VYKON IO-28U JACE IO Module
VYKON IO-28U JACE IO Module
monitoring of specific voltage,resistance and temperature sensor), eight Digital Outputs (Relay), and four
Analogue Output (current and voltage).
logic controlled equipment
High Accuracy Analog Channels
fooled controller uses. • 12-bits A/D converter with programmable gain amplifier yields a high resolution and
accuracy reading on analogue input points.
• 12-bits D/A converter provides more accurate analogue output control.
Communication
Port 1 EIA-485 Standard Two Wire, Half Duplex, 1/8 Load
Baudrate 9.6K, 19.2K, 38.4K, 76.8K, 115.2K bit/s
Data Bit 8 bits
Parity None, Even, Odd
Protocol Bacnet MSTP, Modbus RTU
Input/Output
Analogue Input 8 Channels, 12-bits with PGA
Voltage 0 - 10V (±0.01V), 0 - 5V (± 0.01V)
Current 4 - 20mA (±0.01mA) , 0 - 20mA (±0.01mA)
Resistance 0 - 30K (±10 Ohm), 0 - 10K(±5 Ohm),0 - 1.5K (±1 Ohm)
Thermistor Sensor NTC: 10K TYPE 2/3,3K,20K(±0.1°C) RTD: 1K Balco, 1K Platinum(±0.2°C)
Others
CPU ARM Cortex 32-bit, 80MHz
Size L 198mm × W 122mm × H 41mm
Casing Material UL94 ABS
Weight 410±5g
Certification
• C-Tick
• UL
• CE
• FCC
contact us
Tridium AP Sales and Technical Service Center
Email: [email protected]
Ethernet, TCP/IP, BA
www.vykon.com
All specifications subject to change without notice or liability to provide changes to prior purchasers. Information and specifications published here are current as of
the date of publication of this document. Tridium, Inc. reserves the right to change or modify specifications without prior notice. Thelatest product specifications can
be found by Tridium AP Sales and Technical Service Center . Products or features contained herein may be covered by one or more patents. © 2013 Tridium, Inc.