Fire Pump System Test Report
Fire Pump System Test Report
Others
Name: ____________________________________
Signature: _________________________________
Date: _____________________________________
Division Head / Authorized Person
PLAN REVIEW CHECKLIST
GENERAL
Building type :
New Existing Renovation
Pump make : Peerless / WEG__________ Drive : Electric Diesel
Model : 5AEF15 / Pump rating : __1000___ GPM _217.6 PSI
Z250300P3LFP051419____ @
Rated speed : __2950___ RPM
Yes No Suction piping should be proper size (as per NFPA) not less than pump suction
nozzle size.
Yes No Suction piping should be galvanized or painted inside for corrosion protection.
Yes No Isolation valve (OS&Y) in suction piping should be proper location.
Yes No In suction piping, elbow are in the proper orientation or more then straight 10 pipe
diameters away from the suction flange of pump.
Yes No In suction piping eccentric reducer (if needed) installed correctly. (flat side up)
Yes No Suction and discharge pressure gauge.
Yes No Circulation relief valve. (electric pump)
Yes No Discharge piping should be proper size. (as per NFPA)
Yes No Check valve in discharge piping.
Yes No Isolation valve in discharge piping.
Yes No Separate and dedicated sensing line for electrical, diesel and jockey pump.
Yes No The pressure-sensing line connection for each pump is made between that pump’s
discharge non-return valve and discharge control valve.
Yes No The pressure sensing line has ½” none return valve with 2.4 mm hole in the
clapper and will be connection in opposite direction.
Yes No All isolation valves supervised in the open position.
Yes No Test header and flow meter valves supervised in the closed position.
Yes No Diesel pump pressure relief valve (if provided) without isolation valve.
Yes No In diesel engine, two storage batteries provided with charger.
Yes No Cooling system from heat exchanger or cooling water supply pipe line from pump
discharge is installed (engine).
Yes No Cooling line return line one size higher than inlet and this return water should be
visible to monitor.
Yes No Diesel tank located above ground. (outlet of diesel tank should be above or same
level of diesel engine inlet)
Yes No Water supply to the fire pump adequate to meet fire requirements and Local Civil
Defense.
Yes No Alignment of coupling must be checked.
Yes No The surface of the foundation must be completely horizontal and perfectly flat.
Yes No The foundation should be 200 mm larger than the base frame on all four sides.
Yes No Flow meter upstream and downstream consider as per manufacturer’s
recommendation.
Approval
Notes:
_______________________________________________________________________________
_______________________________________________________________________________
____________________________________________________________________________
CONTROLLER
Manufacturer : Tornatech Model : JP3
JOCKEY PUMP
Model : CR5-29 Serial Number : 0002
Manufacturer : Grundfos
Note: All questions are to be answered Yes, No or Not Applicable, All “No” answers are to be explained in
the comments portion at this form.
423/423 232/246
Rated 100% 2979 1000 426 248 +4 217.6 +2 236
150% of
150% 3000 1500 70 90 +4 177 +1 195
rated flow
F. For electric motors operating at rated voltage and frequency, is the ampere demand less than or equal
to the product of the full load ampere rating times the allowable service factor as the stamped on the
motor nameplate?
Yes □ No □ N/A
G. For electric motors operating under varying voltage:
1. Was the product of the actual voltage and current demand less than or equal to the product of the
rated Full load current times the rated voltage times the allowable service factor.
Yes □ No □ N/A
2. Did the voltage stay within the range of 95 to 110% of the rated voltage during the test?
Yes □ No □ N/A
H. Did engine-driven units show no signs of overload or stress?
Yes □ No □ N/A
I. Was the governor set to properly regulate the engine speed at rated pump speed?
Yes □ No □ N/A
J. Did the gear drive assembly operate without excessive objectionable noise, vibration or heating?
Yes □ No □ N/A
K. Was the fire pump unit started and brought up to rated speed without interruption under the Conditions
of a discharge equal to peak load?
Yes □ No □ N/A
L. Did the fire pump perform equal to the manufacturer’s characteristics curve within the accuracy limits
of the test equipment? Yes □ No □ N/A
M. Electric motor pumps passed phase reversal test on normal and alternate (If provided) power?
□ Yes □ No N/A
D. Was the pump run for at least 5 minutes during each of the operations in parts A, B and C above?
Yes □ No □ N/A
Note: An engine driver is not required to run for 5 minutes at full speed between successive
Starts until the cumulative cranking time of successive starts reaches 45 seconds.
E. Were all over current protective devices (including the controller circuit-breaker) selected, Sized and
set in accordance with NFPA 20? Yes □ No □ N/A
F. Electric driven Pump Controllers
1. Were all over current protective devices (including the controller circuit breaker) selected, sized
and set in accordance with NFPA 20? Yes □ No □ N/A
2. Was the pump started at least once from each power service and run for at least 5 minutes?
Yes □ No □ N/A
3. Upon simulation of a power failure, while the pump is operating at peak load, did the Transfer
switch transfer from the normal to the emergency source without opening overcurrent protection
devices on either line?
□ Yes □ No N/A
4. When normal power was restored, did transfer from emergency to normal power occur without
overcurrent protection devices opening on either line?
□ Yes □ No N/A
5. Were at least half of the automatic and manual starts required by parts A and C performed with the
pump connected to the alternate source?
□ Yes □ No N/A
G. Were all signal conditions simulated demonstrating satisfactorily operation/
Yes □ No □ N/A
H. Was the pump run at least 1 hour total during all of the above tests?
Yes □ No □ N/A
I. For engine with ECM fuel management:
Tester: ________
Company: _________
I state that the above information on this form is correct at the time and place of my test, and
that all equipment tested was left in operational condition upon completion of this test except
as noted in the comments section below.
MAIN MEP.
CLIENT CONSULTANT
CONTRACTOR CONTRACTOR
SIGNATURE
NAME
DATE
CLIENT: _____________
CONSULTANT: __________________________
I. FLOW METER
MODEL : 6”-1000-G
FLOW RANGE : 0-2000 GPM
METER SIZE : 6”
SERIAL NUMBER : 04190688
BRAND : GLOBAL VISION
JENSEN HUGHES (shafeeq.alam)
Deficiency: It seems manufacturer's
certified shop curve is plotted on a
Electric Motor Driven Fire Pump
new graph paper.
Serial Number: 50007677
Resolution: Attach manufacturer's
325
certified shop curve for reference.
300
257 PSI (180.74m) @ 100% Flow Actual Curve
275 236 PSI (165.97m) @ 100% Flow
250
185 PSI (130.10m) @ 100% Flow
225
255 PSI (179.33m) @ 0% Flow
200
175 217.6 PSI (153.03m) @ 100% Flow
150
Design Curve 183 PSI (128.70m) @ 150% Flow
125
JENSEN HUGHES (shafeeq.alam)
100 JENSEN HUGHES (shafeeq.alam) Deficiency: Pressure obtained at
75 Discrepancy: Pump head shall be plotted instead of 100% flow is less than 95% of the
pump discharge pressure. rated pressure.
50
25 Resolution: Pump head (discharge pressure minus Resolution: It is not acceptable.
0 suction pressure)
0 150 300 450 600 750 900 1050 1200 1350 1500 1650 1800 1950 2100
Code Reference:
325
300
264 PSI (185.66m) @ 0% Flow
275 Actual Curve
225 PSI (158.23m) @ 100% Flow
250
195 PSI (137.13m) @ 150% Flow
225
255 PSI (179.33m) @ 0% Flow
200
175 217.6 PSI (153.03m) @ 100% Flow
150
Design Curve
125 177 PSI (124.48m) @ 150% Flow
100
75
50
25
0
0 150 300 450 600 750 900 1050 1200 1350 1500 1650 1800 1950 2100
©2005 National Fire Sprinkler Association, P.O. Box 1000, Patterson, NY 12563 (845) 878-4200 (used with permission) Form 20-A Sheet 2 of 2
FIGURE A.14.2.7.4 Centrifugal Fire Pump Acceptance Test Form. (Courtesy of National
Fire Sprinkler Association, Inc.)
Copyright NFPA
PUMP ALIGNMENT REPORT
PROJECT NAME: WOMEN'S HOSPITAL SAFETY IMPROVEMENTS
CLIENT NAME: HYUNDAI ENGINEERING AND CONSTRUCTION CO LTD
CAPACITY: 1000 GPM @ 217.6 PSI
EQUIPMENT DATA
PUMPS
TYPE HORIZONTAL SPLIT CASE CENTRIFUGAL PUMP
MODEL 5AEF15
SERIAL NO 50007677
MANUFACTURER PEERLESS PUMP
DRIVER
TYPE INDUCTION MOTOR
MODEL Z250300P3LFP051419
SERIAL NO 1049410538
MANUFACTURER WEG
FIELD DATA
RADIAL PUMP SIDE DRIVER SIDE
VERTICAL 00 0.00 mm 0.00 mm
VERTICAL 1800 +0.01 mm +0.16 mm
HORIZONDAL 900 +0.20 mm +0.01 mm
HORIZONDAL 2700 -0.13 mm +0.15 mm
MAIN
NAFFCO CONSULTANT CLIENT
CONTRACTOR
SIGANTURE
NAME: ROLLEN TEAM
DATE: 05-10-2020