General Data
Manufacturing plant Taicang, China Factory charge Part Charge (HFC-134a) <12kg
Cooling efficiency 2.88 COP
Evaporator Information
Evaporator Application Standard Cooling (4 To 20C) Saturated evap temp - ckt 1 19.1 C
Evap fouling factor 0.00176 m2-deg K/kW Saturated evap temp - ckt 2 15.9 C
Leaving fluid evap 18.00 C Min flow evap 692.8 gpm
Entering fluid evap 25.00 C Press drop at min evap flow 5.12 ft H2O
Flow evap 983.2 gpm Max flow evap 109.3 L/s
Fluid pressure drop evap 9.13 ft H2O Fluid pressure drop max flow evap 30.8 ft H2O
Evap configuration 1 Pass arrangement, insulated
Condenser Information
Electrical Information
Incoming Power Line Dual Point Power Connection RLA - compressor 2A 185.00 A
Unit voltage 415.V/50.Hz/3 Phase Single point power MCA
Unit power 628.9 kW Single point power MOP
Compressor power 593.9 kW RLA - condenser fan (each) 4.70 A
RLA - compressor 1A 185.00 A Fan motor power 31.18 kW
Number of condenser fans 20.00 Each LRA - compressor 1A 185.00 A
Compressor starter type Variable frequency dirver LRA - compressor 2A 185.00 A
Physical Information
Acoustical Performance
Certified in accordance with the AHRI Air-Cooled Water-Chilling Packages Certification Program,
which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units
may be found in the AHRI Directory at www.ahridirectory.org.