Lecture Notes - Part 1
Lecture Notes - Part 1
University of Newcastle-upon-Tyne
School of Electrical, Electronic and Computer Engineering
Module EEE8047
Design and Automation
8 – 9 February 2010
Domestic Component
1
Lecture Notes Session 1 - Introduction
Nuclear
Gas Turbines
Single Cycle
Combined Cycle
TRANSMISSION VOLTAGE
LEVELS
•POWER TO BE TRANSMITTED
•DISTANCE OF
TRANSMISSION
•1 KV per Kilometre
2
Lecture Notes Session 1 - Introduction
•66 kV
•33 kV
•13.8 kV
•11 kV
•6.6 kV
•3.3 kV
3
Lecture Notes Session 1 - Introduction
Early Generation in UK
after
Sir Thomas Edison built first Generating Station
New York 1878
4
Lecture Notes Session 1 - Introduction
Current Reaction
9-30 Milliamperes (men) This is called the freezing current or “let-go” range.
C1: Threshold of
cardiac
fibrillation
5
Lecture Notes Session 1 - Introduction
132kV
154kV
66kV
G1 G2 G3
13.8kV
G4 G5 G6
To 33kV
Typical Oil Refinery Grid Voltage Key
Network - OMAN 33 kV
6.6 kV
Auto Transfer 1000V
415V
A1
NO
Standby G
B1 B2
B8A Emergency Power Dist. Panel B8
M Misc.
CHC
60 kW EFLCHL
Typical for each
Bus-Section (See Fig.6)
Fire
Cooling
Water B22
B3 B4 See Fig.5
SWB B2R
SWB B2L
6
Lecture Notes Session 1 - Introduction
M M M M M M M M M M M M M M
P-8551 P-800 1 P-800 3 P-8011 P-8101 P-8 575 P-857 9 P-85 81 P-8 583 P-82 11 P-80 43 P-8 051 K -8251 KM -8203
185 kW 3 50 kW 350 kW 220 kW 220 kW 200 kW 25 0 kW 250 kW 4 205 kW 185 kW 2 20 kW 170 kW 400 HP 800 kW
Compre ssor Co mp ressor
M M M M
North South
Satellite Satellite
245-KH-001 Gas Compressors West
A/B/C/D (6MW)
Satellite
Circuit Breaker
M M M M M Disconnector
M M M M M M M M Motor
11kV
22kV
6.6kV
ZADCO – APCT
M M M M M M M UAE
7
Lecture Notes Session 1 - Introduction
11 kV
3.3 kV
415V
M
M
TR341
6.6/0.725kV Dyn11 TR342 TR343
1250 kVA uk = 5.3% 6.6/0.725kV Dyn11 6.6/0.725kV Dyn11
1250 kVA uk = 5.3% 400 kVA uk = 3.91%
76.2Ω
NS41 690V
M M M
144-ONP1B
144-OPM-1010B
144-OPM-1020A
M M
144-OPM-1010A
144-OPM-1020B
Instrument Instrument
Electrical Supply Supply to 1TR2 ?
Supply to 1TR2
Heat Tracing
Tank Area M
Welding
Receptacles
30kW
Lighting 15kW
Tank Area
8
Lecture Notes Session 1 - Introduction
TR131 TR132
33/6.9kV Dyn11 33/6.9kV Dyn11
16 MVA uk = 8.35% 16 MVA uk = 8.35%
5 Off-load Taps 5 Off-load Taps
+ or – 5% 76.2Ω + or – 5% 76.2Ω
6.6kV
NS31 A8 NS31 A7 A6 A5 A4 A1 A3 A2 B2 B1 B3 B4 B5 B6 NS31 B7
Spare
Spare
M M M
SEEHT M M SEEHT
From 6.6kV Supply
400kVA 400kVA
600 2050 3950 2050 600 SS1 – ES13
Xfr Xfr
Dist Fdr kW kW kW kW kW Dist Fdr
(Line “A”) (Line “B”)
TR342
TR344
TR343
TR341
NS42 ES41
NS41
?
M M M M M M
MOV1042
Typical Dist
MOV1043
Fdr
TR451
NS51
M
6A1 6A2 6A3 6A4
M
NL51 Supplementary
Heating
100A
49 50N
3
75/1A I >
PDCS Interface
U < 59
55kW
M PF=?
Space Torque v Speed?
Heater Other Characteristics?
Check Manufacturer’s Data
9
Lecture Notes Session 1 - Introduction
40 20
7108 7320
35
40
10
7118 7057
7016
8016
ST1 ST2
G1 G2 G3 G4
33kV
33kV
11kV
7118
11kV
7016
415V
Typical Utility
To Consumers Medium Voltage
Primary Substations
10
Lecture Notes - Session 2 - Network
Components
Distribution Network
Components
There are many factors to take into consideration
when choosing components
for a Distribution Network
Environmental Considerations
Safety Considerations
A Set of 3-wires
Insulator Strings (Conductors)
1
Lecture Notes - Session 2 - Network
Components
136 feet
And
6 inches
(41.6 meters)
The choice of support structure, wood pole, steel pole, steel latticed
is governed by Mechanical and Civil Considerations
Conductor Spacing.
2
Lecture Notes - Session 2 - Network
Components
Back-fill
Warning Tiles
Soft Layers
Tre-foil
Outer Jacket
Screen
Phase
Insulation
Cores
Copper or
Aluminium
3
Lecture Notes - Session 2 - Network
Components
B Y B Y B Y B
R Y B R Y B R Y
Y axis
Or Like This (Jackets separated)
Or Like This (Jackets separated) (4) R
(3) B Y
R Y B etc X axis
a
b
If like 3 or 4, I need dimensions of separation
Distribution Transformers
LowVoltage Bushings N
High Voltage Bushings Star-
Point
TANK
Laminated
Steel
Core
4
Lecture Notes - Session 2 - Network
Components
Delta-Star
Delta- Star
Star-Delta Star-Delta
Star- Star
Star-Star
Star- Star
with Auto-Tap Changer Star-Star
with
Auto-Tap
IEE - UK Changer
IEEE - USA
(B)
CIRCUIT
BREAKER
Circuit Breakers
OPENING
CIRCUIT
BREAKER SPRING
(COMPRESSED)
A3 AUXILIARY
CIRCUITS (ALARMS ETC)
A2
TRIP COIL
BATTERY
MAIN LATCH (D)
HV CIRCUIT MAIN
T A1
CONTACTS RELAY
(C) TRIPPING
CONTACT
CT
(A)
RELAY
5
Lecture Notes - Session 2 - Network
Components
Often employed
when
contacts are linked
contacts of another CB in
an automation scheme
Non Rack-out
type
Transmission or Rack-out type LV Distribution
Rack-out type Rack-out type
Distribution (GIS) Distribution (1) 415V etc
Distribution (2) Distribution (3)
Oil or Vacuum Air-break or
Oil or Vacuum Oil or Vacuum
Magnetic
As German or
Contactor with
thermal overload
releases
Isolating
circuit
breaker
Circuit or or or or or or
or CB
breaker
6
Lecture Notes - Session 2 - Network
Components
Double Busbars
3
Disconnector/Earth Switch
1
Voltage Transformer Interrupter
3
Current Transformer
2
Alternative Arrangement
with disconnector in
voltage Transformer circuit
4
5 Single Line Diagram
Notes:- Disconnectors (Refer to section 2.7)
Voltage and Current Transformers (Refer to Section 2.15)
Technical Characteristics
Rated Voltage KV 12 17.5 24 36 38 40.5 52 *±27.5
Rated Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50
Rated power frequency withstand
KV 28 38(42) 50 70 80 80 95 95
voltage
Rated lightning impulse withstand
KV 75 95 125 170 200 200 250 250
voltage (BIL)
Rated current: busbar up to A 2500 2500 2500 2500 2500 2500 2500 2000
Rated current: feeder up to A 2500 2500 2500 2500 2500 2500 2500 2000
Rated short-time withstand current
kA 40 40 40 40 31.5 40 31.5 25
(3s) up to
7
Lecture Notes - Session 2 - Network
Components
Typical Reclosers
Courtesy Whipp & Bourne
(a)
(b)
(c)
(a) Cross-section
(b) Typical Pole Mounting
(c) Showing Control Cubicle (d)
(d) Control Cubicle Door Open
Control Cubicle
8
Lecture Notes - Session 2 - Network
Components
In Common Use
International
Symbol
Operating Bar
9
Lecture Notes - Session 2 - Network
Components
10
Lecture Notes - Session 2 - Network
Components
In-line Mounting
11
Lecture Notes - Session 2 - Network
Components
To
Transformer
and Consumers
Cable Cable
Feeder Feeder
RING MAIN UNIT
Transformer LVDB
RMU
Cable Feeder Cable Feeder
(c)
Package (d)
Substation
Cable Feeders
Cable Feeders
(e)
Step-down
Transformers (f)
12
Lecture Notes - Session 2 - Network
Components
Communication
(Refer to Sections 9 and 11)
Power Frequency
kV 28/38/50 28/38/50 28/38/50 28/38/50 28/38/38/50
Withstand Voltage
Impulse Withstand
kV 95/95/125 95/95/125 95/95/125 95/95/125 95/95/95/125
Voltage
630/630/630/63
Rated Current A 630/630/630
0
Breaking Capacities
Of Load Cable
A 135/135/135
Charging Current
13
Lecture Notes - Session 2 - Network
Components
Circuit Breaker
Disconnector
or Fuse
MCCB
MCCB’s to
Outgoing 415V feeders
14
Lecture Notes - Session 2 - Network
Components
Fused Cut-outs
Oil Switches
15
Lecture Notes - Session 2 - Network
Components
A
These fuse types are
D usually employed on
outdoor distribution
equipment and overhead
line poles
B
The mechanism allows the top contact to disengage on fuse operation so that
the fuse carrier tube falls outwards about the lower hinge
11kV
Primary Busbar
16
Lecture Notes - Session 2 - Network
Components
Earth leakage protection, shunt trip coils and undervoltage releases may
also be incorporated in the designs
Normally the MCB requires manual resetting after a trip situation but
solenoid or motor driven closing is also possible for remote control.
17
Lecture Notes - Session 2 - Network
Components
A Selection of MCC’s
A Selection of MCCB’s
18
Lecture Notes - Session 2 - Network
Components
Current Out
Current In Spring
Latch
Circuit Breaker
Latch Contacts
Armature
Current Out
Spring
Electromagnet
Current In Conductor
19
Lecture Notes - Session 2 - Network
Components
Line Capacitors
Front
Controls
Rear
Surge
Protection
Capacitors
20
Lecture Notes - Session 2 - Network
Components
Reactors
Voltage Regulators
(a) Single-Phase Unit (b) Two Single-Phase Units (c) Three Single-Phase Units
Line Connections – Open Delta Line Connections – Star/Star
21
Lecture Notes - Session 2 - Network
Components
(a) (b)
Three Single-phase Units Two Single-phase Units
Connected Star Connected Open Delta
Europe
Europe
Europe North
North America
America
R
Reference (Yellow Phase)
Y
B
Line Voltage
60O
0.05 pu 0.05 pu
V”BR (1.1 p.u)
Reversing Switch
Current Transformer
Source Bushing V.R V.L
Load Bushing
S L
1 2 3 4 5 6 7 8 N
Regulated Load
Unregulated Source
+
Control
SL
22
Lecture Notes - Session 2 - Network
Components
Line Drop
G Co-generation
Consumer
Forward Power Flow Substation
Consumer
Load
Point of
Voltage Control
Grid
Line Drop
Consumer
Reverse Power Flow Substation
Consumer
Load
Series Reactors
23
Lecture Notes - Session 2 - Network
Components
132kV
154kV
Series Reactors (Cont)
66kV
G1 G2 G3
13.8kV
G4 G5 G6
Shunt Reactors
Line
Line
24
Lecture Notes - Session 2 - Network
Components
A 380 kV
Substation Connected in
the tertiary windings
Double Bus of the 380/110kV
transformers
Double Circuit Breaker
Status
T1 Symbol T2 T3
Key Isolator (Disconnector)
CT
Relay
(Meter)
US VT (PT)
Primary Circuit
Secondary Circuit
Europe
25
Lecture Notes - Session 2 - Network
Components
Line
Arrester
Surge Arrester
Line Line
26
Lecture Notes - Session 2 - Network
Components
Volts
Normal
Voltage Earth Connection
Operating
Range
Dimensions in mm
27
Lecture Notes - Session 2 - Network
Components
OR
Single-phase CT’s
3-phase CT External Visible
MV O/H Local and
MV U/G Indicating Unit
Networks Remote Indications
Networks Via SCADA
28
Lecture Notes - Session 2 - Network
Components
(a) (b)
Radio Transceiver
PMT
Protection Relays
A relay is used as the signal to trip
Instantaneous Overcurrent
Directional Overcurrent
Impedance
Voltage
29
Lecture Notes - Session 2 - Network
Components
30
Lecture Notes - Session 2 - Network
Components
Type MCND 04
Negative Sequence
Overcurrent Relay
Composite Microprocessor
based Relays and Meters
C60
31
Lecture Notes - Session 2 - Network
Components
52
Reclose
Trip 79
Monitoring
81
METERING
27X 27P
25
C60
Breaker Management Relay
Composite Microprocessor
based Relays and Meters (Cont)
Relay Type
Local/Remote Switch
Communication Port
32
Lecture Notes - Session 2 - Network
Components
Composite Microprocessor
based Relays and Meters (Cont)
Display
3 types of messages: RS45
•Actual value Comms Port
•Setpoint, (Rear
•Target messages
Note:- Ethernet Options
also available
LED Displays
Control Keys etc
RS232 Comms
Port (Front)
Courtesy of GE Multilin
SCADA Master
10 Mbps Ethernet RS485
LAN
or Modem
Engineering
RS232 for
Troubleshooting
and Setting Changes
33
Lecture Notes - Session 2 - Network
Components
100A
49 50N
3
75/1A I >
PDCS Interface
U <59
M 55kW
Space
Heater
34
Lecture Notes - Session 3
Generation/Transmission Utilities
Peak Load
1
Lecture Notes - Session 3
To Grid System
Demonstrating
FIRM CAPACITY
Grid T1 Grid T2
60 MVA 60 MVA
Distribution Network
Peak Load = 60 MVA
To Grid System
Grid T1 Grid T2
60 MVA 60 MVA
2
Lecture Notes - Session 3
38 amp
38 amp
154kVA 86kVA 186kVA 56kVA
75 amp
154kVA 86kVA 186kVA 56kVA
3
Lecture Notes - Session 3
Minimum Load
Voltage Problems
Protection Problems
(Low Fault Levels)
Load Flow
Voltage Control
Quality of Supply
Fault Levels
4
Lecture Notes - Session 3
Load Flows
Short-Term Overload
Ratings
Load Flows
Cable Ratings
Voltage Control Important
Maximum Insulation
Temperature
5
Lecture Notes - Session 3
18 9
7108 40
7320 20
21
7 29 7
1 29
0
1 31 32 5
8 40 7 40
7016 10
19
50 50 50
8016 - 132kV
32 36
7108 40
7320 20
16
7 36 7
1 36
0
1 44 5
8 40 7 40
7016 10
24
8016 - 132kV
6
Lecture Notes - Session 3
23
7 27.5 7
1 27.5
27 13 0
1 28 5
8 40 7 40
7016 10
17
8016 - 132kV
NO
7905 7108 7320
7611 7605
7118
7057 7017
7016
132kV 8017
33kV
11kV
Interconnection 8016
7
Lecture Notes - Session 3
Cyclic Rating
30
25
Normal Rating
20
Xfr.
Load 15
MVA
10
00.00 02.00 04.00 06.00 08.00 10.00 12.00 14.00 16.00 18.00 20.00 22.00
Time of Day
AVC Scheme
with Line Drop
130 kVA 154 kVA 136 kVA 146 kVA
Compensation
Key
Closed
33/11 kV
Open Substation B
8
Lecture Notes - Session 3
• Loose connections/joints
9
Lecture Notes - Session 3
•Circuit Breakers
•Fusable Switches
FLOW of WATER
in a Hydro-Electric
Plant
A Good
Analogy
FLOW of WATER
does not depend
on size/capacity
of reservoir
10
Lecture Notes - Session 3
Flow now
depends
very much
on the
Whoosh ! capacity of
the
reservoir!
5 amp
100 V
100 A
Motor Load
ZT = 0.1 OHM
Current
5 amp
Apparent
Impedance = 20 ohm
E 100
SHORT CIRCUIT CURRENT = = = 1000 Amperes
ZT 0.1
Figure 2
Must be capable of interrupting
10,000 Amperes 10,000 amps
5 amp
100 V
1000 A
Motor Load
ZT = 0.01 OHM
Current
5 amp
E 100
SHORT CIRCUIT CURRENT = = = 10,000 Amperes
ZT 0.01
11
Lecture Notes - Session 3
Sources of Short-Circuit
Currents
. Generators
. Synchronous Motors
Induction Motors
STEADY STATE
CURRENT DETERMINED
BY SYNCHRONOUS
REACTANCE
SHORT-CIRCUIT
BECAUSE OF GREAT LENGTH
CURRENT
SHORT-CIRCUIT OF TOTAL OSCILLOGRAM
used for calculations ONLY TWO ENDS SHOWN
OCCURS AT THIS
HERE. THIS REPRESENTS
TIME
E THE BREAK BETWEEN THE TWO PARTS
X”d
12
Lecture Notes - Session 3
kVA
MVA
13
Lecture Notes - Session 4
Asymmetrical
Short-Circuit Currents
Envelopes of Peaks are not
Symmetrical about the Zero Axis
ZERO
AXIS
Totally Offset
Partially Offset
1
Lecture Notes - Session 4
R
(R 2
+ X2 )
X/R Ratio = 13.6
GENERATED VOLTAGE
SHORT-CIRCUIT CURRENT
ZERO
AXIS
2
Lecture Notes - Session 4
SHORT-CIRCUIT CURRENT
ZERO
AXIS
GENERATED VOLTAGE
SHORT-CIRCUIT OCCURRED AT THIS POINT
3
Lecture Notes - Session 4
Components of Asymmetrical
Current
TOTAL ASYMMETRICAL DECAYING CURRENT
DECAYING DC COMPONENT
Iac
AC COMPONENT
Idc
A
e
4160 Volts Feeders
(Record Cable sizes b d Page C12-12
c
and lengths)
j
Load Centre Unit 415V Busbar
Substation
Transformers
i
(Record kVA
X
B
and Impedance)
A particular
h 415V Busbar feeder to be
investigated
f g (Record cable
size and
4000 Volts Synchronous l Load length)
Compressor Motors k
(Record HP or KVA, and
Low - Voltage Substation Motor Loads
speed) Switchgear Collective (Record total HP)
X A
4
Lecture Notes - Session 4
Short-Circuit Currents
Required at A, B or C
-
d
THIS NETWORK HAS NO GENERATION
b c
j
415V Busbar
i B
X
h 415V Busbar
f g
l Load
k
Low - Voltage
Switchgear X A
5
Lecture Notes - Session 4
-
b c d
j
415V Busbar
i
X
B
h 415V Busbar
f g
l Load
k
Low - Voltage
Switchgear X A
6
Lecture Notes - Session 4
Short-Circuit Currents
Required at A, B or C
-
b c d
j
415V Busbar
i B
X
h 415V Busbar
f g
l Load
k
Low - Voltage
Switchgear X
e
4160 Volts Feeders
(Record Cable sizes b c d Page C12-12
and lengths)
j
Load C entre Unit 415V Busbar
Substation
Transform ers
i (Record kVA
X
B
and Impedance)
A particular
h 415V Busbar feeder to be
investigated
f g (R ecord cable
size and
4000 Volts Synchronous l Load length)
Compressor M otors k
Low - Voltage Substation M otor Loads
(Record HP or KVA, and
speed) Switchgear Collective (Record total HP)
X A
7
Lecture Notes - Session 4
REFERENCE BUSBAR
Node A
X
G
m
Node B
X
f g k l
n Zn
415V Busbar
Zh Zi Zj
Zb Zc Zd Ze X
Node C
4160V Busbar
Node A
X
G
m
Node B
X
f g k l
Zn
415V Busbar
h i j
Zb Zc Zd Ze X
Node C
4160V Busbar
8
Lecture Notes - Session 4
V V V V V V
S S S S S S
S = Current
Source
ZG Zf Zg Zk Zl Zm
X B
h Zh i Zi Zj Zn
Zb
c
Zc Zd Ze X
A
XC
4160V Busbar
ZG Zf Zg Zk Zl Zm
X B
Pig-Tail
connection
h Zh i Zi Zj Zn to
Zb A, B or C
c
Zc Zd Ze X
A
4160V Busbar XC
9
Lecture Notes - Session 4
Source Bus)
GZG f
Zf g Zg l
Zl Zm
m k
Zk
415V Bus
X
i Zi n
Zn
b
Zb j Zj
d
Zd X
e A
4160V Bus
XC
cZc
Another Point
Zh
h
of short-circuit
X D
REFERENCE BUS
10
Lecture Notes - Session 4
e
4160 Volts Feeders
(Record Cable sizes b d Page C12-12
c
and lengths)
j
Load Centre Unit 415V Busbar
Substation
Transformers
i
(Record kVA
X
B
and Impedance)
A particular
h 415V Busbar feeder to be
investigated
f g (Record cable
size and
4000 Volts Synchronous l Load length)
k
Compressor Motors
(Record HP or KVA, and
Low - Voltage Substation Motor Loads
speed) Switchgear Collective (Record total HP)
X A
but
11
Lecture Notes - Session 4
Equipment Parameters
The Positive sequence impedance of Cables usually
given by the manufacturer in ohms per unit length
Ohms-per-phase
Per-cent or Per-unit
on rated kVA
or reference kVA base
12
Lecture Notes - Session 4
Per-Unit
or straightforward ohms.
so which one ?
Yes !
13
Lecture Notes - Session 4
Per-Unit Representation
Four Basic Quantities
•kVA We usually
go for
KVA and Volts
•Volts
•Ohms
•Amperes
Give a value to any two and the others can
be derived
Per =
A Number
Unit Base Number
14
Lecture Notes - Session 4
Electrical Example
Case A Case B
15
Lecture Notes - Session 4
Base Volts
Base Amps
Base Ohms
16
Lecture Notes - Session 4
Base Volts
and
Base kVA
17
Lecture Notes - Session 4
10 kVA
100 kVA
1000 kVA
10 MVA
100 MVA
18
Lecture Notes - Session 4
and
Per-unit Per-unit
New base kVA
ohms on = ohms on x (10)
new old
Old base kVA
base kVA base kVA
19
Lecture Notes - Session 4
and
Expression (13)
20
Lecture Notes - Session 4
10
T1
15 MVA
X=7%
Bus 1 - 13.8kV
1.0 PF SYN
M1 M2 6000 HP M3 XF1
IND X”d = 15%
4500 HP 0.8 PF SYN X’d = 24%
X” = 20% 5000 HP
X”d = 10%
T2 X’d = 15%
1500 KVA
X = 5.75%
T3
1250 KVA - 1ph
IND X= 5.75%
MOT.
X” = 25% ON 1500 MVA 480v Bus 3
X F2
IND MOT.
700 FT 3 CORE 250 MCM CABLE
Z = (O.O552 + j0.0379 /1000 ft X F4 750 HP TOTAL
X CONNECTED
X= 25%
LIGHTS ON 750 KVA
Utility Infeeds
X = (pu X u) x (Study Base kVA)
(Util. Base kVA)
1500,000
21
Lecture Notes - Session 4
Induction Motors
Positive Sequence
X” (subtransient - used extensively
with
a multiplier) Xm = 1.5 times X””d for 3.3kV motor
Zero Sequence
X0 (Induction machine neutrals will
almost
never be grounded, so the need for X0
is almost entirely eliminated
= 7150 kVA
22
Lecture Notes - Session 4
= 12.8
Ohms
Per Unit Ohms = = 1.6
Base Ohms 12.8
= 0.125
Bus 1 - 13.8kV
1.0 PF SYN
M1 M2 6000 HP M3 XF1
IND X”d = 15%
4500 HP 0.8 PF SYN X’d = 24%
X” = 20% 5000 HP
X”d = 10%
T2 X’d = 15%
1500 KVA
X = 5.75%
T3
IND 1250 KVA - 1ph
MOT. X= 5.75%
X” = 25% ON 1500 MVA 480v Bus 3
XF2
IND MOT.
700 FT 3 CORE 250 MCM CABLE
Z = (O.O552 + j0.0379 /1000 ft X F4 750 HP TOTAL
X CONNECTED
X= 25%
LIGHTS ON 750 KVA
23
Lecture Notes - Session 4
Transformers
X = % XT (Study Base kVA)
x
100 (Transformer Base kVA)
The transformer nameplate reactance always represents the
positive sequence reactance - if we require zero sequence
I.e. Z0 this is another evaluation, which will depend upon
the earthing arrangements
15000 0.07 = 0.07
Transformer T1: X = x
15000
24
Lecture Notes - Session 4
10
T1
15 MVA
X=7%
Bus 1 - 13.8kV
1.0 PF SYN
M1 M2 6000 HP M3
Convert all impedances to p.u X
IND
4500 HP 0.8 PF SYN
X”d = 15%
X’d = 24%
F1
X” = 20% 5000 HP
X”d = 10%
T2 X’d = 15%
1500 KVA
X = 5.75%
T3
1250 KVA - 1ph
IND X= 5.75%
MOT.
X” = 25% ON 1500 MVA 480v Bus 3
XF2
IND MOT.
700 FT 3 CORE 250 MCM CABLE
Z = (O.O552 + j0.0379 /1000 ft X F4 750 HP TOTAL
X CONNECTED
X= 25%
LIGHTS ON 750 KVA
60 MVA
X’’d XT
240 MVA
25
Lecture Notes - Session 4
3- Node Example
B
X’’d = 25% XT = 15% X = 4%
G
X = 4%
G
X = 4%
G
C
G
A
I am going to work
this time on 100MVA Base
with percentage values
X’’d =25% A C
Fault Level at A
Developing the Equivalent Circuit
Fault-Level
= 1000 MVA
for a 3-phase fault at Node B
given by
100 x 100
I
I B Xequivalent
B
A
10 4 12.67 =
8
790 MVA
26
Lecture Notes - Session 4
Power Station
at C running B
XT = 15% X = 4%
X = 4%
X = 4%
X’’d = 25% A C
Fault Level at A has increased from 1000 to 1626 MVA
8 1626 MVA
27
Lecture Notes - Session 4
Additional Circuit
is B
added
XT =15% X = 4%
X = 5%
X = 4%
X = 4%
X’’d =25% A
C
Fault Level at A has increased from 1626 to 1663 MVA
Developing the Equivalent Circuit
for a 3-phase fault at Node A
Fault-Level
I given by
10 100 x 100
I A
5 A Xequivalent
13.33 4 6.01 =
C
8 1663 MVA
X = 5%
X = 4% X = 5%
X = 5%
X = 4%
Calculated Fault Level at C = 1621 MVA
X’’d =25% A C
Developing the Equivalent Circuit
for a 3-phase fault at Node A
Fault-Level
given by
100 x 100
I
I A Xequivalent
10 A
A
12.33 2.22 5.97 =
4.44
`1675 MVA
28
Lecture Notes - Session 4
Conclusions
Open Points
Series Reactors
Transformer Reactance
29
Lecture Notes - Session 4
The total cable length between the two primary substations is 2.86 km
1 4 20MVA
F2
0.16 km 0.24 km 2 0.42 km 3 0.21km
10MVA XT = 0.24 p.u
F2 BS-1
XT = 0.16 p.u F3 on rating
on rating 0.17km
T2
5
BS
8 0.15 km 7 0.25 km 6 0.34 km
F4
Normal F3
BS-2 20MVA
T2 Open XT = 0.24 p.u
Point
9 0.24 km 10 0.14 km 11 0.15 km 12 0.17 km F4
on rating
F5 0.21 km
10MVA T3
XT = 0.16 p.u F5
F6
on rating 20MVA
F6
XT = 0.24 p.u
F7 on rating
We shall choose a base kVA of 1000 and 11kV as the base volts.
30
Lecture Notes - Session 4
1 4 20MVA
F2
0.16 km 0.24 km 2 0.42 km 3 0.21km
10MVA XT = 0.24 p.u
F2 BS-1
XT = 0.16 p.u F3 on rating
on rating 0.17km
T2
5
BS
8 0.15 km 7 0.25 km 6 0.34 km
F4
Normal F3
BS-2 20MVA
T2 Open XT = 0.24 p.u
Point
9 0.24 km 10 0.14 km 11 0.15 km 12 0.17 km F4
on rating
F5 0.21 km
10MVA T3
XT = 0.16 p.u F5
F6
on rating 20MVA
F6
XT = 0.24 p.u
F7 on rating
1 4 20MVA
F2
0.16 km 0.24 km 2 0.42 km 3 0.21km
10MVA XT = 0.24 p.u
F2 BS-1
XT = 0.16 p.u F3 on rating
on rating 0.17km
T2
5
BS
8 0.15 km 7 0.25 km 6 0.34 km
F4
Normal F3
BS-2 20MVA
T2 Open XT = 0.24 p.u
Point
9 0.24 km 10 0.14 km 11 0.15 km 12 0.17 km F4
on rating
F5 0.21 km
10MVA T3
XT = 0.16 p.u F5
F6
on rating 20MVA
F6
XT = 0.24 p.u
F7 on rating
31
Lecture Notes - Session 4
Voltage
Source
0.000286
7016 7118
Cable
Impedance 0.00842
32
Lecture Notes - Session 4
0.000286
0.000286
0.000286
F
F
F
0.00842
Fault at 7118
Standby G
B1 B2
B8A Emergency Power Dist . Panel B8
M Misc.
CHC
60 kW EFL CHL
Typical for each
Bus-Section (See Fig.6)
Fire
Cooling
Water B22
B3 B4 See Fig.5
SWB B2R
SWB B2L
33
Lecture Notes - Session 4
Short-Circuit
Current
Limiting
Reactors
G1
employed
G2 G3
in an Industrial
13.8kV network
G4
34
Lecture Notes - Session 4
33kV Busbar
2.9 4
X = 33% X = 33%
Total Total
=19.4% =20.5%
16.5 16.5
F F
Short-Circuit Infeed is
Peak = 515 MVA or approx 27 kA
Minimum = 488 MVA or approx 26 kA
132kV
13.8kV 13.8kV
35
Lecture Notes - Session 4
132kV
13.8kV 13.8kV
Xfr Feedrs
(b) (c) with Tie - Bkr (d)
(c) 2 - Bkr Mesh (d) 2 - Bkr Mesh (f) Xfr Feedrs
(Pi) (Inverted Pi) with By - pass disc.
(a)
Note – Earthing (Grounding) Switches Not Shown
36
Lecture Notes - Session 4
T1 Part of 110 kV
substation
Double-Busbar
Saudi Arabia
Next Bay
is the Bus-
VT’s
(See Fig.2b)
110/13.8 kV 110/13.8 kV
T1 T2
A 380 kV
Substation
Double Bus
37
Lecture Notes - Session 4
38
Lecture Notes - Session 4
Closed 33kV
11kV
1 2 3 4
Normal Open
Point 6
10 9 8 7
39
Lecture Notes - Session 4
1 2 3
7 6 5 4
Normal Open
Point
8 9 10
33kV
33kV
Open 33kV
Closed 33kV
A B
Two 15MVA
Demand Demand 20MVA Three
30 MVA Open 30 MVA
Xfrs Supplied Points
Supplied Xfrs
30 MVA 60 MVA
20MVA
15MVA
B
All
27MVA Three
All Normal Demand
Open 30 MVA
Points Closed
Supplied Xfrs
80 MVA 27MVA
A
Two 30MVA
Demand
30 MVA Some Normal
Xfrs Supplied Open
60 MVA Points Closed
(2/ 3)
30MVA
40
Lecture Notes - Session 4
415V
RMU1
RMU1
RMU2
RMU2
RMU1
RMU1
S/S AS2
S/S AS4
RMU2
RMU2
RMU2
RMU1
S/S AS3
All 11/0.415kV
Transformers
800 kVA
All RMU’s
OIL
41