acts) or agreed to in writing, shall any
Contributor be liable to You for damages, including any direct, indirect, special,
incidental, or consequential damages of any character arising as a result of this
License or out of the use or inability to use the Work (including but not limited to
damages for loss of goodwill, work stoppage, computer failure or malfunction, or
any and all other commercial damages or losses), even if such Contributor has
been advised of the possibility of such damages.
9. Accepting Warranty or Additional Liability. While redistributing the Work or
Derivative Works thereof, You may choose to offer, and charge a fee for,
acceptance of support, warranty, indemnity, or other liability obligations and/or
rights consistent with this License. However, in accepting such obligations, You
may act only on Your own behalf and on Your sole responsibility, not on behalf of
any other Contributor, and only if You agree to indemnify, defend, and hold each
Contributor harmless for any liability incurred by, or claims asserted against, such
Contributor by reason of your accepting any such warranty or additional liability.
END OF TERMS AND CONDITIONS
7EN02-0390-04 255
Printed in:
Schneider Electric
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
www.se.com