Basic Flow Measurement
1 September 23, 2004
Contents
1) Introduction
2) Types of Flows
3) Basic Requirements for Flow Measurement
4) Definition of Quantities to be Measured
5) Types of Measurement
6) Types of Flow Meters
7) Selection of Flow Meters
8) Flow Measurement Information
9) Questions & Answers
2 September 23, 2004
Introduction
Since 1989 there were at least 23 distinct type of
technologies available for the measurement of flow in
closed conduit. Flow meters selection are part of the
basic art of the instrument engineer, and while only
handful of these technologies contribute to the majority
of installations.
And wide product knowledge is essential to find the most
cost effective solution to any flow measurement
application.
3 September 23, 2004
Types of Flows
Reynolds Number
The performance of flowmeters is also influenced by a dimensionless unit called the
Reynolds Number. It is defined as the ratio of the liquid's inertial forces to its drag
forces.
The Reynolds number is used for determined whether a flow is laminar or turbulent.
Laminar flow within pipes will occur when the Reynolds number is below the critical
Reynolds number of 2300 and turbulent flow when it is above 2300. The value of 2300
has been determined experimentally and a certain range around this value is considered
the transition region between laminar and turbulent flow.
Or
ѵ s = Mean Fluid Velocity,
η - (Absolute) Dynamic fluid Viscosity
v = Kinematics Fluid Viscosity (ν = η/ρ)
ρ = Fluid Density
L = Characteristic Length (Equal to diameter, 2 r if a Cross Section is
Circular)
4 September 23, 2004
Types of Flows
5 September 23, 2004
Basic Requirements for Flow
Ability to CalibrateMeasurement
Ability to Integrate Flow Fluctuation
Easy Integration with Piping System
High Accuracy
High Turn-Down Ratio
Low Cost
Low Sensitivity to Dirt Particles
Low Pressure Loss
No Moving Parts
Resistant to Corrosion and Erosion
6 September 23, 2004
Definition of Quantities to be measured
Volume Flow Rate
The definition of volume flow rate is the volume of fluid that
flows past a given cross sectional area per second. Therefore,
V = Aѵ
V = Volume Flow Rate
A = Cross Section Area
Ѵ = Velocity of Fluid
Standard SI Unit is m 3 /hr
Other Common Units :
1L/s = 10 3 cm 3 /s = 10 -3 m 3 /s
1gal/s = 3.788 L/s = 0.003788 m 3 /s
1cf/min = 4.719x10 -4 m 3 /s
7 September 23, 2004
Definition of Quantities to be Measured
Mass Flow Rate
The definition of mass flow rate is the number of kilograms of
mass flow that flows past a given cross sectional area per
second. Therefore,
m = ρV = ρAѵ
m = Mass Flow Rate
ρ = Specific Density
V = Volume Flow Rate
A = Cross Section Area
Ѵ = Velocity of Fluid
Standard SI Unit is kg/hr
8 September 23, 2004
Types of Measurement
Direct Rate Measurement
Required large device if the volume rates are high. And in case
a smaller device is used then the measured values will not be
accurate.
Fluctuations in the measuring values due to the opening/closing
of valves during start/stop of the measurements.
Devices that measure the volume/mass of the fluid and the timing
may not be concurrent.
9 September 23, 2004
Types of Measurement
Direct Rate Measurement
10 September 23, 2004
Type of Measurement
Indirect Rate Measurement
For many practical applications, indirect measuring techniques
are
employed using various kind of principles.
Here are some of the basic working principles:
Differential Pressure
Force on Bodies in the Flow
Heat Transfer
Corriolis Force
Magneto-Inductive
Frequency of Vortices
Ultrasonic
11 September 23, 2004
Type of Flowmeters
1. Correlation Method 13. Rotary Vane
2. Corriolis 14. Swirl
3. Elbow Tap “Elbow Meter” 15. Target
4. Electro-Magnetic 16. Thermal Dispersion
5. Flow Nozzles 17. Turbine
6. Flow Tube 18. Ultrasonic Doppler
7. Nutating Disk 19. Ultrasonic Transit Time
8. Orifices 20. Variable Area
9. Oval Gear 21. Venturi Tube
10. Pitot Tube 22. Vortex
11. Positive Mass 23. Weir & Flume
12. Reciprocating Piston
12 September 23, 2004
Type of Flowmeters
Industrial Flowmeter Usage
13 September 23, 2004
Type of Flowmeters
Orifice, Nozzle & Venturi “Differential Pressure”
Basic Equation v = Fluid Velocity
Q = Volume Flow Rate
A = Cross Sectional Area of Pipe
m = Mass Flow Rate
k = Constant
h = Differential Pressure
p = Density of Fluid
The (lateral) pressure exerted by an
incompressible fluid varies inversely
with the square of the speed of the
fluid.
14 September 23, 2004
Type of Flowmeters
Orifice, Nozzle & Venturi “Differential Pressure”
Basic Equation QA = Flow (m3/hr)
A) Liquid Volumetric QB = Flow (Nm3/hr) at 0 0C & 1.013 bara
QC = Flow (kg/hr)
S = Specific Gravity (Air = 1)
B) Gas Volumetric
D = Density at actual conditions (kg/m3)
A = Pipe Internal C.S.A (cm2)
Tf = Actual Temperature (0C)
Pf = Actual Pressure (bara)
C) Liquid/Gas Mass K = TORBAR Coefficient (See Table)
The orifice, nozzle and venturi flow
meters use the Bernoulli’s Equation
to calculate the fluid flow rate by
using the pressure difference
between an obstruction in the flow.
15 September 23, 2004
Type of Flowmeters
Bernoulli’s Equation
For Pitot Tube:
P + ½ ρ ѵ 2 + ρgh = Constant
If no change in the elevation, ρgh = 0 = z
And point 2 is stagnation point, i.e. ѵ2 = 0
P = Static Pressure
ρ = Density of Fluid
v = Velocity of Fluid
g = Gravitational Acceleration (9.81m/s2)
h = Height
16 September 23, 2004
Type of Flowmeters
Thermal Mass
Q = WCp (T 2 -T 1 ) and therefore
W = Q/Cp (T 2 -T 1 )
Q = Heat Transfer
W = Mass Flow Rate
Cp = Specific Heat of Fluid
T 1 = Temperature Upstream
T 2 = Temperature Downstream
17 September 23, 2004
Type of Flowmeters
Thermal Mass
18 September 23, 2004
Type of Flowmeters
Thermal Mass
19 September 23, 2004
Type of Flowmeters
Turbine
Working Principle
Reluctance
The coil is a permanent magnet and the turbine blades are made of a material attracted to
magnets. As each blade passes the coil, a voltage is generated in the coil. Each pulse
represents a discrete volume of liquid. The number of pulses per unit volume is called the
meter's K-factor.
Inductance
A permanent magnet is embedded in the rotor, or the blades of the rotor are made of
permanently magnetized material. As each blade passes the coil, it generates a voltage pulse.
In some designs, only one blade is magnetic and the pulse represents a complete revolution of
the rotor.
Capacitive
Capacitive sensors produce a sine wave by generating an RF signal that is amplitude-modulated
by the movement of the rotor blades.
Hall-Effect
Hall-effect transistors also can be used. These transistors change their state when they are in
the presence of a very low strength (on the order of 25 gauss) magnetic field.
20 September 23, 2004
Type of Flowmeters
Turbine
21 September 23, 2004
Type of Flowmeters
Turbine
22 September 23, 2004
Type of Flowmeters
Turbine
23 September 23, 2004
Type of Flowmeters
Electromagnetic
The operation of magnetic flow meters is based on Faraday's law of
electromagnetic induction. Magflow meters can detect the flow of conductive
fluids only. Early magflow meter designs required a minimum fluidic conductivity
of 1-5 microsiemens per centimeter for their operation. The newer designs have
reduced that requirement a hundredfold to between 0.05 and 0.1.
E = BDV/C
E = Induced Voltage
B = Magnetic Field Strength
D = Inner Diameter of Pipe
V = Average Velocity
C = Constant
24 September 23, 2004
Type of Flowmeters
Electromagnetic
The magnetic flow meter’s coil can be powered by either alternating or direct
current.
In AC excitation, line voltage is applied to the magnetic coils and as a result, the
flow signal (at constant flow) will also look like a sine wave. The amplitude of the
wave is proportional to velocity. Addition to the flow signal, noise voltages can be
induced in the electrode loop. Out-of-phase noise is easily filtered, but in-phase
noise requires that the flow be stopped (with the pipe full) and the transmitter
output set to zero. The main problem with ac magflow meter designs is that noise
can vary with process conditions and frequent re-zeroing is required to maintain
accuracy.
And as for DC excitation designs, a low frequency (7-30 Hz) dc pulse is used to
excite the magnetic coils. When the coils are pulsed on the transmitter reads both
the flow and noise signals. In between pulses, the transmitter sees only the noise
signal. Therefore, the noise can be continuously eliminated after each cycle.
25 September 23, 2004
Type of Flowmeters
Electromagnetic
Today, DC excitation is used in about 85% of installations while AC types
claim the other 15% when justified by the following conditions:
• When air is entrained in large quantities in the process stream.
• When the process is slurry and the solid particle sizes are not uniform.
• When the solid phase is not homogeneously mixed within the liquid.
• When the flow is pulsating at a frequency under 15 Hz.
26 September 23, 2004
Type of Flowmeters
Electromagnetic
E = Induced Voltage
B = Magnetic Field Strength
D = Inner Diameter of Pipe
V = Average Velocity
C = Constant
E = BDV/C
C is a constant to take care of the engineering proper units
27 September 23, 2004
Type of Flowmeters
Electromagnetic
28 September 23, 2004
Type of Flowmeters
Corriolis
The principle of angular momentum can be best described by Newton’s 2 nd Law of angular
motion and the definitions using these following notations:
Newton’s 2 nd Law of angular motion states that
γ = Iα and defines that H = I ω and since by definition I = mr 2
Then γ = mr 2 α and then H = mr 2 ω
Since α = ω/t then becomes γ = mr 2 * ω/t and solving mass flow rate, m/t we get
m/t = γ/r 2 ω also divide H = mr 2 ω by t then H/t = m/t * r 2 ω
H = Angular Momentum
I = Moment of Inertia
ω = Angular Velocity
Y = Torque
α = Angular Acceleration
r = Torque of Gyration
m = Mass
t = Time
29 September 23, 2004
Type of Flowmeters
Corriolis
30 September 23, 2004
Type of Flowmeters
Corriolis
31 September 23, 2004
Type of Flowmeters
Corriolis
32 September 23, 2004
Type of Flowmeters
Positive Displacement
Positive displacement meters provide high accuracy, ±0.1% of actual flow rate in
some cases and good repeatability as high as 0.05% of reading. Accuracy is not
affected by pulsating flow unless it entrains air or gas in the fluid. PD meters do not
require a power supply for their operation and do not require straight upstream and
downstream pipe runs for their installation. Typically, PD meters are available 1” up
to 12” in size and can operate with turndowns as high as 100:1, although ranges of
15:1 or lower are much more common. Slippage in the flowmeter is reduced and
metering accuracy is therefore increased as the viscosity of the process fluid
increases.
The process fluid must be clean. Particles greater than 100 microns in size must be
removed by filtering. PD meters operate with small clearances between their
precision-machined parts; wear rapidly destroys their accuracy. For this reason, PD
meters are generally not recommended for measuring slurries or abrasive fluids. In
clean fluid services, however, their precision and wide rangeability make them ideal
for custody transfer and batch charging. They are most widely used as household
water meters. Millions of such units are produced annually at a unit cost of less
than US$50. In industrial and petrochemical applications, PD meters are commonly
used for batch charging of both liquids and gases.
33 September 23, 2004
Type of Flowmeters
Positive Displacement
34 September 23, 2004
Type of Flowmeters
Positive Displacement
35 September 23, 2004
Type of Flowmeters
Vortex
Types of Working Principles
1. Vortex Shedding
2. Vortex Precession
3. Fluidic Oscillation (Coanda Effect)
36 September 23, 2004
Type of Flowmeters
Vortex
Vortex shedding frequency is directly proportional to the velocity of the fluid in the pipe and
therefore to volumetric flow rate. The shedding frequency is independent of fluid properties such
as density, viscosity, conductivity, etc., except that the flow must be turbulent for vortex shedding
to occur. The relationship between vortex frequency and fluid velocity is:
St = f (d/v)
Q = AV = (AfdB)/St
Q = fK
St = Strouhal Number
f = Vortex Shedding Frequency
d = Width of the Bluff Body
A = Cross Sectional Area
V = Average Fluid Velocity
B = Blockage Factor
K = Meter Coefficient
37 September 23, 2004
Type of Flowmeters
Vortex
The value of the Strouhal number is determined experimentally, and is generally
found to be constant over a wide range of Reynolds numbers. The Strouhal number
represents the ratio of the interval between vortex shedding (l) and bluff body width
(d), which is about six. The Strouhal number is a dimensionless calibration factor
used to characterize various bluff bodies. If their Strouhal number is the same, then
two different bluff bodies will perform and behave similarly.
38 September 23, 2004
Type of Flowmeters
Vortex Shedding
St = Strouhal Number
f = Vortex Shedding
Frequency
d = Width of the Bluff Body
A = Cross Sectional Area
V = Average Fluid Velocity
B = Blockage Factor
K = Meter Coefficient
Q = AV = (AfdB)/St
39 September 23, 2004
Type of Flowmeters
Vortex Shedding
40 September 23, 2004
Type of Flowmeters
Vortex Precession
Vortex Precession
41 September 23, 2004
Type of Flowmeters
Fluidic Oscillation (Coanda Effect)
1. Fluidic Oscillation (Coanda Effect)
42 September 23, 2004
Type of Flowmeters
Ultrasonic
Ultrasonic waves travel in the same manner as light or microwaves however being an
Elastic waves, they can propagates through any substance like solid, liquid and
gases. And by utilizing the properties of ultrasonic waves, clamp on flowmeters with
unique feature of being able to measure fluid flow in the pipe externally was
developed.
Generally, ultrasonic flowmeters works in 2 different kind of principles:
1) Doppler Effect Ultrasonic Flowmeter
The Doppler Effect Ultrasonic Flowmeter uses reflected ultrasonic
sound to measure the fluid velocity. By measuring the frequency shift
between the ultrasonic frequency source, the receiver and the fluid
carrier. In this the relative motion are measured. The resulting
frequency shift is named the ”Doppler Effect”.
2) Transit Time Difference Ultrasonic Flowmeter
With the Time of Flight Ultrasonic Flowmeter the time for the sound to
travel between a transmitter and a receiver is measured. This method
is not dependable on the particles in the fluid.
43 September 23, 2004
Type of Flowmeters Upstream Sensor
Ultrasonic
Kdt
Vf =
TL D θf Q
Cross Average Cf
Sectional Velocity
Area on C.S.A
Downstream
ҴD 2 1 D ΔT τ/2 τ/2 Sensor
Q = 4 x K x x
sin2θ (T 0 - Ҭ) 2 T1
f
T2
Average
Velocity
Q = Flow Rate on Propagation
D = Inner Pipe Diameter Path
K = Conversion Factor of Average Velocity
Θf = Incident angle into liquid
T1 & T2= Transit time
T0 = Transit time between sensors when flow is at rest ≒ (T 1+ T2 )/2
Ҭ = Transit time in pipe walls and sensors = ΔT = T 2 - T1
Note that ultrasonic waves are carried with the motion of fluid
44 September 23, 2004
Type of Flowmeters
Ultrasonic
45 September 23, 2004
Type of Flowmeters
Ultrasonic
46 September 23, 2004
Selection of Flowmeters
Ultrasonic Electromagnetic Differential Vortex
Pressure
Fluid
Gas X X
Measuring
Vapor X X
Media
Slurry X Ο X X
Control
Application Monitor
Supply X X X
Temperature -40 to 200 °C -20 to 120 °C -40 to 600 °C -10 to 200 °C
Operating Pressure - -1 to 2MPa -0.1 to 42MPa 5MPa
Condition
Pressure Loss None None Yes Yes
Rangeability Large Large Large Large
Bore ∅ 13 ~ 6,000mm 2.5 ~ 300mm 25 ~ 3,000mm 4 ~ 100mm
Installation Upstream/Downstrea 10D/5D 5D/2D 10D/5D 7D/3D
Condition m
Piping Works Not Required Required Required Required
Explosion Proof X X
Accuracy ± 0.5 % of Rate ± 0.5 % of Rate ± 2.0 % of FS ± 1.0 ~ 3. 0 % of Rate
Performance Velocity Range -32 to 32m/s 0 to 15m/s - 0.3 to 4m/s
47 September 23, 2004
Flow Measurement Information
Useful links:
a) http://www.iceweb.com.au/Technical/flow_measurements_info_notes.htm
b) http://www.engineeringtoolbox.com/49.html
c) http://www.engineeringtoolbox.com/49_530qframed.html
d) http://www.torbar.co.uk/calcdata.htm
e) http://thcentral.com/fluiddynamicscalcs.htm
48 September 23, 2004
Questions & Answers
49 September 23, 2004