Advanced Metering Applications PDF
Advanced Metering Applications PDF
Advanced
metering
applications
Advanced high performance meters are designed for mains or critical loads
on MV/LV networks. They provide analysis of efficiency, losses and capacity,
bill verification, power quality compliance monitoring, problem notification and
diagnosis and control of loads, etc.
Advanced
metering
Power quality meters are classified as advanced meters designed to monitor service entrances and
critical network locations to maximize power availability and reliability by providing a comprehensive
system load profile, power quality and root cause analyses.
• • PowerLogic™ PM8000
• • PowerLogic™ ION9000
PB113687
P115913
METSEPM8240 M7650
PM8000 Series
The PowerLogic™ PM8000 series meters are compact, cost-effective multifunction power meters that
will help you ensure reliability and efficiency of your power-critical facility.
Reveal and understand complex power quality conditions. Measure, understand and act on insightful data gathered from
your entire power system. Designed for key metering points throughout your energy infrastructure, the PowerLogic PM8000
series meter has the versatility to perform nearly any job you need a meter to do, wherever you need it!
Applications
Ideal for low to high voltage applications in industrial facilities, data centers, infrastructure and other
critical power environments.
PB113687
METSEPM8240
PM8000 series
The solution for Power management solutions
Markets that can benefit from a solution that includes PowerLogic Schneider Electric provides innovative
PM8000 series meters: power management solutions to increase
• Industry your energy efficiency and cost savings,
• Data centers maximize electrical network reliability and
• Infrastructure availability, and optimise electrical asset
• Healthcare performance.
• Buildings
Conformity of standards
Benefits • EN 50160 • IEC 62053-11
• EN 50470 • IEC 62053-22
• Makes understanding power quality simple to help
• IEC 61000-4-30 • IEC 62053-23
operations personnel avoid downtime and helps ensure
increased productivity and equipment life. • IEC 61010-1 • IEC 62053-24
• Makes energy and power quality immediately relevant and • IEC 61326-1 • IEC 62586-2
actionable to support your operational and sustainability • IEC 61557-12 • IEEE 519
goals. • IEC 62052-11 • UL 61010-1
Competitive advantages
• Modular, flexible patented ION technology architecture
enables a simple building block approach.
• Disturbance direction detection, modularity and compliance
with latest power quality standards.
• Color screen.
• Multiple communication options.
• Excellent accuracy.
–– Pass/fail report for IEEE 519 for voltage and current harmonic limits.
–– Harmonic analysis:
–– THD on voltage and current, per phase, min/max, custom alarming.
–– Individual harmonic magnitudes and angles on voltage and current,
up to the 63rd harmonic.
–– High resolution waveform capture: triggered manually or by alarm,
captured waveforms available directly from the meter via FTP in a
COMTRADE format.
–– Disturbance detection and capture: sag/swell on any current and voltage channel,
alarm on disturbance event, waveform capture with pre-event information.
–– Patented disturbance direction detection: provides indication of the captured
disturbance occurring upstream or downstream of the meter; timestamped results
provided in the event log, with degree of certainty of disturbance direction.
PowerLogic PM8000 series meter - rear view.
• Used with Schneider Electric’s sophisticated software tools, provides
detailed PQ reporting across entire network:
–– EN 50160 report.
–– IEC 61000-4-30 report.
PB113692
• Cybersecurity:
–– Security events logging with Syslog protocol support.
PowerLogic PM8000 DIN rail mounted meter. –– HTTPS secure protocol.
–– Ability to enable or disable any communication port and any protocol per port.
–– Anti-tamper protection seals and hardware metrology lock.
–– User accounts with strong passwords.
Usability
• Easy installation and setup:
–– Panel and DIN rail mounting options, remote display option.
–– Pluggable connectors.
–– Free setup application simplifies meter configuration.
PowerLogic I/O module. –– Auto-discovery using DPWS (Device Profile Web Services).
–– DHCP for automatic IP address configuration.
• Front panel:
–– Easy to read color graphic display.
–– Simple, intuitive menu navigation with multi-language (8) support.
PM8000 series
• Time synchronization via:
PB113686
Adaptability
–– ION™ frameworks allow customisable, scalable applications, object-oriented
programming, compartmentalizes functions, and increases flexibility and
adaptability.
–– Applications include: access and aggregate data from Modbus devices
on serial port or across the network (Modbus TCP/IP), logging and/or
PowerLogic PM8000 series meter with I/O modules. processing data by totaling, unit conversion or other calculations, applying
complex logic for alarming or control operations, data visualization via web
pages.
PM8000 series
PB113696
General
Use on LV, MV, and HV systems b
Current accuracy 0.1 % reading
Voltage accuracy 0.1 % reading
Active energy accuracy 0.2 Class
Number of samples/cycle or sample frequency 256
Instantaneous rms values
Current, voltage, frequency b
Active, reactive, apparent power Total and per phase b
Power factor Total and per phase b
Current measurement range (autoranging) 0.05 - 10 A
Energy values
Active, reactive, apparent energy b
Settable accumulation modes b
Demand values
Underside of PM8000 meter (DIN rail version).
Current Present and max. values b
Active, reactive, apparent power Present and max. values b
Predicted active, reactive, apparent power b
Synchronization of the measurement window b
Feature selection Setting of calculation mode Block, sliding b
Commercial Power quality measurements
Description
reference number b
Harmonic distortion Current and voltage
96 x 96 panel mount meter, Via front panel and web page 63
METSEPM8240 Individual harmonics
AC/DC power.
Via EcoStruxure™ software 127
96 x 96 panel mount meter, Waveform capture b
METSEPM8210
LV DC power. b
Detection of voltage swells and sags
DIN rail mount meter, Fast acquisition 1/2 cycle data b
METSEPM8243
AC/DC power. b
EN 50160 compliance checking
DIN rail mount meter, IEEE 519 compliance checking b
METSEPM8213
LV DC power. b
Customizable data outputs (using logic and math functions)
DIN rail mount meter with remote Data recording
METSEPM8244
display, AC/DC power.
Min/max of instantaneous values b
DIN rail mount meter with remote b
METSEPM8214 Data logs
display, LV DC power.
Event logs b
METSEPM82401 MID approved panel mount meter. Trending/forecasting b
SER (Sequence of event recording) b
RMICAN approved panel mount
METSEPM82403 Time stamping b
meter.
GPS synchronization (+/- 1 ms) b
RMICAN sealed panel mount
METSEPM82404 Memory (in Mbytes) 512
meter.
Display and I/O
Accessories Description Front panel display b
Wiring self-test b
Remote display, 3 metre cable,
mounting hardware for Pulse output 1
30 mm hole (nut & centering pin),
METSEPM89RD96 27 digital
mounting hardware Digital or analog inputs(max)
16 analog
for DIN96 cutout (92 x 92 mm)
adapter plate 1 digital
Digital or analog outputs (max, including pulse output) 8 relay
Digital I/O module (6 digital 8 analog
METSEPM89M2600
inputs & 2 relay outputs)
Communication
Analog I/O module (4 analog
METSEPM89M0024 RS-485 port 1
inputs & 2 analog outputs)
Ethernet port 2
Replacement hardware kit
Serial port (Modbus, ION, DNP3) b
METSEPM8HWK (connectors, screws, retainer
clips, mounting template) Ethernet port (Modbus/TCP, ION TCP, DNP3 TCP, DHCP, DNS, IPv4, IPv6, b
IEC 61850)
Ethernet gateway b
Alarm notification via email b
HTTP/HTTPs web server with waveform viewer b
SNMP with custom MIB and traps for alarms b
SMTP email b
PTP and NTP time synchronization b
FTP file transfer b
PM8000 series
Technical specifications
Electrical characteristics
Type of measurement True rms to 256 samples per cycle
DC 20 to 60 V DC ±10 %
Power supply
LV DC
Burden Fully optioned: max. 18 W at 18 to 60 V DC
Mechanical characteristics
Integrated Display Model 0.581 kg
DIN rail mounted Model 0.528 kg
Weight
IO modules 0.140 kg
Remote display 0.300 kg
IP 54, UL type 12: Panel mount and Remote display, front.
IP degree of protection
IP 30: Panel mount rear, DIN rail mount, I/O modules.
Excellent quality ISO 9001 and ISO 14000 certified manufacturing.
Panel mount model 96 x 96 x 77.5 mm
DIN model 90.5 x 90.5 x 90.8 mm
Dimensions
Remote display 96 x 96 x 27 mm
IO modules 90.5 x 90.5 x 22 mm
PM8000 series
Environmental conditions
Operating temperature -25 ºC to 70 ºC
Electromagnetic compatibility
EMC standards IEC 62052-11 and IEC 61326-1
Conducted and radiated emissions EN 55022, EN 55011, FCC part 15 Class B, EN55011, EN55022 Class B, ICES-003 Class B
Safety
IEC/EN 61010-1 ed.3, CAT III, 400 V L-N / 690 V L-L
Safety Construction UL 61010-1 ed.3 and CSA-C22.2 No. 61010-1 ed.3, CAT III, 347 V L-N / 600 V L-L
IEC/EN 62052-11, protective class II.
Communication
Ethernet to serial line gateway Communicates directly with up to 31 unit load devices.
Web server Customisable pages, new page creation capabilities, HTML/XML compatible.
Serial port RS-485 Baud rates of 2400 to 115200, pluggable screw terminal connector.
Protocol Modbus, ION, DNP3, IEC 61850, HTTPS, FTP, SNMP, SMTP, DPWS, RSTP, NTP, PTP, NTP/SNTP, GPS, IPv4 /IPv6, DHCP, Syslog protocols.
Firmware characteristics
Down to 1/2 cycle interval burst recording, stores detailed characteristics of disturbances or outages. Trigger
High-speed data recording
recording by a user-defined setpoint, or from external equipment.
Harmonic distortion Up to 63rd harmonic (127th via Schneider Electric software) for all voltage and current inputs.
Analyse severity/potential impact of sags and swells: magnitude and duration data suitable for plotting on voltage
Sag/swell detection
tolerance curves per phase triggers for waveform recording, control.
Determine the location of a disturbance more quickly and accurately by determining the direction of the
Disturbance direction detection disturbance relative to the meter. Analysis results are captured in the event log, along with a timestamp and
confidence level indicating level of certainty.
High accuracy of standard speed (1s) and high-speed (1/2 cycle) measurements, including true rms per phase
Instantaneous and total for: voltage, current, active power (kW),reactive power (kvar), apparent power (kVA), power factor,
frequency, voltage and current unbalance, phase reversal.
Channel assignments (800 channels via 50 data recorders) configurable for any measurable parameter, including
Load profiling historical trend recording of energy, demand, voltage, current, power quality, or any measured parameter. Trigger
recorders based on time interval, calendar schedule, alarm/event condition, or manually.
Historical trends and future forecasts to better manage demand, circuit loading, and other parameters. Provides
Trend curves average, min, max and standard deviation every hour for last 24 hours, every day for last month, every week for last
8 weeks and every month for last 12 months.
Simultaneous capture of all voltage and current channels, sub-cycle disturbance capture, ability to record from 210
Waveform captures cycles at 256 sample per cycle to over 2880 cycles at 16 points per cycle with user selectable sampling speed as
well as pre- and post-trigger length.
Threshold alarms: adjustable pickup and dropout setpoints and time delays, numerous activation levels possible for a given type
Alarms
of alarm, user-defined or automatic alarm threshold settings, user-defined priority levels (optional automatic alarm setting).
Advanced Time of Use (TOU) 6 seasons; 3 different day types: weekend, weekday, and holiday; up to 8 tariffs per day type.
PM8000 series
Firmware characteristics (cont.)
Advanced security Up to 50 users with unique access rights. Perform resets, time sync, or meter configurations based on user privileges.
Display characteristics
Integrated or Remote display 320 x 240 (1/4 VGA) Color LCD, configurable screens , 5 buttons and 2 LED indicators (alarm and meter status).
Meter setup, communications setup, display setup, date/time/clock setup, alarm setup, language setup, time of use
Setup Menu setup, resets, password setup.
PB113642
PM8000 series
PM8000 panel mount meter dimensions
PB119087
PB119086
Please see the appropriate Installation Guide for accurate and complete information on the installation of this product.
ION9000 Series
The PowerLogic™ ION9000 is your 24/7 power quality expert, providing information, not just data.
With a comprehensive, industry-leading Power Quality Instrument (PQI) performance designation according to IEC 62586-
1/-2, the PowerLogic ION9000 is third-party certified ANSI C12.20 Class 0.1 and IEC 62053-22 Class 0.1S accurate, the
most accurate power meter available today. Lab-verified power quality and safety ensure reliable, precision performance
that is perfect for supply- or demand-side applications. Its patented Disturbance Direction Detection also helps you pinpoint
the source of power quality issues faster. Capable of sampling at 10 MHz, the ION9000T captures extremely fast voltage
events that are missed by most other power meters, enabling advanced diagnostics and high-resolution event associations
for fast, conclusive diagnosis and resolution to transient voltages.
Highly customizable and modular, the ION9000’s field programmability can adapt to satisfy any solution, protecting your
investment now and in the future. All designed to align with your comprehensive grid cybersecurity policies and backed by
Schneider Electric’s global services and support.
Applications
Ideal for critical power and large energy users who cannot afford to be shut down, the ION9000T has High-Speed Transient
Capture (HSTC) to detect and record transient events that exceed the voltage withstand of sensitive equipment.
PB115917
METSEION92040
Competitive advantages
• Modular, flexible, patented ION™ programmable technology
• Utility grade energy accuracy
• Patented Disturbance Direction Detection
• Third-party, lab-verified compliance with latest PQ standards
• Onboard pass/fail PQ characterization and assessment
according to EN50160 and IEEE519
• Cybersecurity event logging, Syslog protocol, HTTPS, SFTP,
and full control of each communication port
• High-speed impulsive and oscillatory transient detection
Main characteristics
• PQ compliance reporting and basic PQ analysis:
–– Monitors and logs parameters according to IEC 61000-4-30 Class A
PB115917
disturbance direction.
• Transient detection and capture: events 20 microseconds or longer in
duration on any voltage channel with alarm, event log, and waveform capture.
• PowerLogic ION9000T also provides High-Speed Transient Capture (HSTC)
of voltage events 100 nanoseconds or longer in duration and up to 10,000 V
in magnitude with high-speed and disturbance waveform captures, as well as
per-event statistics on each transient.
• Metering precision:
–– IEC 61557-12 PMD/SD/K70/0.2 and PMD/SS/K70/0.2 3000m (Performance
Measuring and Monitoring devices (PMD)).
–– Class 0.1S accuracy IEC 62053-22, ANSI C12.20 Class 0.1 (active energy).
–– Industry leading Class 0.5S accuracy for reactive energy (IEC 62053-24).
PowerLogic™ ION9000 RD192 remote display –– Cycle-by-cycle RMS measurements updated every ½ cycle.
–– Full ‘multi-utility’ WAGES metering support.
–– Net metering.
–– Anti-tamper protection seals and hardware metrology lock.
PB115918
• Cybersecurity:
–– Security events logging with Syslog protocol support.
–– HTTPS and SFTP secure protocols.
–– Ability to enable or disable any communication port and any protocol per
port.
–– Anti-tamper protection seals and hardware metrology lock.
–– User accounts with strong passwords.
Usability
• Auto-discovery using DPWS (Device Profile Web Services).
• DHCP for automatic IP address configuration.
• Full function web server enables simple web commissioning.
PowerLogic ION9000 bottom with two option modules • Free setup wizard simplifies meter configuration.
• Front panel:
–– Easy to read color graphic display.
–– Simple and intuitive menu navigation with multiple language
interface and support.
• DIN rail mounting options.
• Remote display option.
• Pluggable connectors.
Adaptability
ION9000 series
Technical specifications
ION9000 ION9000T
Electrical characteristics
Type of measurement True rms to 1,024 samples per cycle b b
High-speed transient detection, 10 MHz, 10 kV b
Measurement accuracy Current & voltage Class 0.1 as per IEC 61557-12 b b
Active Power Class 0.1 as per IEC 61557-12 b b
Power factor Class 0.5 as per IEC 61557-12 b b
Frequency Class 0.02 as per IEC 61557-12 b b
Active energy Class 0.1S IEC 62053-22 b b
Class 0.1 IEC 61557-12
Class 0.1 ANSI C12.20
Input-current Rated nominal current 1 A (0.1S), 5 A (0.1S); current class 2, 10, 20 A (0.1 ANSI) b b
characteristics
Specified accuracy Starting Current: 1 mA (no accuracy) b b
current range Accurate Range: 10 mA - 20 A
Mechanical characteristics
Weight DIN rail mount meter 1.5 kg b b
IO modules 0.140 kg
Touchscreen display 0.300 kg
IP degree of protection IP 65, UL type 12: Panel mount and touchscreen display, front. b b
IP 30: Panel mount rear, DIN rail mount, I/O modules.
Excellent quality ISO 9001 and ISO 14000 certified manufacturing. b b
(1) Consult the ION7550 / ION7650 installation guide for complete specifications. (2) IEC 62051-22B with serial ports only.
ION9000 series
Environmental conditions ION9000 ION9000T
Operating temperature -25 to 70 ºC b b
Remote Display Unit -25 to 60 ºC b b
Storage temperature -40 to 85 ºC b b
Humidity rating 5 to 95 % non-condensing b b
Communication
Ethernet to serial line gateway Communicates directly with up to 31 serial devices. b b
Web server Customizable pages, new page creation capabilities, HTML/XML compatible. b b
Serial port RS-485 2x, Baud rates of 2,400 to 115,200, pluggable screw terminal connector. b b
Ethernet port(s) 2x 10/100BASE-TX, RJ45 connector, CAT5/5e/6/6a cable. b b
Protocol HTTPS, SFTP, SNMP, SMTP, DPWS, RSTP, PTP, NTP/SNTP, GPS, Syslog, DHCP, IPv4, IPv6. b b
Firmware characteristics
High-speed data recording Down to 1/2 cycle interval recording, stores detailed characteristics of disturbances b b
or outages. Trigger recording by a user-defined setpoint, or from external equipment.
Harmonic distortion Up to 63rd harmonic (511th via Schneider Electric EcoStruxure software) for all b b
voltage and current inputs.
Sag/swell detection Analyze severity/potential impact of sags and swells: magnitude and duration data suitable for b b
plotting on voltage tolerance curves per phase triggers for waveform recording.
Disturbance direction detection Determine the location of a disturbance more quickly and accurately by determining b b
the direction of the disturbance relative to the meter. Results are captured in the
event log, along with a timestamp and confidence level indicating level of certainty.
Instantaneous High accuracy of standard speed (1s) and high-speed (1/2 cycle) measurements, b b
including true rms per phase and total for: voltage, current, active power
(kW),reactive power (kvar), apparent power (kVA), power factor, frequency, voltage
and current unbalance, phase reversal.
Load profiling Channel assignments (1600 channels via 100 recorders) configurable for any b b
measurable parameter, including historical trend recording of energy, demand,
voltage, current, power quality, or any measured parameter. Trigger recorders based
on time interval, calendar schedule, alarm/event condition, or manually.
Trend curves Historical trends and future forecasts to better manage demand, circuit loading, and other b b
parameters. Provides average, min, max, and standard deviation every hour for last 24 hours,
every day for last month, every week for last 8 weeks and every month for last 12 months.
ION9000 series
Firmware characteristics (cont.) ION9000 ION9000T
Waveform captures Simultaneous capture of voltage and current channels, sub-cycle disturbance captures of b b
180-cycles @ 1,024 samples/cycle to 7,200-cycles @ 16 sample/cycle, retriggerable.
High-speed transient waveform Simultaneous capture of voltage channels, impulsive and oscillatory transient capture b
captures of up to 1-cycle @ 200 k samples per cycle (50 Hz) along with coincidence disturbance
waveform capture (PowerLogic ION9000T).
Alarms Threshold alarms: adjustable pickup and dropout setpoints and time delays, numerous activation b b
levels possible for a given type of alarm, user-defined or automatic alarm threshold settings, user-
defined priority levels (optional automatic alarm setting).
Advanced Time of Use (TOU) 4 seasons; 5 different day types: weekend, weekday, and holiday; up to 4 tariffs per day type. b b
Advanced network security Up to 50 users with unique access rights. Perform resets, time sync, or meter b b
configurations based on user privileges.
192 mm touchscreen display 800 x 480 pixels, 177.8 mm (7”) Color LCD, +/- 85 degree view angle, sunlight readable, b b
dual capacitive touch, usable when wet or through Class 0 lineman gloves, impact
resistant to 5 joules, IP65 rating.
METSEION92040 ION9000 meter, DIN mount, 192 mm display, B2B adapter, hardware kit
METSEION95040 ION9000T meter, HSTC, DIN mount, 192 mm display, B2B adapter, hardware kit
METSE9HWK ION9000 meter hardware kit – plugs, terminal guards, spare grounding screw, DIN clips
METSE9CTHWK ION9000 current input hardware kit – terminal screws and covers
ION9000 series
ION9000 meter dimensions ION9000 mounting template
PB119714_m
PB119707
PB119705
Please refer to ION9000 Series Meter Installation Sheet for accurate and complete information on the installation of this product.
ION9000 series
ION9000 meter DIN rail dimensions ION7x50 mounting adapter dimensions
PB119706
PB119714
ION9000 meter click installation
PB119708