SHEAR 

WALL DESIGN
Shear 
Axial Load Moment Force
Dl+LL= 600kN 30 30
Seismic Load= 84kN 3 12

Thickness of Wall= 200mm
Length of Wall= 5000mm
2
fck= 25 N/mm
fy= 500
P1= 581kN (From Cl. 9.4.3; IS 13920; Pg13)
P2= 821kN (From Table 18; IS 456; Pg 68)
Moment, Mu= 40kNm
Shear, Vu= 50kN
I= 2.0833E+12 mm4
2
A= 1000000 mm
3
Z= 833333333 mm
f c= P/A±M/z
2
fc.max= 0.87 N/mm FALSE
2
fc.min= 0.77 N/mm
fc.allow=0.2fck 5N/mm2 (From Cl. 9.4.1; IS 13920)

Adopt a bar bell type wall with two enlarged ends of size 300mm x 300mm


Central Part= 4400mm   
I= 2.4151E+12
2
Total Area (A)= 1060000 mm
Z= 966053333
2
fc.max= 0.82 N/mm
2
< fc.allow OKEY
fc.min= 0.73 N/mm

Depth of the section resisting shear= 4700mm
2
Shear Stress, Tv=Vu/bd 0.05 N/mm (From Cl. 9.2.1. IS 13920)
2
Limiting Shear Stress= =0.25*√fck 1.25 N/mm (From Cl. 9.1.5)

Min Steel= 0.0025
2
Ag= 500 mm (Cl. 9.1.4; IS 13920)
2
Steel in one layer= 250 mm
Assuming # 10mm  Ø bars spacing @  314 mm C/C
Max Spacing= Min of (L/5 or 3b or 450mm) ( From Cl 9.1.7; IS 13920)
450
Provide  10mm bars at 250mm c/c on both faces horizontally and vertically
2
Ast Provided= 628 mm
Pt= 0.314%

Shear taken by steel
Pt.provided= 0.314%
2
Tc = 0.37 N/mm (From Table 19, IS 456)
3
Tc.max= 3.5 N/mm (From Table 20, IS 456)
Vus= (Tv‐Tc)bd= ‐63.38 kN
Vus= 0.87fyAscd/Sv (From Cl. 40.4a, IS456)
Asv/Sv= ‐0.146

Provided Asv/Sv per meter from min. steel
Asv/Sv= 0.628 OKEY
Minimum Steel provided satisfies shear requirements.
Load on web Pw= Load*Web Area/Total Area= 482.174 kN
From Annex A" IS 13920
ʎ= Pu/fcktwlw= 0.0219
Ø=0.87fyρ/fck= 0.051
β=0.87fy/0.0035Es= 0.621
Xu/lw=(Ø+ʎ)/(2Ø+0. 0.157
Xu*/lw= 0.0035/(0.0035+(0.87fy/ 0.62

Muv=0.026*fcktwlw2= 2516.8 kNm

Force on boundary elements (BE)
Moments on BE= ‐2477kNm
Equivalent Axial Load= ‐527.1kN

Compression load from vertical loads (Max downward force)
Load on boundary element = Load*Area of BE/Total area= 69.7kN
Tension load from vertical loads (Min. downward force)
Load on boundary element = Load*Area of BE/Total area= 49.3kN
Boundary elements are designed as columns with lateral ties confinement, anchorage and splice length
Design of Boundary Elements
Design the BE as a short column
Pu=0.4fckAc+0.67fyAsc (From Cl. 39.3, IS 456)
Assuming pc= 0.80% min. pc
2
Asc= 720 mm
Pu= 1141.2kN SAFE
Same steel will be provided on both the boundary elements.
Provide 8Nos 12mm  Ø bars
2
Area= 905 mm OKEY
Special Confining Reinforcement

Ash=0.18Sh(fck/fy)(Ag/Ak)‐1) (From Cl. 7.4.8. IS 13920:1993)
h= 220mm (taking cover= 40mm
Introducing cross tie as h exceeds,  300mm
h= 110mm
s=0.25*b or 100mm= 75mm
2
Ak= 48400 mm
2
Ash= 63.82 mm
Provide  8mm Ø bars @ 100mm c/c as special confining R/f.