Indramat Conexoes Eletricas
Indramat Conexoes Eletricas
Indramat Conexoes Eletricas
mannesmann
Rexroth
Electrical Connections
of Main Spindle Drives
DOK-GENERL-MAIN*EL*CON-PRJ1-EN-P
258653 Indramat
About this documentation
Documenttype DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44
Reference This electronic document is based on the hardcopy document with document
desig.: 209-0042-4111-00 EN/04.94
This documentation
– applies to all main spindle drives,
– correlates with the „Project Planning Notes“ for main spindle controllers and
main spindle motors. This documentation can be referenced via text strings.
Validity All rights reserved with respect to the content of this documentation and the
availability of the products.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 2
Table of Contents
1. Electrical Connections 7
2. Power Connections 15
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 3
Table of Contents
4. Installation Guidelines 85
6. Customizing Specifications 91
7. Index 94
8. Supplementary Documentation 99
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 4
Table of Contents
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 5
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 6
1. Electrical Connections
1. Electrical
Connections
1.1. Standardization The electrical connections in the entire INDRAMAT main spindle
drive program have been standardized with the goal of reducing the
range of cables available.
Power connections The motor connections to the main spindle controller always have the
same terminal assignment, regardless of the controller implemented.
The cable cross sectional area is dependent on the motor power
requirements.
Feedback and Plug assignment is the same regardless of controller and motor type.
CNC connections
Controller-specific connections The KDA/TDA controllers used in modular drive packages have
controller-specific electrical connections. This documentation does
not deal with their connection. It is dealt with in the documentation on
main spindle controllers KDA 3.2, or TDA 1.1, „Project Planning
Notes“. The cables needed are part of the electrical connecting
accessories E...-.DA.
The mains contactor and the respective control circuits are integrated
into the RAC controllers for direct mains connection. The facility
control system must operate this control circuit. The controller-
specific connections are outlined in the mains connection plans in
Section 2.2.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 7
1. Electrical Connections
Control
- Position set-point
KDA/TDA
unit
Speed set-point
of the controller
Mains
Feedback
and CNC
connections
Controller-
specific Motor
connections (only with KDA) feedback
connection
Mains Motor fan connection
Motor
connections
Power connections
Spindle
feedback
Katelvem
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 8
1. Electrical Connections
RAC
Mains contactor
X6
monitoring
DANGER HIGH VOLTAGE
- Position set-point
Speed set-point
of the controller
AC-MAINSPINDLE DRIVE RAC 2
Controller-
Internal specific
control X1 connections
circuit and
mains
Mains contactor
AS
SWITCH OFF VOLTAGE BEFORE
CHANGING MODULE AS
Prog. Modul AS nicht unter Spannung wechseln
X13 X4
X2
X5
X3
Feedback
and CNC
connections
Mains connections
Motor
Power feedback
connections connections
Motor fan connections
Motor connections
Spindle
feedback
Katelvek
Figure 1.3: Categories of electrical connections for main spindle drives with RAC
(here RAC 2.2)
Holding brake
Motor fans cannot be connected to the controller in main spindle
drives with RAC3 and RAC4! They are connected directly to the three-
phase mains via appropriate protective motor switches!
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 9
1. Electrical Connections
Power connections
Assembled Components
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 10
1. Electrical Connections
Should only component cables be used with the feedback and CNC
connections, then the plug accessory sets offered guarantee a
complete connection to the controller by means of appropriate plug
connectors.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 11
1. Electrical Connections
Controller Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 12
1. Electrical Connections
1.3. Determination
of Size and Guidelines
Sizing the The conductor cross sections of the assembled INDRAMAT cables
conductor cross sections are sized in accordance with guidelines EN 60 204, Section 1/ 2/86.
0,75 9 30 1
1 12 35 0,93
1,5 15,5 40 0,87
2,5 21 45 0,79
4 28 50 0,71
6 36 55 0,61
10 50 60 0,50
16 68
25 89
35 111
503) 134
3)
actual cross section equals 47 mm 2
Figure 1.7: Load capacity and conversion factor table for ambient temperatures
greater than 30 degrees C., in acc. with EN 60 204-1/ 2/86.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 13
1. Electrical Connections
Sizing maximum cable lengths Maximum cable length is limited by the electro-magnetic distortions
and the loss of voltage along the cable. Transit time effects in the
motor power cable cause cable-length dependent voltage increases
at the motor terminals. This also limits cable lengths.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 14
2. Power Connections
2. Power Connections INDRAMAT main spindle drives have power connections between
the controller and motor and between the RAC controller and the
three-phase mains.
2.1. Motor-Controller The power connections between motor and controller are broken
Power Connections down into Sections:
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 15
2. Power Connections
2.1.1. Breakdown of the There are four types of assembled power connections between
Types of Connections motor and controller.
A terminal point for the strand pair of the holding brake must be
located close to the motor power connection on the controller in the
control cabinet, if main spindle drives with holding brakes are used!
Symbols:
Power plug Power plug wire end ferrule crimping cable lug Flange
connector (plug) connector (coupling) for line-up terminals for stay bolts connector
st_verb1
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 16
2. Power Connections
Motor-controller connection with With this type of connection it is easy for the CNC control to take
intermediate terminal charge of the electrical holding brake, or to be integrated into the
control circuit.
(Controllers
(2AD main spindle motor, KDA/TDA or RAC4)
1MB frameless spindle motor)
(Controllers RAC2/RAC3)
(2AD main spindle motor,
1MB frameless spindle motor)
Symbols:
st_verb2
Figure 2.3: Assembled power cable with intermediate terminal at terminal strip
(also see Figs. 2.19 and 2.20 for 2AD, Figs. 2.25 through 2.27 for 1MB).
Motor-controller connection This type of connection makes it possible to finish the control cabinet
with plug design entirely independent of the machines.
Symbols:
Power plug Power plug Wire-end ferrule for Crimping cable lug Flange
connector (plug) connector (coupling) line-up terminals for stay bolts connector
ST_VERB3
Figure 2.4: Assembled power cable with plug design (also see Figs. 2.21and
2.22 for 2AD, see Figs. 2.28 through 2.30) for 1MB.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 17
2. Power Connections
Motor-controller connection This connection type is advantageous for larger facilities because it
with plugin testing points is possible to quickly and reliably exchange the damaged section of
a cable.
Symbols:
Power plug Power plug Wire-end ferrule Crimping cable lug Flange
connector (plug) connector (coupling) for line-up terminals for stay bolts connector
ST_VERB4
Figure 2.5: Assembled power cable with plugin testing points (also see figure
2.23, 2.24 for 2AD, see Figs. 2.31 through 2.33 for 1MB) .
The assembled cable with the power plug connectors at both ends
(plug/coupling) can be added as an extension piece between the
plugin testing points.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 18
2. Power Connections
2.1.2. Connection Plans for Only the connection plans for the direct connection of the motor-
Direct Connections controller power connections are depicted. They also, however,
apply to all other connections types. The respective testing points do
not alter the arrangement of motor and controller connections.
Technical Data The technical specifications for the motor, the holding brake (op-
tional) and the motor fan are dealt with in the documentation on the
respective main spindle motor - project planning notes. The docu-
mentation also includes a recommendation for the selection of the
protective motor switch for the motor fan.
Motor with Holding Brake If a main spindle motor with holding brake is used, then the control
cabinet must supply it with +24V +/-10%. The facility control system
controls the holding brake.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 19
2. Power Connections
2AD 100 motor connection (cooling air flow A => B) and 2AD 101 (motor fan with terminal box)
30 30 140 200 (Assembled power cable IKL•••/IKF•••) approx. 130
ge/gr Tightening
1 length
2
50
3
7
8 Cable
5
Crimping cable lug 6 (numbering of strands Power plug connector
Shield
for stay bolts M6 as per INDRAMAT IN 172/••
Plug terminal standard)
part of elec.
connection
E • • - • DA
operated by
control circuit
2
7 0,75 … 1,5 mm F
+24V
U
KDA / TDA 8 0,75 … 1,5 mm2 G
0V
controller
X8 E
gn/yel cross section motor type D
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
3
L 0,75 … 1,5 mm2 1
I>>
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 20
2. Power Connections
50
7
8 Cable
5
Crimping cable lug 6 (numbering of strands Power plug connector
Shield
for stay bolts M6 as per INDRAMAT IN 172/••
Plug terminal, standard)
part of elec.
connection
E • • - • DA
operated by
control circuit
7 0,75 … 1,5 mm2 F
+24V
U
KDA / TDA 8 0,75 … 1,5 mm2 G
0V
controller
X8 E
gn/yel cross section motor type D
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
approx. 50 untightened
Motor fan connection: 40
Mains connection
26,5
5...8 mm
15,5
L N PE 26,5
Plug connector
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 21
2. Power Connections
50
7
8 Cable
5
Crimping cable lug 6 (numbering of strands Power plug connector
Shield
for stay bolts M6 as per INDRAMAT IN 172/••
Plug terminal, standard)
part of elec.
connection acc.
E • • - • DA
operated by
control circuit
2
7 0,75 … 1,5 mm F
+24V
U
KDA / TDA 8 0,75 … 1,5 mm2 G
0V
controller
X8 E
gn/yel cross section motor type D
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
2 H
3 6 0,75 … 1,5 mm
2 ϑ
2 5 0,75 … 1,5 mm J
1 main spindle motor
X12 2AD 101 • - • • • • • • - . . .
C, D, E or F
Mains connection
6...10 mm 28
4
3
N 0,75 … 1,5 mm2 2 M
I>>
3
L 0,75 … 1,5 mm2 1
I>>
Figure 2.8: Connection of 2AD 101 motor with plug connector to motor fan.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 22
2. Power Connections
50
3
7
8 Cable
5
Crimping cable lug 6 (numbering of strands Power plug connector
Shield
for stay bolts M6 as per INDRAMAT IN 172/••
Plug terminal, standard)
part of elec.
connection acc.
E • • - • DA
operated by
control circuit
7 0,75 … 1,5 mm2 F
+24V
U
KDA / TDA 8 0,75 … 1,5 mm2 G
0V
controller
X8 E
gn/yel cross section motor type D
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
Mains connection 28
6...10 mm
2
0,75 … 1,5 mm 3
I>>
M
0,75 … 1,5 mm2 2
I>>
2 3
0,75 … 1,5 mm 1
I>>
motor fan
Dimension as per tech. specs APMOT003
of motor fan (see doc. 2AD•••,
project planning notes)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 23
2. Power Connections
50
3
7
Wire-end ferrule 8 Cable
5
in RAC2/RAC3 6 (numbering of strands Power plug connector
Schirm
as per INDRAMAT IN 172/••
Plug terminal, standard)
part of elec.
connection acc.
E1 - RAC
operated by
control circuit
7 0,75 … 1,5 mm2 F
+24V
U
RAC 8 0,75 … 1,5 mm2 G
0V
controller
X14 E
gn/yel cross section motor type D
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
Mains connection
6...10 mm 28
M
0,75 … 1,5 mm2 2
I>>
3
0,75 … 1,5 mm2 1
I>>
motor fan
APMOT004
Figure 2.10: Connection of 2AD 132 motor with power plug to RAC controller.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 24
2. Power Connections
L1 L2 L3 PE motor fan W
windings
terminal box
Dimension as per tech. specs of motor fan
(see doc. 2AD•••, project planning notes)
bn
ge
0,75 … 1,5 mm2 U
I>>
win-
0,75 … 1,5 mm2 V
dings ws M
I>>
connec- bl
3
0,75 … 1,5 mm2 W tion
I>>
gn motor fan
sw
APMOT007
Windings connection for:
Permissible 3xAC400V ±15%, 50...60Hz bn ge bn ge 3xAC220V ±10%,
mains voltage is 3xAC460V ±10%, 60Hz 50...60Hz
(Condition at delivery) U U
dependent upon
ws ws
windings V V
bl bl
connection of terminal
motor fan! terminal block
W W
block
sw gn sw gn
Figure 2.11: Connection of 2AD 132 motor with terminal box to KDA/TDA controller.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 25
2. Power Connections
2AD 132 motor connection (terminal box), 2AD 160, 2AD 180 and 2AD 200 to RAC
L1 L2 L3 PE Motor fan W
windings
3
0,75 … 1,5 mm2 W
I>>
motor fan
APMOT008
Figure 2.12: Connection of 2AD 132, 2AD 160, 2AD 180 and 2AD 200 motors
(all have terminal box)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 26
2. Power Connections
(Substitute NTC-resistor,
KDA / TDA function not guaranteed!)
controller
ϑ
X8
gn/yel cross section motor type
1 dep. (see table U
A1 1
A2
2 assembled specifications)
V
M
3 1 3
A3
W
3 6 0,75 … 1,5 mm2 1 0,75...1,5 mm2
Fig. 2.13: Connection via terminal box of 1MB frameless spindle motors to KDA/
TDA controllers
7
8 Cable
5
Crimping cable lug 6 (numbering of strands Power plug connector Flange
Shield
for stay bolts M6 as per INDRAMAT IN 172/•• connector
Plug terminal, standard) IN 192/••
part of elec.
connection acc.
E • • - • DA
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 27
2. Power Connections
(Substitute NTC-resistor,
function not guaranteed!)
ϑ
X14
RAC
controller gn/yel cross section motor type
1 dep. (see table U
A1 1
A2
2 assembled specifications)
V
M
3 1 3
A3
W
1 6 0,75 … 1,5 mm2 1 0,75...1,5 mm2
X16
1MB
frameless spindle motor
Fig. 2.15: Connection via terminal box of 1MB frameless spindle motor to RAC
controller
3
7
8 Cable
5
Wire-end ferrule 6 (numbering of strands Power plug connector Flange
Shield
in RAC2/RAC3 as per INDRAMAT IN 172/•• connector
Plug terminal, standard) IN 192/••
part of elec.
connection acc.
E • • - • DA
(Substitute NTC-resistor,
G function not guaranteed!)
ϑ
X14 E
RAC
gn/yel cross section motor type D
controller
1 dep. (see table A
A1
2 assembled specifications) B M
A2
A3
3 C 3
Fig. 2.16: 1MB frameless spindle motor connection to RAC controller via power
plug connector.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 28
2. Power Connections
2.1.3. Assembled
Data List
Assembled
Specifications Table
ZuordTab
Table listing assembled specifications for... Table listing assembled specifications for...
Figure 2.18: Allocation of main spindle motors in table
The tables list the available flexible and highly flexible assembled
cables and their significant components.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 29
Section 1: 2AD power connections - direct connections and intermediate terminals
Cable Assembled cables Assembled cable components for direct Assembled cables for intermediate
cross for direct connection connection
terminals on terminal strips
section on the Cable on the on the motor on the controller
2 motor
A [mm ] flex./highly flex. flex./highly flex. controller flex./highly flex. flex./highly flex.
For...
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
(KDA /TDA)
2AD132D-B·····-BD·3-····· 25 IKL170/IKF170 IN172/25 IN207/IN407 ...stay bolt M6 *) not available
(KDA /TDA)
For...
30
Section 2: 2AD power connections - direct connections and intermediate terminals
Cable Assembled cables Cable components Assembled cables for intermediate
cross for direct connection for direct connection terminals on terminal strips
section on the Cable on the on the motor on the controller
A [mm2] motor flex./highly flex. controller flex./highly flex. flex./highly flex.
Für... For...
For... For...
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
M8 available
(PG 29) (RAC2 /RAC3)
2AD160B-B·····-BS·3-···· 25 IKL171/IKF171 ..stay bolt M8 IN207/IN407 ...line-up terminals IKL171/IKF171 not
(PG 29) M8 (RAC2 /RAC3) available
2AD160C-B·····-BS·3-····· 35 IKL182/ *) ..stay bolt M10 IN267 ...line-up terminals IKL182/ *) not
(PG 42) M10 (RAC2 /RAC3) available
2AD180C-B·····-BS·3-····· 35 IKL182/ *) ..stay bolt M10 IN267 ...line-up terminals IKL182/ *) not
(PG 42) M10 (RAC2 /RAC3) available
For... For...
2AD200C-B·····-AS·3-····· 2 x 25 2 x IKL 175/2 x IKF 175 ..stay bolt M12 2 x IN207/ 2 x IN 407 ...Screws *) not
(PG 48) M12 M12 (RAC4) available
31
Section 1: 2AD power connections - plug design
Cable Assembled cables for plug The components of assembled cables with plug
cross connector design
section
on the motor on the controller on the motor Cable Plug design L. on the
A[mm2]
flex. /highly flex. flex. /highly flex. flex./highly flex. controller
see
"Attention" For..
below!
2AD100B-B•••••-AS•3-•••• 4 IKL073/IKF073 *) IN172/25 IN203/IN403 IN217/25 IN218/25 dto. ..stay bolt M6
(KDA/TDA)
2AD100C-B•••••-AS•3-•••• 4 IKL073/IKF073 *) IN172/25 IN203/IN403 IN217/25 IN218/25 dto. ..stay bolt M6
(KDA/TDA)
2AD100D-B•••••-AS•3-•••• 6 IKL111/IKF111 IKL114/IKF114 IN172/06 IN204/IN404 IN217/06 IN218/06 dto. ..stay bolt M6
(KDA/TDA)
2AD101D-B•••••-BD•3-•••• 10 IKL133/IKF133 *) IN172/10 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
(KDA/TDA)
2AD132B-B•••••-BS•3-•••• 10 IKL133/IKF133 *) IN172/10 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
(KDA/TDA)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
(KDA/TDA)
2AD132D-B•••••-BD•3-••• 25 *) *) IN172/25 IN207/IN407 IN217/25 IN218/25 dto. ..stay bolt M6
(KDA/TDA)
see
"Attention" For..
below!
2AD132B-B•••••-DS•3-•••• 6 IKL111/IKF111 *) IN172/6 IN204/IN404 IN217/06 IN218/06 dto. ..line-up terminals
(RAC2/RAC3)
2AD132C-B•••••CS•3-•••• 10 IKL133/IKF133 *) IN172/10 IN205/IN405 IN217/10 IN218/10 dto. ..line-up terminals
(RAC2/RAC3)
2AD132D-B•••••-AS•3-•••• 16 IKL154/IKF154 *) IN172/16 IN206/IN406 IN217/16 IN218/16 dto. ..line-up terminals
(RAC2/RAC3)
Symbols:
Figure 2.21: Specifications table for assembled cables with plug connectors for
Alkab03
32
Section 2: 2AD power connections - plug design
Cable Assembled cables for plug Assembled cable components with
cross connector plug connector
section on the motor on the controller on the motor Cable plug design L. on the
A[mm]2
flex. /highly flex. flex. /highly flex. flex./highly flex. controller
see
For.. "attention" For..
below!
2AD132B-B•••.•-BS•3-•••• 10 IKL137/IKF137 *) ..stay bolt M6 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
2AD132C-B•••.•-BS•3-•••• 16 IKL153/IKF153 *) ..stay bolt M8 IN206/IN406 IN217/16 IN218/16 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
2AD132D-B•••.•-BD•3-•••• 25 IKL173/IKF173 *) ..stay bolt M8 IN207/IN407 IN217/25 IN218/25 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
2.
see
For.. "attention" For..
below!
(PG29) M8 (RAC2/RAC3)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
2AD160B-B•••.•-BS•3-•••• 25 *) *) ..stay bolt M8 IN207/IN407 IN217/25 IN218/25 dto. ..line-up terminals
(PG29) M8 (RAC2/RAC3)
2AD160C-B•••.•-BS•3-•••• 35 not available not available ..stay bolt M10 IN267 not available not available dto. ..line-up terminals
(PG42) M10 (RAC2/RAC3)
2AD180C-B•••.•-BS•3-•••• 35 not available not available ..stay bolt M10 IN267 not available not available dto. ..line-up terminals
(PG42) M10 (RAC2/RAC3)
see
For.. "attention" For..
below!
2AD180D-B•••.•-BS•3-•••• 50 not available not available ..stay bolt M10 IN268 not available not available dto. ..screws
(PG42) M10 M12(RAC4)
2AD200C-B•••.•AS•3-•••• 2X25 not available not available ..stay bolt M12 2 x IN207/2 x IN 407 not available not available dto. ..screws
(PG48) M12 M12(RAC4)
Symbols:
ALKAB04
33
Figure 2.22: Specifications for connection with plug design for 2AD motors-Section
Section 1: 2AD power connections - plugin testing points
Cable Preassembled cables for plugin Components of preassembled cables with plugin
cross testing points testing points
section
on the motor on the controller on the motor Cable plugin testing points L. on the
A[mm2]
flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
For..
2AD100B-B•••••-AS•3-•••• 4 IKL072/IKF072 IKL071/IKF071 IN172/25 IN203/IN403 IN210/25 IN172/25 dto. ..stay bolt M6
(KDA/TDA)
2AD100C-B•••••-AS•3-•••• 4 IKL072/IKF072 IKL071/IKF071 IN172/25 IN203/IN403 IN210/25 IN172/25 dto. ..stay bolt M6
(KDA/TDA)
2AD100D-B•••••-AS•3-•••• 6 IKL113/IKF113 IKL112/IKF112 IN172/06 IN204/IN404 IN210/06 IN172/06 dto. ..stay bolt M6
(KDA/TDA)
2AD101D-B•••••-BD•3-•••• 10 IKL138/IKF138 IKL130/IKF130 IN172/10 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(KDA/TDA)
2AD132B-B•••••-BS•3-•••• 10 IKL138/IKF138 IKL130/IKF130 IN172/10 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(KDA/TDA)
2AD132C-B•••••-BS•3-•••• 16 IKL158/IKF158 *) IN172/10 IN206/IN406 IN210/16 IN172/16 dto. ..stay bolt M6
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
(KDA/TDA)
2AD132D-B•••••-BD•3-••• 25 IKL178/IKF178 IKL170/IKF170 IN172/25 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(KDA/TDA)
Symbols: ALKAB05
Figure 2.23: Table of assembled specifications for connections with plug testing
34
Section 2: 2AD power connections - plugin testing points
Cable Preassembled cable for plugin Components of preassembled cables with plugin
cross testing points testing points
section
on the motor on the controller on the motor Cable plugin testing points L. on the
A[mm2]
flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
For.. For..
2AD132B-B•••••-BS•3-•••• 10 IKL129/IKF129 IKL130/IKF130 ..stay bolt M6 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
2AD132C-B•••••-BS•3-•••• 16 IKL149/IKF149 *) ..stay bolt M8 IN206/IN406 IN210/16 IN172/16 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
2AD132D-B•••••-BD•3-•••• 25 IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(PG29) M8 (KDA/TDA)
For.. For..
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
(PG29) M8 (RAC2/RAC3)
2AD160B-B•••••-BS•3-•••• 25 IKL169/IKF169 *) ..stay bolt M8 IN207/IN407 IN217/25 IN172/25 dto. ..line-up terminals
(PG29) M8 (RAC2/RAC3)
2AD160C-B•••••-BS•3-•••• 35 not available not available ..stay bolt M10 IN267 not available not available dto. ..line-up terminals
(PG42) M10 (RAC2/RAC3)
For..
For..
2AD180D-B•••••-BS•3-•••• 50 not available not available ..stay bolt M10 IN268 not available not available dto. ..Screws
(PG42) M10 M12(RAC4)
2AD200C-B•••••AS•3-•••• 2X25 not available not available ..stay bolt M12 2 x IN207/2 x IN 407 not available not available dto. ..Screws
(PG48) M12 M12(RAC4)
ALKAB06
Symbols:
35
Section 1: 1MB power connections - plugin testing points
Cable Assembled cables Components of assembled cables for direct Assembled cables for intermediate
cross for direct connection connections terminals on terminal strips
section on the Cable on the on the motor on the controller
A [mm2] motor flex./highly flex. controller flex./highly flex. flex./highly flex.
For... For...
1MB160E-4B...
(PG )
1MB160B-4A... 10 IKL135/IKF135 ..stay bolt M6 IN205/IN405 ..stay bolt M6 IKL136/IKF136 not
(PG 29) M8 (KDA /TDA) available
1MB200D-4C...
(PG )
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB240B-4A... 10 IKL135/IKF135 ..stay bolt M6 IN205/IN405 ..stay bolt M6 IKL136/IKF136 not
(PG 29) M8 (KDA /TDA) available
1MB240D-4A... 10 IKL135/IKF135 ..stay bolt M6 IN205/IN405 ..stay bolt M6 IKL136/IKF136 not
(PG 29) M8 (KDA /TDA) available
1MB310B-6A...
(PG )
Symbols: ALKAB07
Figure 2.25: Table of assembled specifications for direct connection and for
*) Available. For inquiries on type information contact Development Dept., INDRAMAT.
36
Section 2: 1MB power connections - plugin testing points
1MB Frameless Spindle Motor
Cable Assembled cables Components of the assembled cable for Assembled cables for intermediate
cross for direct connection direct connection terminals on terminal strips
section on the Cable on the on the motor on the controller
A [mm2] motor flex./highly flex. controller flex./highly flex. flex./highly flex.
For... For...
1MB160F-4B...
(PG )
1MB200D-4B... 10 IKL136/IKF136 ..stay bolt M6 IN205/IN405 ...line-up terminals IKL136/IKF136 not
(PG 29) M8 (RAC2 /RAC3) available
1MB200D-4D...
(PG )
1MB200E-4B...
(PG )
1MB200H-4B...
(PG )
1MB240F-4B...
(PG )
1MB240H-4B... 16 IKL151/IKF151 ..stay bolt M8 IN206/IN406 ...line-up terminals IKL151/IKF151 not
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
M8 available
(PG 29) (RAC2 /RAC3)
1MB241H-6D... 10 IKL136/IKF136 ..stay bolt M6 IN205/IN405 ...line-up terminals IKL136/IKF136 not
(PG 29) M8 (RAC2 /RAC3) available
1MB310F-6B... 35 IKL182/ *) ..stay bolt M10 IN267 ...line-up terminals IKL182/ *) not
(PG 42) M10 (RAC2 /RAC3) available
1MB312B-4A... 25 IKL171/IKF171 ..stay bolt M8 IN207/IN407 ...line-up terminals IKL171/IKF171 not
(PG 29) M8 (RAC2 /RAC3) available
1MB312C-4A... 35 IKL182/ *) ..stay bolt M10 IN267 ...line-up terminals IKL182/ *) not
(PG 29) M10 (RAC2 /RAC3) available
ALKAB08
Symbols:
Figure 2.26: Table of assembled specifications for direct connection and for
*) Available. For inquiries on type information contact Development Dept., INDRAMAT.
37
Section 3: 1MB power connections - direct connections and intermediate terminals
Cable Assembled cables Components of the assembled cables Assembled cable for intermediate
cross for direct connections for direct connections terminals on terminal strips
section on the Cable on the on the motor on the controller
A [mm2] motor flex./highly flex. controller flex./highly flex. flex./highly flex.
For... For...
For...
2. Power Connections
For...
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB375D-6B... ..Screws
(PG ) M12(RAC4)
ALKAB09
Symbols:
38
Figure 2.27: Table listing information on assembled cables for direct connections
Section 1: 1MB power connections - plug design
1MB Frameless Spindle Motor
Cable Assembled cables Components of assembled cables
cross for plug design with plug design
section on the motor on the controller on the motor Cable plug L. on the
A[mm2] flex. /highly flex. flex. /highly flex. flex. /highly flex. design controller
see
For.. "Attention" For..
below
1MB160E-4B...
(PG )
10 IKL137/IKF137 *) ..stay bolt M6 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
1MB160B-4A...
(PG 29) M8 (KDA/TDA)
10 IKL137/IKF137 *) ..stay bolt M6 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
1MB160D-4A...
(PG 29) M8 (KDA/TDA)
1MB200D-4C...
(PG )
1MB240B-4A... 10 IKL137/IKF137 *) ..stay bolt M6 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
(KDA/TDA)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
(PG 29) M8
1MB240D-4A... 10 IKL137/IKF137 *) ..stay bolt M6 IN205/IN405 IN217/10 IN218/10 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
25 IKL173/IKF173 *) ..stay bolt M8 IN207/IN407 IN217/25 IN218/25 dto. ..stay bolt M6
1MB240F-4A...
(PG 29) M8 (KDA/TDA)
1MB310B-6A...
(PG )
Symbols:
Figure 2.28: Table of specifications for assembled cables with plug design in
*) Available. For inquiries on type information contact Development Dept., INDRAMAT. Do not use any other type!
39
ALKAB10
Section 2: 1MB power connections - plug design
1MB Frameless Spindle Motor
Cable Assembled cable for Components of assembled cable with plug
cross plug design design
section on the motor on the controller on the motor Cable Plug design L. on the
A[mm2] flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
see
For.. "Attention" For..
below!
1MB160F-4B...
(PG )
1MB200D-4B... 10 IKL137/IKF137 *) ..stay bolts M6 IN205/IN405 IN217/10 IN218/10 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB200D-4D...
(PG )
1MB200E-4B...
(PG )
1MB200H-4B...
(PG )
1MB240F-4B...
(PG )
motors - Section 2.
1MB240H-4B... 16 IKL153/IKF153 *) ..stay bolts M8 IN206/IN406 IN217/16 IN218/16 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB241H-6D... 10 IKL137/IKF137 *) ..stay bolts M6 IN205/IN405 IN217/10 IN218/10 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB310B-6B... 25 IKL173/IKF173 *) ..stay bolts M8 IN207/IN407 IN217/25 IN218/25 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB310D-6B... IKL173/IKF173 *) ..stay bolts M8 IN207/IN407 IN217/25 IN218/25 dto. ..line-up terminals
25
(PG 29) M8 (RAC2/RAC3)
1MB310F-6B... 35 not available not available ..stay bolts M10 IN267 not available not available dto. ..line-up terminals
M10 (RAC2/RAC3)
(PG 42)
1MB312B-4A... IKL173/IKF173 *) ..stay bolts M8 IN207/IN407 IN217/25 IN218/25 dto. ..line-up terminals
25
(PG 29) M8 (RAC2/RAC3)
1MB312C-4A... not available not available ..stay bolts M10 IN267 not available not available dto. ..line-up terminals
35
(PG48) M10 (RAC2/RAC3)
(PG 29)
Symbols:
Figure 2.29: Table of specs on assembled cables with plug design for 1MB
*) Available. For inquiries on type information contact Development Dept., INDRAMAT. Do not use any other types!
ALKAB11
40
Section 3: 1MB power connections - plug design
Cable Assembled cable for Components of assembled cables with
cross plug design plug design
section on the motor on the controller on the motor Cable Plug design L. on the
A[mm2] flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
see
For.. "Attention" For..
below!
motors - Section 3.
2. Power Connections
see
For.. For..
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
"Attention"
below!
1MB375D-6B... ..screws
(PG ) M12(RAC4)
Symbols:
Figure 2.30: Specifications table on assembled cables with plug design for 1MB
ALKAB12
41
Section 1: 1MB power connections - plugin testing points
1MB Frameless Spindle Motor
Cable Assembled cable for plugin testing Components of preassembled cables with plugin
cross points testing points
section
on the motor on the controller on the motor Cable Plug testing points L. on the
A[mm2]
flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
For.. For..
1MB160E-4B...
(PG )
1MB160B-4A... 10 IKL129/IKF129 IKL130/IKF130 ..stay bolt M6 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(PG 29) (KDA/TDA)
M8
1MB160D-4A... 10 IKL129/IKF129 IKL130/IKF130 ..stay bolt M6 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(PG 29) (KDA/TDA)
M8
1MB160F-4A... 25 IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
1MB200D-4E... 25 IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
1MB200D-4C...
(PG )
1MB240B-4A... 10 IKL129/IKF129 IKL130/IKF130 ..stay bolt M6 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB240D-4A... 10 IKL129/IKF129 IKL130/IKF130 ..stay bolt M6 IN205/IN405 IN210/10 IN172/10 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
1MB240F-4A... 25 IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
1MB241H-6C... 25 IKL169/IKF169 IKL170/IKF170 ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..stay bolt M6
(PG 29) M8 (KDA/TDA)
1MB310B-6A...
(PG )
ALKAB13
Symbols:
Figure 2.31: Specifications table on assembled cables for connection with plugin
42
Section 2: 1MB power connections - plugin testing points
1MB Frameless Spindle Motor
Cable Assembled cable for plugin testing Components of a assembled cables with plugin testing
cross points points
section
on the motor on the controller on the motor Cable Plug testing point L. on the
A[mm2]
flex. /highly flex. flex. /highly flex. flex. /highly flex. controller
For.. For..
1MB160F-4B...
(PG )
1MB200D-4B... 10 IKL129/IKF129 IKL134/ *) ..stay bolt M6 IN205/IN405 IN217/10 IN172/10 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB200D-4D...
(PG )
1MB200E-4B...
(PG )
1MB200H-4B...
(PG )
1MB240F-4B...
(PG )
1MB240H-4B... IKL149/IKF149 *) ..stay bolt M8 IN206/IN406 IN210/16 IN172/16 dto. ..line-up terminals
16
2. Power Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB241H-6D... 10 IKL129/IKF129 IKL134/ *) ..stay bolt M6 IN205/IN405 IN217/10 IN172/10 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB310B-6B... IKL169/IKF169 *) ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..line-up terminals
25
(PG 29) M8 (RAC2/RAC3)
IKL169/IKF169 *) ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..line-up terminals
1MB312B-4A... 25 IKL169/IKF169 *) ..stay bolt M8 IN207/IN407 IN210/25 IN172/25 dto. ..line-up terminals
(PG 29) M8 (RAC2/RAC3)
1MB312C-4A... not available not available ..stay bolt M10 IN267 not available not available dto. ..line-up terminals
(PG 29) 35 M10 (RAC2/RAC3)
ALKAB14
Symbols:
Figure 2.32: Specifications table on assembled cables for connection with plugin
43
Section 3: 1MB power connections - plugin testing points
Cable Assembled cable for plugin Components of the assembled cable with plugin
cross testing points testing points
section
on the motor on the controller on the motor Cable Plug testing point L. on the
A[mm2]
flex. /highly flex. flex. /hochflex. flex. /hochflex. controller
For.. For..
For..
2. Power Connections
For..
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
1MB375D-6B... ..Screws
(PG ) M12(RAC4)
44
2. Power Connections
Cable Type Cable cross Cable Construction Diameter Bending Radius Weight
Section in mm in mm in kg/m
in mm2 fixed flexible
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 45
2. Power Connections
2.2. Power connections of the The power connections between the RAC main spindle controller and
RAC three-phase mains the three-phase mains are arranged in ...
Types The power connections of the RAC controller three-phase mains are
generally internal control cabinet cables which are, for the sake of
expediency, constructed with single strands. Motor connection
cables from INDRAMAT can, however, also be used.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 46
2. Power Connections
Permissible mains voltage Dependent upon the „AC supply voltage“ option, the following mains
voltages are permissible for RAC controllers:
Periodic voltages Voltage at the RAC should not be permitted to periodically exceed
1000 V (peak value) between the outer wire (terminal L1, L2, L3) and
the housing!
Non-periodic overvoltage Non-periodic overvoltages between the outer wire and housing are
tolerable for RAC controllers, if these are in accordance with VDE
0160 (see Fig. 2.36)!
UN+∆U
UN
3
2,6
2,4
2,3
2,2
∆U
2
∆U
T
2
1,8
1,6
UN
1,4
1,2
1,15
1,1
1
0,1 0,2 0,4 0,6 1 1,3 2 4 6 10 20
T (ms)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 47
2. Power Connections
The peak value of the rated voltage equals UN = 460V* square root
of 2=650V. Maximum tolerable, non-periodic voltage peak equals
1500 V for T<1.3 ms.
Grounded Three-Phase Mains RAC controllers can be directly connected to Wye-point and three-
phase mains grounded on the outer wire. Should the mains voltage
not agree with the RAC rated connection voltage, then an
autotransformer is needed to equalize the voltage (see Figure 2.37)!
Ungrounded Three-Phase Mains Ungrounded three-phase mains run increased danger of unsafe
overvoltages occurring between the outer wire and the housing. RAC
controllers can only be operated on these mains
– if the drive is connected via an isolating transformer, or,
– if surge arresters safeguard the facility.
Connection via an The RAC controller is most protected against damage from overvoltage
Isolating Transformer when it is connected via an isolating transformer. The drive operates
with the greatest possible safety. The use of an isolating transformer
is recommended in that case where an ungrounded three-phase
mains also requires voltage to be matched to the permissible connec-
tion voltage of the unit (see Figure 2.38).
Surge Arresters as Safeguards RAC controllers may only then be operated with ungrounded three-
phase mains if the facility is secured with a surge arrester. An
autotransformer can be used in the event that voltage must be
matched to the permissible rated connection voltage of the unit.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 48
2. Power Connections
L2
L3
PE
F1 F1 200VA
Does not apply if 220V ±10%
voltage matching not 50...60Hz
needed!
Does not
For information on connection
0,75...2,5mm2
0,75...2,5mm2
apply to
cross sections, rated fuse AC 220 V!
currents and transformers (if
needed), see Sec. 2.2.3, "List of
Connecting Components
Specifications".
X14 X14
L1 L2 L3 L1 L2 L3 L N
Figure 2.37: Connecting RAC2, RAC3 and RAC4 to a grounded three-phase mains.
L2
L3
F1 F1
200VA
220V ±10%
Ungrounded 50...60Hz
Three-Phase
Mains
Does not
apply to
0,75...2,5mm2
0,75...2,5mm2
X14 X14
L1 L2 L3 L1 L2 L3 L N
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 49
2. Power Connections
L2
L3
Remote control
F1 F1 200VA
220V ±10%
50...60Hz
F3
Does not
0,75...2,5mm2
apply to
0,75...2,5mm2
AC 220 V!
F2
F2
For information on connection
cross sections, rated fuse currents
and transformers (if needed), see
Sec. 2.2.3, "List of Connecting
Components Specifications".
Control cabinet - L1 L2 L3 L1 L2 L3 L N
earth potential. X14 X14
RAC2, RAC4 RAC3
APRAC003
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 50
2. Power Connections
L1
L2
L3
F3 Does not
apply to
AC 220 V!
0,75...2,5mm2
0,75...2,5mm2
F2 F2
L1 L2 L3 L1 L2 L3 L N
OFF
3 4 3 4
RAC3
RAC2, RAC4
APRAC004
Response from F2
triggers break.
Control Control
An earth leakage circuit breaker (Fl) must not be built into the
RAC controller!
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 51
2. Power Connections
Connection cross section, The dimensions of the mains fuse and the mains connection cable
type of fuse are dependent upon the rated output of the main spindle motor
operated on the RAC controller.
If the rated output of the main spindle motor is fully utilized during a
processing cycle, then the following values are achieved:
2AD132B-...-DS 10 19
1MB200E-4B-... 11 21 3xNH25gl 4
1MB240F-4B-... 11 26
2AD132C-..-CS 15 29
1MB240H-4B-... 15 29
1MB241H-6D-... 16 30 3xNH35gl 6
1MB200D-4D-... 19 36
1MB310B-6B-... 19 36
1MB200H-4B-... 19,5 37
1MB312B-4A-... 20 38
2AD132D-...-AS 22 42 3xNH50gl 10
1MB310D-6B-... 25 48
1MB312C-4A-... 25 48
2AD160B-...-BS 30 57 3xNH63gl 16
1MB310F-6B-... 35 66
2AD160C-...-BS 37 70 3xNM80gl 25
1MB375B-6B-... 40 76
2AD180C-...-BS 52 99 3xNH100gl 35
1MB375B-6B-... 55 105
Figure 2.41: Mains connection specifications with rated service of main spindle
motors, or frameless spindle motors (valid for 3 x AC 380 V ... 3 X AC 460 V).
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 52
2. Power Connections
Should the rated power of the main spindle motor not be completely
utilized during the duty cycle, including acceleration and braking, then
the RAC mains connection can be engineered lower. The minimum
values for the connecting components must, however, be adhered to!
Wiring and overload problems could occcur (with load peak current),
if these minimum values are not achieved!
RAC3.1-100-... 3xNH25gl 4
RAC3.1-150-... 3xNH35gl 6
RAC2.2-200-... 3xNH50gl 10
RAC2.2-250-... 3xNH63gl 16
RAC4.1-300-... 3xNH80gl 25
RAC4.1-400-... 3xNH25gl 25
IMainsRAC=1,9*PCont.Motor*A/kW
Using the load capacity table in Fig. 1.7, the calculated mains current,
lmainsRAC, is allocated to a cable cross section. The selected cross
section and its corresponding fuse must not fall short of the minimum
values listed in Figure 2.42!
Sizing the Autotransformer The output, Smains, of a possibly needed autotransformer, corre-
sponds to the rated output, or the actually required continuous output
of the main spindle motor. The inductive components of the relative
short-circuit voltage, Ukx, must be smaller than 4%!
SMains = √3*UX14/L1-L2*IMainsRAC
uKX = UKX1/URated1*100%
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 53
2. Power Connections
Sizing the Isolating Transformer The output, Smains, of an isolating transformer, if needed, also de-
pends upon the rated output, or the actual continuous output required
of the main spindle motor.
RAC3.1-100-... 25
RAC3.1-150-... 40
RAC2.2-200-... 50
RAC2.2-250-... 65
RAC4.1-300-... 80
RAC4.1-400-... 100
Figure 2.43: Minimum transformer output if the RAC controller is connected via i
an isolating transformer.
The already stated formulae are used to calculate the mains current,
ImainsRAC, and the mains connection output, Smains, of the main spindle
motor:
ImainsRAC=1,9*Pcont.Motor*A/kW
Pcont.Motor= continuous output (kw) actually
demanded of motor
(Formula valid for 3 x AC 380 V ... 3 x AC 460 V.)
Smains = √3*UX14/L1-L2*ImainsRAC
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 54
2. Power Connections
Overvoltage Protectors
Controller Type Fuse F3 Surge arrester
Type F2, Type
RAC3.1-100-... ---
RAC2.2-200-... ---
RAC4.1-400-... 3x100Agl
Controller Lay-Out
on the mains cable on the controller
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 55
3. Feedback and CNC Connections
3. Feedback and Signal exchange with the CNC control takes place via the CNC
connections; feedback of position or speed of the motor shaft and the
CNC Connections spindle to the main spindle controller via the feedback connections.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 56
3. Feedback and CNC Connections
3.1. Types of feedback and There are four types of assembled feedback and CNC connections.
CNC connections
CNC side
Symbols:
XXkab01
Figure 3.2: Assembled cables for direct connections (also see figure 3.22).
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 57
3. Feedback and CNC Connections
Connection with This type of connection permits an easy diagnosis of the signal
Intermediate Terminals exchange to the CNC control at the intermediate terminal points.
CNC side
Symbols:
XXkab02
Figure 3.3: Assembled cables for intermediate terminals on the terminal strip
(also see Figure 3.22).
Connection with plug design The control cabinet can be finished entirely independent of the
machine with this type of connection. The melding of machine and
control cabinet is quick and simple.
CNC side
Symbols:
XXkab03
Figure 3.4: Assembled cables for plug design (also see Figure 3.23).
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 58
3. Feedback and CNC Connections
CNC side
Symbols:
XXkab04
Figure 3.5: Assembled cable with plugin testing points (also see Figure 3.24)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 59
3. Feedback and CNC Connections
3.2. Connecting plans for Only the connection plans for the direct connection of feedback and
direct connections CNC connections are depicted. They do, however, apply to all other
types of connections. The respective testing points do not alter the
allocation of the connections for feedback or CNC control and main
spindle controller.
Standard interfaces Main spindle controllers are always equipped with motor feedback
and optional interfaces connection (X3, standard) and control input, signal and analogue
outputs (X2, standard). The controllers can optionally be equipped
with additional feedback and CNC interfaces.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 60
3. Feedback and CNC Connections
61
assembled cable IKS 032
47
IKS 315
plug connector (9 way)
IN 309
52
assembled cable IKS 315/..
26
45
cable IN 209
plug connector (9 way)
(Color coded as per
IN 401
INDRAMAT standards)
D-Sub-plug connector (15 way)
IN 290
X3
1 pk 0,25 mm2 2 0
3 gn 0,25 mm2 13 B
5 bl 0,25 mm2 7 A
9 9
7 br 1 mm2 12 + 5Vint
8 wh 1 mm2 10 0Vint
Motor feedback
high-resolution Controller
(insulated sensor attachment)
SBDSUB7
IKS315
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 61
52
Assembled cable IKS 315/.. Assembled cable IKS 617/..
26
45
45
45
cable IN 209 cable IN 209
Plug connector (9 way) (color coded as per
(color coded as per
IN 401 INDRAMAT standards)
INDRAMAT standards)
D-sub-plug connector (15 poles) Plug connector (15 way) D-sub-plug connector (15 way)
IN 290 IN 289 IN 290
X1 X2 X3
1 pk 0,25 mm2 2 0 0 2 pk 0,25 mm2 2 0
9 9 9 9
feedback cable.
Motor feedback
high-resolution (insulated
sensor attachment) Controller
B
B
0
0
A
A
0V
+ 5V
B
B
0
0
A
A
0V
+ 5V
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
"motor feedback = 3") X3 X4
8
1
3
4
5
6
8
1
3
4
5
6
9
9
10
10
12
12
45
*)
Ground shield only on one end of
see *)
see *)
"
"
"
"
"
"
"
"
"
"
0,25 mm2
0,25 mm2
source.
1 mm2
1 mm2
gr
pk
rd
bk
bn
gn
wh 1 mm2
bn
gr
pk
rd
bk
bn
gn
wh 1 mm2
bn
70
Figure 3.7: HGV1 connection plan switched into the high-resolution motor
HGV1_1
62
3. Feedback and CNC Connections
52
Assembled cable IKS 331/..
26
45
Cable IN 209
Plug connector (12 way)
(color coded as per
IN 301
INDRAMAT standards) 1
4 bk 0,25 mm2 4 0
8 gr 0,25 mm2 8 B
1 pk 0,25 mm2 1 B
5 br 0,25 mm2 5 A
6 gn 0,25 mm2 6 A
9 9
12 br 1 mm2 12 + 5Vint
10 wh 1 mm2 10 0Vint
Motor feedback
incremental encoder Controller
(insulated attachment)
SBDSU1
Figure 3.8: Connection plan for incremental encoder motor feedback (motor type
key field „motor feedback = 1“).
IKS 331
IKS 317
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 63
3. Feedback and CNC Connections
61
47
52
Assembled cable IKS 327/..
26
45
Cable IN 209
Plug connector (12 way)
(color coded as per
IN 301
INDRAMAT standards) 1
4 bk 0,25 mm2 4 0
8 gr 0,25 mm2 8 B
1 pk 0,25 mm2 1 B
5 br 0,25 mm2 5 A
6 gn 0,25 mm2 6 A
9 9
12 br 1 mm2 12 + 5Vint
10 wh 1 mm2 10 0Vint
Spindle feedback
incremental encoder Controller
(insulated sensor attachment)
SBDSU3
Figure 3.9: Connection plan for high-resolution main spindle position encoder as
spindle feedback (controller with „additional encoder input = P“ option).
IKS314
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 64
52
Assembled cable IKS 314/.. Assembled cable IKS 049/..
26
45
45
45
Cable IN 209 Cable IN 209
Plug connector (9 way)
(color coded as per (color coded as per
IN 401 1 1 1
INDRAMAT standards) INDRAMAT standards)
Plug connector (15 way)
D-sub-plug connector (15 way) D-sub-plug connector (15 way)
IN 290
IN 289 IN 289
X2 X1 X2
1 pk 0,25 mm2 2 0 0 2 pk 0,25 mm2 2 0
9 9 9 9
(The outputs A A, B B, and 0 0 of X3 and X4 are
7 br 1 mm2 12 + 5Vint
CD-decoupled from the controller) + 5Vint 12 br 1 mm2 12 + 5Vint
Spindle feedback
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
high-resolution
B
B
0
0
A
A
B
B
0
0
A
A
(insulated X3 X4
8
1
3
4
5
6
8
1
3
4
5
6
9
9
sensor attachment)
10 0V
10 0V
12 + 5V
12 + 5V
45
3. Feedback and CNC Connections
1
"
"
"
"
"
"
"
"
"
"
1 mm2
see *)
see *)
0,25 mm2
0,25 mm2
1 mm2
set-point line. If possible, at voltage
source.
wh
bn
gr
pk
rd
bk
bn
gn
wh 1 mm2
bn
gr
pk
rd
bk
bn
gn
70
(X3 and X4) are connected!
512 or 1024 1024 or 2048
Voltage supply
for A A, B B, 0 0
see **)
Voltage supply
for A A, B B, 0 0
see **)
cycles ( ) cycles ( )
HGV1_2
Figure 3.10: HGV1 connection plan switched into the high-resolution main
65
3. Feedback and CNC Connections
61
47
52
Assembled cable IKS 327/..
26
45
Cable IN 209
Plug connector (12 way)
(color coded as per
IN 301
INDRAMAT standards) 1
4 bk 0,25 mm2 4 0
8 gr 0,25 mm2 8 B
1 pk 0,25 mm2 1 B
5 br 0,25 mm2 5 A
6 gn 0,25 mm2 6 A
9 9
12 br 1 mm2 12 + 5Vint
10 wh 1 mm2 10 0Vint
Spindle feedback
incremental encoder Controller
(insulated sensor attachment)
SBDSU3
Figure 3.11: Connection plan for incremental encoder in the capacity of spindle
feedback (controller with „additional encoder input = P“ option).
IKS327
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 66
3. Feedback and CNC Connections
47 61
52
Assembled cable IKS 331/..
26
45
Cable IN 209
Plug connector (12 way)
(color coded as per
IN 301
INDRAMAT standards) 1
4 bk 0,25 mm2 4 0
8 gr 0,25 mm2 8 B
1 pk 0,25 mm2 1 B
5 br 0,25 mm2 5 A
6 gn 0,25 mm2 6 A
9 9
12 br 1 mm2 12 + 5Vint
10 wh 1 mm2 10 0Vint
Figure 3.12: Connection plan for incremental encoder in the capacity of lead
spindle feedback (controller with „additional encoder input = Y“ option).
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 67
3. Feedback and CNC Connections
200
Assembled cable IKS 610/..
Cable IN 271
45
(color coded as per
INDRAMAT standards)
IKS 610 1
D-sub-plug connector (37 way)
IN 293
X2
gr 0,5 mm2 1 0V ext
Voltage level input wh 0,25 mm2 2 0V int
bn " 3 AS (KDA/TDA only)
+36 V
ye/blck " 4 READY
yel " 5 N = CMD
+24 V
gn/bk " 6 N < MIN
+18 V rd 7 IN POS
"
bl " 8 90% LOAD
+5 V
rd " 9 TEMPWARN
0V bk " 10 LIMIT
0 (low) 1 (high)
vio " 11 SPEED CHANGE 1
gr/pk " 12 SPEED CHANGE 2
bl/rd " 13 LOAD LIMIT
wh/gn " 14 RF SLAVE
" 15 SPINDLE CONT
Voltage level output
Figure 3.13: Connection plan for control input, signal and analogue outputs, Bb-
contact (standard).
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 68
3. Feedback and CNC Connections
The control and signal outputs are DC-decoupled from the controller.
The control must supply the outputs with *24V/0 V. Should this not
be possible, then connect terminal 1 with 2 and 18 with 19!
70
Assembled cable IKS 045/..
Cable IN 233
45
(color coded as
per INDRAMAT standards)
X4
IKS 045
wh 0,22 mm2 1 E1
*)
bn 0,22 mm2 2 E2
gn 0,22 mm2 *) 5 E3
(see below!) 4
Voltage level
analogue inputs
9 +15VM
+15 V
8 - 15VM
-15 V Controller
SBDSUB6
Inputs E1/E2 and E3/E4 for the analogue set-point are designed as
IKS045
differential inputs.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 69
3. Feedback and CNC Connections
200
Assembled cable IKS 612
Cable 20x0,25
(color coded as per
45
INDRAMAT standards)
IKS 612
1
X4
wh 0,25 mm2 1 Bit 1
bn " 2 Bit 2
gn " 3 Bit 3
yel " 4 Bit 4
gr " 5 Bit 5
Voltage level pk " 6 Bit 6
+36 V bl " 7 Bit 7
rd " 8 Bit 8
+24 V bk " 9 Bit 9
vio " 10 Bit 10
+18 V
wh/bn " 11 Bit 11
wh/gn " 12 Bit 12
+5 V
wh/yel " 13 Bit 13
0V
0 (low) 1 (high) wh/gr " 14 Bit 14
wh/pk " 15 Bit 15
wh/bl " 16 DATA VALID
(see below!) 25
Controller
SBDSUB3
The inputs for the digital speed set-point (bit 1 ... bit 15, DATA VALID)
are DC-decoupled from the controller. Terminal 21 should be con-
nected to the OV potential of the control! The inputs are then set with
the +24V potential of the control! If the control does not supply *24V/
0, then connect terminal 18 with 21 and set the inputs via terminal 19!
Current consumption approx. 15mA per input!
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 70
3. Feedback and CNC Connections
Receiver diode
Fiber optic cable
from the control or
additional controllers
Electrical output
IC 1
Transmitter Driver
Fiber optic cable
diode control
to the control
or additional
controllers
Electrical input
IC 2
LED (red)
LED (green)
Controller
APSerc
Additional fiber optic cable For specifications on assembled fiber optic cables, attenuation calcu-
specifications lations, for specifications on constructing custom cables see doc. no.
209.0090-4101, „LWL Handling; description of application“.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 71
3. Feedback and CNC Connections
200
45
In KDA/TDA
Cable 20x0,25
IKS 614
D-sub-plug connector (25 way)
200 IN 295
Cable 20x0,25
(color coding as per
45
INDRAMAT standards) In RAC
1
D-sub-plug connector (25 way)
IN 291
X6 KDA/TDA
X13 RAC
wh 0,25 mm2 1 Bit 1
bn " 2 Bit 2
gn " 3 Bit 3
ye " 4 Bit 4
Voltage level gr " 5 Bit 5
+36 V pk " 6 Bit 6
bl " 7 Bit 7
+24 V
rd " 8 Bit 8
blck " 9 Bit 9
+18 V
vio " 10 Bit 10
wh/bn " 11 Bit 11
+5 V
wh/gn " 12 Bit 12
0V
0 (low) 1 (high) wh/ye " 13 Bit 13
wh/gr " 14 Bit 14
wh/rs " 15 Bit 15
wh/bl " 16 DATA VALID
(see below!) 25
Controller
SBDSUB2
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 72
3. Feedback and CNC Connections
The digital position set-point inputs (bit 1 ... bit 15, DATA VALID) are
DC-decoupled from the controller. Terminal 21 should be connected
to the OV potential of the control! The inputs are set with the +24V
IKS015/IKS016
potential of the control! If the control does not supply +24V/0 V, then
connect terminal 18 with 21 and the inputs via terminal 19! Current
consumption is approx. 15 mA per input!
45
Cable IN 234
In KDA/TDA
IKS 015
IKS 016
D-sub-plug connector (25 way)
D-sub-plug connector (25 way) IN 296
IN 291 Assembled cable IKS 016
Cable IN 234
45
(color coding
as per In RAC
INDRAMAT standards)
1
X6 KDA/TDA
X13 RAC
1 1
TxD 2 wh 0,25 mm2 *) 2 TxD
RxD 3 bn 0,25 mm2 3 RxD
RTS 4 gn 0,25 mm2 4 RTS
*)
CTS 5 ye 0,25 mm2 5 CTS
DSR 6
GND 7 gr 0,50 mm2 7 GND
RS 232C
20
DTR
Programming equipment,
PC, or something similar Controller
SBDSUB4
*) Internal shielding can be dropped if INDRAMAT cables are not used!
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 73
3. Feedback and CNC Connections
70
Assembled cable IKS 620
45
In TDA/KDA
IKS 620 Line IN 209
IKS 618
D-sub plug connector (15 way)
IN 328
70
Assembled cable IKS 618
Cable IN 209
45
In RAC
(color coded
as per
Voltage level outputs INDRAMAT standards) 1
X6 KDA/TDA
X13 RAC
+1,8 V
gr 0,25 mm2 8 B
+0,5 V pk 1 B
"
0V rd " 3 0
0 (low) 1 (high)
blck " 4 0
bn " 5 A
Voltage level gn " 6 A
for +5V supply
U
+5,25 V (see below!) 9
wh 1 mm2 10 0V
+5 V
+4,75 V
bn 1 mm2 12 + 5V
X17
0V (This is not available as an 1
assembled cable!) 2 Reference switch
3
Plug terminal 3 way, Controller
mat. no.: 220 856
SBDSUB5
Figure 3.19: Connection plan for incremental encoder output and reference
switch signal („additional interface=l“ option)
IKS618/IKS620 Outputs AA, BB and OO are DC-decoupled from the controller. The
CNC control must supply them with +5V/0.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 74
3. Feedback and CNC Connections
6
(max. 24V, 1A
Ready Bb intermittent and
5 continuous)
Mains contactor ON
2
ON
1
APRACKON
Figure 3.20: Connection plan for control of the mains contactor integrated into
the RAC controller.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 75
3. Feedback and CNC Connections
3.3. Assembled Cable Specifi- Specifications of the assembled cables for the four types of connec-
cations tions is dependent upon the functional options of the main spindle
controller and are summarized in tables.
The tables indicate both the assembled cable and its construction.
Table Summarizing
Assembled Specifications
....plugin testing points
....plug design
ZuTAB
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 76
3. Feedback and CNC Connections
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 77
Feedback and CNC connections - direct connection and link terminal
Interfaces on the Assembled cable Cable design for direct connection Assembled cable for intermediate terminals
main spindle controller for direct on terminal strip
controller.
connection
On the Cable Feedback On the Feedback
controller or CNC controller or CNC
Standard Interfaces
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
IKS 315 IN 290 IN 209 IN 401 not permitted! not permitted!
Motor feedback connection X3
For..
Control input, signal X2
and analogue outputs
IKS 610 IN 293 IN 271 ..line-up terminals IKS 610 not available
A
analog IKS 045 IN 287 IN 209 ..line-up terminals IKS 613 not available
Type
key field
"speed D IKS 612 IN 291 20 x 0,25 ..line-up terminals IKS 612 not available
digital X4
set-point"
78
Connected Connected Connected
P to.. to.. to..
controller.
( ) *) IN 290 IN 209 IN 351 not permitted! not permitted!
D
digit. IKS 614/IKS 612 IN 295/IN 291 20 x 0,25 IKS 614/IKS 612 not available
Type key Pos.-set-point X6/X13
field (*TA/RAC)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
"additional I IN 328/IN 289 IN 209 IKS 620/IKS 618 not available
Incre. output IKS 620/IKS 618
encoder
input"
S
RS232
IKS 015/IKS 016 IN 296/IN 292 IN 234/IN 234 IN 291/IN 291 *) / *) *)
3. Feedback and CNC Connections
Legend:
Legend:
D-sub Plug connector (plug) Plug connector (plug) Plug connector (coupling) Wall
plug connector for feedback connection, for feedback connection, Multi-core cable end
for feedback connection breakthrough
straight type elbow type
alkabf2
79
Feedback and CNC Connections - plug type
Main spindle Assembled cables Cable structure for plug design
controller interfaces for plug design
on the feedback side on the cable Plug type cable Feedback side
controller controller
Standard interfaces
IKS 332 IN 314 IKS 321 IN 290 IN 209 IN 304 IN 314 IN 342 IN 209 IN 401
*) *) IN 209 IN 401
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
*) *) IN 209 IN 309
Type
key field A,D,L X4 - not available - - not available -
"speed set-point"
*) / *) *) IN 234 IN 291
plugin testing points allocated to the interfaces on the main spindle controller.
80
Figure 3.24: Table summarizing assembled specifications for connections using a
ALKABF5
Connected
to..
P IKS 330 incremental IN 313 IKS 305 IN 289 IN 209 IN 303 IN 313 IN 305 IN 209 IN 301
encoder
high-resolution
IKS 330 encoder IN 314 IKS 321 IN 289 IN 209 IN 304 IN 314 IN 342 IN 209 IN 401
second motor
IKS 330 feedback IN 314 IKS 321 IN 289 IN 209 IN 304 IN 314 IN 342 IN 209 IN 401
Connected
to..
X5 IKS 330
second motor IN 314 *) IN 289 IN 209 IN 304 IN 314 IN 342 IN 209 IN 309
feedback
Connected
to..
IKS 330 incremental IN 313 *) IN 289 IN 209 IN 303 IN 313 IN 323 IN 209 IN 301
encoder
high-resolution *) *)
IKS 330 encoder IN 314 IN 289 IN 209 IN 304 IN 314 IN 209 IN 401
second motor *)
IKS 330 feedback IN 314 *) IN 289 IN 209 IN 304 IN 314 IN 209 IN 401
Connected
to..
IKS 330 incremental IN 313 *) IN 289 IN 209 IN 303 IN 313 IN 323 IN 209 IN 351
encoder
high-resolution IN 314 *)
IKS 330 encoder IN 289 IN 209 IN 304 IN 314 *) IN 209 IN 309
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
IKS 330
second motor IN 314 *) IN 289 IN 209 IN 304 IN 314 *) IN 209 IN 309
feedback
X5a
*) IN 313 IKS 305 IN 290 IN 209 IN 303 IN 313 IN 305 IN 209 IN 301
3. Feedback and CNC Connections
Legend:
D-sub Plug connector (plug) Plug connector (plug) Plug connector (coupling) Wall
plug connector for feedback connection, for feedback connection, Multi-core cable end
for feedback connection breakthrough
plugin testing points allocated to the interfaces on the main spindle controller.
straight type elbow type
alkabf2
81
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
Feedback and CNC Connections - plugin testing points
Main spindle Assembled cable for Cable construction with plugin testing points
3. Feedback and CNC Connections
IKS 315 IKS 322 IN 290 IN 209 IN 401 IN 309 IN 209 IN 401
Motor feedback connection X3
IKS 315 IKS 360 IN 290 IN 209 IN 401 IN 306 IN 209 IN 309
82
Functional option interfaces
Connected
to..
P IKS 327 incremental IKS 303 IN 289 IN 209 IN 301 IN 318 IN 209 IN 301
encoder
high-resolution
IKS 314 encoder IKS 322 IN 289 IN 209 IN 401 IN 306 IN 209 IN 401
second motor
IKS 314 feedback IKS 322 IN 289 IN 209 IN 401 IN 306 IN 209 IN 401
X5
Connected
to..
IKS 331 IKS 303 IN 290 IN 209 IN 301 IN 318 IN 209 IN 301
X5a
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
( ) IKS 331 IN 290 IN 209 IN 301 IN 318 IN 209 IN 351
Type key
field X6/X13
(*TA/RAC)
ALKABF4
Legend:
D-sub Plug connector (plug) Plug connector (plug) Plug connector (coupling) Wall
plug connector for feedback connection, for feedback connection, Multi-core cable end
for feedback connection breakthrough
straight type elbow type
alkabf2
83
3. Feedback and CNC Connections
3.4. Cable Specifications List The cable specifications used in the assembled cables are summa-
rized below in table form. All necessary specifications and measure-
ments are listed.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 84
4. Installation Guidelines
4. Installation Guide-
lines
Cable routing guidelines There must be a clearance of at least 100 mm between the power
connections and the feedback or CNC connections if the cables are
routed parallel. Otherwise, it is necessary to separate the cable
conduit with metal (see Fig. 4.1)
>=100 mm 2 - 4 mm
Kab_Kan
Feedback units Feedback units which the main spindle controller evaluates must be
mounted and electrically insulated at the machine or motor.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 85
4. Installation Guidelines
Power plug connectors The dimensioning of the contact distances and leakage paths of the
power plug connectors is based on the degree of contamination as
outlined in DIN VDE 0160.
Spindle housing
IN316
IN172 IN217 IN172 IN210 IN172 IN217 IN218
V3
IN192
V1 V1 V1 V1
V2 V2 V2 V2 V2 V3
2AD...
Machine housing Control cabinet wall
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 86
4. Installation Guidelines
Installing Cables The plug connectors of the power cable and the feedback connec-
tions must be firmly screwed into place when the drive is operating!
Category of Protection Category IP65 protects assembled INRAMAT cables when they are
for the Cable firmly screwed in and attached. This does not, however, apply to the
open side of control cabinet and housing breakthroughs as well as d-
sub plug connectors!
General Controller – Do not detach the AS programming module when unit is still under
Installation Guidelines power. The knurling screw must be firmly affixed during operation!
– The d-sub plug connectors must be firmly screwed into place!
– Twist the motor power cable strands!
Modular Drive System Installa- – The transparent panes on the safety guards on the front side of the
tion Guidelines unit must be firmly affixed during operation!
– Ground the motor on the controller and ground the controller directly
on the supply module!
– Plug the control voltage bus end plug (supply module accessories)
into the last controller on the drive configuration!
– Adhere to maximum tightening torque of the stay bolts, otherwise
there is the risk of tearing!
– Plug in heatsink fan cable, if present.
RAC Installation Guidelines – The power connection safety guards on the front of the RAC4 must
be closed when the unit is switched on and during operation!
– Ground the motor on the controller and ground the controller
housing to the main incoming earth terminal!
Measures Against Sources of If contacts or semi-conductors are used in connection with electronic
Interference from Inside the equipment and components to switch such inductive loads as chokes,
Control Cabinet contactors and relays, then these must be appropriately cleared of
interference. If direct current is used, then this is achieved by the
arrangement of freewheeling diodes, and if alternating current is
used, then this is achieved with the arrangement of commercial safety
RC suppressor components situated directly at the inductivity. Do not
use varistors as protective circuits!
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 87
5. Delivery, Identification, Storage
5. Delivery, Identifica-
tion,
Storage
Assembled Cables Assembled cables are rolled up and loosely packed in with the
delivery. They do have a label (cable marker), which bears the order
designation and the length of the assembled cable.
INDRAMAT - Cable
No.
Length: m
TSKabel
Plug accessories The plug accessory sets contain the plug connector (D-sub) for the
optional interfaces of the controller. They are packed in plastic bags
and bear a packaging slip (see Figure 5.3).
Note: The plug accessory sets are not necessarily needed (see Fig.
1.2)!
Designation: S•-•••
Speed set-point:
analog +/- 10V A
digital (16 Bit parallel) D
SERCOS interface L
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 88
5. Delivery, Identification, Storage
Packaging slip
Page 1 Page 2
X3
239 164
Additional plug accessories X3, X5, X13
RAC •.• - • • • - • • • - API - • •
X2 X5, X13
1 housing 37 way 221659
X2
Page 3 Page 4
X4
X4
1 2 3
X17
10 screw 221657
Date: 24.05.93
Acc. pack. slip S2-API
File: S2-API
Z.No.:109-0743-4248-00
Mat. No. BPZ: 253227
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 89
5. Delivery, Identification, Storage
Individual plug connectors Individual cables are rolled up and loosely packed in with the delivery.
and cables The sequential order number is always printed on them.
Single plug connectors are packed into plastic bags. The bags have
a label which indicate order number, appearance and dimensions of
the mounted plug connector.
bushing
Pin
Pin
View "X"
View "X"
INVERP
Controller-specific connections The controller-specific connections are also packed in plastic bags
and labelled with the respective order number. E••-• for KDA/TDA
controllers (depending upon the arrangement within the drive pack-
age), E1-RAC for RAC controllers.
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 90
6. Customizing Specifications
6. Customizing Specifi-
cations
Working
guidelines
Construction
diagrams
Request construction with
1 documentation parts list
from INDRAMAT
Order the
2 individual parts
and tools needed
Soldering Crimping
3 Constructing the cable (tools) (tools)
Cable construction
Attaching
pins, or Fertigungsunterlagen
bushings into Werkzeuge
the insulator
casing (tools) Löten
Crimpen
Isolierkörper
Hochspannungstest
High-voltage Durchgangsprüfung
4 Testing the cable test Isolationsprüfung
Run-through
crimping test
run-through test
high-voltage test
insulation test
insulator casing Insulation
soldering test
(tools)
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 91
Motor Crimping Reduction Screws Cable Cross section ... on the
cable lug in mm2 controller
Customizing a
Terminal
box bolts
motor power cable
Reduzierung
(dropped) PG29 IN204 (flex.) 6
Verschraubung
Mat. no. 220 874
2.1.3.
(dropped) PG29 IN206 (flex.) 16
Mat. no. 220 472
terminal boxes.
Frameless spindle motor 1MB PG29/PG36 PG36 IN207 (flex.) 25
Mat. no. 226 349 Mat. no. 220 473
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
25
Mat. no. 220 472
Symbols: PGREDKLK
Figure 6.2: Screw and reduction specifications for motor power connections via
92
box is listed in the table outlining assembled specifications in Section
Motor Power Reduction Bolts Cable Cross section ... on the
plug in mm2 controller
connector
IN217/25!
IN172/••
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97
via power plug connectors.
PG36/PG29 PG29 IN206 (flex.) 16
Mat. no. 220 474 Mat. no. 220 472
6. Customizing Specifications
Symbols:
PGRED172
Figure 6.3: Specifications for bolts and reduction for motor power connections
93
7. Index
7. Index Symbole
1MB connected to RAC 28
1MB to KDA/TDA 27
2AD 100 with KDA/TDA 21
2AD 100 and 2AD 101 connections 20
2AD 132 CONNECTED TO KDA/TDA 23
2AD 132 connected to KDA/TDA 25
2AD to KDA/TDA 27
2S 100 WITH KDA/TDA 22
A
Ambient temperatures 13
Analogue outputs 68
AS programming module 87
Autotransformer 48
B
Bending radius 45
C
Cable conduit 85
Cable construction 91
Category of Protection for the Cable 87
CNC Connections 56
Conductive contamination 86
Conductor cross sections, sized 13
Connecting an RAC to a three-phase mains 49
Connecting components 53
Connecting RAC with overvoltage surge arresters 50
Connection 2AD 132 with KDA/TDA 21
Connection 2AD 180 26
Connection of 1MB to KDA/TDA 27
Connection of 2AD 100 to KDA/TDA 20
Connection plans for feedback and CNC 60
Connection plans, motor-controller 19
Connection with intermediate terminals, feedback/C 58
Connection with plug design 58
Connection with plugin testing point 59
Contamination, degree of 86
Control circuits RAC 75
Control input 68
Control voltage bus end plug 87
Controller-specific connections 12
Crimping 91
Customizing specification 91
D
Diameter 45
Direct connections, feedback and CNC 57
Drive configuration 87
Drive shutdown 75
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 94
7. Index
E
Earth leakage circuit breaker 49
Environmental conditions 86
Equalizing the voltage 48
F
Feedback and CNC Connections 11, 56
Feedback and CNC connections 76
Feedback connections 56
Flanged socket 86
Freewheeling diodes 87
Fuse type 52
G
Grounded Three-Phase Mains 48
H
Heatsink fan cable 87
High-resolution motor feedback 61
High-voltage test 91
Holding Brake 19
Holding brake 9
I
IKS015/IKS016 73
IKS045 69
IKS314 64, 66
IKS610 68
IKS612 70
IKS614 72
IKS618/IKS620 74
IN 203 45
IN 204 45
IN 205 45
IN 206 45
IN 207 45
IN 209 84
IN 233 84
IN 234 84
IN 267 45
IN 271 84
IN 403 45
IN 404 45
IN 405 45
IN 406 45
IN 407 45
Incremental encoder output 74
Individual plug connectors 11, 90
Installation guidelines 85
Insulation test 91
Insulator casing 91
Interference sources inside the control cabinet 87
Interference-free operation 85
Isolating transformer 48
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 95
7. Index
K
KDA/TDA elec. conn. 8
L
Lead Spindle Feedback 67
Line 10
Line construction 45
Line lengths 14
Line routing 85
Line specifications for feedback and CNC connectio 45
Load capacity table 13
M
Mains connection line for RACs 55
Mains connection specifications 52
Mains voltage 47
Mass potential loops 85
Motor fan 19
Motor feedback, incremental encoder 63
Motor with blocking brake 19
Motor-controller connection with plug design 17
Motor-controller connection with plugin testing po 18
Motor-controller direct connection 16
Motor-controller power connections 15
N
Non-conductive contamination 86
O
Operating temperature, cable 13
Outer wire 47
Overvoltages 47
P
Packaging slip 89
PG thread 92
Plug accessory sets 88
Plug connector 90
Position set-point, digital 72
Power cable with intermediate terminal at terminal 17
Power cable with plug design 17
Power cable with plugin testing points 18
Power cables for direct connections 16
Power connections of the RAC three-phase mains 46
Power motor-controller connections 29
Power plug 90
Power plug connectors 86
Processing cycle 53
Protective caps 86
Protective circuits 87
Protective motor switch 19
R
RAC elec. conn. 9
Rated connection voltag 47
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 96
7. Index
S
Screws 92
SERCOS Interface 71
Serial interface 73
Shielding of bunched conductors 85
Sizing the Autotransformer 53
Sizing the Isolating Transformer 54
Soldering 91
Soldering of power plug connectors 93
Specifications of the power connection 10
Speed set-point, analog 69
Speed set-point, digital 70
spindle feedback 66
Storage 90
Storage temperature 90
Supply module 87
Surge arresters 48, 55
T
Table of power connections to the motor 29
Tables, feedback and CNC conn. 76
Terminal box 92
Three-Phase Mains 47
Tools 91
U
Ungrounded Three-Phase Mains 48
V
Varistors 87
Viewing panes 87
W
Weight 45
Wetting from coolants or lubricants 86
Wiring 85
Wye-point and outer wire grounded three-phase main 48
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 97
8. Supplementary Documentation
AC Main spindle
drive with controlled – Summary of the AC main drive system
Dokumentation 2AD main
spindle motor – Power range
– Applications of the technical functions
of the AC main spindle drive
– Selection protocol and item order list
– Delivery program
Asynchronous motor
Asynchronous motor 225
RAC4 Asynchronous motor 200
RAC3 Asynchronous motor 180
RAC2 Elektrische Asynchronous motor 160
Asynchronous motor
TDA1 132
Verbindungen Asynchronous motor 101
Controller KDA3 für Haupt- 2AD100
spindelan-
triebe
Planning and Design
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 98
8. Supplementary Documentation
(details, order)
with controlled frame- AC main spindle
less spindle motor 1MB – Power range drive with Selection specifications
Selection
changeover
1MB – Applications of the technical functions gearboxess 2K – Summary of the
of the AC main spiindle drive AC main drive system
– Selection protocol and items order list – Power range
– Delivery program – Order guidelines
• DOK-GENERL-MAIN*EL*CON-PRJ1-EN-E1,44 • 07.97 99