Model: P15D5

Generator Specification
Performance Data
Service PRP (1) ESP (2)
Model P15D5
Power (kVA) 13 15
Engine brand Perkins
Power (kW) 10 12
Engine model 403A-15G1
Rated speed ( r.p.m) 1500
Speed control type Mechanical
Standard voltage (V) 400/230V
Phase 1
Rated at power factor(cos phi) 0.8
Control system Digital
Star ter motor voltage 12V
AU VE
RI
BURE

ISO 9001
TA S

BUREAU VERITAS
Certification
182 8
Frequency 50HZ
Engine speed (RPM) 1500
AGG Power gensets are compliant with ISO 9001 and CE standard, which include the
following directives: 100% standby power 4.1
·2006/42/EC Machinery safety. Fuel 3.7
100% prime power
·2006/95/EC Low voltage Consumption
·EN 60204-1: 2006+A1: 2009, EN ISO 12100: 2010, EN ISO 13849-1: 2008, EN 75% prime power 2.8
12601 : 2010 (L/H)
50% prime power 2
(1) PRP (Prime Power):
According to ISO8528-1, prime power is the maximum power available during a variable
Standard reference Conditions
power sequence, which may be run for an unlimited number of hours per year, between
Note: Standard reference condition 25℃ (77℉) air inlet temp, 100m(328ft) A.S.L 30%
stated maintenance intervals. The permissible average power output during at 24 hours
relative humidity. Fuel consumption dat with diesel fuel with specific gravity of 0.85 and
period shall not exceed 80% of the prime power. 10% overload available for governing
conforming to BS 2869: 1998, Class A2
purposes only.

(2) ESP (Standby Power):


L L
According to ISO 8528-1, It is defined as the maximum power available, under the
agreed operating conditions, for which the generating set is capable of delivering for up
to 500 hours of operation per year (of which no more than 300 hours for continuative
H H
use) with the maintenance intervals and procedures being carried out as prescribed by
W W
the manufacturers. No overload capability is available.

Dimension and Weight


Dimension Open Silent
Powers ESP PRP Standby
Length (L) 1450mm 1930mm
Voltage (V) KVA KW KVA KW Amps
Width (W) 550mm 800mm
415/240V 15 12 13 10 20.9
Height (H) 1190mm 1136mm
400/230V 15 12 13 6.4 21.7 Net Weight REQ 630KG
380/220V 15 12 13 6.4 22.8 Fuel Tank (L) 75 50
Note: This parameters allows for some acceptable deviations.

www.aggpower.co.uk
Engine Specification: 403A-15G1

Basic technical data Induction system

No. of cylinders 3 Clean filter 3.0kpa

Cylinder arrangement In-line Dir ty filter 6.4kpa

Cycle 4 stroke Air filter type Dry

Induction system Naturally aspirated

Compression ratio 23:1

Bore 77mm

Stroke 81mm Lubrication system


Displacement 1.1L Total lub capacity 4.9L
All ratings cer tified to within ± 3% Sump minimum 3.4L
Speed variation at constant load ±0. 25% Sump maximum TBD
Maximum engine operating angles

-front up, front down, right side

Cooling system or left side


35℃
Total coolant capacity Lubricating oil pressure

-with radiator 5.2L -Relief valve opens 262-359 KPA


-without radiator 1.9L - at maximum no-load speed TBD
Maximum top tank temp 112℃ Oil consumption at full load

Thermostat operation range 75-87℃ as a % of fuel consumption TBD


Radiator face area 0.147 m²
Rows and material 2 rows aluminium
Pressure cap setting Electrical system
90 kPa
Fan diameter Type Negative ground
320,0 mm
Drive ratio Alternator voltage 12 volts
1.285 : 1
Number of blades Alternator output 40 amps
7
Star ter motor voltage 12 volts

Star ter motor power 1.1KW

Fuel system

Injection system Indirect

Fuel injection pump Cassette type General installation Prime power

Combustion air flow 0.7 m³/min


Fuel atomiser Pintle nozzle
Exhaust gas temp 420°C
Nozzel opening pressure 14,7 MPa
Exhaust gas flow, wet 1.8 m³/min
Fuel lift pump type Mechanical
Engine coolant flow 27.3 I/min
- flow/hour 63 l/h
Cooling fan air flow 0.2KW
- pressure 10 kPa

Maximum suction head:

-1500 rev/min 3m

www.aggpower.co.uk
Alternator Specification
Emergency voltage curve

Sudden increase warp


Alternator Sudden voltage warp Sudden decrease warp
520
Number of phase 1

Power factor (Cos Phi) 0.8 464

+1%
Poles 4 408 +1%
380
380
-1%
Winding Connections (standard) Star-serie 352

Terminals 12 296

Insulation type H class 240


0 1 2 3 4 5 6 7 8 9 10 11 12
δu%: -18.18 1.95s
Winding Pitch 2/3 δu%: 8.89
Benchmark phase: A
Benchmark phase: A
Min. voltage: 310.9V Recovery time:
Recovery time: 0..12ss
Max. voltage: 413.8V

IP rating IP23

Excitation system Self-excited

Bearing Single bearing Emergency frequency curve


Coating Vacuum impregnation Sudden increase warp
Sudden voltage warp Sudden decrease warp
70
Voltage regulator A.V.R

Couping Flexible disc 62

54 +1%
50
-1%
+1%
50
-1%
46

38

30
0 1 2 3 4 5 6 7 8 9 10 11 12
δf%%: -10.64 Benchmark phase: A Min. frequency: 44.68Hz Recovery time: 1..95s
Three phase Reliable Single phase
δf%%: 7.74 Benchmark phase: A Max. frequency: 53.87Hz Recovery time: 0..54s

Options

Engine Alternator Generator Sets Fuel System

· Water Jacket · Winding Temp measuring · Tools with the machine · Low fuel level alarm
Pre-heater Instrument · Extended range fuel tank · Automatic fuel
· Fuel heater · Alternator Pre-heater · Bunded fuel tank feeding system
· PMG · Fuel T-valves
· Anti-damp and anti-corrosion
treatment
· Anti-condensation heater
· Winding and bearing RTD

Canopy Lub oil system Cooling System Control Panel

· Rental type · Oil Pre-heater · Front heat protection · Remote control panel
Canopy · Oil temp sensor · ATS
· Trailer · Synchronizing controller
· Adjustable ear th leakage
relay

www.aggpower.co.uk
Control Panel

Configuration Benefits

· Emergency stop button · Less wiring and components


· Integrated solution
· Protection MCB
· Less engineering and programming
· Battery charger · User friendly set-up and button layout
· Integrated aviation plug · Module can be configured to suit individual applications
· ATS connection · PC software for simplified configuration
· Digital control module · Wide range of communication capabilities

Operation conditions
Features
· Operation temp: -20 ˚C to + 70 ˚C
· Storage temp: -30 ˚C to + 80 ˚C
· Operating humidity: 95% w/o condensation
· Vibration: 5-25Hz, ±1.6 mm
5-1 00 Hz, a= 4g
· Shocks: a= 500m/s²

Options

· Ethernet interface (Remote monitoring and control)


· GSM modem/wireless internet (Remote monitoring and control)
· RS232-RS485 Dual por t interface
· Synchronizing control panel
· Distribution board with sockets kit and power busbar
· Battery trickle charge ammeter
· Ear th leakage protection
· Ear th fault protection
· Low fuel level alarm
· Low fuel level shutdown
· High fuel level alarm
· Fuel transfer system control
· Low coolant level shutdown
· High lube oil temp shutdown
· Overload via alarm switch on breaker
· Engine coolant heater controls
· Control panel heater
· S peed adjust switch
· Oil temp displayed on LCD screen
· Additional 8 inputs and outputs
Publication No. GYH0518N, ISSUE 1 @ AGG UK

AGG UK | AGG China | AGG USA | AGG UAE Distributed by

[email protected] | www.aggpower.co.uk

Follow us @facebook.com/aggpowergroup

Follow us @linkedin.com/company/agg-power

Follow us @ AGGPOWER

All information in the document is substantially correct a the time of printing


but may be subsequently altered by the company.

You might also like