M-Thermal Hydraulic Indoor PDF
M-Thermal Hydraulic Indoor PDF
M-Thermal Hydraulic Indoor PDF
These installation instructions are an integral part of the product and must be given to the installer
and kept by the user.
The warnings and indications contained in the present handbook must be carefully read and under-
stood as they provide important information relative to handling and operating safety. This hand-
book must therefore always be kept available for later consultation.
Installation must be carried out in compliance with valid regulations and the manufacturer’s instruc-
tions by a qualified professional.
An installation error could result in physical injury to persons or animals as well as mechanical
damage for which the manufacturer may under no circumstances be held responsible.
After having unpacked the heat pump, the content should be checked for possible damage.
Before connecting the heat pump, ensure that the data is compatible with the true installation condi-
tions and does not exceed the maximum authorised limits for the product in question.
Before beginning any installation, handling or repair work on the heat pump, always isolate the
electrical power supply to the unit.
In the case of a fault and/or operating error on the heat pump, the electrical power supply must be
isolated and no attempt should be made to repair the fault.
Repair work may only be carried out by an authorised technical assistance service using original
spare parts only. Non-respect of the aforementioned clauses may have a negative influence on the
operating safety of the heat pump.
To guarantee the efficiency and correct operation of the heat pump, it is important to ensure it is
regularly maintained in compliance with the instructions.
In the case where a heat pump is sold or transferred to another user, always ensure that all techni-
cal documentation is sent with the equipment to be used by the new user or installer.
This heat pump may only be used for the purpose for which it was designed: to heat a swimming
pool; all other uses must be considered inappropriate, incorrect or even dangerous.
This heat pump may only be used for the purpose for which it was designed to space heating or
cooling, under floor heating, sanitary water heating, all other used must be considered inappropri-
ate, incorrect or even dangerous.
This unit should be installed in a water proof place, or the safety of the unit and the operator cannot
be ensured.
If the indoor unit is not running for 24 hours, the pump in the indoor unit will turn on and run for 3
minutes to preventing pump from blocking.
CONTENTS PAGE
TYPICAL APPLICATION EXAMPLES...................................................... 2 A creepage breaker must be installed near the powe
OVERVIEW OF THE INDOOR UNIT......................................................... 4 supply
Do not tear off the labels on the units for the purpose of
INSTALLATION OF THE INDOOR UNIT.................................................... 7
warning or reminding.
START-UP AND CONFIGURATION......................................................... 13
WATER CIRCUIT AIR PURGE FUNCTION............................................... 13 WARNING
PRE-OPERATION CHECKS..................................................................... 13
Ask the professional installer for installation of the air source
FIELD SETTINGS .................................................................................. 14
heat pump water heating unitsˈimproper installation may
FINAL CHECK........................................................................................ 18 result in water leakage, electric shock, or fire.
MAINTENANCE..................................................................................... 18
Ask the professional service person for the repair and
ERROR CODE........................................................................................ 18 maintenance.Improper repair and maintenance may result in
water leakage, electric shock or fire.
SPECIFICATIONS................................................................................... 19
In order to avoid electric shock,fire or injury,if any abnormality
is detected,such as smell of fire,turn off the power supply and
call your service agent for instructions.
Never use the wire and fuse with wrong rated current.Use of
wrong wire or fuse may cause the unit to break down or a fire.
Do not insert fingers, rods or other objects into the air inlet or
outlet.When the fan is rotating at high speed, it will cause injury.
Never touch the air outlet or the horizontal blades while the
swing flap is in operation.Fingers may become caught or the
unit may break down.
I&O Manual
1
of the outdoor unit. The auxiliary heater models are available for a
CAUTION heating capacity of 3kW.
It’s normal if some water drops from the hole of pressure relief Accessory name Qty. Shape
valve during operation. However, if the water is in a great
amount, call your service agent for instructions. Owner's & Installation This
1 manual
Manual
After a long term use, check the unit stand and fittings. Mounting bracket 1
If damaged, the unit may fall and result in injury.
Owner's
1
Manual of Wire Controller
2. INTRODUCTION
4. TYPICAL APPLICATION EXAMPLES
2.1 General information
Thank you for purchasing this indoor unit.
The indoor unit is the indoor part of the air to water heat pumps.
These units are designed for wall mounted installation and used for CAUTION
both heating and cooling applications. The units can be combined
with fan coil units, under floor heating applications, low temperature When the M-thermal system is used in series with another heat
radiators, sanitary water heating applications and solar kit for source (eg:gas,boil),it shall be make sure that the return water
sanitary hot water applications. temperature to the refrigerant to water heat exchanger does not
exceed 50ć.We should not be hold liable for any damage
■ Heating/cooling units resulting from not observing this rule .
The indoor unit range consists of one seriel: a heating/cooling seriel.
The seriels is delivered with an integrated auxiliary heater for The application examples given below are for illustration
additional heating capacity during cold outdoor temperatures. The purposes only.
auxiliary heater also serves as a auxiliary in case of malfunctioning
I&O Manual
2
Example 1
12
outdoor indoor
13
9
11
M
1 2 3 4 5 6 7 10 31 16
Fan Coil1 Fan Coil 2 Fan Coil n
M
17 15
18 M
14
19
35
Sanitary
Water Outlet
FHC1 FHC2 FHCn
FHC - Floor Heating Coil
32 20
22 24
21
Sanitary 26 23
Water Inlet
30
28
27
29 25
Fig.4-1
Example 2
12
outdoor indoor
13
9
11
34 M
1 2 3 4 5 6 33 7 31 16
Fan Coil 1 Fan Coil 2 Fan Coil n
M
15 14
M
19
17
35
Sanitary
Water Outlet
FHC 1 FHC 2 FHC n
FHC - Floor Heating Coil
32
20
22 24
21
Sanitary 26 23
Water Inlet
30
27
28
29 25
Fig.4-2
I&O Manual
3
Table4-1 5. OVERVIEW OF THE INDOOR UNIT
1 Outdoor unit
5.1 Opening the indoor unit
2 Indoor unit (Hydro kit)
■ The front flap on the indoor unit cover gives access to the
3 Refrigerant to water heat exchanger manometer and user interface.
4 Auxiliary heater vessel ■ The indoor unit cover can be removed by removing the 6
5 Pump 1 side screws and unhitching the cover.
22 Non-return valve
23 Non-return valve
24 Water to water heat exchanger
25 Solar kit (optional)
26 Pump for solar kit, Pump 3
I&O Manual
4
5.2 Main components water outlet circuit.If the indoor unit is not running for 24 hours ,the
pump will run for 3 minutes to prevent the block of the pump.
1 16 Expansion Vessel
19 The expansion vessel automatically stabilizes the pressure of
2
18 water circuit.
3
4 17 Pressure relief valve
The pressure relief valve prevents excessive water pressure in
5 17
the water circuit by opening at 3 bar and discharging some water.
18 Refrigerant to water heat exchanger
16 19 Control box
The control box contains the main electronic and electrical parts
15 of the indoor unit.
10 13
11 12
Fig.5-2
1 Air purge valve
Remaining air in the water circuit will be automatically removed via
the air purge valve.
2 Auxiliary heater cover and auxiliary heater
The auxiliary heater consists of two electrical heating element that
will provide additional heating capacity to the water circuit if the
heating capacity of the outdoor unit is insufficient due to low outdoor
temperature
3 Manual reset thermal protector
The auxiliary heater is equipped with two thermal protectors. The
thermal protectors are validated when the temperature becomes too
high. The manual reset thermal protector cut off temperature is 75ć.
4 Automatically reset thermal protector
The automatically reset thermal protector cut off temperature is 68
ć.
5 Auxiliary heater vessel
The auxiliary heater heats the water in the auxiliary heater vessel.
6 Manometer
The Manometer allows readout the water pressure in the water Fig.5-3
circuit.
7 Temperature sensors
1 Transformer
Five temperature sensors determine the water and refrigerant
temperature at various points in the water circuit. 2 PCB
The main PCB (Printed Circuit Board) controls the functioning
8 Flow switch
of the unit
The flow switch checks the flow in the water circuit and protects
the heat exchanger against freeing and the pump against damage. 3 Auxiliary heater circuit breaker
The circuit breaker protects the auxiliary heater electrical
9 Insulation
circuit against overload or short circuit
The insulation layers are equipped in order to prevent the
condensate in the water and refrigerant inlet and outlet. 4 Auxiliary heater contactor
10 Water outlet connection 5 Terminal blocks
The terminal blocks allow easy connection of field wiring
11 Water inlet connection
Two shut-off valve (field supply) should be connected to the water 6 Terminal blocks for power supply of the indoor unit
inlet and outlet connections.
7 Grounding hole
12 Refrigerant liquid connection Make the machine grounding safely and reliably
13 Refrigerant gas connection 8 Terminal blocks for power supply of the electric heater for
sanitary hot water tank
14 User interface
The user interface allows the installer and user to set up, use and 9 Electric heater contactor
maintain the unit.
10 Electric heater circuit breaker
15 Pump The circuit breaker protects the electric heater in the sanitary
The pump circulates the water in the water circuit. If the pressure hot water tank against overload or short circuit
loss is too high, an additional pump is needed to be connected in the
I&O Manual
5
Communication Communication
Solar signal ON/OFF Flow Transformer Power for P,Q,E
output cable for computer for UI
input switch UI
T2_RL
Room
T2B_RG
thermostat
TW_i
TW_o
Auxiliary
heater output T1
Electric
T5
heater output
T1B
Feedback of
electric heater Reverse2
Reverse1
Power supply
for PCB
Query
Thermal
protect of
auxiliary heater
Power supply for Pump SV1 SV2 SV3 Anti Pump Boiler RUN Alarm CT1 CT2
transformer freeze of output
heater solar
kit
Fig.5-4
14 13 12 11
TW_o
T2B
10
9
T1 F
TW_i
T2
1 2 3 4 5 6 7 8
Fig.5-5
I&O Manual
6
6. INSTALLATION OF THE INDOOR UNIT 6.2 Dimensions and service space
■ Unit of measurement: mm
Dimensions of the wall bracket:
158 158
CAUTION
40
The indoor unit should be installed in a water proof place, or the
safety of the unit and the operator cannot be ensured. 3× 12
Fig.6-1
■ Dimensions of the unit, see figure 6-2.
6.1 Selecting an installation location
The indoor unit is to be wall mounted in an indoor location
that meets the following requirements:
373
The installation location is frost-free.
82
45
The space around the unit is adequate for serving, see figure
6-3.
90 95 70 47 50 35
The space around the unit allows for sufficient air circula- 158 158
tion. 500
There is a provision for condensate drain and pressure relief
valve blow-off.
CAUTION
When the unit running in the cooling mode, Condensate may drop
947
900
from the water inlet and water outlet pipes. Please make sure the
726
dropping condensate will not result in damage of your furniture and
other devices.
500
NOTE
Fig.6-3
If the installation is equipped with a sanitary hot water tank
(optional), please refer to the sanitary hot water installation
manual.
I&O Manual
7
6.3 Inspecting, handling and unpacking the
unit
The indoor unit is packed in a box.
1 2
At delivery, the unit must be checked and any damage must
be reported immediately to the carrier claims agent.
Check if all indoor unit accessories are enclosed.
Bring the unit as close as possible to the final installation
position in its original package in order to prevent damage
during transport.
The indoor unit weights approximately 60kg and should be
lifted by two persons using the two lifting bars provided.
3
WARNING
Fig.6-5
Do not grasp the control box or piping to lift the unit! Two lifting
bars are provided to lift the unit. 6.5 Refrigerant pipework
For all guidelines, instructions and specifications regarding
refrigerant pipework between the indoor unit and outdoor unit,
please refer to the outdoor unit installation and owner’s
manual.
The location of the gas pipe and liquid pipe on the indoor unit
is shown under “Main components” in section 5.2.
Table6-2
Refrigerant piping Outdoor
Indoor unit
specifications unit
15.9mm
Gas pipe connection 15.9mm (5/8 inch)
(5/8 inch)
9.52mm
Liquid pipe connection 9.52mm (3/8 inch)
(3/8 inch)
WARNING
When connecting the refrigerant pipes, always use two
wrenches/spanners for tightening or loosening nuts! Failure to
do so can result in damaged piping connections and leaks.
WARNING
WARNING
The unit is only to be used in a closed water system. Applica-
The weight of the indoor unit is approximately 60kg. tion in an open water circuit can lead to excessive corrosion of
Two persons are required to mount the unit. the piping.
I&O Manual
8
● Cover the pipe end when inserting it through a wall so that no
● Air vents must be provided at all high points of the system. The dust and dirt enter.
vents should be located at points which are easily accessible for
servicing. An automatic air purge is provided inside the indoor unit. ● Use a good thread sealant for the sealing of the connections. The
Check that this air purge is not tightened too much so that automatic sealing must be able to withstand the pressures and temperatures
release of air in the water circuit remains possible. of the system.
● Take care that the components installed in the field piping can ● When using non-brass metallic piping, make sure to insulate both
withstand the water pressure. materials from each other to prevent galvanic corrosion.
● The filter (accessory of indoor unit) must be connected into the ● Because brass is a soft material, use appropriate tooling for
water circuit as shown in Fig 5-5. connecting the water circuit. Inappropriate tooling will cause damage
to the pipes.
CAUTION WARNING
When the unit running in the cooling mode, Condensate may ● The unit is only to be used in a closed water system. Applica-
drop from the water inlet and water outlet pipes. Please make tion in an open water circuit can lead to excessive corrosion of the
sure the dropping condensate will not result in damage of your water piping.
furniture and other devices.
● Never use Zn-coated parts in the water circuit. Excessive
corrosion of these parts may occur as copper piping is used in the
■ Checking the water volume and expansion vessel pressure unit’s internal water circuit.
The unit is equipped with an expansion vessel of 6.5 liter which has
a default pre-pressure of 1 bar.
When it is required to change the default pre-pressure of the ■ Fill with water until the manometer indicates a pressure of
expansion vessel (1bar), keep in mind the following guidelines: approximately 1.0~2.0 bar. Remove air in the circuit as much as
possible using the air purge valves. Air present in the water
● Use only dry nitrogen to set the expansion vessel pre-pressure. circuit might cause malfunctioning of the auxiliary heater.
● Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system. Therefore, the pre-pressure
■ Check that the auxiliary heater vessel is filled with water by
screw off the vent valve two laps, it will be full of water until
should be adjusted by a licensed installer.
finish draining off the air.
■ calculating the water circuit pressure drop
If the water circuit pressure drop excluding the indoor is too high, an NOTE
auxiliary pump (pump 2 as described in Fig 4-1 and Fig 4-2) is
necessary to be installed in the water circuit. ● During filling, it might not be possible to remove all air in the
system. Remaining air will be removed through the automatic
CAUTION air purge valve during first operating hours of the system.
Additional filling with water afterwards might be required.
Failure to install an auxiliary pump in the water circuit when the
● The water pressure indicated on the manometer will vary
pressure drop is too high may result in heating/cooling capacity
depending on the water temperature (higher temperature at
reduction, the heat exchanger freeing and the pump damage.
higher water temperature).However, at all times water pressure
should remain above 0.3 bar to avoid air entering the circuit.
● The unit might dispose some excessive water through the
WARNING pressure relief valve.
If the indoor unit is not running for 24 hours, the pump in the ● Water quality must be according to EN directive 98/83 EC.
indoor unit and the auxiliary pump(if installed) will turn on and run
for 3 minutes to preventing pump from blocking.
If air, moisture or dust gets in the water circuit, problems may occur. CAUTION
Therefore, always take into account the following when connecting
the water circuit: Failure to do good piping insulation may result in cooling/heating
capacity reduction a,d condensate drop and destroy of the
● Use clean pipes only.
furniture and other devices.
● Hold the pipe end downwards when removing burrs.
I&O Manual
9
Table6-3
6.9 Field wiring
A Outdoor unit
B Indoor unit
WARNING C Room thermostat (optional)
D Boiler (optional)
A main switch or other means for disconnection, having a
contact separation in all pipes, must be incorporated in the E Auxiliary pump, Pump 2
fixed wiring in accordance with relevant local and national
Motorised 2-way valve for Sanitary
legislation. F hot water tank loop, SV1
Switch off the power supply before making any connection.
Motorised 2-way valve for Fan
G coil units loop, SV2
All field wiring and component must be installed by a
licensed electrician and must comply with relevant Motorised 2-way valve for Floor
European and national regulations. H
heating loop, SV3
The field wiring must be carried out on accordance with the I Pump of Solar kit, Pump 3
wiring diagram supplied with the unit and the instructions
given below. J Sanitary hot water tank (optional)
K Electric heater (optional)
Be sure to establish an earth. Do not earth the unit to a
utility pipe, surge absorber, or telephone earth. Incomplete Single phase power supply or
L outdoor unit, indoor unit and
earth may cause electrical shock. electric heater
Be sure to install an earth leakage protector (30mA). Failure M Solar kit
to do so may cause electrical shock. N Solar pump station
O Temperature sensor T1B
P Solar panel
■ Overview Table6-4
The illustration below gives an overview of the required field
wiring between several parts of the installation. Refer also to Require Section of the
Item Description number of
“Typical application examples” section. conductors conductor
Fig.6-7 3×0.5 mm 2
Communication cable between
12 indoor unit and outdoor unit 3 (P, Q, E) (3 - Shield
wire)
Power supply cable for outdoor 2
13 unit 2+GND 4.0 mm
I&O Manual
10
■ The wiring diagram of the indoor unit is shown as page 19 This power circuit must be protected with the required safety devices
PCB Main Control Board according to local and national regulations.
UI User interface, or wire controller Select the power cable in accordance with relevant local and national
T2_RL Refrigerant liquid tube temperature sensor regulations.
T2B_RG Refrigerant gas tube temperature sensor
■ Procedure
Table6-5 ● Using the appropriate cable, connect the power circuit to the appro-
priate terminals as shown on the wiring diagram.
T-W-in Inlet water temperature sensor (Inlet water
temperature sensor of heat exchanger) ● Connect the earth conductor (yellow/green) to the earth screw on
T-W-out Outlet water temperature sensor of heat exchanger the block terminal.
● Fix the cable with cable ties to the cable tie mountings to ensure
T1 Outlet water temperature sensor of indoor unit
strain relief.
T5 Sanitary hot water tank temperature sensor
■ Connection of the thermostat cable
T1B Outlet water temperature sensor of indoor unit and boiler
Connection of the thermostat cable depends on the application.
K1M AC contactor See section7.2 “Room thermostat installation configuration” for more
information and configuration options on pump configuration in combi-
K2M AC contactor
nation with room thermostat.
K3M AC contactor
● Thermostat requirements
K4M AC contactor 1.Power supply: 220-240V~ 50Hz or battery operated
CT1, CT2 Current detector 2.Contact voltage: 220-240V~ 50Hz
SV1 2-way valve for sanitary hot water tank circuit ● Procedure
1.Connection of the thermostat cable to the appropriate terminals
SV2 2-way valve for fan coil circuit
shown on the wiring diagram.
SV3 2-way valve for underfloor heating circuit
Pro-hyd Flow switch
13 14 15 16
● Cable tie mountings are provided at the bottom of the control box.
Fix all cables using cable ties (field supply). THERMOSTAT
● A dedicated power circuit is required for the auxiliary heater.
● Installations equipped with a sanitary hot water tank (optional), Fig.6-8
require a dedicated power circuit for the electric heater.
Please refer to the sanitary hot water installation manual. 2. Fix the cable with cable ties to the cable tie mountings to ensure
strain relief.
■ Connection of the indoor unit power supply and communica- 3. Set the “Field setting ” about the selection of Room Thermostat.
tion cable Power circuit and cable requirements
■ Connection of the valve cable
● Power supply for the indoor units is to be provided through the
● Valve requirements
indoor side. Data communication with the outdoor unit is provided
1.Power supply: 220-240V~ 50Hz
through the cable which labeled as P, Q, E.
2.Maximum running current: 100mA
● For all guidelines and specifications regarding field wiring between
● Wiring the 2-way valve
the indoor unit and the outdoor unit, please refer to the outdoor unit
1.Using the appropriate cable, connect the valve control cable to the
installation manual.
terminal as shown on the wiring diagram.
■ Procedure
● Using the appropriate cable, connect the power circuit to the appro-
priate terminals as shown on the wiring diagram and the illustration NOTE
below.
● Connect the earth conductor (yellow/green) to the earthing screw on Wiring is different for a NC (normal closed) valve and a NO
the control box mounting plate. (normal open) valve. Make sure to connect to the correct
● Fix the cable with cable ties to the cable tie mountings to ensure terminal numbers as detailed on the wiring diagram and
strain relief. illustrations below.
● When routing out cables, make sure that these do not obstruct
mounting of the indoor unit cover.
■ Connection of the auxiliary heater power supply 4 5 6 7 8 9 10 11 12
Be sure to use a dedicated power circuit for the auxiliary heater. Fig.6-8
Never use a power circuit shared by another appliance.
3-wire NO (normal open) and NC (normal close 2-way)
motorized valve
I&O Manual
11
4 5 6 7 8 9 10 11 12
NOTE
This control terminal of the indoor unit only outputs one switch
SV1 SV2 SV3 signal; it needs to change wiring when matching with different
external heat sources.
Fig.6-9
2-wire NC(normal close) 2-way motorized valve
4 5 6 7 8 9 10 11 12 1. If the external heat source needs OUTSIDE ROOM
one switch signal to control the input HEAT THERMOSTAT
SOURCE
situation, then directly connect the
25 26
corresponding wire terminal of this
SV1 SV2 SV3 machine with the corresponding
terminals of the external heat source, INDOOR
BOLLER
UNIT
Fig.6-10 as describing in Fig.6-11.
2-wire NO (normal open) 2-way motorized valve
Fig.6-11
2. If the external heat source
needs one control signal of the OUTSIDE ROOM
NOTE specified voltage (such as HEAT
SOURCE
THERMOSTAT
Fig.6-13
● Fix the cable with cable ties to the cable tie mountings to ensure
strain relief. ■ Remote ON/OFF Terminal
■ Connection of Solar Pump Station( See the Instruction Manual “A B” terminal is used for remote ON/OFF switch; it needs to connect
of Solar Pump Station) external control switch, the control logic as follow:
■ Electrical Connection of Anti-frozen electric heater (Reserved) A B
UI ON ON OFF OFF
■ Electrical Connection of External Heat Source External switch Close Disconnect Close Disconnect
● Using the appropriate cable, and connect the control terminal of Machine state Stop Operate Stop Stop
heat source such as gas boiler etc., the control terminal of this unit is
25-26 terminals in the connector base. The connecting as Fig.6-14
Fig.6-14
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
L N ON OFF N ON OFF N ON OFF N L N C H 1 2 1 2 L N L N 1 2 1 2
2-WAY 2-WAY 2-WAY ROOM SOLAR SOLAR WATER HEATER OUTSIDE HEAT RUN/STOP ALARM
PUMP VALVE-1 VALVE-2 VALVE-3 THERMOSTAT PUMP PUMP BELT SOURCE OUTPUT OUTPUT
L N L1 N1 L2 N2 A B P Q (E)
Fig.6-15
I&O Manual
12
6.10 Installation of drain pan kit ■ Without room thermostat
When no thermostat is connected to the indoor unit, pump operation
will be determined by leaving water temperature.
Drain pan kit 7.4 Sanitary hot water tank installation con-
figuration
When no sanitary hot water tank is installed, the value of field setting
Fig.6-16 “0-2” should be set to be “0”.
Take out the drain pan kit from the packing foam, then insert it and When a sanitary hot water tank is installed, the value of field setting
drill two screws on it as the figure. “0-2” should be set to be “1”.
The indoor unit should be configured by the installer to match During initial start-up and when water temperature is low, it is
the installation environment (outdoor climate, installed options, important that the water is heated gradually. Failure to do so may
etc) and user expertise. result in cracking of concrete floors due to rapid temperature change.
Please contact the responsible cast concrete building contractor for
further details.
CAUTION To do so, the lowest leaving water set temperature can be decreased
to a value between 15ć and 25ć by adjusting the field setting “6-3”
It is important that all information in this chapter is read sequen-
(heating set point lower limit).
tially by the installer and that the system is configured as
application.
NOTE
7.1 Dip switch setting overview Heating between 15ć and 25ć is performed by the auxiliary
Dip switch is located on the control box PCB and are for future heater only.
use . Switch off the power supply before opening the control box
service panel and making any changes to the switch settings.
NOTE Make sure that the field wiring between local supply panel and indoor
unit, outdoor unit and indoor unit, indoor unit and valves (when
To set the pump speed, refer to the section of “Setting the pump applicable), indoor unit and room thermostat (when applicable), and
speed” in section 9.3. indoor unit and sanitary hot water tank has been carried out according
to the instructions described in the chapter “Field wiring”, according to
I&O Manual
13
the wiring diagrams and according to European and national regula- 9.3 Setting the pump speed
tions. The pump speed can be selected on the pump.
● Fuses or protection devices The default setting is high speed. If the water flow in the system is too
Check that the fuses or the locally installed protection devices are of high (e.g., noise of running water in the installation) the speed can be
the size and type specified in the chapter “Technical specifications”. set to low speed.
Make sure that neither a fuse nor a protection device has been
bypassed.
NOTE
● Electric heater circuit breaker
Do not forget to turn on the electric heater circuit breaker in the control The speed dial on the pump indicates 3 speed setting
box (applies only to units with optional sanitary hot water tank
installed).
The available external static pressure (ESP, expressed in mmH2O) in
● Earth wiring function of the water flow (l/min) is shown in the previous section.
Make sure that the earth wires have been connected properly and that
the earth terminals are tightened.
■ Pump hydraulic performance
● Fixation 8
7
Check that the unit is properly fixed, to avoid abnormal noises and
6
vibrations when starting up the unit.
5
● Damaged equipment 4
3
Check the inside of the unit on damaged components or squeezed
pipes. 2
1
● Refrigerant leak 0
1000 2000 3000 4000 5000 6000
Check the inside of the unit on refrigerant leakage. If there is a refriger- Q(L/h)
ant leak, call your local dealer.
● Power supply voltage Top grade medium grade Low grade
Check the power supply voltage on the local supply panel. The voltage
must correspond to the voltage on the identification label of the unit.
● Air purge valve Fig.9-1
Make sure the air purge valve is open (at least 2 turns).
● Pressure relief valve CAUTION
Check if the auxiliary heater vessel is completely filled with water by
operating the pressure relief valves. It should purge water instead of If the external pressure loss of the water circuit is too high,it is
air. necessary to install an auxiliary pump(Pump 2) as describing in
Fig.4-1 and Fig.4-2. Fail to install an auxiliary pump will result in
cooling/heating capacity reduction.
CAUTION
Operating the system with closed valves will damage the Each field setting is assigned a 4-digit number or code, for example,
“3-1-15”, which is indicated on the user interface display. The first digit
pump !
“3” indicates the “first code” or field setting group. The second digit
indicates the second code. The last 2-digit number “15” indicate the
value of code “3-1”.
9.2 Powering up the indoor unit
When power supply to the indoor unit is turned on, “888.8” is 3 1 15
displayed on the user interface during its initialization, which might
First code The value of code
take up to 30 seconds. During this process the user interface cannot
Second code “3-1” is “15 ”
be operated.
Fig.10-1
I&O Manual
14
A list of all field settings and default values is given under “Field
settings table” . In this same list, we provided for 2 columns to register NOTE
the date and value of altered field settings at variance with the default
value. ■ Before shipping, the set values have been set as shown
A detailed description of each field setting is given under the section under “Field setting table ”.
of “Detailed description” .
■ When exiting FIELD SET MODE, “8-8-88” may be displayed
on the user interface LCD while the unit initializes itself.
10.1 Procedure
10.2 Detailed description
■ To change one or more field settings, ■ Basic option
proceed as follows. This part of field setting determines the basic option of the heat
pump system, so that the control system can select the appropriate
control mode.
● “0-0” Under floor heating terminal: defines whether the system
installations with under floor heating “1” or not “0”.
● “0-1” Fan coil: defines whether the system installations with fan
coil “1” or not “0”.
● “0-2” Sanitary hot water tank: defines whether the system
installations with sanitary hot water tank “1” or not “0”.
● “0-3” Electric heater for sanitary hot water tank: defines whether
an electric heater was assembled in the sanitary hot water tank “1”
or not “0”.
● “0-4” Auxiliary heating source: defines whether there is a boiler as
an auxiliary heating source for the system “1” or not “0”.
● “0-5” Solar kit: defines whether there is a solar kit to heating the
sanitary hot water tank “1” or not “0”.
● “0-6” auxiliary heater: defines whether there are electric heaters
assembled in the indoor unit “1” or not “0”.
● “0-7” Room thermostat: defines whether there is a room thermo-
stat connected with the indoor unit “1” or not “0”.
■ Priority
This part defines the priority of space heating, space cooling and
sanitary hot water tank heating.
Fig.10-2 ● “1-0” Space heating and sanitary heating priority: defines the
priority of space heating and sanitary heating, “0” for sanitary
heating priority, “1” for space heating priority, and “2” means space
1 Press the button to enter FIELD SET MODE .
heating and sanitary heating have the same priority.
The SETTING icon will be displayed. The current selected field ● “1-1” Space cooling and sanitary heating priority: defines the
setting code is indicated “8-8-88”, with the set value displayed as the priority of space cooling and sanitary heating, “0” for sanitary heating
priority, “1” for space cooling priority.
last 2-digit number .
● “1-2” Heat pump maximum running period for sanitary water tank
Prev
2 Press the button to select the appropriate field setting first heating: specifies the maximum time period during which sanitary
water tank heating can be activated, even when the target sanitary
code.
hot water temperature has not yet been reached..
Next
3 Press the button to select the appropriate field setting second ● “1-3” Solar heating priority: defines the priority sanitary hot water
code. tank heating by solar kit “1” or by heat pump & electric heater “0”.
▲ ▼ ■ Disinfection function
4 Press the button and button to change the set value
Applies only to installations with a sanitary hot water tank.
of the select field setting.
The disinfection function disinfects the sanitary hot water tank by
OK
5 Save the new value by pressing the button. periodically heating the sanitary water to a specific temperature.
6 Repeat step 2 through 4 to change other field settings as required. The disinfection function field settings must be configured by the
installer according to national and local regulations.
7 When finished, press the button for the second time to exit ● “2-0” Operation interval: day(s) of the week at which the sanitary
FIELD SET MODE. water should be heated.
● “2-1” Status: defines whether the disinfection function is turned on
(1) or off (0).
NOTE
● “2-2” Start time: defines the time of the day at which the sanitary
Changes made to a specific field setting are only stored when water should be heated.
OK
the button is pressed. Navigating to a new field setting ● “2-3” Set point: defines the hot water temperature to be reached to
code or pressing the button will discard the change made. realize disinfection function.
● “2-4” Interval: time period defining how long the set point tempera-
ture should be maintained.
I&O Manual
15
T1 ε T1s
Fig.10-5
T4
TU User set point temperature (as set on the user interface) Heater Turn ON
TH High set point temperature “2-03” for disinfection function “ 5-3”
“ 5-3” -1
t Time Heater Turn OFF
Fig.10-4
● “4-0” Electric heater delay time: defines the time period behind ● “6-0” Cooling set point upper limit: maximum leaving water
which the electric heater of the sanitary hot water tank will be turned temperature for cooling operation.
on.
● “6-1” Cooling set point lower limit: minimum leaving water tempera-
● “4-1” Heat pump start temperature difference: defines the ture for cooling operation.
temperature difference between set temperature and water tank
● “6-2” Heating set point upper limit: maximum leaving water
temperature, below which heat pump turning on will be allowed.
temperature for heating operation.
● “4-2” Set point correction for sanitary hot water tank temperature: ● “6-3” Heating set point lower limit: minimum leaving water tempera-
specifies the temperature difference above the set temperature for ture for heating operation.
the electric heater to heating the water tank.
● “6-4” Sanitary heating set point upper limit: maximum leaving water
■ Auxiliary heater operation temperature for sanitary heating operation.
● “5-0” Auxiliary heater delay time: defines the time period behind ● “6-5” Sanitary heating set point lower limit: minimum leaving water
which the auxiliary heater of the indoor unit will be turned on. temperature for sanitary heating operation.
I&O Manual
16
■ Field setting table
Table10-1
First 2nd Setting name Default Range Step Unit Remark
Code Code value
Basic selection
0 floor heating 0 0/1 0-No selection; 1-Selection
1 fan coil or low temperature radiat 0 0/1 0-No selection; 1-Selection
2 sanitary hot water tank 0 0/1 0-No selection; 1-Selection
0/1 0-No selection; 1-Selection
3 Electric heater for sanitary hot water tank 1
0
4 Auxilary Heating source such as gas boiler 0 0/1 0-No selection; 1-Selection
5 Solar kit 0 0/1 0-No selection; 1-Selection
6 Auxiliary heater of indoor unit 1 0/1 0-No selection; 1-Selection
7 Room thermostat 0 0/1 0-No selection; 1-Selection
2 HP Max. Running period for heating sanitary water tank 10 10~95 5 min
Disinfection function
0 Operation interval 5(Fri.) 0~7 - - 0-Sun, 1-Mon,…,6-Sat, 7-all
I&O Manual
17
11. FINAL CHECK 13. ERROR CODE
Before switch on the unit, read following recommendations: Table13-1
■ When the complete installation and all necessary settings Error code Meaning
have been carried out, close all front panels of the unit and
refit the indoor unit cover. Flow switch error( continuous for
E0 3 times, and should be reset by
switch off the power supply )
■ The service panel of the control box may only be opened by
a licensed electrician for maintenance purposes. E1 T2 error
E2 UI communication error
12. MAINTENANCE E3 Outdoor unit communication error
● Make sure that before starting any maintenance or repair EA TW_out error
activity, also the power supply to the outdoor unit is switched off.
Eb T4 error
Ed Phase protection
■ The described checks must be executed at least once a
year: EE Eeprom error
● Water pressure P0 T2 high temperature protection
Check if the water pressure is above 0.3 bar. If necessary add
water. P1 T2B low temperature protection
● Water filter P2 TW_out high temperature protection
Clean the water filter.
P3 TW_out low temperature protection
● Water pressure relief valve
P4 TW_in high temperature protection
Check for correct operation of the pressure relief valve by turning
the red knob along the valve counter-clockwise: P5 T1 high temperature protection
1.If you do not hear a clacking sound, contact your local dealer.
P6 T1B high temperature protection
2.In case the water keeps running out of the unit, close both the
water inlet and outlet shut-off valves first and then contact your P7 Outdoor unit protection
local dealer.
P8 Sanitary hot water tank electric heater protection
● Pressure relief valve hose
Check that the pressure relief valve hose is positioned appropri- P9 Auxiliary heater protection
ately to drain the water. Pb Anti - freezing protection
If the drain pan kit is installed, make sure that the pressure relief
valve hose end is positioned in the drain pan. t0~t7 Run test
● Auxiliary heater vessel insulation cover dF Defrost
Check that the auxiliary heater insulation cover is fastened tightly d0 Oil return function
around the auxiliary heater vessel.
● Sanitary hot water tank pressure relief valve (field supply)
Applies only to installations with a sanitary hot water tank.
Check for correct operation of the pressure relief valve on the
sanitary hot water tank.
● Sanitary hot water electric heater
Applies only to installations with a sanitary hot water tank.
It is advisable to remove lime buildup on the electric heater to
extend its life span, especially in regions with hod water. To do so,
drain the sanitary hot water tank, remove the electric heater from
the sanitary hot water tank and immerse in a bucket (or similar)
with lime-removing product for 24 hours.
● Indoor unit control box
1.Carry out a through visual inspection of the control box and look
for obvious defects such as loose connections or defective wiring.
2.Check for correct operation of contactors by the use of an
ohmmeter. All of these contactors must be in open position.
I&O Manual
18
14. SPECIFICATIONS
Table.14-1
Model SMK-120/CD30GN1
NOTE
I&O Manual
19
C O N N E C T TO S O L A R
P U M P S TAT I O N
S A N I TA R Y TA N K
E2H E3H
E1H
72'
C1
C2
C O N N E C T TO O U T D O O R C O N N E C T TO C O N N E C T TO C O N N E C T TO
C O M M U N I C AT I O N P O R T PUMP3 PUMP1
ON/OFF SWITCH H E AT E R B E LT BOLIER
T H E R M O S TAT
MDV10IU-027AW
202000171568