v90 Operating Instructions
v90 Operating Instructions
Preface
___________________
Safety instructions 1
___________________ 2
SINAMICS/SIMOTICS General information
___________________
Mounting 3
SINAMICS V90, SIMOTICS S-1FL6
___________________
Connecting 4
___________________
Commissioning 5
Operating Instructions
___________________
Basic operator panel (BOP) 6
7
___________________
Control functions
___________________
Safety Integrated function 8
9
___________________
Tuning
10
___________________
Parameters
11
___________________
Diagnostics
A
___________________
Appendix
09/2015
A5E36037884
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Documentation components
Document Content
Operating Instructions (this manual)
Getting Started Describes how to install, connect, operate, and perform
basic commissioning of the SINAMICS V90 servo system.
SIMOTICS S-1FL6 Servo Motors Installation Guide Describes how to install the SMOTICS S-1FL6 servo motor
and relevant safety notices.
Target group
This manual provides information about the SINAMICS V90 servo system for planners,
operators, mechanical engineers, electrical engineers, commissioning engineers, and
service engineers.
Technical support
Country Hotline
China +86 400 810 4288
Germany +49 911 895 7222
Italy +39 (02) 24362000
India +91 22 2760 0150
Turkey +90 (216) 4440747
Further service contact information:
Support contacts (http://support.automation.siemens.com/WW/view/en/16604999)
Preface ................................................................................................................................................... 3
1 Safety instructions ................................................................................................................................. 11
1.1 Fundamental safety instructions .............................................................................................11
1.1.1 General safety instructions .....................................................................................................11
1.1.2 Handling electrostatic sensitive devices (ESD) ......................................................................16
1.1.3 Industrial security ....................................................................................................................17
1.1.4 Residual risks of power drive systems....................................................................................17
1.1.5 Residual risks during the operation of electric motors ............................................................19
1.2 Additional safety instructions ..................................................................................................20
2 General information .............................................................................................................................. 27
2.1 Deliverables ............................................................................................................................27
2.1.1 Drive components ...................................................................................................................27
2.1.2 Motor components ..................................................................................................................30
2.2 Device combination.................................................................................................................33
2.3 Product overview ....................................................................................................................35
2.4 System configuration ..............................................................................................................38
2.5 Accessories .............................................................................................................................42
2.6 Function list .............................................................................................................................52
2.7 Technical data .........................................................................................................................54
2.7.1 Technical data - servo drives ..................................................................................................54
2.7.2 Technical data - servo motors ................................................................................................58
2.7.3 Technical data - cables ...........................................................................................................66
3 Mounting ............................................................................................................................................... 67
3.1 Mounting the drive ..................................................................................................................67
3.1.1 Mounting orientation and clearance........................................................................................67
3.1.2 Drill patterns and outline dimensions ......................................................................................68
3.1.3 Mounting the drive ..................................................................................................................72
3.2 Mounting the motor .................................................................................................................72
3.2.1 Mounting orientation and dimensions .....................................................................................72
3.2.2 Mounting the motor .................................................................................................................78
4 Connecting ........................................................................................................................................... 81
4.1 System connection..................................................................................................................81
4.2 Main circuit wirings ..................................................................................................................86
4.2.1 Line supply - L1, L2, L3...........................................................................................................86
4.2.2 Motor power - U, V, W ............................................................................................................87
4.3 Control/Status interface ..........................................................................................................90
4.3.1 Digital inputs/outputs (DIs/DOs) .............................................................................................91
7.6.2.1 Torque control with external analog torque setpoint ............................................................ 208
7.6.2.2 Torque control with fixed torque setpoint ............................................................................. 209
7.6.3 Direction and stop ................................................................................................................ 209
7.6.4 Speed limit ........................................................................................................................... 209
7.7 Communicating with the PLC............................................................................................... 210
7.7.1 USS communication ............................................................................................................ 210
7.7.2 Modbus communication ....................................................................................................... 212
7.8 Absolute position system ..................................................................................................... 224
7.8.1 Transmitting sequence for the absolute position data ......................................................... 225
8 Safety Integrated function ....................................................................................................................227
8.1 Standards and regulations ................................................................................................... 227
8.1.1 General information ............................................................................................................. 227
8.1.1.1 Aims ..................................................................................................................................... 227
8.1.1.2 Functional safety .................................................................................................................. 228
8.1.2 Safety of machinery in Europe ............................................................................................. 228
8.1.2.1 Machinery Directive ............................................................................................................. 228
8.1.2.2 Harmonized European Standards........................................................................................ 229
8.1.2.3 Standards for implementing safety-related controllers ........................................................ 230
8.1.2.4 DIN EN ISO 13849-1 (replaces EN 954-1) .......................................................................... 231
8.1.2.5 EN 62061 ............................................................................................................................. 232
8.1.2.6 Series of standards EN 61508 (VDE 0803) ......................................................................... 234
8.1.2.7 Risk analysis/assessment .................................................................................................... 234
8.1.2.8 Risk reduction ...................................................................................................................... 236
8.1.2.9 Residual risk......................................................................................................................... 236
8.1.3 Machine safety in the USA ................................................................................................... 236
8.1.3.1 Minimum requirements of the OSHA ................................................................................... 236
8.1.3.2 NRTL listing.......................................................................................................................... 237
8.1.3.3 NFPA 79 ............................................................................................................................... 237
8.1.3.4 ANSI B11 ............................................................................................................................. 238
8.1.4 Machine safety in Japan ...................................................................................................... 239
8.1.5 Equipment regulations ......................................................................................................... 239
8.2 General information about SINAMICS Safety Integrated .................................................... 240
8.3 System features ................................................................................................................... 240
8.3.1 STO functional safety data ................................................................................................... 240
8.3.2 Certification .......................................................................................................................... 240
8.3.3 Safety instructions ................................................................................................................ 241
8.3.4 Probability of failure of the safety function ........................................................................... 242
8.3.5 Response time ..................................................................................................................... 243
8.3.6 Residual risk......................................................................................................................... 243
8.4 Safety Integrated basic functions ......................................................................................... 243
8.4.1 Safe Torque Off (STO) ......................................................................................................... 243
8.4.2 Forced dormant error detection ........................................................................................... 245
9 Tuning .................................................................................................................................................247
9.1 Controller overview .............................................................................................................. 247
9.2 Tuning mode ........................................................................................................................ 249
9.3 One-button auto tuning ........................................................................................................ 250
DANGER
Danger to life due to live parts and other energy sources
Death or serious injury can result when live parts are touched.
• Only work on electrical devices when you are qualified for this job.
• Always observe the country-specific safety rules.
Generally, six steps apply when establishing safety:
1. Prepare for shutdown and notify all those who will be affected by the procedure.
2. Disconnect the machine from the supply.
– Switch off the machine.
– Wait until the discharge time specified on the warning labels has elapsed.
– Check that it really is in a no-voltage condition, from phase conductor to phase
conductor and phase conductor to protective conductor.
– Check whether the existing auxiliary supply circuits are de-energized.
– Ensure that the motors cannot move.
3. Identify all other dangerous energy sources, e.g. compressed air, hydraulic systems, or
water.
4. Isolate or neutralize all hazardous energy sources by closing switches, grounding or
short-circuiting or closing valves, for example.
5. Secure the energy sources against switching on again.
6. Ensure that the correct machine is completely interlocked.
After you have completed the work, restore the operational readiness in the inverse
sequence.
WARNING
Danger to life through a hazardous voltage when connecting an unsuitable power supply
Touching live components can result in death or severe injury.
• Only use power supplies that provide SELV (Safety Extra Low Voltage) or PELV-
(Protective Extra Low Voltage) output voltages for all connections and terminals of the
electronics modules.
WARNING
Danger to life when live parts are touched on damaged motors/devices
Improper handling of motors/devices can damage them.
For damaged motors/devices, hazardous voltages can be present at the enclosure or at
exposed components.
• Ensure compliance with the limit values specified in the technical data during transport,
storage and operation.
• Do not use any damaged motors/devices.
WARNING
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
• As a minimum, connect cable shields and the cores of cables that are not used at one
end at the grounded housing potential.
WARNING
Danger to life due to electric shock when not grounded
For missing or incorrectly implemented protective conductor connection for devices with
protection class I, high voltages can be present at open, exposed parts, which when
touched, can result in death or severe injury.
• Ground the device in compliance with the applicable regulations.
WARNING
Danger to life due to electric shock when opening plug connections in operation
When opening plug connections in operation, arcs can result in severe injury or death.
• Only open plug connections when the equipment is in a no-voltage state, unless it has
been explicitly stated that they can be opened in operation.
WARNING
Danger to life due to fire spreading if housing is inadequate
Fire and smoke development can cause severe personal injury or material damage.
• Install devices without a protective housing in a metal control cabinet (or protect the
device by another equivalent measure) in such a way that contact with fire is prevented.
• Ensure that smoke can only escape via controlled and monitored paths.
WARNING
Danger to life through unexpected movement of machines when using mobile wireless
devices or mobile phones
Using mobile wireless devices or mobile phones with a transmit power > 1 W closer than
approx. 2 m to the components may cause the devices to malfunction, influence the
functional safety of machines therefore putting people at risk or causing material damage.
• Switch the wireless devices or mobile phones off in the immediate vicinity of the
components.
WARNING
Danger to life due to the motor catching fire in the event of insulation overload
There is higher stress on the motor insulation through a ground fault in an IT system. If the
insulation fails, it is possible that death or severe injury can occur as a result of smoke and
fire.
• Use a monitoring device that signals an insulation fault.
• Correct the fault as quickly as possible so the motor insulation is not overloaded.
WARNING
Danger to life due to fire if overheating occurs because of insufficient ventilation clearances
Inadequate ventilation clearances can cause overheating of components with subsequent
fire and smoke. This can cause severe injury or even death. This can also result in
increased downtime and reduced service lives for devices/systems.
• Ensure compliance with the specified minimum clearance as ventilation clearance for
the respective component.
WARNING
Danger of an accident occurring due to missing or illegible warning labels
Missing or illegible warning labels can result in accidents involving death or serious injury.
• Check that the warning labels are complete based on the documentation.
• Attach any missing warning labels to the components, in the national language if
necessary.
• Replace illegible warning labels.
NOTICE
Device damage caused by incorrect voltage/insulation tests
Incorrect voltage/insulation tests can damage the device.
• Before carrying out a voltage/insulation check of the system/machine, disconnect the
devices as all converters and motors have been subject to a high voltage test by the
manufacturer, and therefore it is not necessary to perform an additional test within the
system/machine.
WARNING
Danger to life when safety functions are inactive
Safety functions that are inactive or that have not been adjusted accordingly can cause
operational faults on machines that could lead to serious injury or death.
• Observe the information in the appropriate product documentation before
commissioning.
• Carry out a safety inspection for functions relevant to safety on the entire system,
including all safety-related components.
• Ensure that the safety functions used in your drives and automation tasks are adjusted
and activated through appropriate parameterizing.
• Perform a function test.
• Only put your plant into live operation once you have guaranteed that the functions
relevant to safety are running correctly.
Note
Important safety notices for Safety Integrated functions
If you want to use Safety Integrated functions, you must observe the safety notices in the
Safety Integrated manuals.
WARNING
Danger to life or malfunctions of the machine as a result of incorrect or changed
parameterization
As a result of incorrect or changed parameterization, machines can malfunction, which in
turn can lead to injuries or death.
• Protect the parameterization (parameter assignments) against unauthorized access.
• Respond to possible malfunctions by applying suitable measures (e.g. EMERGENCY
STOP or EMERGENCY OFF).
WARNING
Danger to life from permanent magnet fields
Even when switched off, electric motors with permanent magnets represent a potential risk
for persons with heart pacemakers or implants if they are close to converters/motors.
• If you are such a person (with heart pacemaker or implant) then keep a minimum
distance of 2 m.
• When transporting or storing permanent magnet motors always use the original packing
materials with the warning labels attached.
• Clearly mark the storage locations with the appropriate warning labels.
• IATA regulations must be observed when transported by air.
WARNING
Injury caused by moving parts or those that are flung out
Touching moving motor parts or drive output elements and loose motor parts that are flung
out (e.g. feather keys) in operation can result in severe injury or death.
• Remove any loose parts or secure them so that they cannot be flung out.
• Do not touch any moving parts.
• Safeguard all moving parts using the appropriate safety guards.
WARNING
Danger to life due to fire if overheating occurs because of insufficient cooling
Inadequate cooling can cause overheating resulting in death or severe injury as a result of
smoke and fire. This can also result in increased failures and reduced service lives of
motors.
• Comply with the specified coolant requirements for the motor.
WARNING
Danger to life due to fire as a result of overheating caused by incorrect operation
When incorrectly operated and in the case of a fault, the motor can overheat resulting in fire
and smoke. This can result in severe injury or death. Further, excessively high
temperatures destroy motor components and result in increased failures as well as shorter
service lives of motors.
• Operate the motor according to the relevant specifications.
• Only operate the motors in conjunction with effective temperature monitoring.
• Immediately switch off the motor if excessively high temperatures occur.
CAUTION
Risk of injury due to touching hot surfaces
In operation, the motor can reach high temperatures, which can cause burns if touched.
• Mount the motor so that it is not accessible in operation.
When maintenance is required
• allow the motor to cool down before starting any work.
• Use the appropriate personnel protection equipment, e.g. gloves.
WARNING
Danger to life from electromagnetic fields
Electromagnetic fields (EMF) are generated by the operation of electrical power equipment
such as transformers, converters or motors.
People with pacemakers or implants are at a special risk in the immediate vicinity of these
devices/systems.
• Ensure that the persons involved are the necessary distance away (minimum 2 m).
NOTICE
Damage through electric fields or electrostatic discharge
Electric fields or electrostatic discharge can cause malfunctions through damaged
individual components, integrated circuits, modules or devices.
• Only pack, store, transport and send electronic components, modules or devices in their
original packaging or in other suitable materials, e.g conductive foam rubber of
aluminum foil.
• Only touch components, modules and devices when you are grounded by one of the
following methods:
– Wearing an ESD wrist strap
– Wearing ESD shoes or ESD grounding straps in ESD areas with conductive flooring
• Only place electronic components, modules or devices on conductive surfaces (table
with ESD surface, conductive ESD foam, ESD packaging, ESD transport container).
Note
Industrial security
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, Siemens’
products and solutions undergo continuous development. Siemens recommends strongly
that you regularly check for product updates.
For the secure operation of Siemens products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered. For more information about industrial security, visit this address
(http://www.siemens.com/industrialsecurity).
To stay informed about product updates as they occur, sign up for a product-specific
newsletter. For more information, visit this address (http://support.automation.siemens.com).
WARNING
Danger as a result of unsafe operating states resulting from software manipulation
Software manipulation (e.g. by viruses, Trojan horses, malware, worms) can cause unsafe
operating states to develop in your installation which can result in death, severe injuries
and/or material damage.
• Keep the software up to date.
You will find relevant information and newsletters at this address
(http://support.automation.siemens.com).
• Incorporate the automation and drive components into a holistic, state-of-the-art
industrial security concept for the installation or machine.
You will find further information at this address
(http://www.siemens.com/industrialsecurity).
• Make sure that you include all installed products into the holistic industrial security
concept.
These components may only be handled by qualified and trained technical personnel who
are knowledgeable and observe all of the safety instructions on the components and in the
associated technical user documentation.
When assessing the machine's risk in accordance with the respective local regulations (e.g.,
EC Machinery Directive), the machine manufacturer must take into account the following
residual risks emanating from the control and drive components of a drive system:
1. Unintentional movements of driven machine components during commissioning,
operation, maintenance, and repairs caused by, for example,
– Hardware and/or software errors in the sensors, control system, actuators, and cables
and connections
– Response times of the control system and of the drive
– Operation and/or environmental conditions outside the specification
– Condensation/conductive contamination
– Parameterization, programming, cabling, and installation errors
– Use of wireless devices/mobile phones in the immediate vicinity of the control system
– External influences/damage
2. In the event of a fault, exceptionally high temperatures, including an open fire, as well as
emissions of light, noise, particles, gases, etc. can occur inside and outside the inverter,
e.g.:
– Component failure
– Software errors
– Operation and/or environmental conditions outside the specification
– External influences/damage
Inverters of the Open Type/IP20 degree of protection must be installed in a metal control
cabinet (or protected by another equivalent measure) such that contact with fire inside
and outside the inverter is not possible.
3. Hazardous shock voltages caused by, for example,
– Component failure
– Influence during electrostatic charging
– Induction of voltages in moving motors
– Operation and/or environmental conditions outside the specification
– Condensation/conductive contamination
– External influences/damage
4. Electrical, magnetic and electromagnetic fields generated in operation that can pose a
risk to people with a pacemaker, implants or metal replacement joints, etc., if they are too
close
5. Release of environmental pollutants or emissions as a result of improper operation of the
system and/or failure to dispose of components safely and correctly
Note
The components must be protected against conductive contamination (e.g. by installing them
in a control cabinet with degree of protection IP54 according to IEC 60529 or NEMA 12).
Assuming that conductive contamination at the installation site can definitely be excluded, a
lower degree of cabinet protection may be permitted.
For more information about residual risks of the components in a drive system, see the
relevant sections in the technical user documentation.
Delivery check
Note
Intact deliverables
Deliverables received must be intact. It's not permissible to put a damaged unit into use.
NOTICE
Property loss
Notify Siemens service personnel immediately of any damage discovered after delivery. If
the equipment is put into storage, keep it in a dry, dust-free, and low-vibration environment.
The storage temperature ranges from -40 °C to +70 °C.
Otherwise you will suffer property loss.
Mechanical installation
WARNING
Death or severe personal injury from harsh installation environment
A harsh installation environment will jeopardize personal safety and equipment. Therefore,
• Do not install the drive and the motor in an area subject to inflammables or
combustibles, water or corrosion hazards.
• Do not install the drive and the motor in an area where it is likely to be exposed to
constant vibrations or physical shocks.
• Do not keep the drive exposed to strong electro-magnetic interference.
• Make sure that no foreign body (e.g., chips of wood or metal, dust, paper, etc.) can be
seen inside the drive or on the heat sink of the drive.
• Make sure that the drive is installed in an electrical cabinet with an adequate degree of
protection.
Note
Mounting clearance
To guarantee good heat dissipation and ease of cabling, keep sufficient clearance between
drives, one drive and another device/inner wall of the cabinet.
Note
Screw tightening
Make sure you fix the screw to the terminal door of the drive after you have completed the
installation work.
Electrical installation
DANGER
Death or severe personal injury from electrical shock
The earth leakage current for the drive can be greater than AC 3.5 mA, which may cause
death or severe personal injury due to electrical shock.
A fixed earth connection is required to eliminate the dangerous leakage current. In addition,
the minimum size of the protective earth conductor shall comply with the local safety
regulations for high leakage current equipment.
DANGER
Danger to life when PE connectors are touched
When the equipment is working, hazardous touch current can be present at the PE
connectors; if touched, this can result in death or severe personal injury.
• Do not touch the PE connector during operation or within a certain period since power
disconnection.
WARNING
Personal injury and damage to property from improper connections
Improper connections have high risks of electrical shock and short circuit, which will
jeopardize personal safety and equipment.
• The drive must be directly connected with the motor. It is not permissible to connect a
capacitor, inductor or filter between them.
• Make sure that all connections are correct and reliable, the drive and the motor are well
grounded.
• The line supply voltage must be within the allowable range (refer to the drive rating
plate). Never connect the line supply cable to the motor terminals U, V, W or connect
the motor power cable to the line input terminals L1, L2, L3.
• Never wire up the U, V, W terminals in an interchanged phase sequence.
• If the CE marking for cables is mandatory in some cases, the motor power cable, line
supply cable and brake cable used must all be shielded cables.
• For terminal box connection, make sure that the clearances in air between non-insulated
live parts are at least 5.5 mm.
• Route signal cables and power cables separately in different cable conduits. The signal
cables shall be at least 10 cm away from the power cables.
• Cables connected may not come into contact with rotating mechanical parts.
CAUTION
Personal injury and damage to property from inadequate protection
Inadequate protection may cause minor personal injury or damage to property.
• The drive must have been disconnected from the power supply for at least five minutes
before you perform any wiring to it.
• Check that the equipment is dead!
• Make sure that the drive and the motor are properly grounded.
• Route a second PE conductor with the cross section of the supply system lead in
parallel to the protective earth via separate terminals or use a copper protective earth
conductor with a cross section of 10 mm2.
• Terminals for equipotential bondings that exist in addition to terminals for PE conductors
must not be used for looping-through the PE conductors.
• To ensure protective separation, an isolating transformer must be used for the
200 VAC/380 VAC line supply system.
NOTICE
Damage to property from incorrect input voltage
Incorrect input voltage will cause severe damage to the drive.
It is recommended that the actual input voltage should not be greater than 110% of the
rated voltage or smaller than 75%.
Note
STO wiring
The safe torque off (STO) function can stop a motor using safety relays without involving any
upper level control. It is disabled in the factory configuration by short-circuiting the STO
terminals. The safety function of the servo drive is SIL 2 (EN61800-5-2).
Connect the STO terminals as the actual requirements.
Commissioning/Operation
CAUTION
Burns from hot surface
The operating temperature of drive base-plate and heat sink is higher than 65 °C, and the
surface temperature of the motor may reach up to 80 °C. The hot surface may burn your
hands.
Do not touch the motor or the heat sink of the drive during operation or within a certain
period since power disconnection.
NOTICE
Shortening the service life of motor brake
The motor brake is used for holding purpose only. Frequent emergency stops with the
motor brake will shorten its service life.
Unless absolutely necessary, do not apply the motor brake as an emergency stop or
deceleration mechanism.
NOTICE
Damage to the equipment from frequent power-on/off
Frequent power-on/off will cause damage to the drive.
Do not switch on/off the power frequently.
Note
Voltage requirement
Before switching the power on, make sure that the drive system has been reliably installed
and connected, and the line supply voltage is within the allowable range.
Note
Drive functioning interfered by use of radio devices
Some environmental factors may result in power derating, e.g. altitude and surrounding
temperature. In this case, the drive cannot work normally.
Environmental factors must be taken into account during commissioning or operation.
Troubleshooting
WARNING
Drive remaining charged
The drive may remain charged in a short period after it is powered off.
Touching terminals or disassembling cables may cause minor injury due to electrical shock.
Do not touch terminals or disassemble cables until the drive system has been disconnected
for at least five minutes.
WARNING
Personal injury due to unexpected restart
The machine might unexpectedly restart after the power supply that was suddenly switched
off is switched on again. Touching the machine at this time may cause personal injury.
Do not approach the machine after the power supply is switched on again.
Disposal
Note
Equipment disposal
Disposal of the equipment must be made in accordance with the regulations of the
competent environmental protection administration on the disposal of electronic wastes.
Certification
WARNING
Requirements for United States/Canadian installations (UL/cUL)
Suitable for use on a circuit capable of delivering not more than 65000 rms Symmetrical
Amperes, 480 VAC maximum for 400 V variants of drives or 240 VAC maximum for 200 V
variant drives, when protected by UL/cUL listed (JDDZ) fuse or type E combination motor
controller. For each frame size AA, A, B, C and D, use 75 °C copper wire only.
This equipment is capable of providing internal motor overload protection according to
UL508C.
For Canadian (cUL) installations the drive mains supply must be fitted with any external
recommended suppressor with the following features:
• Surge-protective devices; device shall be a Listed Surge-protective device (Category
code VZCA and VZCA7)
• Rated nominal voltage 480/277 VAC, 50/60 Hz, 3-phase
• Clamping voltage VPR = 2000 V, IN = 3kA min, MCOV = 508 VAC, SCCR = 65 kA
• Suitable for Type 2 SPD application
• Clamping shall be provided between phases and also between phase and ground.
WARNING
Harms to human health from electromagnetic radiation
This product may cause high-frequency electromagnetic radiation, which will affect human
health. Therefore, in a residential environment, make sure that necessary suppression
measures are taken.
Note
Low Voltage Directive complied
Our products comply with EN61800-5-1: 2007 standards and Low Voltage Directive (Low
Voltage Directive 2006/95/EC).
Note
EMC instructions
• To comply with the EMC standards, all cables connected with the SINAMICS V90 system
must be shielded cables, which include cables from the line supply to the line filter and
from the line filter to the SINAMICS V90 drive.
• The SINAMICS V90 drives have been tested in accordance with the emission
requirements of the category of C2 (domestic) environment. The conductive emissions
and radiated emissions are in compliance with the standard of EN 55011 and reached
Class A.
• In a residential environment, this product can cause high-frequency interferences that
may necessitate suppression measures.
• For a radiated emission test, an external AC filter (between the mains supply and the
drive) will be used to meet the EMC requirement and the drive will be installed inside the
shielded metallic chamber, other parts of the motion control system (including the PLC,
DC power supply, spindle drive, motor) will be put inside the shielded chamber.
• For a conductive emission test, an external AC filter (between the mains supply and the
drive) will be used to meet the EMC requirement.
• For the radiated emission and conductive emission test, the length of the line supply
cable between the line filter and the drive must be shorter than 1 m.
• The harmonic current value of SINAMICS V90 exceed the class A limit of IEC 61000-3-2,
but the SINAMICS V90 system installed within the Category C2 First Environment require
supply authority acceptance for connection to the public low-voltage power supply
network. Please contact your local supply network provider.
Note
Non-Siemens products
This document contains recommendations relating to non-Siemens products. Non-Siemens
products whose fundamental suitability is familiar to us. It goes without saying that equivalent
products from other manufacturers may be used. Our recommendations are to be seen as
helpful information, not as requirements or dictates. We cannot accept any liability for the
quality and properties/features of non-Siemens products.
Warning labels
Warning labels attached to the motor or drive have the following meanings:
Symbol Description
Risk of electric shock
Do not touch any terminals or disassemble cables until the drive has been
disconnected from power for at least five minutes.
Caution
Pay attention to the information given on the rating plate and operating
instructions.
For more information, refer to this manual.
Hot surface
Do not touch the heatsink of the drive during operation or within a certain
period since power disconnection because its surface temperature may
reach up to 65 °C.
No knocking at the shaft
Do not exert any shock at the shaft end; otherwise, the encoder may be
damaged.
2.1 Deliverables
Component Illustration Rated power Outline dimension Frame size Order number
(kW) (Width x Height x
Depth, mm)
SINAMICS V90, 0.1/0.2 45 x 170 x 170 FSA 6SL3210-5FB10-1UA0
single/three-phase, 6SL3210-5FB10-2UA0
200 V
0.4 55 x 170 x 170 FSB 6SL3210-5FB10-4UA1
0.75 80 x 170 x 195 FSC 6SL3210-5FB10-8UA0
1.0/1.5/2.0 95 x 170 x 195 FSD 6SL3210-5FB11-0UA1
6SL3210-5FB11-5UA0
6SL3210-5FB12-0UA0
Connectors for FSA and FSB
Component Illustration Rated torque (Nm) Shaft height (mm) Order number
SIMOTICS S-1FL6, low • 0.16 20 1FL6022-2AF21-
inertia 1❑❑1
• 0.32
1FL6024-2AF21-
1❑❑1
• 0.64 30 1FL6032-2AF21-
1❑❑1
• 1.27
1FL6034-2AF21-
1❑❑1
• 2.39 40 1FL6042-2AF21-
1❑❑1
• 3.18
1FL6044-2AF21-
1❑❑1
• 4.78 50 1FL6052-2AF21-
0❑❑1
• 6.37
1FL6054-2AF21-
0❑❑1
Component Illustration Rated torque (Nm) Shaft height (mm) Order number
SIMOTICS S-1FL6, high • 1.27 45 1FL6042-1AF61-
inertia 0❑❑1
• 2.39
1FL6044-1AF61-
0❑❑1
• 3.58 65 1FL6061-1AC61-
0❑❑1
• 4.78
1FL6062-1AC61-
• 7.16
0❑❑1
• 8.36 1FL6064-1AC61-
• 9.55 0❑❑1
1FL6066-1AC61-
0❑❑1
1FL6067-1AC61-
0❑❑1
• 11.90 90 1FL6090-1AC61-
0❑❑1
• 16.70
1FL6092-1AC61-
• 23.90
0❑❑1
• 33.40 1FL6094-1AC61-
0❑❑1
1FL6096-1AC61-
0❑❑1
User documentation SIMOTICS S-1FL6 Servo Motors Installation Guide
Combination between V90 200 V variant drives and low inertia motors
SIMOTICS S-1FL6 servo motor SINAMICS V90 servo drive
Type Rated Rated Rated Shaft Motor ID Order number1) Order number Frame Power
torque power speed height Without With size supply
(Nm) (kW) (rpm) (mm) brake brake
Low 0.16 0.05 3000 20 42 * 43 1FL6022-2AF21- 6SL3210-5FB10- FSA 1/3-
inertia 1A❑1 1UA0 phase
0.32 0.1 3000 20 46 47 1FL6024-2AF21- 200 VA
1A❑1 C to
240 VA
0.64 0.2 3000 30 50 * 51 1FL6032-2AF21- 6SL3210-5FB10-
C
1A❑1 2UA0
1.27 0.4 3000 30 54 * 55 1FL6034-2AF21- 6SL3210-5FB10- FSB
1A❑1 4UA1
2.39 0.75 3000 40 58 * 59 1FL6042-2AF21- 6SL3210-5FB10- FSC
1A❑1 8UA0
3.18 1 3000 40 62 * 63 1FL6044-2AF21- 6SL3210-5FB11- FSD 3-phase
1A❑1 0UA1 200 VA
4.78 1.5 3000 50 66 * 67 1FL6052-2AF21- 6SL3210-5FB11- C to
0A❑1 5UA0 240 VA
C
6.37 2 3000 50 70 * 71 1FL6054-2AF21- 6SL3210-5FB12-
0A❑1 0UA0
Combination between V90 400 V variant drives and high inertia motors
SIMOTICS S-1FL6 servo motor SINAMICS V90 servo drive
Type Rated Rated Rated Shaft Motor ID Order number1) Order number Frame Power
torque power speed height Without With size supply
(Nm) (kW) (rpm) (mm) brake brake
High 1.27 0.4 3000 45 18 * 19 1FL6042-1AF61- 6SL3210-5FE10- FSAA 3-phase
inertia 0A❑1 4UA0 380 VA
10009 10038 1FL6042-1AF61- C to
0L❑1 480 VA
C
2.39 0.75 3000 45 20 * 21 1FL6044-1AF61- 6SL3210-5FE10- FSA
0A❑1 8UA0
10010 10039 1FL6044-1AF61-
0L❑1
3.58 0.75 2000 65 22 23 1FL6061-1AC61- 6SL3210-5FE11-
0A❑1 0UA0
10011 10040 1FL6061-1AC61-
0L❑1
4.78 1.0 2000 65 24 * 25 1FL6062-1AC61-
0A❑1
10012 10041 1FL6062-1AC61-
0L❑1
V90 drives. If you have connected a different motor to the drive, you need to configure the
motor ID manually.
Shaft-height: 50 mm
The illustration below takes the connection between FSD and low inertia servo motor of
50 mm shaft-height when used on the three phase power network for an example.
2.5 Accessories
You can select cables and connectors according to the table below:
10 m 5BK02-1BA0
20 m 5BK02-1CA0
Brake cable (a1) 3m 5BL02-1AD0 Brake connector 0LL51
5m 5BL02-1AF0 (a2)
7m* 5BL02-1AH0
10 m 5BL02-1BA0
15 m * 5BL02-1BF0
20 m 5BL02-1CA0
Power cable (B1) 3m 5CK01-1AD0 Power connector 0LL12 - -
5m 5CK01-1AF0 (B2)
10 m 5CK01-1BA0
20 m 5CK01-1CA0
Power cable (b1) 3m 5CL01-1AD0 Power connector 0LL11
5m 5CL01-1AF0 (b2)
7m* 5CL01-1AH0
10 m 5CL01-1BA0
15 m * 5CL01-1BF0
20 m 5CL01-1CA0
Power cable (C1) 3m 5CK31-1AD0
5m 5CK31-1AF0
10 m 5CK31-1BA0
20 m 5CK31-1CA0
Power cable (c1) 3m 5CL11-1AD0
5m 5CL11-1AF0
7m 5CL11-1AH0
10 m 5CL11-1BA0
15 m 5CL11-1BF0
20 m 5CL11-1CA0
7m* 2DB10-1AH0
10 m 2DB10-1BA0
15 m * 2DB10-1BF0
20 m 2DB10-1CA0
* The cables with length of 7 m and 15 m are only supplied for high inertia motor.
Fuse/circuit breaker
A fuse/circuit breaker can be used to protect the system. Integral solid state short circuit
protection does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and any additional local codes.
Refer to the table below for the selection of fuses and circuit breakers:
Braking resistor
The SINAMICS V90 has a built-in braking resistor, the table below shows the information of
the built-in resistor:
SINAMICS V90 Resistance (Ω) Max. power Rated power (W) Max. energy (kJ)
Power sup- Frame size (kW)
ply
1/3-phase, FSA 150 1.09 13.5 0.55
200 VAC to FSB 100 1.64 20.5 0.82
240 VAC
FSC 50 3.28 41 1.64
3-phase, FSD 50 3.28 41 1.64
200 VAC to (1 kW)
240 VAC FSD 25 6.56 82 3.28
(1.5 kW to
2 kW)
SINAMICS V90 Resistance (Ω) Max. power Rated power (W) Max. energy (kJ)
Power sup- Frame size (kW)
ply
3-phase, FSAA 533 1.2 17 1.8
380 VAC to FSA 160 4 57 6
480 VAC
FSB 70 9.1 131 13.7
FSC 27 23.7 339 35.6
When the motor works in a fast round-trip process, the voltage of the line supply increases.
The braking resistor starts to work if the voltage reaches to the set threshold. The
temperature of the heat sink increases (>100 °C) when the braking resistor is working. If
alarm A52901 and A5000 appear at the same time, you need to switch the internal braking
resistor to the external braking resistor. You can select a standard braking resistor according
to the table below:
SINAMICS V90 Resistance (Ω) Max. power Rated power (W) Max. energy (kJ)
Power sup- Frame size (kW)
ply
1/3-phase, FSA 150 1.09 20 0.8
200 VAC to FSB 100 1.64 21 1.23
240 VAC
FSC 50 3.28 62 2.46
3-phase, FSD 50 3.28 62 2.46
200VAC to (1 kW)
240 VAC FSD 25 6.56 123 4.92
(1.5 kW to
2 kW)
3-phase, FSAA 533 1.2 30 2.4
380 VAC to FSA 160 4 100 8
480 VAC
FSB 70 9.1 229 18.3
FSC 27 23.7 1185 189.6
Filter
Siemens recommends you to use a line filter to protect the system from high frequency noise.
The line filter restricts the conductive interference emitted from the SINAMICS V90 to the
permissible values. The SINAMICS V90 drives with these external line filters have been
tested in accordance with the emission requirements of the Category C2 environment. The
conductive emissions and radiated emissions are in compliance with the Class A
requirements of the EN 55011 standard.
Insertion loss
The table below shows the insertion loss of the line filters.
Parameter Description
Rated current 5A
Noise frequency (MHz) 0.15 0.5 1.0 5.0 10 30
CM (dB) 60 65 55 45 35 20
DM (dB) 50 60 55 50 50 40
Parameter Description
Rated current 12 A
Noise frequency (MHz) 0.15 0.5 1.0 5.0 10 30
CM (dB) 60 70 70 55 45 15
DM (dB) 60 65 60 50 45 30
Rated current 18 A
Noise frequency (MHz) 0.15 0.5 1.0 5.0 10 30
CM (dB) 32 70 82 88 81 90
DM (dB) 40 67 68 72 69 59
Rated current 20 A
Noise frequency (MHz) 0.15 0.5 1.0 5.0 10 30
CM (dB) 60 60 60 55 35 15
DM (dB) 40 55 55 50 45 30
Connecting (example)
The figure below provides a connection example. It shows how to connect a line filter to a
SINAMCIS V90 drive.
Filter used on the single phase power network
Replacement fans
For SINAMICS V90 400 V variant:
● Fan kits for frame size B: 6SL3200-0WF00-0AA0
● Fan kits for frame size C: 6SL3200-0WF01-0AA0
Parameter Description
24 VDC Voltage (V) 24 (-15% to +20%) 1)
power Maximum current (A) 1.6 A (when using a motor without a brake)
supply
3.6 A (when using a motor with a brake)
Overload capability 300%
Parameter Description
Environ- Surrounding air Opera- 0 °C to 45 °C: without power derating
mental temperature tion 45 °C to 55 °C: with power derating
condi-
tions
Degree of protection IP 20
Degree of pollution Class 2
Certifica-
tions
1) When SINAMICS V90 works with a motor with a brake, the voltage tolerance of 24 VDC power supply must be -10% to
+10% to meet the voltage requirement of the brake.
2) Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with the National Electrical Code and any additional local codes.
3) SINAMICS V90 does not support motor overtemperature protection. Motor overtemperature is calculated by I2t and
protected by the output current from the drive.
Order No. 6SL3210-5FB... 10-1UA0 10-2UA0 10-4UA1 10-8UA0 11-0UA1 11-5UA0 12-0UA0
Frame size FSA FSA FSB FSC FSD FSD FSD
Rated output current (A) 1.2 1.4 2.6 4.7 6.3 10.6 11.6
Max. output current (A) 3.6 4.2 7.8 14.1 18.9 31.8 34.8
Max. supported motor power (kW) 0.1 0.2 0.4 0.75 1.0 1.5 2
Output frequency (Hz) 0 to 330
Power sup- Voltage/frequency FSA, FSB and FSC: single phase/three phase 200 VAC to 240 VAC, 50/60 Hz
ply FSD: three phase 200 VAC to 240 VAC, 50/60 Hz
Permissible voltage -15% to +10%
fluctuation
Permissible frequency -10% to +10%
fluctuation
Rated input 1-phase 2.5 3.0 5.0 10.4 - - -
current (A) 3-phase 1.5 1.8 3.0 5.0 7.0 11.0 12.0
Power supply 1-phase 0.5 0.7 1.2 2.0 - - -
capacity 3-phase 0.5 0.7 1.1 1.9 2.7 4.2 4.6
(kVA)
Inrush current (A) 8.0
Cooling method Self-cooled Fan-cooled
Vibration Operation Shock: Operational area II
Peak acceleration: 5 g, 30 ms and 15 g, 11 ms
Quantity of shocks: 3 per direction × 6 direction
Duration of shock: 1 s
Vibra- Operational area II
tion: 10 Hz to 58 Hz: 0.075 mm deflection
58 Hz to 200 Hz: 1g vibration
Transport Vibra- 2 Hz to 9 Hz: 7.5 mm deflection
tion: 9 Hz to 200 Hz: 2 g vibration
Quantity of cycles: 10 per axis
Sweep seed: 1 octave/min
Storage Vibra- 2 Hz to 9 Hz: 3.5 mm deflection
tion: 9 Hz to 200 Hz: 1 g vibration
Quantity of cycles: 10 per axis
Sweep seed: 1 octave/min
Mechanical Outline dimensions (W x 45 x 170 x 170 55 x 170 80 x 170 95 x 170 x 195
design H x D, mm) x 170 x 195
Weight (kg) 1.1 1.3 2.0 2.3 2.4
Order No. 6SL3210-5FE... 10- 10- 11- 11- 12- 13- 15- 17-
4UA0 8UA0 0UA0 5UA0 0UA0 5UA0 0UA0 0UA0
Frame size FSAA FSA FSA FSB FSB FSC FSC FSC
Rated output current (A) 1.2 2.1 3.0 5.3 7.8 11.0 12.6 13.2
Max. output current (A) 3.6 6.3 9.0 13.8 23.4 33.0 37.8 39.6
Max. supported motor power (kW) 0.4 0.75 1.0 1.75 2.5 3.5 5.0 7.0
Output frequency (Hz) 0 to 330
Power sup- Voltage/frequency 3-phase 380 VAC to 480 VAC, 50/60 Hz
ply Permissible voltage fluc- -15% to +10%
tuation
Permissible frequency -10% to +10%
fluctuation
Rated input current (A) 1.5 2.6 3.8 5.8 9.8 13.8 15.8 16.5
Power supply capacity 1.7 3.0 4.3 6.6 11.1 15.7 18.0 18.9
(kVA)
Inrush current (A) 8.0 8.0 8.0 4.0 4.0 2.5 2.5 2.5
Cooling method Self-cooled Fan-cooled
Vibration Operation Shock: Operational area II
Peak acceleration: 5 g
Duration of shock: 30 ms
Vibra- Operational area II
tion: 10 Hz to 58 Hz: 0.075 mm deflection
58 Hz to 200 Hz: 1g vibration
Transport & Vibra- 5 Hz to 9 Hz: 7.5 mm deflection
storage tion: 9 Hz to 200 Hz: 2 g vibration
Vibration class: 2M3 transportation
Mechanical Outline dimensions (W x 60 x 80 x 180 x 200 100 x 180 x 220 140 x 260 x 240
design H x D, mm) 180 x
200
Weight (kg) 1.800 2.500 2.510 3.055 3.130 6.515 6.615 6.615
Parameter Description
Type of motor Permanent-magnet synchronous motor
Cooling Self-cooled
Relative humidity [RH] 90% (non-condensing at 30°C )
Installation altitude [m] ≤ 1000 (without power derating)
Thermal class B
Vibration severity grade A (according to IEC 60034-14)
Shock resistance [m/s2] 25 (continuous in axial direction); 50 (continuous in radial direction); 250
(in a short time of 6 ms)
Bearing lifetime [h] > 20000 1)
Paint finish Black
Protection degree of shaft IP 65, with shaft oil seal
Type of construction IM B5, IM V1, and IM V3
Positive rotation Clockwise (default setting in SINAMICS V90 servo drives)
Certification
1) This lifetime is only for reference. When a motor keeps running at rated speed under rated load, replace its bearing after
20,000 to 30,000 hours of service time. Even if the time is not reached, the bearing must be replaced when unusual
noise, vibration, or faults are found.
Note
The data of rated torque, rated power, maximum torque, and armature resistance in the
above table allow a tolerance of 10%.
Torque-Speed characteristics
Note
• Continuous operating area is a series of states when a motor can operate continuously
and safely. The effective torque must be located in this area.
• Short-term operating area is a series of states when a motor can operate for a short
duration if its effective torque is larger than the rated torque.
• For the motors with different rated and maximum speeds, the output torque will decline at
a faster rate after the speed exceeds the rated speed.
• The feature in short-term operating area varies with power supply voltages.
• The continuous operating area becomes smaller and the voltage consumptions on the
cables grow larger when the cables in the major loop exceed 20 m.
Note
The data of rated torque, rated power, and maximum torque in the above table allow a
tolerance of 10%.
Power derating
For deviating conditions (surrounding temperature > 40 °C or installation altitude > 1000 m
above sea level) the permissible torque/power must be determined from the following table.
Surrounding temperatures and installation altitudes are rounded off to 5 °C and 500 m
respectively.
Torque-Speed characteristics
Note
• Continuous operating area is a series of states when a motor can operate continuously
and safely. The effective torque must be located in this area.
• Short-term operating area is a series of states when a motor can operate for a short
duration if its effective torque is larger than the rated torque.
• For the motors with different rated and maximum speeds, the output torque will decline at
a faster rate after the speed exceeds the rated speed.
• The feature in short-term operating area varies with power supply voltages.
• The continuous operating area becomes smaller and the voltage consumptions grows
larger when the cables in the major loop exceed 20 meters.
• For 1FL6096 motors, the maximum speed can be ensured when the line supply voltage is
higher than 380V.
Note
1FL604❑ and 1FL609❑ have a 5 mm of shaft sheltered in sleeves, and 1FL606❑ has an 8
mm of shaft in sleeves. Therefore, the distances to flange in the above three figures begin
respectively from 5 mm, 8mm, and 5 mm.
Note
The drive must be derated to 80% when the following conditions are satisfied:
• The surrounding temperature is 0 °C to 45 °C, and the mounting clearance is less than
10 mm. In this case, the minimum mounting clearance should not be less than 5 mm.
• The surrounding temperature is 45 °C to 55 °C. In this case, the minimum mounting
clearance should not be less than 20 mm.
Note
Taking EMC factors into account, you are recommended to mount the drive in a shielded
cabinet.
Mounting orientation
SIMOTICS S-1FL6 supports flange mounting only and three types of constructions, so it can
be installed in three orientations as shown in the following figure.
Note
When configuring the IM V3 type of construction, pay particular attention to the permissible
axial force (weight force of the drive elements) and the necessary degree of protection.
WARNING
Personal injury and material damage
Some motors, especially the 1FL609❑ are heavy. The excessive weight of the motor
should be considered and any necessary assistance required for mounting should be
sought.
Otherwise, the motor can fall down during mounting. This can result in serious personal
injury or material damage.
NOTICE
Damage to the motor
If the liquid enters the motor, the motor may be damaged
During motor installation or operation, make sure that no liquid (water, oil, etc.) can
penetrate into the motor. Besides, when installing the motor horizontally, make sure that the
cable outlet faces downward to protect the motor from ingress of oil or water.
Note
Using the eyebolts
The 1FL609❑ motor (90 mm shaft height) has two M8 screw holes for screwing in two
eyebolts. Lift the 1FL609❑ motor only at the eyebolts.
Eyebolts that have been screwed in must be either tightened or removed after mounting.
To ensure better heat dissipation, install a flange between the machine and the motor. You
can install the motor onto the flange with four screws as shown in the following figure.
The connection for FSD when used on the three phase power network:
NOTICE
Important wiring information
In order to meet EMC requirements, all cables must be shielded cables.
The cable shields of shielded twisted-pair cables should be connected to the shielding plate
or the cable clamp of the servo drive.
NOTICE
Drive damage caused by short-circuiting between the shielding wire and the unused pin on
the setpoint connector
The shielding wire may inadvertently be short-circuited to the unused pin on the to-be-
assembled setpoint connector. This can cause damage to the drive.
Exercise caution when connecting the shielding cable to the setpoint connector.
You can see the assembly method of encoder connector in chapter "Assembly of cable
terminals on the drive side (Page 337)" for reference.
Note
For low inertia motors with shaft-heights of 20 mm, 30 mm and 40 mm, the encoder cable
connectors may only be accessible to electrically skilled personnel.
Note
The mini-USB interface of the SINAMICS V90 is used for fast commissioning and
diagnostics with SINAMICS V-ASSISTANT installed in the PC. Do not use it for long
monitoring.
Note
Rotating the connectors
All the three motor-side connectors can be rotated only within 360°.
Signal Description
SINAMICS V90 200 V variant
L1 Line phase L1
L2 Line phase L2
L3 Line phase L3
Required wire range and tightening torque:
FSA and FSB: 26 AWG to 12 AWG
FSC and FSD: 20 AWG to 12 AWG, 0.4 Nm to 0.5 Nm
Signal Description
SINAMICS V90 400 V variant
L1 Line phase L1
L2 Line phase L2
L3 Line phase L3
Maximum conductor cross-section:
FSAA and FSA: 1.5 mm2 (M2.5 screws, 4.43 lb.in/0.5 Nm)
FSB and FSC: 2.5 mm2 (M4 screws, 19.91 lb.in/2.25 Nm)
Note
For 200 V variant, when using the FSA, FSB and FSC on the single phase power network,
you can connect the power supply to any two connectors of L1, L2, and L3.
Signal Description
SINAMICS V90 200 V variant
U Motor phase U
V Motor phase V
W Motor phase W
Required wire range and tightening torque:
FSA and FSB: 26 AWG to 12 AWG
FSC and FSD: 20 AWG to 12 AWG, 0.4 Nm to 0.5 Nm
Signal Description
SINAMICS V90 400 V variant
U Motor phase U
V Motor phase V
W Motor phase W
Maximum conductor cross-section:
FSAA and FSA: 1.5 mm2 (M2.5 screws, 4.43 lb.in/0.5 Nm)
FSB and FSC: 2.5 mm2 (M4 screws, 19.91 lb.in/2.25 Nm)
Wiring
For detailed information about default DI/DO signal assignments, see the table below:
Note
The selected DI signal will respond with a delay time of 8 to 16 ms.
Note
DO signal inverse
The logics of digital output signals DO1 to DO6 can be inversed. You can inverse the logics
of DO1 to DO6 by setting the bit 0 to bit 5 of parameter p0748.
4.3.1.1 DIs
You can assign a maximum of 28 internal digital input signals to the SINAMICS V90 servo
drive. For detailed information about these signals, see the table below:
Note
When working in the torque control mode, the torque setpoint equals to 0 if CWE and CCWE
are at the same status. For more information, please refer to section Direction and stop
(Page 209).
Note
Invalid circumstances for DI signals
• When SINAMICS V-ASSISTANT is communicating with the drive or you are operating the
drive on SINAMICS V-ASSISTANT, some DI signals are invalid:
– When referencing by SINAMICS V-ASSISTANT, the DI signal SREF is invalid.
– During trial run test, the DI signal SON is invalid; meanwhile, DI7 and DI8 are
occupied by SINAMICS V-ASSISTANT.
For example, if you set p29300 = 1 to force the signal SON to a logical high signal, DI1 can
then be assigned to other desired signals.
Note
The parameter p29300 has higher priority than the DIs.
The bit 6 of p29300 is used for emergency stop. You are not allowed to modify it when the
drive is in the servo on state.
Wiring
The digital inputs support both PNP and NPN types of wirings. You can find detailed
information from the following diagrams:
4.3.1.2 DOs
You can assign a maximum of 14 internal digital output signals to the SINAMICS V90 servo
drive. For detailed information about these signals, see the table below:
Wiring
The digital outputs only support NPN type of wiring as illustrated below:
4.3.2.1 PTIs
Two channels of pulse train input are available for the SINAMICS V90 servo drive:
● 24 V single end pulse train input
● High-speed 5 V differential pulse train input (RS485)
When using the 24 V single end PTI: When using the 5 V differential PTI:
Note
Only one channel can be used. The 24 V single end PTI is the factory setting of the
SINAMICS V90 servo drives.
When you choose to use the high-speed 5 V differential PTI (RS485), you must change the
value of parameter p29014 from 1 to 0. Refer to "Selecting a setpoint pulse train input
channel (Page 171)".
4.3.2.2 PTOs
High-speed 5 V differential signals (A+/A-, B+/B-, Z+/Z-) and open collector (zero pulse) are
supported.
Wirings
When not using the open collector: When using the open collector:
4.3.3.1 AIs
SINAMICS V90 has two analog input terminals. The input voltage at each analog input
varies with control modes.
* If the AI input voltage is higher than 10 V, the speed is not limited to the value at 10 V (p29060), but
scaled according to p29060. For example, if p29060 = 3000 rpm, the speed is 3300 rpm at 11 V and
3600 rpm at 12 V.
Command voltage
The command voltage of the analog inputs always follows the formula below:
Vinput = (AI+) - (AI-)
4.3.3.2 AOs
The SINAMICS V90 has two analog outputs. You can find detailed information about these
two analog outputs from the table below:
Parameterization
Two parameters, p29350 (selects signal sources for AO1) and p29351 (selects signal
sources for AO2), are used to select the source of analog output:
Wiring
Do wiring of analog outputs as follows:
1) 24 V power supply for SINAMICS V90. All the PTO signals must be connected to the
controller with the same 24 V power supply as SINAMICS V90.
2) Isolated digital input power supply. It can be the controller power supply.
3) Isolated digital output power supply. It can be the controller power supply.
Note
Only one of the pulse train input channels can be used.
1) 24 V power supply for SINAMICS V90. All the PTO signals must be connected to the
controller with the same 24 V power supply as SINAMICS V90.
2) Isolated digital input power supply. It can be the controller power supply.
3) Isolated digital output power supply. It can be the controller power supply.
1) 24 V power supply for SINAMICS V90. All the PTO signals must be connected to the
controller with the same 24 V power supply as SINAMICS V90.
2) Isolated digital input power supply. It can be the controller power supply.
3) Isolated digital output power supply. It can be the controller power supply.
Note
The analog outputs to analog inputs on the servo unit and the 24V input for the servo unit
must use a common ground (M).
1) 24 V power supply for SINAMICS V90. All the PTO signals must be connected to the
controller with the same 24 V power supply as SINAMICS V90.
2) Isolated digital input power supply. It can be the controller power supply.
3) Isolated digital output power supply. It can be the controller power supply.
Note
The analog outputs to analog inputs on the servo unit and the 24V input for the servo unit
must use a common ground (M).
* The resistor R3 (200 Ohm to 500 Ohm) is required only if the speed for searching the
zero position exceeds 300 rpm.
** The resistor R (200 Ohm to 500 Ohm, recommended power ≥ 5 W ) is required only if
the PTI input frequency exceeds 100 KHz.
* The resistor R3 (200 Ohm to 500 Ohm) is required only if the speed for searching the
zero position exceeds 300 rpm.
** The resistor R (200 Ohm to 500 Ohm, recommended power ≥ 5 W ) is required only if
the PTI input frequency exceeds 100 KHz.
Pin assignment
Wiring
WARNING
Material damages and personal injuries by the drop of a hanging axis
When the servo system is used as a hanging axis, the axis will drop if the positive and
negative poles of the 24 V power supply are connected inversely. Unexpected drop of the
hanging axis may cause material damages and personal injuries.
Make sure that the 24 V power supply is correctly connected.
WARNING
Material damages and personal injuries by the drop of a hanging axis
It is not allowed to use the STO with a hanging axis because the axis may drop.
Unexpected drop of the hanging axis may cause material damages and personal injuries.
Note
Using the STO function
The STO1, STO+ and STO2 are short connected at the factory setting.
When the STO function is to be used, you must remove the short-circuit stick before
connecting the STO interfaces. If you do not need to use it any more, you must reinsert the
short-circuit stick; otherwise, the motor will not run.
For detailed information about the STO function, refer to "Safety Integrated basic functions
(Page 243)".
NOTICE
Cable shielding
The encoder cable must be shielded to meet the EMC requirements.
NOTICE
Drive damage caused by short-circuiting between the shielding wire and the unused pin on
the encoder connector
The shielding wire may inadvertently be short-circuited to the unused pin on the to-be-
assembled encoder connector. This can cause damage to the drive.
Exercise caution when connecting the shielding cable to the encoder connector.
For more information, see section "Assembly of cable terminals on the drive side
(Page 337)".
Wiring
Grounding
To ensure better EMC effects, you are recommended to strip the encoder cable and connect
the cable shield to earth, as shown in the following figure:
WARNING
Damage to the drive
Before connecting an external resistor to DCP and R1, remove the short-circuit stick on the
connectors. Otherwise, the drive may be damaged.
For the connection of the external braking resistor, refer to System connection (Page 81).
Note
Motor holding brake
For detailed information about the function of motor holding brake, refer to the section "Motor
holding brake (Page 165)".
Wiring
Pin assignment
CAUTION
Carefully read the safety instructions
Before your commissioning or operation, read the safety instructions in Section "Safety
instructions (Page 11)" carefully. Failure to observe the instructions may cause serious
effects.
WARNING
Material damages and personal injuries by the drop of a hanging axis
When the servo system is used as a hanging axis, the axis will drop if the positive and
negative poles of the 24 V power supply are connected inversely. Unexpected drop of the
hanging axis may cause material damages and personal injuries.
Before commissioning, a crosstie must be used to hold the hanging axis in prevention of an
unexpected drop. In addition, make sure that the 24 V power supply is correctly connected.
NOTICE
Plugging or unplugging the micro SD card/SD card will cause startup failure.
Do not plug or unplug the micro SD card/SD card during startup; otherwise, the drive will
fail to start up.
NOTICE
Firmware damage due to drive power-off during data transfer
Switching off the 24 VDC power supply for the drive during data transfer from the micro SD
card/SD card to the drive can cause damage to the drive firmware.
• Do not switch off the drive power supply when the data transfer from the micro SD
card/SD card to the drive is in process.
NOTICE
Existing setting data may be overwritten by the setting data on the micro SD card/SD card
during startup.
• When a drive is switched on with a micro SD card/SD card containing user setting data,
the existing setting data on the drive will be overwritten.
• When a drive is switched on with a micro SD card/SD card containing no user setting
data, the drive will automatically save the existing user setting data onto the micro SD
card/SD card.
Before starting up the drive with a micro SD card/SD card, check whether the micro SD
card/SD card contains user setting data. Otherwise, the existing data on the drive may be
overwritten.
Note
In S control mode, if the motor shaft is blocked, the blocked torque is the current effective
torque. Long time shaft blocking can cause damage to the motor.
Commissioning purpose
When the servo drive is powered on for the first time, you can perform a test run with the
BOP or the engineering tool SINAMICS V-ASSISTANT to check:
● Whether the line supply has been connected correctly
● Whether the 24 VDC power supply has been connected correctly
● Whether the cables (power cable, encoder cable, and brake cable) between the servo
drive and the servo motor have been connected correctly
● Whether the motor speed and direction of rotation are correct.
Prerequisites
● The servo drive is connected to the servo motor without load.
● No PLC is connected to the drive system.
Operating sequence
Note
The digital signal EMGS must be kept at high level (1) to ensure normal operation.
Note
When you run the servo motor with an incremental encoder in JOG mode, the servo motor
makes a short buzzing sound indicating that it is identifying the magnetic pole position of the
rotor.
F.xxxxx. Fault code of the first fault In the case of multiple faults
A.xxxxx. Alarm code of the first alarm In the case of multiple alarms
Save Save data in drive Refer to "Save parameters in the servo drive
(Page 155)".
defu Restore drive to default settings Refer to "Reset parameters to default values
(Page 155)".
dr--sd Save data from drive to micro SD Refer to "Copy parameters from the servo
card/SD card drive to a micro SD card/SD card
(Page 156)".
sd--dr Upload data from micro SD Refer to "Copy parameters from a micro SD
card/SD card to drive card/SD card to the servo drive (Page 157)".
Update Update firmware Refer to "Update firmware (Page 157)".
ABS The zero position has not been set Refer to "Set zero position (Page 160)".
A.B.S. The zero position has been set Refer to "Set zero position (Page 160)".
Moves current display to the left page when is displayed at the upper right corner, for
example .
Moves current display to the right page when is displayed at the lower right corner, for
example .
Note
There is no ABS menu function for a servo motor with an incremental encoder.
The ABS menu function is only available for a servo motor with an absolute encoder
Note
Make sure you save p29002 after modification.
Overview
● Editable parameters: all P parameters under the "Para" menu are settable parameters.
Seven groups in total are available:
– P0A: basic
– P0B: gain adjustment
– P0C: speed control
– P0D: torque control
– P0E: position control
– P0F: IO
– P All: all parameters
● Read-only parameters: All r parameters under the "Data" menu are read-only parameters.
You can only read values of these parameters.
NOTICE
It is forbidden to use this function when the servo is ON.
Use this function when the servo is OFF.
Note
The parameters p1414 and p1656 cannot be changed using the SHIFT button.
Note
Invalid parameter number
If the input parameter number is unavailable, the nearest parameter number to the input
value is displayed.
6.5.1 Jog
Note
The digital signal EMGS must be kept at high level (1) to ensure normal operation.
With the Jog function, you can run the connected motor and view Jog speed or Jog torque.
To run the connected motor with the Jog function and view the Jog speed, proceed as
follows:
To run the connected motor with the Jog function and view the Jog torque, proceed as
follows:
NOTICE
Exit the Jog mode after completing Jog run.
The servo motor cannot run if the servo drive is in the Jog mode.
NOTICE
Plugging or unplugging the micro SD card/SD card will cause saving failure.
Do not plug or unplug the micro SD card/SD card during saving; otherwise, the saving
operation will fail.
Note
• If a micro SD card/SD card has been inserted, the parameter set will be saved onto the
micro SD card/SD card simultaneously.
• All signal functions become inactive during the saving process. Use the signal functions
afterwards.
Reference
Editing parameters (Page 149)
Note
You must save the parameter set after setting the parameter set to the default values;
otherwise, the default values will not be activated.
Reference
Saving parameters (RAM to ROM) (Page 155)
NOTICE
It is forbidden to use this function when the servo is ON.
Use this function when the servo is OFF.
NOTICE
Plugging or unplugging the micro SD card/SD card will cause copying failure.
Do not plug or unplug the micro SD card/SD card during copying; otherwise, the copying
operation will fail.
Note
Write protection function is not supported by SINAMICS V90. Data in the micro SD card/SD
card will be overwritten even if the write protection function of the micro SD card/SD card is
enabled.
NOTICE
It is forbidden to use this function when the servo is ON.
Use this function when the servo is OFF.
NOTICE
Plugging or unplugging the micro SD card/SD card will cause copying failure.
Do not plug or unplug the micro SD card/SD card during copying; otherwise, the copying
operation will fail.
Note
Parameter inconsistency
If the parameters on the micro SD card/SD card are inconsistent with existing parameters in
the drive memory, you must restart the servo drive to apply the changes.
After you have updated the firmware, you need to set parameters to their default values.
Refer to "Setting parameters to default (Page 155)" about the default process.
Note
Before you update the firmware, you can back up the drive data on a micro SD card/SD
card. If you want to use them after the update, you can copy the data from the micro SD
card/SD card to the drive (Page 157).
CAUTION
Improper firmware files will cause update failure.
When the update fails, the RDY indicator flashes red at 2 Hz and the COM indicator
becomes red on. An update failure is probably caused by improper firmware files or files
missing.
• If the firmware files on the micro SD card/SD card are corrupt, the servo drive cannot
start up after power-on.
• If the firmware on the micro SD card/SD card is the same with the current firmware of
the servo drive, only a restart is performed.
When a failure occurs, try to update the firmware again using proper firmware files. If the
failure persists, contact your local distributor.
Note
Update the firmware by restarting the drive.
After inserting the micro SD card/SD card with proper firmware files, you can also update the
firmware by restarting the drive.
NOTICE
Connect to ground
You must firstly connect the AI1 or AI2 to ground and then adjust AI offset.
Refer to section "Analog inputs (Page 101)".
With the BOP function menu "A OFF1" or "A OFF2", AI offset can be adjusted automatically.
Proceed as follows to adjust AI offset:
● Adjust AI1 offset
Note
Save parameter
Offset value is set into parameter p29042 (for AI1) or parameter p29061 (for AI2). You must
perform parameter saving after the automatic adjustment of AI offset.
Parameter range
p29042 or p29061 ranges from -0.5 V to + 0.5 V. A value that is out of this range causes an
alarm.
Refer to chapter "Parameter list (Page 275)".
NOTICE
Motor type
This function is only available when you are using a servo motor with the absolute encoder.
Stop servo motor
You must stop servo motor before adjusting absolute encoder.
With the BOP function menu "ABS", you can set current position of absolute encoder to be
zero position. To do this, proceed as follows:
Note
Save parameter
The position value is set in parameter p2525. You must save the parameters after setting the
zero position.
Control modes
Nine control modes are available for the SINAMICS V90 servo drive:
p29003 C-MODE
0 (the first control mode) 1 (the second control mode)
4 PTI S
5 IPos S
6 PTI T
p29003 C-MODE
0 (the first control mode) 1 (the second control mode)
7 IPos T
8 S T
Refer to Section "DIs (Page 92)" for detailed information about DIs.
Note
Note that if p29003 = 5 and the motor has been working in speed control mode for a certain
perido of time; or p29003 = 7 and the motor has been working in torque control mode for a
certain period of time, the fault code F7493 might appear on the drive BOP. This, however,
will not cause the motor to stop. The motor remains operative under this circumstance and
you can clear the fault code manually.
Note
Fault F52904 occurs when the control mode is changed via p29003. You must save the
parameter and then re-power on the servo drive to apply relevant configurations. For more
information about the remedy and acknowledgement of this fault, refer to Section "List of
faults and alarms (Page 318)".
Note
Switching conditions
For the switching from PTI or IPos to S or T, you are recommended to perform control mode
switching after the INP (in position) signal is at high level.
For the switching from S or T to PTI or IPos, you can perform control mode switching only
after the motor speed is lower than 30 rpm.
7.2.1 Servo ON
Note
Refer to Section "Digital inputs/outputs (DIs/DOs) (Page 91)" for detailed information about
DI parameterization.
Refer to Chapter "Parameters (Page 275)" for detailed information about parameters.
• PTO: • PTO:
• PTO: • PTO:
Note
After modifying parameter p29001, you must save the parameter and then restart the drive
to ensure normal operation. In this case, you must perform referencing again because the
reference point will be lost after p29001 changes.
7.2.3 Over-travel
When the servo motor travels over distance limit, limit switch is turned on and servo motor
then has an emergency stop.
NOTICE
Some important information about the travel limit signals (CWL/CCWL)
• Both of the signals must be at the high level when the servo drive is powered on.
• When the drive is under the S or T control mode, operation is possible after you
acknowledge the fault; while when the drive is under the PTI or IPos control mode,
operation is possible only when both CWL and CCWL are at the high level (logic 1) after
you acknowledge the fault.
• In all the modes, signal CWL/CCWL can be responded, which means when F7492 or
F7491 happens, the motor can run over the travel limit if the fault is acknowledged.
– For a positive traversing direction, if the STOP cam plus is reached, F7492 will
happen. To clear the fault, acknowledge it with RESET, and then leave away from
the STOP cam plus in the negative traversing direction to return the axis to the valid
traversing range.
– For a negative traversing direction, if the STOP cam minus is reached, F7491 will
happen. To clear the fault, acknowledge it with RESET, and then leave away from
the STOP cam minus in the positive traversing direction to return the axis to the valid
traversing range.
Signal CWL functions as the clockwise travel limit while signal CCWL functions as the
counter-clockwise travel limit. Both of them are level and edge sensitive signals.
Note
DI parameterization
Refer to Section "Digital inputs/outputs (DIs/DOs) (Page 91)" for detailed information about
DI parameterization.
Refer to Chapter "Parameters (Page 275)" for detailed information about parameters.
Note
• Use this brake for the "hold" purpose only, that is, to hold the stalling state only. Never
use this for the "brake" purpose to stop the load in motion. Use the holding brake only to
hold a stopped motor.
• The holding brake is activated at the same time when the motor power is cut off.
• Refer to Section "System connection (Page 81)" for the standard wiring of the holding
brake.
Signal status
The following table describes the states of various interfaces and components when the
brake works.
● SINAMICS V90 200 V variant
Status MBR (DO) Brake control Relay Motor brake Motor shaft
(Brake) function
Brake en- High level (1) Brake off Without cur- Opened Cannot run
gagement rent
Brake release Low level (0) Brake on With current Closed Can run
Status MBR (DO) Brake control Motor brake func- Motor shaft
(B+, B-) tion
Brake engage- High level (1) 0V Opened Cannot run
ment
Brake release Low level (0) 24 V Closed Can run
DO signal
You can also change the assignment of the digital output signal MBR and assign it to any
DO pin with one of the following parameters:
Note
Refer to Section "Digital inputs/outputs (DIs/DOs) (Page 91)" for detailed information about
the digital outputs.
Note
1)It is the Isolated digital output power supply. When you use the 24 VDC power supply, it
can be also the controller power supply.
The motor brake can be controlled not only by the brake control signal from the SINAMICS
2)
Relevant parameters
You can configure the holding brake with the parameter p1215 according to the actual
application. When you set p1215=1, the motor holding brake is open once the digital input
signal SON has a rising edge and becomes closed once a falling edge comes to SON.
If the servo motor is used to control a vertical axis, the machine movable part can have a
slight shift when the holding brake becomes open or closed simultaneously with the action of
SON. To eliminate such slight shift, you can configure a delay time for the close or open time
of the motor holding brake by setting the parameters p1216 and p1217.
Note
The default values of p1216 and p1217 depend on the rated power of the motor which
connects to the SINAMICS V90 servo drive.
Note
For SINAMICS V90 200 V variant servo drives, the actual motor holding brake time consists
of the time delay of the motor brake and the time delay of the current amplifying component
(a relay in the example above); therefore, you can set the values of p1216 and p1217 as
follows:
p1216 = motor brake opening time + relay opening time
p1217 = motor brake closing time + relay closing time
Braking sequence
The operating principle of the holding brake is configured during motor selection for motors
with incremental encoders and configured automatically for motors with absolute encoders.
The start of the closing time for the brake depends on the expiration of the shorter of p1227
(zero speed detection monitoring time) and p1228 (pulse suppression delay time).
SON in T mode
For detailed information about the digital input signals SON and EMGS, refer to Section
"Digital inputs/outputs (DIs/DOs) (Page 91)".
Timing diagram
The position pulse train inputs come from either of the following two terminal groups:
● PTIA_D+, PTIA_D-, PTIB_D+, PTIB_D-
● PTIA_24P, PTIA_24M, PTIB_24P, PTIB_24M
For more information about wiring, refer to Section "Control/Status interface (Page 90)" and
"PTIs (Page 100)".
Pulse + Direction
You can select one of the setpoint pulse train input forms by setting the parameter p29010:
Note
After modifying parameter p29010, you must save the parameter and then restart the drive
to ensure normal operation. In this case, you must perform referencing again because the
reference point will be lost after p29010 changes.
Parameter settings
DO configuration
Parameter setting
Encoder specifications
The encoder specifications are shown as follows:
Type Resolution
A Incremental encoder 2500 ppr
L Absolute encoder 20 bit single turn + 12 bit multi-turn
Electronic gear
With the function of electronic gear, you can define the motor revolutions according to the
number of setpoint pulses, and sequentially define the distance of mechanical movement.
The minimum travelling distance of load shaft according to one setpoint pulse is called a
length unit (LU); for example, one pulse results in 1 µm movement.
The electronic gear ratio is a multiplier factor to pulse train setpoint. It is realized with a
numerator and a denominator. Four numerators (p29012[0], p29012[1], p29012[2].
p29012[3]) and one denominator (p29013) are used for the four electronic gear ratios:
These four electronic gear ratios can be selected with the combination of the digital input
signals EGEAR1 and EGEAR2 (refer to Section "DIs (Page 92)"):
Note
After a gear ratio is switched to another one via digital inputs, you need to wait five seconds
and then perform SERVO ON.
Note
The range of electronic gear ratio is from 0.02 to 200.
The electronic gear ratio can be set at SERVO OFF state only. After the setting, you need to
reference the drive again.
Note
P-TRG in PTI mode
Note that the function "inhibiting pulse train by P-TRG in PTI mode" as described in this
section and the rest of the manual is reserved for future use.
The digital input signal P-TRG is the default connection of DI6 in the position control mode.
In the pulse train input position control mode, P-TRG is level sensitive and can be used to
allow or inhibit positioning operation according to pulse train input setpoint:
● 0: positioning according to pulse train input setpoint
● 1: inhibit pulse train input setpoint
Timing diagram
DI configuration
The signal P-TRG is the factory setting of DI6:
Note
Refer to Section "Digital inputs/outputs (DIs/DOs) (Page 91)" for detailed information about
DI parameterization.
• The signal P-TRG is active only when the digital input signal SON is in OFF state.
• When the signal P-TRG is active in the PTI mode or a compound mode with PTI, the
alarm A7585 occurs.
Note
Control mode
The above four sources are valid in all control modes. You can switch among them when the
servo drive is running.
Note
Fault F7901 occurs when the actual speed exceeds the positive speed limit + hysteresis
speed (p2162) or the negative speed limit - hysteresis speed (p2162). Go to "List of faults
and alarms (Page 318)" for information about the acknowledgment of this fault.
Note
If the drive is working with external speed limit, the system continues to work automatically
after you repower on the 24 VDC power supply which is shut off unexpected for the drive. In
this case, do not touch the equipment.
Refer to "DIs (Page 92)" for more information about the digital input signals SLIM1 and
SLIM2.
Note
After the motor is commissioned, p1082, p1083, p1086, p29070 and p29071 set to the
maximum speed of the motor automatically.
When the torque setpoint reaches torque limit, the torque is limited to the value selected by
TLIM1/TLIM2.
Note
Control mode
The above four sources are valid in the PTI mode, the IPos mode and the S mode. You can
switch among them when the servo drive is running.
Note
When the motor torque exceeds the torque limit, fault F52911/F52912 appears. The fault
indicates the motor torque exceeds the torque limitation of the selected group which is
determined by TLM1 and TLM2.
Refer to "DIs (Page 92)" for more information about the digital input signals TLIM1 and
TLIM2.
The following diagram shows how the internal torque limit functions:
In this case, analog input of 5 V corresponds to 50% of rated torque and 10 V corresponds to
100% of rated torque.
p29242 = 0
p29242 = 1
p29242 = 2
Note
When you use the CLR high level to clear the pulses (p29242 = 1), the high level need to be
kept for more than 8 ms.
When the signal CLR is active in the PTI mode or a compound mode with PTI, the alarm
A7585 occurs.
If there are overshoot when you use the CLR function, you need to increase the integral time
(p29121).
Function
A pulse train encoder output (PTO) which provides pulse signals can transmit the signals to
the controller to realize a closed-loop control system inside the controller, or transmit them to
another drive as pulse train setpoint for a synchronous axis.
Electronic gear
The electronic gear ratio is a multiplier factor to the PTO to a controller. It is realized with a
numerator and a denominator. One numerator (p29031) and one denominator (p29032) are
used for the PTO electronic gear ratio:
Note
When you use the PTO electronic gear function, for the absolute encoder, the electronic
gear is based on the resolution of 8192 ppr.
The range of electronic gear ratio is from 0.02 to 200.
The electronic gear ratio can be set at SERVO OFF state only.
Note
PTO direction
For an application of fully closed-loop position control using PTI and PTO, you can set the
PTO direction with parameter p29033.
Note
When using the PTO function, the drive will output some pulses before the motor servo on if
you executing the following operations.
• Default the drive with the BOP instruction.
• Configure the motor ID on the drive.
Note
When you use the PTO electronic gear ratio function, zero mark will not be generated.
The unit of the fixed position setpoint is the Length Unit (LU). All subsequent position
setpoint, related speed value, and acceleration value will maintain the LU as the unit in
internal position control mode.
Taking a ball screw system for example, if the system has a pitch of 10 mm/revolution
(10000 µm/revolution) and the resolution of the length unit is 1 µm (1 LU = 1 µm), one load
revolution corresponds to 10000 LU (p29247 = 10000).
Note
If the value of p29247 increases by N times, the values of p2542, p2544 and p2546 should
increase by N times accordingly. Otherwise, the fault F7450 or F7452 occur.
Relevant parameters
Parameter settings
Note
When the motor is working in the IPos control mode, you need to check that whether the
values of the parameters p2542, p2544, p2546, p2547 and p2573 are your desired values.
The values are set automatically by the drive based on the encoder resolution.
NOTICE
Pre-conditions for using the absolute mode
The absolute mode can be used only after:
• the axis has been referenced for incremental measuring system. Refer to Section
"Referencing (Page 190)" for detailed information about referencing.
• the axis has been adjusted for absolute measuring system. Refer to Section "Adjusting
an absolute encoder (Page 160)" for reference.
Example
Note
After modifying parameter p29245, you must perform the referencing again.
Note
Pre-conditions for backlash compensation
The backlash compensation is active after
• the axis has been referenced for incremental measuring system. Refer to Section
"Referencing (Page 190)" for detailed information about referencing.
• the axis has been adjusted for absolute measuring system. Refer to Section "Adjusting an
absolute encoder (Page 160)" for reference.
In order to compensate the backlash, the determined backlash must be specified in p2583
with correct polarity. At each direction of rotation reversal, the axis actual value is corrected
dependent on the actual traversing direction.
If the axis has been referenced or adjusted, then the setting of parameter p2604 (reference
point approach, starting direction) is used to activate the compensation value:
Parameter settings
7.4.6 Referencing
Referencing modes
If the servo motor has an incremental encoder, five referencing modes in total are available:
● Setting reference point with the digital input signal REF
● External reference cam (signal REF) and encoder zero mark
● Encoder zero mark only
● External reference cam (signal CWL) and encoder zero mark
● External reference cam (signal CCWL) and encoder zero mark
If the servo motor has an absolute encoder, the five referencing modes are available. You
can also adjust the absolute encoder (by setting current position as the zero position) with
the BOP function "ABS". Refer to Section "Adjusting an absolute encoder (Page 160)" for
details.
You can select one of these referencing modes by setting the parameter p29240:
Note
Referencing mode for absolute encoder
If an absolute encoder is connected, the five referencing modes are available. You can
select the different referencing modes with parameter p29240. When p29240 = 1 to 4, the
referencing process can only be implemented before you use the "ABS" function. Once the
"ABS" function is implemented, the four referencing modes are not available any more.
Note
p29240 can be modified only when the drive is in IPos mode.
Setting reference point with the digital input signal REF (p29240=0)
Note
Preconditions for this referencing mode
• The servo motor must be in servo on state and keep standstill.
• The signal REF must be OFF under the following conditions:
– before power-on
– when switching from another referencing mode to this referencing mode
– when switching from another control mode to internal position control mode
The current position is set to zero at a rising edge of the signal REF and the servo drive is
referenced:
CAUTION
The referencing point may not be fixed during referencing.
The servo motor must be in servo on state so that the referencing point is fixed during
referencing.
External reference cam (signal REF) and encoder zero mark (p29240=1)
The referencing is triggered by signal SREF. After that, the servo motor accelerates to the
speed specified in p2605 to find the reference cam. The direction (CW or CCW) for
searching the reference cam is defined by p2604. When the reference cam is reached
(signal REF: 0→1), the servo motor decelerates to standstill. After that, the servo motor
accelerates again to the speed specified in p2608 and the running direction is opposite to the
direction defined by p2604. Then the signal REF should be switched off (1→0). When the
servo motor reaches the first zero mark, it starts to travel towards the reference point defined
in p2600 with the speed specified in p2611. When the servo motor reaches the reference
point (p2599), the signal REFOK is output. Switch off the signal SREF (1→0) and the
referencing finishes successfully.
The whole process is shown in the diagram below:
Note
During the referencing, if SREF is OFF, the referencing stops.
4. If the servo motor reaches the reference point, the signal REFOK (if configured) is output.
5. Switch off the signal SREF, and the referencing finishes successfully.
Note
During the referencing, if SREF is OFF, the referencing stops.
4. If the servo motor reaches the reference point, the signal REFOK (if configured) is output.
5. Switch off the signal SREF, and the referencing finishes successfully.
External reference cam (signal CCWL) and encoder zero mark (p29240=3)
The referencing is triggered by signal SREF. After that, the servo motor accelerates to the
speed specified in p2605 to find the reference cam. The direction (CCW) for searching the
reference cam is defined by p2604. When the signal CCWL is detected (1→0), the servo
motor decelerates to standstill with maximum deceleration. After that, the servo motor
accelerates again to the speed specified in p2608 and the running direction (CW) is opposite
to the direction defined by p2604. The signal CCWL switches to high level (0→1). When the
servo motor finds the first zero mark, it starts to travel towards the reference point defined in
p2600 with the speed specified in p2611. When the servo motor reaches the reference point
(p2599), the signal REFOK is output. Switch off the signal SREF (1→0) and the referencing
finishes successfully.
The whole process is shown in the diagram below:
Note
• During the referencing process, the signals CWL and CCWL are unavaiable. Once the
process is complete, the signals will act as limits signal again.
• For the safety purpose, the maximum distance for searching the cam (p2606) and the
maximum distance for searching the zero mark (p2609) must be set.
Note
During the referencing, if SREF is OFF, the referencing stops.
4. If the servo motor reaches the reference point, the signal REFOK (if configured) is output.
5. Switch off the signal SREF, and the referencing finishes successfully.
External reference cam (signal CWL) and encoder zero mark (p29240=4)
The referencing is triggered by signal SREF. After that, the servo motor accelerates to the
speed specified in p2605 to find the reference cam. The direction (CW) for searching the
reference cam is defined by p2604. When the signal CWL is detected (1→0), the servo motor
decelerates to standstill with maximum deceleration. After that, the servo motor accelerates
again to the speed specified in p2608 and the running direction (CCW) is opposite to the
direction defined by p2604. The signal CWL switches to high level (0→1). When the servo
motor finds the first zero mark, it starts to travel towards the reference point defined in p2600
with the speed specified in p2611. When the servo motor reaches the reference point
(p2599), the signal REFOK is output. Switch off the signal SREF (1→0) and the referencing
finishes successfully.
The whole process is shown in the diagram below:
Note
• During the referencing process, the signals CWL and CCWL are unavaiable. Once the
process is complete, the signals will act as limits signal again.
• For the safety purpose, the maximum distance for searching the cam (p2606) and the
maximum distance for searching the zero mark (p2609) must be set.
Note
During the referencing, if SREF is OFF, the referencing stops.
4. If the servo motor reaches the reference point, the signal REFOK (if configured) is output.
5. Switch off the signal SREF, and the referencing finishes successfully.
Parameter settings
Selecting the target position with the signals POS1, POS2 and POS3, and starting the positioning
with the trigger signal P-TRG
Select one of the eight fixed position setpoints with the co-settings of signals POS1, POS2
and POS3:
In the fixed position control mode, the signals POS1 and POS2 are default assignments of
DI7 and DI8 while the signal POS3 is not assigned:
Note
Configuration of POS3
If the POS3 is not assigned to any DI, its status is assumed to be 0, which means only the
following fixed position setpoints can be used:
• Fixed position setpoint 1
• Fixed position setpoint 2
• Fixed position setpoint 3
• Fixed position setpoint 4
After selecting a fixed position setpoint, the servo motor can start positioning at a rising edge
of the signal P-TRG.
The digital input signal P-TRG is the default assignment of DI6 in the internal position control
mode:
The timing diagram for starting positioning with the trigger signal P-TRG is shown as follows:
Selecting the target position and starting the positioning with the rising edge of the signal STEPF,
STEPB or STEPH
If the signal STEPF is enabled, the servo motor, at a rising edge of STEPF, traverses to next
fixed position setpoint. For example, if the servo motor currently locates at the fixed position
setpoint 3, the servo motor traverses to the fixed position setpoint 4 at a rising edge of
STEPF.
If the signal STEPB is enabled, the servo motor, at a rising edge of STEPB, traverses to
previous fixed position setpoint.
If the signal STEPH is enabled, the servo motor, at a rising edge of STEPH, traverses to the
fixed position setpoint 1.
Note
The servo drive can respond to the rising edge of the signal STEPF, STEPB or STEPH only
when the servo motor is at a standstill.
If the servo motor is at fixed position 8, a rising edge of STEPF is not responded.
If motor is at fixed position 1, a rising edge of STEPH is responded, but a rising edge of
STEPB is not responded.
During positioning, if the motor stops unexpectedly, the drive assumes that the target
position has been reached; for example, if the motor stops between POS2 and POS3
because of a fault after the signal STEPB (traversing to POS2) is given, the drive assumes
that POS2 has been reached.
Refer to "DIs (Page 92)" for more information about the digital signals SPD1, SPD2 and
SPD3.
The relationship between the analog voltage and the speed setpoint is shown as follows:
Note
If the drive is working with external analog speed setpoint, the system continues to work
automatically after you repower on the 24 VDC power supply which is shut off unexpected
for the drive. In this case, do not touch the equipment.
Parameter settings
In the S mode, when at least one of the three digital input signals SPD1, SPD2 and SPD3 is
at high level, one of the following parameter values is used as speed setpoint:
Note
In S mode or T mode, when the servo motor is ready to run, signal CWE or CCWE is a must
to start running the motor.
For more information about signals CWE and CCWE, refer to "DIs (Page 92)".
This function is available only when the analog input 1 is used as the source of speed
setpoint. The digital input signal ZSCLAMP is used to activate this function. When both
motor speed setpoint and motor actual speed are below the parameterized threshold level
and signal ZSCLAMP is logic "1", the motor is locked. Drive exits from clamping state either
when the motor speed setpoint is above the threshold level or when the signal ZSCLAMP is
logic "0".
Parameter settings
DI configuration
Note
When p29003=4 and CMODE is "1", the drive is working in speed control mode. In this case
if ZSCLAMP is activated, the drive will switch to PTI control mode and PTI pulse input will
lead motor running under PTI control mode.
Note
For more information about the signal ZSCLAMP, refer to "DIs (Page 92)".
The maximum speed p1082 is used as the reference value for calculating the ramp-up and
ramp-down times.
You can see the properties of the ramp-function generator from the diagram below:
Parameter settings
Refer to "DIs (Page 92)" for detailed information about the signal TSET.
Note
The value of analog input 2 can be monitored through parameter p29351.
Parameter settings
Note
In S mode or T mode, when the servo motor is ready to run, signal CWE or CCWE is a must
to start running the motor.
For more information about the signals CWE and CCWE, refer to "DIs (Page 92)".
Telegram format
The telegram format is shown as follows:
Relevant parameters
You can access the following parameters by USS.
Note
There is no priority when BOP, V-ASSISTANT, and USS access the same parameter at the
same time, the value of the parameter depends on the last access operation.
Operating steps
② Configure the RS485 bus address by parameter The RS485 bus is used to transfer current absolute position of
p29004. the servo drive to the upper controller/PLC. You can configure
the slaver address from 1 to 31.
③ Select the USS communication protocol by parameter • p29007 = 0: no protocol
p29007.
• p29007 = 1: USS protocol
• p29007 = 2: Modbus protocol
⑦ Access the parameters via USS. For IPos control mode, you can change the following parame-
ters via USS:
• p2617[0...7], p2618[0...7], p2572, p2573
For S control mode, you can change the following parameter
via USS:
• p1001 to p1007
Ten monitor parameters can be read by USS:
• r0020, r0021, r0026, r0027, r0031, r0032, r0034, r0807,
r2556, and r2521
Note
The USS protocol communication libraries of S7-200, S7-200 SMART V1.0, and S7-1200 do
not support the communication with the SINAMICS V90 servo drive.
Byte 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 Byte 7 Byte 7 + Byte 8 + Byte 9 + Byte 10 +
n n n n
Address FC Start Start Number Number Number nth nth CRC CRC
(0x10) address address of regis- of regis- of bytes value value
(most (least ters ters (most (least
signifi- signifi- (most (least signifi- signifi-
cant cant signifi- signifi- cant cant
byte) byte) cant cant byte) byte)
byte) byte)
Operating steps
Description Comment
① Configure the RS485 bus address by parameter You can configure the slaver address from 1 to 31.
p29004.
② Select the communication protocol by parameter • p29007 = 0: No protocol
p29007.
• p29007 = 1: USS protocol
• p29007 = 2: Modbus protocol
③ Select the command and setpoint source by parame- • p29008 = 1: Setpoint and control word from Modbus PZD
ter p29008.
• p29008 = 2: No control word.
Description Comment
⑧ Write the control word via PLC. Note:
Bit 10 of the register 40100 must be set to 1 to allow the PLC
to control the drive.
You need to trigger a rise edge for OFF1 to enable SON sta-
tus for the motor, and OFF2 and OFF3 must be set to 1. The
step must be executed when you enable SON for the first
time.
⑨ Write the setpoint and read the status word via PLC.
Example 1
This example shows the operating procedures when we the use setpoint and control word
from Modbus as the Modbus control source in S control mode.
Note:
Keep the PLC baud rate the same as the drive setting.
Set even parity check for the PLC (parity = 2).
8. Write the control word you desired via the register 40100.
Note:
Bit 10 of the register 40100 must be set to 1 to allow the PLC to control the drive.
You need to trigger a rise edge for OFF1 to enable SON status for the motor, and
OFF2 and OFF3 must be set to 1. The step must be executed when you enable SON
for the first time.
For example, we write 0x41E to the register 40100 firstly and then write 0x41F to the
register. The motor now is in SON status. You can check the control word definition
table below to see the meaning of "0x41E" and "0x41F".
9. Write the speed setpoint via the register 40101.
Note:
You can calculate the actual speed value with the scale factor. Value 0x4000 repre-
sents the value of 100% × motor rated speed. Therefore, 0x2000 represents half of
the motor rated speed.
Example 2
This example shows the operating procedures when we use the setpoint and control word
from Modbus as the Modbus control source in IPos control mode.
Note:
Keep the PLC baud rate the same as the drive setting.
Set even parity check for the PLC (parity = 2).
8. Write the control word you desired via the register 40100.
Note:
Bit 10 of the register 40100 must be set to 1 to allow the PLC to control the drive.
You need to trigger a rise edge for OFF1 to enable SON (0→1) status for the motor,
and OFF2 and OFF3 must be set to 1. The step must be executed when you enable
SON for the first time.
For example, we write 0x46E to the register 40100 firstly and then write 0x46F to the
register. The motor now is in SON status. You can check the control word definition
table below to see the meaning of "0x46E" and "0x46F".
Mapping table
The SINAMICS V90 servo drive supports the following registers. "R", "W", "R/W" in the
column access stand for read, write, read/write.
Note
The following signals are occupied by Modbus control word when you use the setpoint and
control word from Modbus as the Modbus control source (p29008 = 1). They can only be
enabled by Modbus control word while cannot be enabled by external DI terminals.
• PTI control mode: SON
• IPos control mode: SON, SREF (REF for reference mode 0)
• S control mode: SON, CWE/CCWE
• T control mode: SON
Note
In IPos control mode, when the relative positioning mode is selected, the method for
accepting MDI setpoint must be a rising edge (bit 5 = 0); otherwise, fault F7488 occurs.
Note
In IPos control mode, when you implement the absolute positioning for the modular axis with
Modbus, you can select the MDI direction with parameter p29230.
Note
All the reserved bits in register 40100 must be set to 0.
Parameter scaling
Due to the limits of the integer data in the Modbus protocol, it is necessary to convert the
drive parameters before transmitting them. This is done by scaling, so that a parameter,
which has a position after decimal point, is multiplied by a factor, to get rid of the fractional
part. The scaling factor is as defined in the above table.
Restrictions
The absolute position system cannot be configured under the following conditions:
● Internal position control (IPos)
● Speed control (S)
● Torque control (T)
● Control change mode
● Strokeless coordinate system, for example, rotary shaft, infinitely long positioning
operation
● Change of electronic gear after referencing
● Use of alarm code output
④ Referencing with the BOP or SINAMICS V- 1. Run the servo motor for a proper distance.
ASSISTANT. 2. Adjust the absolute encoder with the BOP menu function
NOTE: "ABS" or SINAMICS V-ASSISTANT.
You must perform the referencing operation under the
following conditions:
• System setup is performed.
• The servo drive has been changed.
• The servo motor has been changed.
• An alarm occurs.
⑥ Configure the parameters for selected communication 1. Set RS485 address (p29004).
protocol. 2. Set baud rate (p29009).
3. Set the command and setpoint source if you use Modbus
protocol (p29008).
⑩ Transmit the absolute position data to the PLC. 1. If the absolute encoder is calibrated, and meanwhile, the
servo drive is ready (the digital output RDY is logic 1) and
in standstill status (the digital output signal INP is logic 1),
the PLC sends a data request to drive through the RS485
cable.
2. In response to the data request from the PLC, the servo
drive transmits the absolute position data (r2521) to the
PLC.
8.1.1.1 Aims
Manufacturers and operating companies of equipment, machines, and products are
responsible for ensuring the required level of safety. This means that plants, machines, and
other equipment must be designed to be as safe as possible in accordance with the current
state of the art. To ensure this, companies describe in the various standards the current
state of the art covering all aspects relevant to safety. When the relevant Standards are
observed, this ensures that state-of-the-art technology has been utilized and, in turn, the
erector/builder of a plant or a manufacturer of a machine or a piece of equipment has fulfilled
his appropriate responsibility.
Safety systems are designed to minimize potential hazards for both people and the
environment by means of suitable technical equipment, without restricting industrial
production and the use of machines more than is necessary. The protection of man and
environment must be assigned equal importance in all countries, which is it is important that
rules and regulations that have been internationally harmonized are applied. This is also
designed to avoid distortions in the competition due to different safety requirements in
different countries.
There are different concepts and requirements in the various regions and countries of the
world when it comes to ensuring the appropriate degree of safety. The legislation and the
requirements of how and when proof is to be given and whether there is an adequate level of
safety are just as different as the assignment of responsibilities.
The most important thing for manufacturers of machines and companies that set up plants
and systems is that the legislation and regulations in the country where the machine or plant
is being operated apply. For example, the control system for a machine that is to be used in
the US must fulfill local US requirements even if the machine manufacturer (OEM) is based
in the European Economic Area (EEA).
The protective goals must be implemented responsibly to ensure compliance with the
Directive.
Manufacturers of a machine must verify that their machine complies with the basic
requirements. This verification is facilitated by means of harmonized standards.
The application areas of EN ISO 13849-1, EN 62061, and EN 61508 are very similar. To
help users make an appropriate decision, the IEC and ISO associations have specified the
application areas of both standards in a joint table in the introduction to the standards. EN
ISO 13849-1 or EN 62061 should be applied depending on the technology (mechanics,
hydraulics, pneumatics, electrics, electronics and programmable electronics), risk
classification and architecture.
Note
DIN EN ISO 13849-1 and machinery directive
Since May 2007, DIN EN ISO 13849-1 has been harmonized as part of the Machinery
Directive.
8.1.2.5 EN 62061
EN 62061 (identical to IEC 62061) is a sector-specific standard subordinate to IEC/EN
61508. It describes the implementation of safety-related electrical machine control systems
and looks at the complete life cycle, from the conceptual phase to decommissioning. The
standard is based on the quantitative and qualitative analyses of safety functions, whereby it
systematically applies a top-down approach to implementing complex control systems
(known as "functional decomposition"). The safety functions derived from the risk analysis
are sub-divided into sub-safety functions, which are then assigned to real devices, sub-
systems, and sub-system elements. Both the hardware and software are covered. EN 62061
also describes the requirements placed on implementing application programs.
A safety-related control system comprises different sub-systems. From a safety perspective,
the sub-systems are described in terms of the SIL claim limit and PFHD characteristic
quantities.
Programmable electronic devices (e.g. PLCs or variable-speed drives) must fulfill EN 61508.
They can then be integrated in the controller as sub-systems. The following safety-related
characteristic quantities must be specified by the manufacturers of these devices.
Safety-related characteristic quantities for subsystems:
● SIL CL: SIL claim limit
● PFHD: Probability of dangerous failures per hour
● T1: Lifetime
Simple sub-systems (e.g. sensors and actuators) in electromechanical components can, in
turn, comprise sub-system elements (devices) interconnected in different ways with the
characteristic quantities required for determining the relevant PFHD value of the sub-system.
Safety-related characteristic quantities for subsystem elements (devices):
● λ: Failure rate
● B10 value: For elements that are subject to wear
● T1: Lifetime
For electromechanical devices, a manufacturer specifies a failure rate λ with reference to the
number of operating cycles. The failure rate per unit time and the lifetime must be
determined using the switching frequency for the particular application.
Parameters for the sub-system, which comprises sub-system elements, that must be defined
during the design phase:
● T2: Diagnostic test interval
● β: Susceptibility to common cause failure
● DC: Diagnostic coverage
The PFHD value of the safety-related controller is determined by adding the individual PFHD
values for subsystems.
The user has the following options when setting up a safety-related controller:
● Use devices and sub-systems that already comply with EN ISO 13849-1, IEC/EN 61508,
or IEC/EN 62061. The standard provides information specifying how qualified devices
can be integrated when safety functions are implemented.
● Develop own subsystems:
– Programmable, electronic systems and complex systems: Application of EN 61508 or
EN 61800-5-2.
– Simple devices and subsystems: Application of EN 62061.
EN 62061 does not include information about non-electric systems. The standard provides
detailed information on implementing safety-related electrical, electronic, and programmable
electronic control systems. EN ISO 13849-1 must be applied for non-electric systems.
Note
Function examples
Details of simple sub-systems that have been implemented and integrated are now available
as "functional examples".
Note
EN 62061 and machinery directive
IEC 62061 has been ratified as EN 62061 in Europe and harmonized as part of the
Machinery Directive.
Risks must be reduced by designing and implementing the machine accordingly (e.g. by
means of controllers or protective measures suitable for the safety-related functions).
If the protective measures involve the use of interlocking or control functions, these must be
designed according to EN ISO 13849-1. For electrical and electronic controllers, EN 62061
can be used as an alternative to EN ISO 13849-1. Electronic controllers and bus systems
must also comply with IEC/EN 61508.
http://www.osha.gov
The application of standards is regulated in 29 CFR 1910.5 "Applicability of standards". The
concept is similar to that used in Europe. Product-specific standards have priority over
general standards insofar as they cover the relevant aspects. Once the standards are
fulfilled, employers can assume that they have fulfilled the core requirements of the OSH Act
with respect to the aspects covered by the standards.
In conjunction with certain applications, OSHA requires that all electrical equipment and
devices that are used to protect workers be authorized by an OSHA-certified, "Nationally
Recognized Testing Laboratory" (NRTL) for the specific application.
In addition to the OSHA regulations, the current standards defined by organizations such as
NFPA and ANSI must be carefully observed and the extensive product liability legislation
that exists in the US taken into account. Due to the product liability legislation, it is in the
interests of manufacturing and operating companies that they carefully maintain the
applicable regulations and are "forced" to fulfill the requirement to use state-of-the-art
technology.
Third-party insurance companies generally demand that their customers fulfill the applicable
standards of the standards organizations. Self-insured companies are not initially subject to
this requirement but, in the event of an accident, they must provide verification that they
have applied generally-recognized safety principles.
8.1.3.3 NFPA 79
Standard NFPA 79 (Electrical Standard for Industrial Machinery) applies to electrical
equipment on industrial machines with rated voltages of less than 600 V. A group of
machines that operate together in a coordinated fashion is also considered to be one
machine.
For programmable electronics and communication buses, NFPA 79 states as a basic
requirement that these must be listed if they are to be used to implement and execute safety-
related functions. If this requirement is fulfilled, then electronic controls and communication
buses can also be used for Emergency Stop functions, Stop Categories 0 and 1 (refer to
NFPA 79 9.2.5.4.1.4). Like EN 60204-1, NFPA 79 no longer specifies that the electrical
energy must be disconnected by electromechanical means for emergency stop functions.
The core requirements regarding programmable electronics and communication buses are:
system requirements (see NFPA 79 9.4.3)
Japanese standards
Japanese standards
Safety-related issues (e.g. operating modes, operator actions with access to hazardous
areas, EMERGENCY STOP concepts, etc.) should be clarified with customers early on so
that they can be integrated in the risk assessment/risk reduction process.
8.3.2 Certification
The safety function of the SINAMICS V90 drive system meets the following requirements:
● Category 3 according to ISO 13849-1:2006
● Performance Level (PL) d to ISO 13849-1:2006
● Safety integrity level 2 (SIL 2) to IEC 61508
In addition, the safety function of SINAMICS V90 has been certified by independent institutes.
An up-to-date list of certified components is available on request from your local Siemens
office.
Note
Additional safety information and residual risks not specified in this section are included in
the chapter "Safety instructions (Page 11)".
DANGER
Safety Integrated can be used to minimize the level of risk associated with machines and
plants.
Machines and plants can only be operated safely in conjunction with Safety Integrated,
however, when the machine manufacturer is familiar with and observes every aspect of this
technical user documentation, including the documented general conditions, safety
information, and residual risks.
Precisely knows and observes this technical user documentation - including the
documented limitations, safety information and residual risks;
Carefully constructs and configures the machine/plant. A careful and thorough acceptance
test must then be performed by qualified personnel and the results documented.
Implements and validates all the measures required in accordance with the machine/plant
risk analysis by means of the programmed and configured Safety Integrated functions or by
other means.
The use of Safety Integrated does not replace the machine/plant risk assessment carried
out by the machine manufacturer as required by the EC machinery directive.
In addition to using Safety Integrated functions, further risk reduction measures must be
implemented.
WARNING
The Safety Integrated functions cannot be activated until the system has been completely
powered up. System startup is a critical operating state with increased risk. No personnel
may be present in the immediate danger zone in this phase.
The drives of vertical axes must be in torque state.
A complete forced dormant error detection cycle is required after power on.
WARNING
EN 60204-1:2006
Emergency Stop function must bring the machine to a standstill in accordance with STO.
The machine must not restart automatically after EMERGENCY STOP.
When the safety function is deactivated, an automatic restart is permitted under certain
circumstances depending on the risk analysis (except when Emergency Stop is reset). An
automatic start is permitted when a protective door is closed, for example.
WARNING
After hardware and/or software components have been modified or replaced, all protective
equipment must be closed prior to system startup and drive activation. Personnel shall not
be present within the danger zone.
Before allowing anybody to re-enter the danger zone, you should test steady control
response by briefly moving the drives in forward and reverse direction (+/–).
To observe during power on:
The Safety Integrated functions are only available and can only be selected after the
system has completely powered up.
WARNING
Due to the intrinsic potential of hardware faults, electrical systems are subject to additional
residual risk, which can be expressed by means of the PFH value.
WARNING
Simultaneous failure of two power transistors (one in the upper and the other offset in the
lower inverter bridge) in the inverter may cause brief movement of the drive, depending on
the number of poles of the motor.
Maximum value of this movement:
Synchronous rotary motors: Max. movement = 180° / no. of pole pairs
● When the "Safe Torque Off" function is selected, the following applies:
– The motor cannot be started accidentally.
– The pulse suppression safely disconnects the torque-generating energy feed to the
motor.
– The power unit and motor are not electrically isolated.
● By selecting/deselecting STO, in addition to the fault messages, the safety messages are
also automatically withdrawn.
The STO function can be used wherever the drive naturally reaches a standstill due to load
torque or friction in a sufficiently short time or when "coasting down" of the drive will not have
any relevance for safety.
WARNING
Appropriate measures must be taken to ensure that the motor does not undesirably move
once the energy feed has been disconnected, e.g. against coasting down.
CAUTION
If two power transistors simultaneously fail in the power unit (one in the upper and one in
the lower bridge), then this can cause brief momentary movement.
The maximum movement can be:
Synchronous rotary motors: Max. movement = 180 ° / No. of pole pairs
Synchronous linear motors: Max. movement = pole width
Note
Closing delay of the holding brake
The closing signal (low level) of the holding brake is output 30 ms after the STO is triggered.
Note
If "Safe Torque Off" is selected and de-selected through one channel within 2 seconds, the
pulses are suppressed without a message being output.
Restart after the "Safe Torque Off" function has been selected
1. Deselect the function in each monitoring channel via the input terminals.
2. Issue drive enable signals.
3. Switch the drive back on.
– 1/0 edge at input signal "ON/OFF1"
– 0/1 edge at input signal "ON/OFF1" (switch on drive)
4. Operate the drives again.
Forced dormant error detection or test of the switch-off signal paths for Safety Integrated Basic
Functions
The forced dormant error detection function at the switch-off signal paths is used to detect
software/hardware faults at both monitoring channels in time and is automated by means of
activation/deactivation of the "Safe Torque Off" function.
To fulfill the requirements of ISO 13849-1:2006 regarding timely error detection, the two
switch-off signal paths must be tested at least once within a defined time to ensure that they
are functioning properly. This functionality must be implemented by means of forced dormant
error detection function, triggered either in manual mode or by the automated process.
A timer ensures that forced dormant error detection is carried out as quickly as possible.
8760 hours for the forced dormant error detection.
Once this time has elapsed, an alarm is output and remains present until forced dormant
error detection is carried out.
The timer returns to the set value each time the STO function is deactivated.
When the appropriate safety devices are implemented (e.g. protective doors), it can be
assumed that running machinery will not pose any risk to personnel. For this reason, only an
alarm is output to inform the user that a forced dormant error detection run is due and to
request that this be carried out at the next available opportunity. This alarm does not affect
machine operation.
Examples of when to carry out forced dormant error detection:
● When the drives are at a standstill after the system has been switched on (POWER ON).
● When the protective door is opened.
● At defined intervals.
● In automatic mode (time and event dependent)
Note
The timer will be reset if the associated forced dormant error detection is executed. The
corresponding alarm is not triggered.
The forced dormant error detection procedure of Safety Function (STO) always has to be
executed through the terminals.
The mission time of the devices is 40000 hours.
In theory, frequency width of the inside control loop must be wider than that of the outer
control loop; otherwise, the whole control system can vibrate or have a low response level.
The relationship between the frequency widths of these three control loops is as follows:
Current loop > speed loop > position loop
Since the current loop of SINAMICS V90 servo drive already has a perfect frequency width,
it is only necessary for you to adjust the speed loop gain and the position loop gain.
Servo gains
● Position loop gain
Position loop gain directly influences the response level of the position loop. If the
mechanical system does not vibrate or produce noises, you can increase the value of
position loop gain so that the response level can be increased and positioning time can
be shortened.
NOTICE
Effectiveness of servo gains
The tuning function only uses the first group of servo gains (position loop gain 1, speed
loop gain 1 and speed loop integral time 1).
The following tuning functions are available for the SINAMICS V90 servo drive.
Select a tuning mode by setting the parameter p29021:
Auto-tuning modes
The SINAMICS V90 supplies two auto-tuning modes: one-button auto tuning and real-time
auto tuning. The auto tuning function can optimize control parameters with ratio of machine
load moment of inertia (p29022) and set suitable current filter parameters to suppress the
machine resonance automatically. You can change the dynamic performance of the system
by setting different dynamic factors.
● One-button auto tuning
– One-button auto tuning estimates the machine load moment of inertia and mechanical
characteristics with internal motion commands. To achieve the desired performance,
you can execute the process many times before you control the drive with the host
controller. The maximum speed is limited by the rated speed.
● Real-time auto tuning
– Real-time auto tuning estimates the machine load moment of inertia automatically
while the drive is running with the host controller command. After enabling the servo
on (SON), the real-time auto tuning function stays effective for the servo drive. If you
do not need to estimate the load moment of inertia continuously, you can disable the
function when the system performance is acceptable.
For IPos control mode, if you have obtained the machine load inertia (p29022) and desired
dynamic performance with tuned dynamic factor, you can set the drive to the servo off state
and set p29025.5 = 1 to make sure that there is no position overshoot on the axis.
You are recommended to save the tuned parameters when the tuning is completed and the
drive performance is acceptable.
Note
The function is valid for firmware version V1.04.00 and higher.
Note
Before using the one-button auto tuning, move the servo motor to the middle of mechanical
position to avoid approaching the actual machine position limit.
Parameter settings
You can set the ratio of machine load moment of inertia (p29022) with the following methods:
● Enter it manually if you have known the ratio of machine load moment of inertia.
● Estimate the ratio of manchine load moment of inertia with one-button auto tuning
(p29023.2 = 1). When you have executed the one-button tuning many times and obtained
a stable value of p29022, you can stop estimating it by setting p29023.2 = 0.
If the dynamic factor setting cannot be increased up to the desired level because of machine
resonance beyond 250 Hz, the function of resonance suppression can be used to suppress
machine resonance and thus increase dynamic factor. Refer to Section "Resonance
suppression (Page 260)" for detailed information about the function of resonance
suppression.
Note
The tuning configuration parameters must be set carefully when the auto tuning function is
disabled (p29021=0).
After servo on, the motor will run with the test signal.
When the one-button auto tuning process completes successfully, the parameter p29021 will
be set to 0 automatically. You can also set the parameter p29021 to 0 before servo on to
interrupt the one-button tuning process. Before you save the parameters on the drive, make
sure that p29021 has changed to 0.
Note
Do not use the JOG function when you use the one-button tuning function.
Note
After the one-button tuning is activated, no operation will be allowed except the servo off and
emergency stop.
With one-button auto tuning, the servo drive can automatically estimate the ratio of load
moment of inertia and set the following relevant parameters accordingly.
After one-button tuning, four current setpoint filters can be activated at most. The following
parameters related to the filters may be tuned accordingly.
Note
After one-button auto tuning is activated, do not change other auto tuning related
control/filter parameters since these parameters can be set automatically and your changes
will not be accepted.
Note
One-button auto tuning may cause some changes of the control parameters. When the
system rigidity is low, this may lead to a situation that when you set EMGS = 0, the motor
needs take long time to emergency stop.
Parameter settings
You can set the ratio of machine load moment of inertia (p29022) with the following methods:
● Enter it manually if you have known the ratio of machine load moment of inertia
● Use the ratio of machine load moment of inertia estimated by the one-button auto tuning
function directly
● Estimate the ratio of machine load moment of inertia with real-time auto tuning (p29024.2
= 1). When you have obtained a stable value of p29022, you can stop estimating it by
setting p29024.2 = 0.
If the dynamic factor setting cannot be increased up to the desired level because of machine
resonance beyond 250 Hz, the function of resonance suppression can be used to suppress
machine resonance and thus increase dynamic factor. Refer to Section "Resonance
suppression (Page 260)" for detailed information about the function of resonance
suppression.
Note
The tuning configuration parameters must be set carefully when the auto tuning function is
disabled (p29021=0).
During tuning, you can modify the dynamic factor with p29020[1] to obtain the different
dynamic performance after p29022 has been tuned and accepted by the drive.
After servo on, the real-time auto tuning function will always effective for the servo drive. If
you want to end or interrupt the real-time auto tuning process, set the drive to the servo off
state then set p29021 to 0.
The following relevant parameters can be continuous set in real time when you are using the
real-time auto tuning:
Note
When using the real-time auto tuning function, if the default values are inappropriate, the
host controller cannot run the motor. To run the motor with the host controller, you need to
let the drive tune the parameters automatically through trial run with the real-time auto tuning
function. After the tuning is completed, the host controller can run the motor.
Note
After the real-time auto tuning is activated, do not change other auto tuning related
control/filter parameters since these parameters can be set automatically and your changes
will not be accepted.
Note
The real-time auto tuning may not be performed properly if the following conditions are not
satisfied:
• Accelerate the motor for 100 ms or more with the acceleration torque.
• The acceleration/deceleration torque is 15% or more of the rated torque.
Under operating conditions that impose sudden disturbance torque during
acceleration/deceleration or on a machine that its rigidity is poor, auto tuning may not
function properly, either. In such cases, use the one-button auto tuning or manual tuning to
optimize the drive.
Note
Resonance suppression
For detailed information about the resonance suppression, refer to Section "Resonance
suppression (Page 260)".
Parameter settings
You need to set the following servo gains related parameters manually when using the
manual tuning function:
dent
p2573 1 to 2000000 Motor 1000 IPos maximum deceleration
depen- LU/s
pen- 2
dent
p29110[ 0.00 to Motor 1000 Position loop gain 1
0] 300.00 depen- /min
pen-
dent
p29120[ 0 to 999999 Motor Nms Speed loop gain 1
0] depen- /rad
pen-
dent
p29121[ 0 to 100000 15 ms Speed loop integral time 1
0]
p29111 0.00 to 0.00 % Position loop feed forward gain
200.00
The gain decreasing frequency, width as well as depth can be set by setting the notch filter:
Note
The resonance suppression function is used together with the auto tuning function. In real-
time auto tuning and one-button auto tuning mode, the function is activated by default.
When you use real-time auto tuning function, you are recommended to disable the
resonance suppression function to get a high dynamic performance if there is no resonance
in the machine.
The function can be activated/deactivated with the following parameters:
• For one-button auto tuning: bit 1 of p29023
• For real-time auto tuning: bit 6 of p29024
Note
Notch filter remains active when the resonance suppression function is activated
automatically.
After one-button tuning is completed, four filters can be activated at most. You can
deactivate the notch filters by setting the parameter p1656.
Assume the notch frequency is fsp, notch width is fBB, and notch depth is K, then the filter
parameters can be calculated as follows:
p1663=p1665=fsp
p1664=fBB / (2 × fsp)
p1666=(fBB × 10(k/20) )/ (2 × fsp)
Related parameters
When you use the vibration suppression function, you need to configure the following
parameters accordingly:
Operating steps
⑥ Enable the vibration suppression function by Set p29035 = 1 to activate the function.
p29035.
⑦ Set the drive to servo on status.
Note
The Gain Switching function is not available in T mode (torque control mode).
The function of auto-tuning must be disabled so that the function of gain switching can be
available.
You can select one of the five modes by setting parameter p29130:
DI settings
● Position control mode
Timing diagram
Note
If the pulse duration is shorter than 10 ms, there is no reaction.
Timing diagram
Timing diagram
Timing diagram
Note
PI/P switching
Function of PI/P switching is not available for the T mode (torque control mode).
The functions of auto-tuning and gain switching must be disabled so that the function of PI/P
switching can be available.
The PI/P switching will respond with a delay time of several milliseconds.
Example
Without the function of PI/P switching With the function of PI/P switching
Example 1: If the PI/P switching is not used, the speed of the motor may overshoot or undershoot due to torque saturation
during acceleration or deceleration. The mode switching function suppresses torque saturation and eliminates the over-
shooting or undershooting of the motor speed.
Example 2: The function of PI/P switching can be used to suppress overshooting and undershooting when speed loop gain
is increased
Parameter settings
Note
Speed setpoint
For detailed information about speed setpoint, refer to "Configuring speed setpoint
(Page 201)".
Torque setpoint
For detailed information about torque setpoint, refer to "Torque setpoint (Page 208)".
DI settings
● Position control mode
Parameter settings
Timing diagram
Parameter settings
Note
For detailed information about speed setpoint, refer to "Configuring speed setpoint
(Page 201)".
Parameter settings
Note
Speed setpoint
For detailed information about speed setpoint, refer to "Configuring speed setpoint
(Page 201)".
Acceleration
For detailed information about acceleration, refer to "Setting fixed position setpoint
(Page 186)" of the internal position control mode.
Parameter settings
Note
Speed setpoint
For detailed information about speed setpoint, refer to "Configuring speed setpoint
(Page 201)".
Parameter number
Numbers prefixed with an "r" indicate that parameter is a read-only parameter.
Numbers prefixed with a "P" indicate that the parameter is an editable parameter.
Effective
Indicates the conditions for making parameterization effective. Two conditions are possible:
● IM (Immediately): Parameter value becomes effective immediately after changing.
● RE (Reset): Parameter value becomes effective after repower-on.
Can be changed
This indicates when the parameter can be changed. Two states are possible:
● U (Run): Can be changed in the "Running" state when the drive is in the servo on state.
The "RDY" LED lights up green.
● T (Ready to run): Can be changed in the "Ready" state when the drive is in the servo off
state. The "RDY" LED lights up red.
Note
When judging the state of the drive according to the "RDY" LED, ensure that no faults or
alarms exist.
Data type
Type Description
I16 16-bit integer
I32 32-bit integer
U16 16 bits without sign
U32 32 bits without sign
Uint16 16-bit unsigned integer
Uint32 32-bit unsigned integer
Float 32-bit floating point number
Parameter groups
The SINAMICS V90 parameters are divided into the following groups:
Editable parameters
The values of the parameters marked with an asterisk (*) may be changed after
commissioning. Make sure you back up the parameters first as required if you desire to
replace the motor. The default values of the parameters marked with two asterisks (**) are
motor dependent. They may have different default values when different motor connected.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p0748 CU invert digital outputs 0 63 0 - U32 IM T, U
Description: Inverts the signals at the digital outputs.
• Bit 0: inverts signal DO1.
– Bit 0 = 0: not inverted
– Bit 0 = 1: inverted
• Bit 1: inverts signal DO2.
– Bit 1 = 0: not inverted
– Bit 1 = 1: inverted
• Bit 2: inverts signal DO3.
– Bit 2 = 0: not inverted
– Bit 2 = 1: inverted
• Bit 3: inverts signal DO4.
– Bit 3 = 0: not inverted
– Bit 3 = 1: inverted
• Bit 4: inverts signal DO5.
– Bit 4 = 0: not inverted
– Bit 4 = 1: inverted
• Bit 5: inverts signal DO6.
– Bit 5 = 0: not inverted
– Bit 5 = 1: inverted
p1001 Fixed speed setpoint 1 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 1.
p1002 Fixed speed setpoint 2 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 2.
p1003 Fixed speed setpoint 3 -210000.000 210000.000 00.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 3.
p1004 Fixed speed setpoint 4 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 4.
p1005 Fixed speed setpoint 5 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 5.
p1006 Fixed speed setpoint 6 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 6.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1007 Fixed speed setpoint 7 -210000.000 210000.000 0.000 rpm Float IM T, U
Description: Sets a value for the fixed speed / velocity setpoint 7.
p1058 Jog 1 speed setpoint 0.00 210000.000 100.00 rpm Float IM T
Description: Sets the speed/velocity for jog 1. Jogging is level-triggered and allows the motor to be incremen-
tally moved.
Note: The parameter values displayed on the BOP are integers.
p1082 * Maximum speed 0.000 210000.000 1500.00 rpm Float IM T
0
Description: Sets the highest possible speed.
Notice: After the value has been modified, no further parameter modifications can be made.
Note: The parameter values displayed on the BOP are integers.
The parameter applies for both motor directions.
The parameter has a limiting effect and is the reference quantity for all ramp-up and ramp-down times (e.g.
down ramps, ramp-function generator and motor potentiometer).
The range of the parameter is different when connect with different motors.
p1083 * Speed limit in positive 0.000 210000.000 210000. rpm Float IM T, U
direction of rotation 000
Description: Sets the maximum speed for the positive direction.
Note: The parameter values displayed on the BOP are integers.
p1086 * Speed limit in negative -210000.000 0.000 - rpm Float IM T, U
direction of rotation 210000.
000
Description: Sets the speed limit for the negative direction.
Note: The parameter values displayed on the BOP are integers.
p1115 Ramp-function generator 0 1 0 - I16 IM T
selection
Description: Sets the ramp-function generator type.
Note: Another ramp-function generator type can only be selected when the motor is at a standstill.
p1120 Ramp-function generator 0.000 999999.000 1 s Float IM T, U
ramp-up time
Description: The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the
maximum speed (p1082) in this time.
Dependency: Refer to p1082
p1121 Ramp-function generator 0.000 999999.000 1 s Float IM T, U
ramp-down time
Description: Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to
standstill (setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: Refer to p1082
p1130 Ramp-function generator 0.000 30.000 0.000 s Float IM T, U
initial rounding-off time
Description: Sets the initial rounding-off time for the extended ramp generator. The value applies to ramp-up
and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1131 Ramp-function generator 0.000 30.000 0.000 s Float IM T, U
final rounding-off time
Description: Sets the final rounding-off time for the extended ramp generator. The value applies to ramp-up
and ramp-down.
Note: Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
p1215 * Motor holding brake con- 0 3 0 - I16 IM T
figuration
Description: Sets the holding brake configuration.
Dependency: Refer to p1216, p1217, p1226, p1227, p1228
Caution: For the setting p1215 = 0, if a brake is used, it remains closed. If the motor moves, this will destroy
the brake.
Notice: If p1215 was set to 1 or if p1215 was set to 3, then when the pulses are suppressed, the brake is
closed even if the motor is still rotating.
Note: If a holding brake integrated in the motor is used, then it is not permissible that p1215 is set to 3.
The parameter can only be set to zero when the pulses are inhibited.
p1216 * Motor holding brake 0 10000 100 ms Float IM T, U
opening time
Description: Sets the time to open the motor holding brake.
After controlling the holding brake (opens), the speed/velocity setpoint remains at zero for this time. After this,
the speed/velocity setpoint is enabled.
Dependency: Refer to p1215, p1217
Note: For a motor with integrated brake, this time is pre-assigned the value saved in the motor.
For p1216 = 0 ms, the monitoring and the message A7931 "Brake does not open" are deactivated.
p1217 * Motor holding brake clos- 0 10000 100 ms Float IM T, U
ing time
Description: Sets the time to apply the motor holding brake.
After OFF1 or OFF3 and the holding brake is controlled (the brake closes), then the drive remains closed-loop
controlled for this time stationary with a speed setpoint/velocity setpoint of zero. The pulses are suppressed
when the time expires.
Dependency: Refer to p1215, p1216
Note: For a motor with integrated brake, this time is pre-assigned the value saved in the motor.
For p1217 = 0 ms, the monitoring and the message A07932 "Brake does not close" are deactivated.
p1226 Threshold for zero speed 0.00 210000.00 20.00 rpm Float IM T, U
detection
Description: Sets the speed threshold for the standstill identification.
Acts on the actual value and setpoint monitoring. When braking with OFF1 or OFF3, when the threshold is
undershot, standstill is identified.
The following applies when the brake control is activated:
When the threshold is undershot, the brake control is started and the system waits for the brake closing time
in p1217. The pulses are then suppressed.
If the brake control is not activated, the following applies:
When the threshold is undershot, the pulses are suppressed and the drive coasts down.
Dependency: Refer to p1215, p1216, p1217, p1227
Notice: For reasons relating to the compatibility to earlier firmware versions, a parameter value of zero in
indices 1 to 31 is overwritten with the parameter value in index 0 when the drive boots.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
Note: Standstill is identified in the following cases:
- The speed actual value falls below the speed threshold in p1226 and the time started after this in p1228 has
expired.
- The speed setpoint falls below the speed threshold in p1226 and the time started after this in p1227 has
expired.
The actual value sensing is subject to measuring noise. For this reason, standstill cannot be detected if the
speed threshold is too low.
p1227 Zero speed detection 0.000 300.000 300.000 s Float IM T, U
monitoring time
Description: Sets the monitoring time for the standstill identification.
When braking with OFF1 or OFF3, standstill is identified after this time has expired, after the setpoint speed
has fallen below p1226.
After this, the brake control is started, the system waits for the closing time in p1217 and then the pulses are
suppressed.
Dependency: Refer to p1215, p1216, p1217, p1226
Notice: The setpoint is not equal to zero dependent on the selected value. This can therefore cause the moni-
toring time in p1227 to be exceeded. In this case, for a driven motor, the pulses are not suppressed..
Note: Standstill is identified in the following cases:
- The speed actual value falls below the speed threshold in p1226 and the time started after this in p1228 has
expired.
- The speed setpoint falls below the speed threshold in p1226 and the time started after this in p1227 has
expired.
For p1227 = 300.000 s, the following applies:
Monitoring is de-activated.
For p1227 = 0.000 s, the following applies:
With OFF1 or OFF3 and a ramp-down time = 0, the pulses are immediately suppressed and the motor
"coasts" down.
p1228 Pulse suppression delay 0.000 299.000 0.000 s Float IM T, U
time
Description: Sets the delay time for pulse suppression. After OFF1 or OFF3, the pulses are canceled, if at
least one of the following conditions is fulfilled:
- The speed actual value falls below the threshold in p1226 and the time started after this in p1228 has ex-
pired.
- The speed setpoint falls below the threshold in p1226 and the time started after this in p1227 has expired.
Dependency: Refer to p1226, p1227
Notice: When the motor holding brake is activated, pulse cancellation is additionally delayed by the brake
closing time (p1217).
p1414 Speed setpoint filter acti- 0000 bin 0011 bin 0000 - U16 IM T, U
vation bin
Description: Setting for activating/de-activating the speed setpoint filter.
Dependency: The individual speed setpoint filters are parameterized as of p1415.
Note: The drive unit displays the value in hex format. To know the logic (high/low) assignment to each bit, you
must convert the hex number to the binary number, for example, FF (hex) = 11111111 (bin).
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1415 Speed setpoint filter 1 0 2 0 - I16 IM T, U
type
Description: Sets the type for speed setpoint filter 1.
Dependency:
PT1 low pass: p1416
PT2 low pass: p1417, p1418
General filter: p1417 ... p1420
p1416 Speed setpoint filter 1 0.00 5000.00 0.00 ms Float IM T, U
time constant
Description: Sets the time constant for the speed setpoint filter 1 (PT1).
Dependency: Refer to p1414, p1415
Note: This parameter is only effective if the filter is set as a PT1 low pass.
p1417 Speed setpoint filter 1 0.5 16000.0 1999.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for speed setpoint filter 1(PT2, general filter).
Dependency: Refer to p1414, p1415
Note: This parameter is only effective if the speed filter is parameterized as a PT2 low pass or as general
filter.
The filter is only effective if the natural frequency is less than half of the sampling frequency.
p1418 Speed setpoint filter 1 0.001 10.000 0.700 - Float IM T, U
denominator damping
Description: Sets the denominator damping for speed setpoint filter 1 (PT2, general filter).
Dependency: Refer to p1414, p1415
Note: This parameter is only effective if the speed filter is parameterized as a PT2 low pass or as general
filter.
p1419 Speed setpoint filter 1 0.5 16000.0 1999.0 Hz Float IM T, U
numerator natural fre-
quency
Description: Sets the numerator natural frequency for speed setpoint filter 1 (general filter).
Dependency: Refer to p1414, p1415
Note: This parameter is only effective if the speed filter is set as a general filter. The filter is only effective if the
natural frequency is less than half of the sampling frequency.
p1420 Speed setpoint filter 1 0.001 10.000 0.700 - Float IM T, U
numerator damping
Description: Sets the numerator damping for speed setpoint filter 1 (general filter).
Dependency: Refer to p1414, p1415
Note: This parameter is only effective if the speed filter is set as a general filter.
p1421 Speed setpoint filter 2 0 2 0 - I16 IM T, U
type
Description: Sets the type for speed setpoint filter 2.
Dependency:
PT1 low pass: p1422
PT2 low pass: p1423, p1424
General filter: p1423 ... p1426
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1422 Speed setpoint filter 2 0.00 5000.00 0.00 ms Float IM T, U
time constant
Description: Sets the time constant for the speed setpoint filter 2 (PT1).
Dependency: Refer to p1414, p1421
Note: This parameter is only effective if the speed filter is set as a PT1 low pass.
p1423 Speed setpoint filter 2 0.5 16000.0 1999.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for speed setpoint filter 2 (PT2, general filter).
Dependency: Refer to p1414, p1421
Note: This parameter is only effective if the speed filter is parameterized as a PT2 low pass or as general
filter.
The filter is only effective if the natural frequency is less than half of the sampling frequency.
p1424 Speed setpoint filter 2 0.001 10.000 0.700 - Float IM T, U
denominator damping
Description: Sets the denominator damping for speed setpoint filter 2 (PT2, general filter).
Dependency: Refer to p1414, p1421
Note: This parameter is only effective if the speed filter is parameterized as a PT2 low pass or as general
filter.
p1425 Speed setpoint filter 2 0.5 16000.0 1999.0 Hz Float IM T, U
numerator natural fre-
quency
Description: Sets the numerator natural frequency for speed setpoint filter 2 (general filter).
Dependency: Refer to p1414, p1421
Note: This parameter is only effective if the speed filter is set as a general filter.
The filter is only effective if the natural frequency is less than half of the sampling frequency.
p1426 Speed setpoint filter 2 0.000 10.000 0.700 - Float IM T, U
numerator damping
Description: Sets the numerator damping for speed setpoint filter 2 (general filter).
Dependency: Refer to p1414, p1421
Note: This parameter is only effective if the speed filter is set as a general filter.
p1441 Actual speed smoothing 0.00 50.00 0.00 ms Float IM T, U
time
Description: Sets the smoothing time constant (PT1) for the speed actual value.
Note: The speed actual value should be smoothed for increment encoders with a low pulse number.
After this parameter has been changed, we recommend that the speed controller is adapted and/or the speed
controller settings checked Kp (p29120) and Tn (p29121).
p1520 * Torque limit upper -1000000.00 20000000.0 0.00 Nm Float IM T, U
0
Description: Sets the fixed upper torque limit.
Danger: Negative values when setting the upper torque limit (p1520 < 0) can result in the motor accelerating
in an uncontrollable fashion.
Notice: The maximum value depends on the maximum torque of the connected motor.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1521 * Torque limit lower -20000000.00 1000000.00 0.00 Nm Float IM T, U
Description: Sets the fixed lower torque limit.
Danger: Positive values when setting the lower torque limit (p1521 > 0) can result in the motor accelerating in
an uncontrollable fashion.
Notice: The maximum value depends on the maximum torque of the connected motor.
p1656 * Activates current setpoint 0000 bin 1111 bin 0001 - U16 IM T, U
filter bin
Description: Setting for activating/de-activating the current setpoint filter.
Dependency: The individual current setpoint filters are parameterized as of p1658.
Note: If not all of the filters are required, then the filters should be used consecutively starting from filter 1. The
drive unit displays the value in hex format. To know the logic (high/low) assignment to each bit, you must
convert the hex number to the binary number, for example, FF (hex) = 11111111 (bin).
p1658 * Current setpoint filter 1 0.5 16000.0 1999.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 1 (PT2, general filter).
Dependency: The current setpoint filter 1 is activated via p1656.0 and parameterized via p1658 ... p1659.
p1659 * Current setpoint filter 1 0.001 10.000 0.700 - Float IM T, U
denominator damping
Description: Sets the denominator damping for current setpoint filter 1.
Dependency: The current setpoint filter 1 is activated via p1656.0 and parameterized via p1658 ... p1659.
p1663 Current setpoint filter 2 0.5 16000.0 1000.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 2 (PT2, general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1664 Current setpoint filter 2 0.001 10.000 0.300 - Float IM T, U
denominator damping
Description: Sets the denominator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1665 Current setpoint filter 2 0.5 16000.0 1000.0 Hz Float IM T, U
numerator natural fre-
quency
Description: Sets the numerator natural frequency for current setpoint filter 2 (general filter).
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1662 ... p1666.
p1666 Current setpoint filter 2 0.000 10.000 0.010 - Float IM T, U
numerator damping
Description: Sets the numerator damping for current setpoint filter 2.
Dependency: Current setpoint filter 2 is activated via p1656.1 and parameterized via p1663 ... p1666.
p1668 Current setpoint filter 3 0.5 16000.0 1000.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 3 (PT2, general filter).
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p1669 Current setpoint filter 3 0.001 10.000 0.300 - Float IM T, U
denominator damping
Description: Sets the denominator damping for current setpoint filter 3.
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
p1670 Current setpoint filter 3 0.5 16000.0 1000.0 Hz Float IM T, U
numerator natural fre-
quency
Description: Sets the numerator natural frequency for current setpoint filter 3 (general filter).
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
p1671 Current setpoint filter 3 0.000 10.000 0.010 - Float IM T, U
numerator damping
Description: Sets the numerator damping for current setpoint filter 3.
Dependency: Current setpoint filter 3 is activated via p1656.2 and parameterized via p1668 ... p1671.
p1673 Current setpoint filter 4 0.5 16000.0 1000.0 Hz Float IM T, U
denominator natural fre-
quency
Description: Sets the denominator natural frequency for current setpoint filter 4 (PT2, general filter).
Dependency: Current setpoint filter 4 is activated via p1656.3 and parameterized via p1673 ... p1675.
p1674 Current setpoint filter 4 0.001 10.000 0.300 - Float IM T, U
denominator damping
Description: Sets the denominator damping for current setpoint filter 4.
Dependency: Current setpoint filter 4 is activated via p1656.3 and parameterized via p1673 ... p1675.
p1675 Current setpoint filter 4 0.5 16000.0 1000.0 Hz Float IM T, U
numerator natural fre-
quency
Description: Sets the numerator natural frequency for current setpoint filter 4 (general filter).
Dependency: Current setpoint filter 4 is activated via p1656.3 and parameterized via p1673 ... p1675.
p1676 Current setpoint filter 4 0.000 10.000 0.010 - Float IM T, U
numerator damping
Description: Sets the numerator damping for current setpoint filter 4.
Dependency: Current setpoint filter 4 is activated via p1656.3 and parameterized via p1673 ... p1675.
p2153 Speed actual value filter 0 1000000 0 ms Float IM T, U
time constant
Description: Sets the time constant of the PT1 element to smooth the speed / velocity actual value.
The smoothed actual speed/velocity is compared with the threshold values and is only used for messages and
signals.
p2161 * Speed threshold 3 0.00 210000.00 10.00 rpm Float IM T, U
Description: Sets the speed threshold value for the signal that indicates the axis is stationary.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2162 * Hysteresis speed n_act > 0.00 60000.00 0.00 rpm Float IM T, U
n_max
Description: Sets the hysteresis speed (bandwidth) for the signal "n_act > n_max".
Note:
For a negative speed limit, the hysteresis is effective below the limit value and for a positive speed limit above
the limit value.
If significant overshoot occurs in the maximum speed range (for example, due to load shedding), you are
advised to increase the dynamic response of the speed controller (if possible). If this is insufficient, the hyste-
resis p2162 can only be increased by more than 10% of the rated speed when the maximum speed of the
motor is sufficiently greater than the speed limit p1082.
The range of the parameter is different when connect with different motors.
p2525 LR encoder adjustment 0 429496729 0 LU U32 IM T
offset 5
Description: For the absolute encoder adjustment, a drive determines the position offset.
Note: The position offset is only relevant for absolute encoders. The drive determines it when making the
adjustment and the user should not change it.
p2533 LR position setpoint filter 0.00 1000.00 0.00 ms Float IM T, U
time constant
Description: Sets the time constant for the position setpoint filter (PT1).
Note: The effective Kv factor (position loop gain) is reduced with the filter.
This allows a softer control behavior with improved tolerance with respect to noise/disturbances.
Applications:
- Reduces the pre-control dynamic response.
- Jerk limiting.
p2542 * LR standstill window 0 214748364 1000 LU U32 IM T, U
7
Description: Sets the standstill window for the standstill monitoring function.
After the standstill monitoring time expires, it is cyclically checked whether the difference between the setpoint
and actual position is located within the standstill window and, if required, an appropriate fault is output.
Value = 0: The standstill monitoring is deactivated.
Dependency: Refer to: p2543, p2544, and F07450
Note: The following applies for the setting of the standstill and positioning window:
Standstill window (p2542) ≥ positioning window (p2544)
p2543 * LR standstill monitoring 0.00 100000.00 200.00 ms Float IM T, U
time
Description: Sets the standstill monitoring time for the standstill monitoring function.
After the standstill monitoring time expires, it is cyclically checked whether the difference between the setpoint
and actual position is located within the standstill window and, if required, an appropriate fault is output.
Dependency: Refer to: p2542, p2545, and F07450
Note: The following applies for the setting of the standstill and positioning monitoring time:
Standstill monitoring time (p2543) ≤ positioning monitoring time (p2545)
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2544 * LR positioning window 0 214748364 40 LU U32 IM T, U
7
Description: Sets the positioning window for the positioning monitoring function.
After the positioning monitoring time expires, it is checked once as to whether the difference between the
setpoint and actual position lies within the positioning window and if required an appropriate fault is output.
Value = 0 --> The positioning monitoring function is de-activated.
Dependency: Refer to F07451.
Note: The following applies for the setting of the standstill and positioning window:
Standstill window (p2542) ≥ positioning window (p2544)
p2545 * LR positioning monitoring 0.00 100000.00 1000.00 ms Float IM T, U
time
Description: Sets the positioning monitoring time for the positioning monitoring.
After the positioning monitoring time expires, it is checked once as to whether the difference between the
setpoint and actual position lies within the positioning window and if required an appropriate fault is output.
Dependency: The range of p2545 depends on p2543.
Refer to: p2543, p2544, F07451
Note: The tolerance bandwidth is intended to prevent the dynamic following error monitoring incorrectly re-
sponding due to operational control sequences (for example, during load surges).
p2546 * LR dynamic following 0 214748364 1000 LU U32 IM T, U
error monitoring tolerance 7
Description: Sets the tolerance for the dynamic following error monitoring.
If the dynamic following error (r2563) exceeds the selected tolerance, then an appropriate fault is output.
Value = 0 --> The dynamic following error monitoring is de-activated.
Dependency: Refer to r2563, F07452
Note: The tolerance bandwidth is intended to prevent the dynamic following error monitoring incorrectly re-
sponding due to operational control sequences (e.g. during load surges).
p2571 IPos maximum velocity 1 40000000 30000 100 U32 IM T, U
0
LU/
min
Description: Sets the maximum velocity for the "basic positioner" function (IPos).
Note: The maximum velocity is active in all of the operating modes of the basic positioner.
The maximum velocity for the basic positioner should be aligned with the maximum speed/velocity of the
speed/velocity controller.
p2572 ** IPos maximum accelera- 1 2000000 Motor 100 U32 IM T
tion de- 0
pendent LU/s
²
Description: Sets the maximum acceleration for the "basic positioner" function (IPos).
Note: The maximum acceleration appears to exhibit jumps (without jerk).
"Traversing blocks" operating mode:
The programmed acceleration override acts on the maximum acceleration.
"Direct setpoint input/MDI" mode:
The acceleration override is effective.
"Jog" and "search for reference" modes:
No acceleration override is active. The axis starts with the maximum acceleration.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2573 ** IPos maximum decelera- 1 2000000 Motor 100 U32 IM T
tion de- 0
pendent LU/s
²
Description: Sets the maximum deceleration for the "basic positioner" function (IPos).
Note: The maximum deceleration appears to exhibit jumps (without jerk).
"Traversing blocks" operating mode:
The programmed deceleration override acts on the maximum deceleration.
"Direct setpoint input/MDI" mode:
The deceleration override is effective.
"Jog" and "search for reference" modes:
No deceleration override is effective. The axis brakes with the maximum deceleration.
p2574 IPOS jerk limiting 1 100000000 10000 100 U32 IM T, U
0
LU/s
3
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2583 EPOS backlash compen- -200000 200000 0 LU I32 IM T, U
sation
Description: Sets the amount of play (backlash) for positive or negative play.
• = 0: The backlash compensation is de-activated.
• > 0: Positive backlash (normal case)
When the direction is reversed, the encoder actual value leads the actual value.
• < 0: Negative backlash
When the direction is reversed, the actual value leads the encoder actual value.
Dependency: If a stationary axis is referenced by setting the reference point, or an adjusted with absolute
encoder is powered up, then the setting of p2604 is relevant for entering the compensation value.
p2604 = 1:
Traveling in the positive direction -> A compensation value is immediately entered.
Traveling in the negative direction -> A compensation value is not entered
p2604 = 0:
Traveling in the positive direction -> A compensation value is not entered
Traveling in the negative direction -> A compensation value is immediately entered.
When again setting the reference point (a referenced axis) or for "flying referencing", p2604 is not relevant but
instead the history of the axis.
Refer to p2604
p2599 EPOS reference point -2147482648 214748264 0 LU I32 IM T, U
coordinate value 7
Description: Sets the position value for the reference point coordinate. This value is set as the actual axis
position after referencing or adjustment.
Dependency: Refer to p2525
p2600 EPOS search for refer- -2147482648 214748264 0 LU I32 IM T, U
ence point offset 7
Description: Sets the reference point offset for search for reference.
p2604 EPOS search for refer- - - 0 - U32/Bina IM T
ence start direction ry
Description: Sets the signal sources for the start direction of the search for reference.
• 1 signal: Start in the negative direction.
• 0 signal: Start in the positive direction.
Dependency: Refer to p2583
p2605 EPOS search for refer- 1 40000000 5000 100 U32 IM T, U
ence approach velocity 0
reference cam LU/
min
Description: Sets the approach velocity to the reference cam for the search for reference.
Dependency: The search for reference only starts with the approach velocity to the reference cam when there
is a reference cam.
Refer to p2604, p2606
Note: When traversing to the reference cam, the velocity override is effective. If, at the start of the search for
reference, the axis is already at the reference cam, then the axis immediately starts to traverse to the zero
mark.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2606 EPOS search for refer- 0 214748264 214748 LU U32 IM T, U
ence reference cam max- 7 2647
imum distance
Description: Sets the maximum distance after the start of the search for reference when traversing to the
reference cam.
Dependency: Refer to p2604, p2605, F07458
Note: When using a reversing cam, the maximum distance must be set appropriately long.
p2608 EPOS search for refer- 1 40000000 300 100 U32 IM T, U
ence approach velocity 0
zero mark LU/
min
Description: Sets the approach velocity after detecting the reference cam to search for the zero mark for the
search for reference.
Dependency: If there is no reference cam, the search for reference immediately starts with the axis traversing
to the zero mark.
Refer to p2604, p2609
Caution: If the reference cam is not adjusted so that at each search for reference the same zero mark for
synchronization is detected, then an "incorrect" axis reference point is obtained.
After the reference cam has been left, the search for the zero mark is activated with a time delay due to inter-
nal factors. This is the reason that the reference cam should be adjusted in this center between two zero
marks and the approach velocity should be adapted to the distance between two zero marks.
Note: The velocity override is not effective when traversing to the zero mark.
p2609 EPOS search for refer- 0 214748264 20000 LU U32 IM T, U
ence max. distance ref. 7
cam and zero mark
Description: Sets the maximum distance after leaving the reference cam when traversing to the zero mark.
Dependency: Refer to p2604, p2608, F07459
p2611 EPOS search for refer- 1 40000000 300 100 U32 IM T, U
ence approach velocity 0
reference point LU/
min
Description: Sets the approach velocity after detecting the zero mark to approach the reference point.
Dependency: Refer to p2604, p2609
Note: When traversing to the reference point, the velocity override is not effective.
p2617[0... EPOS traversing block -2147482648 214748264 0 LU I32 IM T, U
7] position 7
Description: Sets the target position for the traversing block.
Dependency: Refer to p2618
Note: The target position is approached in either relative or absolute terms depending on p29241.
p2618[0... EPOS traversing block 1 40000000 600 100 I32 IM T, U
7] velocity 0
LU/
min
Description: Sets the velocity for the traversing block.
Dependency: Refer to p2617
Note: The velocity can be influenced using the velocity override (p2646).
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p2691 MDI speed fixed setpoint 1 40000000 600 100 U32 IM T, U
0
LU/
min
Description: Sets a fixed setpoint for the speed.
p2692 MDI acceleration over- 0.100 100.000 100.000 % Float IM T, U
ride, fixed setpoint
Description: Sets a fixed setpoint for the acceleration override.
Note: The percentage value refers to the maximum acceleration (p2572).
p2693 MDI deceleration over- 0.100 100.000 100.000 % Float IM T, U
ride, fixed setpoint
Description: Sets a fixed setpoint for the deceleration override.
Note: The percentage value refers to the maximum deceleration (p2573).
p29000 * Motor ID 0 65535 0 - U16 IM T
Description: Motor type number is printed on the motor rating plate as motor ID.
For a motor with an incremental encoder, users need to manually input the parameter value. The range of
high inertia motor is 18 to 39; the range of low inertia motor is 42 to 71.
For a motor with an absolute encoder, the drive automatically reads the parameter value. The range of high
inertia motor with multi-turn encoder is 10009 to 10048.
p29001 Reversal of motor direc- 0 1 0 - I16 IM T
tion
Description: Reversal of motor running direction. By default, CW is the positive direction while CCW the nega-
tive direction. After changing of p29001, reference point will lost, A7461 will remind user to referencing again.
• 0: No reversal
• 1: Reverse
p29002 BOP display selection 0 4 0 - I16 IM T, U
Description: Selection of BOP operating display.
• 0: Actual speed (default)
• 1: DC voltage
• 2: Actual torque
• 3: Actual position
• 4: Position following error
p29003 Control mode 0 8 0 - U16 RE T
Description: Selection of control mode.
• 0: Position control with pulse train input (PTI)
• 1: Internal position control (IPos)
• 2: Speed control (S)
• 3: Torque control (T)
• 4: Control change mode: PTI/S
• 5: Control change mode: IPos/S
• 6: Control change mode: PTI/T
• 7: Control change mode: IPos/T
• 8: Control change mode: S/T
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
Note: The compound control mode can be controlled by the digital input signal C-MODE. When DI10 (C-
MODE) is 0, the first control mode of control change mode is selected; otherwise, the second one is selected.
p29004 RS485 address 1 31 1 - U16 RE T
Description: Configuration of the RS485 bus address. The RS485 bus is used to transfer current absolute
position of the servo drive to the controller/PLC.
Note: Changes only become effective after power on. The parameter isn't influenced by default function.
p29005 Braking resistor capacity 1 100 100 % Float IM T
percentage alarm thresh-
old
Description: Alarm triggering threshold for the capacity of the internal braking resistor.
Alarm number: A52901
p29006 Line supply voltage 200 480 400 V U16 IM T
Description: Nominal Line supply voltage, effective value of line to line voltage. Drive can operate within -15%
to +10% error.
For V90 400 V variant, the value range is 380 V to 480 V, default value is 400 V.
For V90 200 V variant, the value range is 200 V to 240 V, default value is 230 V.
p29007 RS485 protocol 0 2 1 - I16 RE T
Description: Set the communication protocol for the field bus interface:
• 0: No protocol
• 1: USS
• 2: Modbus
Note: Changes only become effective after power on. The parameter isn't influenced by default function.
p29008 Modbus control source 1 2 2 - I16 RE T
Description: Select the Modbus control source:
• 1: Setpoint and control word from Modbus PZD
• 2: No control word
– No setpoint and control word from Modbus PZD
Note: Changes only become effective after power on.
p29009 RS485 baud rate 5 13 8 - I16 RE T
Description: Set the baud rate for the RS485 interface:
• 5: 4800 baud
• 6: 9600 baud
• 7: 19200 baud
• 8: 38400 baud
• 9: 57600 baud
• 10: 76800 baud
• 11: 93750 baud
• 12: 115200 baud
• 13: 187500 baud
Note: The change only becomes effective after power on. The parameter is not influenced by default function.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29010 PTI: Selection of input 0 3 0 - U16 RE T
pulse form
Description: Selection of setpoint pulse train input form. After changing of p29010, reference point will lost,
A7461 will remind user to referencing again.
• 0: Pulse + direction, positive logic
• 1: AB phase, positive logic
• 2: Pulse + direction, negative logic
• 3: AB phase, negative logic
p29011 PTI: Number of Setpoint 0 16777215 0 - U32 IM T
Pulse Per Revolution
Description: The number of setpoint pulses per motor revolution. The servo motor rotates for one revolution
when the number of the setpoint pulses reaches this value.
When this value is 0, the number of required setpoint pulses is decided by the electronic gear ratio.
p29012[0.. PTI: Numerator of Elec- 1 10000 1 - U32 IM T
.3] tronic Gear
Description: The numerator of the electronic gear ratio for the setpoint pulses. For the servo system with an
absolute encoder, the value range of p29012 is 1 to 10000.
Four numerators in total are available. You can select one of the numerators by configuring the digital input
signal EGEAR.
For detailed information about the calculation of a numerator, refer to the SINAMICS V90 Operating Instruc-
tions or use SINAMICS V-ASSISTANT to do the calculation.
p29013 PTI: Denominator of 1 10000 1 - U32 IM T
Electronic Gear
Description: The denominator of the electronic gear for the setpoint pulses.
p29014 PTI: Selection of Pulse 0 1 1 - I16 IM T
input Electrical Level
Description: Selection of a logic level for the setpoint pulses.
• 0: 5 V
• 1: 24 V
p29016 PTI: Pulse Input Filter 0 1 [0] 0 - I16 IM T
Description: Select filter for PTI input to get better EMC performance, 0 for low frequency PTI input, 1 for high
frequency PTI input.
p29019 RS485 monitor time 0 1999999 0 ms Float IM T
Description: Sets the monitoring time to monitor the process data received via the RS485 bus interface. If no
process data is received within this time, then an appropriate message is output.
Note: If p29019 = 0, monitoring is deactivated.
p29020[0.. Tuning: Dynamic factor 1 35 18 - U16 IM T, U
.1] Description: The dynamic factor of auto tuning. 35 dynamic factors in total are available.
Index:
• [0]: Dynamic factor for one-button auto tuning
• [1]: Dynamic factor for real-time auto tuning
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29021 Tuning: Mode Selection 0 5 0 - I16 IM T
Description: Selection of a tuning mode.
• 0: Disabled
• 1: One-button auto tuning
• 3: Real-time auto tuning
• 5: Disable with default controller parameters
p29022 Tuning: Ratio of Total 1.00 10000.00 1.00 - Float IM T, U
Inertia Moment to Motor
Inertia Moment
Description: Ratio of total inertia moment to servo motor inertia moment.
p29023 Tuning: One-button auto 0 0xffff 0x0007 - U16 IM T, U
tuning configuration
Description: One-button auto tuning configuration.
• Bit 0: The speed controller gain is determined and set using a noise signal.
• Bit 1: Possible required current setpoint filters are determined and set using a noise signal. As a conse-
quence, a higher dynamic performance can be achieved in the speed control loop.
• Bit 2: The inertia moment ratio (p29022) can be measured after this function is running. If not set, the iner-
tia moment ratio must be set manually with p29022.
• Bit 7: With this bit set, multi-axes are adapted to the dynamic response set in p29028. This is necessary
for interpolating axes. The time in p29028 should be set according to the axis with the lowest dynamic re-
sponse.
p29024 Tuning: Real-time auto 0 0xffff 0x004c - U16 IM T
tuning configuration
Description: Real-time auto tuning configuration.
• Bit 2: The inertia moment ratio (p29022) is estimated while the motor is runing, if not set, the inertia mo-
ment ratio must be set manually with p29022.
• Bit 3: If not set, the inertia moment ratio (p29022) is estimated only once and the inertia estimator is deac-
tivated automatically after the estimation is completed. If the bit is set to 1, the inertia moment ratio is esti-
mated in real time and the controller adapts the parameters continuously. You are recommended to save
the parameters when the estimation result is satisfied. After that, when you power on the drive next time,
the controller will be started with the optimized parameters.
• Bit 6: The adaption of current setpoint filter. This adaption may be necessary if a mechanical resonace
frequency changes in operation. It can also be used to dampen a fixed resonace frequency. Once the con-
trol loop has stabilized, this bit should be deactivated and to save parameters in a non-volatile memory.
• Bit 7: With this bit set, multi-axes are adapted to the dynamic response set in p29028. This is necessary
for interpolating axes. The time in p29028 should be set according to the axis with the lowest dynamic re-
sponse.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29025 Tuning: Configuration 0 0x003f 0x0004 - U16 IM T, U
overall
Description: Overall configuration of auto tuning, apply for both one-button and real-time auto tuning.
• Bit 0: For significant differences between the motor and load moment of inertia, or for low dynamic perfor-
mance of the controller, then the P controller becomes a PD controller in the position control loop. As a
consequence, the dynamic performance of the position controller is increased. This function should only
be set when the speed pre-control (bit 3 = 1) or the torque pre-control (bit 4 = 1) is active.
• Bit 1: At low speeds, the controller gain factors are automatically reduced in order to avoid noise and oscil-
lation at standstill. This setting is recommended for incremental encoders.
• Bit 2: The estimated load moment of inertia is taken into account for the speed controller gain.
• Bit 3: Activates the speed pre-control for the position controller.
• Bit 4: Activates the torque pre-control for the position controller.
• Bit 5: Adapts acceleration limit.
p29026 Tuning: Test signal dura- 0 5000 2000 ms U32 IM T
tion
Description: The duration time of the one-button auto tuning test signal.
p29027 Tuning: Limit rotation of 0 3000 0 ° U32 IM T
motor
Description: The limit position with motor rotations during one-button auto tuning. The traversing range is
limited within +/- p29027 degrees (motor run one revolution is 360 degree).
p29028 Tuning: Pre-control time 0.0 60.0 7.5 ms Float IM T, U
constant
Description: Sets the time constant for the pre-control symmetrization for auto tuning.
As a consequence, the drive is allocated a defined, dynamic response via its pre-control.
For drives, which must interpolate with one another, the same value must be entered.
The higher this time constant is, the smoother the drive will follow the position set point.
Note: This time constant is only effective when multi-axis interpolation is selected (bit 7 of p29023 and
p29024).
p29030 PTO: Number of pulse 0, 30 16384 1000 - U32 IM T
per revolution
Description: Number of output pulses per motor revolution.
If this value is 0, the number of required output pulses is decided by the electronic gear ratio.
p29031 PTO: Numerator of elec- 1 214700000 1 - U32 IM T
tronic gear 0
Description: The numerator of the electronic gear ratio for the output pulses.
For detailed information about the calculation of a numerator, refer to the SINAMICS V90 Operating Instruc-
tions or use the SINAMICS V-ASSISTANT to do the calculation.
p29032 PTO: Denominator elec- 1 214700000 1 - U32 IM T
tronic gear 0
Description: The denominator of the electronic gear ratio for the output pulses.
For detailed information about the calculation of a denominator, refer to the SINAMICS V90 Operating Instruc-
tions or use the SINAMICS V-ASSISTANT to do the calculation.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29033 PTO: Direction change 0 1 0 - I16 IM T
Description: Select the PTO direction.
• 0: PTO positive
PTO direction does not change. PTO A leads PTO B with 90 degrees when the motor rotates in clockwise
direction. PTO B leads PTO A with 90 degrees when the motor rotates in counter- clockwise direction.
• 1: PTO negative
PTO direction changes. PTO A leads PTO B with 90 degrees when the motor rotates in counter-clockwise
direction. PTO B leads PTO A with 90 degrees when the motor rotates in clockwise direction.
p29035 VIBSUP activation 0 1 0 - I16 IM T
Description: Select the VIBSUP on/off.
Position setpoint filter can be activated (p29035) for IPos control mode.
• 0: Disable
With this parameter, you can specify the torque setpoint corresponding to full analog input (10 V).
• [1]The scaling for the analog torque limit.
With this parameter, you can specify the torque limit corresponding to full analog input (10 V).
You can select the internal parameters or the analog input as the source of the torque limit with the combi-
nation of the digital input signals TLIM1 and TLIM2.
Index:
[0]: Torque set scale
[1]: Torque limit scale
p29042 Offset Adjustment for -0.50 0.50 0.00 V Float IM T
Analog input 2
Description: Offset adjustment for the analog input 2.
p29043 Fixed Torque Setpoint -100 100 0 % Float IM U, T
Description: Fixed torque setpoint.
You can select the internal parameters or the analog input as the source of the torque setpoint by configuring
the digital input signal TSET.
p29050[0.. Torque limit upper -150 300 300 % Float IM T
.2] Description: Positive torque limit.
Three internal torque limits in total are available.
You can select the internal parameters or the analog input as the source of the torque limit with the combina-
tion of the digital input signals TLIM1 and TLIM2.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29051[0.. Torque limit lower -300 150 -300 % Float IM T
.2] Description: Negative torque limit.
Three internal torque limits in total are available.
You can select the internal parameters or the analog input as the source of the torque limit with the combina-
tion of the digital input signals TLIM1 and TLIM2.
p29060 * Speed Scaling 6 210000 3000 rpm Float IM T
Description: The scaling for the analog speed setpoint.
With this parameter, you can specify the speed setpoint corresponding to full analog input (10 V).
p29061 Offset Adjustment for -0.50 0.50 0.00 V Float IM T
Analog input 1
Description: Offset adjustment for the analog input 1.
p29070[0.. Speed limit positive 0 210000 210000 rpm Float IM T
.2] * Description: Positive speed limit.
Three internal speed limits in total are available.
You can select the internal parameters or the analog input as the source of the speed limit with the combina-
tion of the digital input signals SLIM1 and SLIM2.
p29071[0.. Speed limit negative -210000 0 - rpm Float IM T
.2] * 210000
Description: Negative speed limit.
Three internal speed limits in total are available.
You can select the internal parameters or the analog input as the source of the speed limit with the combina-
tion of the digital input signals SLIM1 and SLIM2.
p29075 Speed Clamp Threshold 0 200 200 rpm Float IM T
Description: The threshold for the zero speed clamp.
If the function of zero speed clamp has been enabled under the speed control mode, the motor speed is
clamped to 0 when both the setpoint speed and the actual speed are below this threshold.
p29078 Speed Reach Threshold 0.0 100.0 10 rpm Float IM T
Description: Speed reached range (deviation between setpoint and motor speed)
p29080 Overload Threshold for 10 300 100 % Float IM T
Output Signal Triggering
Description: Overload threshold for the output power.
p29090 Offset Adjustment for -0.50 0.50 0.00 V Float IM T
Analog output 1
Description: Offset adjustment for analog output 1.
p29091 Offset Adjustment for -0.50 0.50 0.00 V Float IM T
Analog output 2
Description: Offset adjustment for analog output 2.
p29110[0.. Position Loop Gain 0.000 300.000 [0] 100 Float IM T, U
.1] ** Motor 0/mi
de- n
pendent
[1]
1.000
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
Description: Position loop gain.
Two position loop gains in total are available. You can switch between these two gains by configuring the
digital input signal G-CHANGE or setting relevant condition parameters.
The first position loop gain is the default setting.
Dependency: The parameter value will be set to default after configuring a new motor ID (p29000).
p29111 Speed Pre-control Factor 0.00 200.00 0.00 % Float IM T, U
(Feed Forward)
Description: Setting to activate and weight the speed pre-control value. Value = 0 % --> The pre-control is de-
activated.
p29120[0.. Speed Loop Gain 0.00 999999.00 [0] Nms Float IM T, U
.1] ** Motor /rad
de-
pendent
[1] 0.30
Description: Speed loop gain.
Two speed loop gains in total are available. You can switch between these two gains by configuring the digital
input signal G-CHANGE or setting relevant condition parameters.
The first speed loop gain is the default setting.
Dependency: The parameter value will be set to default after configuring a new motor ID (p29000).
p29121[0.. Speed Loop Integral time 0.00 100000.00 [0] 15 ms Float IM T, U
.1] * [1] 20
Description: Speed loop integral time.
Two speed loop integral time values in total are available. You can switch between these two time values by
configuring the digital input signal G-CHANGE or setting relevant condition parameters.
The first speed loop integral time is the default setting.
Dependency: The parameter value will be set to default after configuring a new motor ID (p29000).
p29130 Gain Switching: Mode 0 4 0 - I16 IM T
Selection
Description: Selects gain switching mode.
• 0: Disabled
• 1: Switch through DI-G-CHANG
• 2: Position deviation as switch condition
• 3: Pulse input frequency as switch condition
• 4: Actual speed as switch condition
Note: Only when the auto tuning function (p20021=0) is disabled can the gain switching function be used.
p29131 Gain Switching Condition: 0 214748364 100 LU I32 IM T
Pulse Deviation 7
Description: Triggers position deviation threshold for gain switching. If the gain switching function is enabled
and this condition is selected:
• Switch from the first group of control parameters to the second group when the position deviation is larger
than the threshold.
• Switch from the second group of control parameters to the first group when the position deviation is small-
er than the threshold.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29132 Gain Switching Condition: 0 214700006 100 100 Float IM T
Position Setpoint Fre- 4 0
quency LU/
min
Description: Triggers pulse input frequency (PTI) threshold or internal position speed (IPos) threshold for gain
switching. If the gain switching function is enabled and this condition is selected:
1. PTI
– Switch from the first group of control parameters to the second group when the pulse train input pulse
is higher than the threshold.
– Switch from the second group of control parameters to the first group when the pulse train input is low-
er than the threshold.
2. IPos
– Switch from the first group of control parameters to the second group when the speed of fixed position
setpoint is larger than the threshold.
– Switch from the second group of control parameters to the first group when the IPos is smaller than the
threshold.
p29133 Gain Switching Condition: 0 214700006 100 rpm Float IM T
Actual Speed 4
Description: Triggers speed threshold for gain switching. If the gain switching function is enabled and this
condition is selected:
• Switch from the first group of control parameters to the second group when the actual motor speed is
larger than the threshold.
• Switch from the second group of control parameters to the first group when the actual motor speed is
smaller than the threshold.
p29139 Gain switching Time 8 1000 20 ms Float IM T
Constant
Description: Time constant for gain switching. Set this parameter to avoid frequent gain switches that reduces
system reliability.
p29140 PI to P: Mode Selection 0 5 0 - U16 IM T
Description: Selects a condition for the switch from PI control to P control under the speed loop.
• 0: Disabled
• 1: Torque is higher than a parameterizable setting value.
• 2: Using the digital input signal (G-CHANGE).
• 3: Speed is higher than a parameterizable setting value.
• 4: Acceleration is higher than a parameterizable setting value.
• 5: Pulse deviation is higher than a parameterizable setting value.
Note: Only when the auto tuning function (p29021=0) and gain switching function are both disabled can the
PI/P switching function be used.
p29141 PI to P Switching Condi- 0 300 200 % Float IM T
tion: Torque
Description: Triggers torque threshold for PI/P switching. If the PI/P switching function is enabled and this
condition is selected:
• Switch from the PI control to the P control when the actual torque is larger than the threshold.
• Switch from the P control to the PI control when the actual torque is smaller than the threshold.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29142 PI to P Switching Condi- 0 210000 2000 rpm Float IM T
tion: Speed
Description: Triggers speed threshold for PI/P switching. If the PI/P switching function is enabled and this
condition is selected:
• Switch from the PI control to the P control when the actual speed is larger than the threshold.
• Switch from the P control to the PI control when the actual speed is smaller than the threshold.
p29143 PI to P Switching Condi- 0 30000 20 rev/ Float IM T
tion: Acceleration s²
Description: Triggers acceleration threshold for PI/P switching. If the PI/P switching function is enabled and
this condition is selected:
• Switch from the PI control to the P control when the actual acceleration is larger than the threshold.
• Switch from the P control to the PI control when the actual acceleration is smaller than the threshold.
p29144 PI to P Switching Condi- 0 214748364 30000 LU U32 IM T
tion: Pulse Deviation 7
Description: Triggers pulse deviation threshold for PI/P switching. If the PI/P switching function is enabled and
this condition is selected:
• Switch from the PI control to the P control when the actual pulse deviation is larger than the threshold.
• Switch from the P control to the PI control when the actual pulse deviation is smaller than the threshold.
p29230 MDI direction selection 0 2 0 - I16 IM T
Description: MDI direction selection:
• 0: absolute positioning through the shortest distance
• 1: absolute positioning through the positive direction
• 2: absolute positioning through the negative direction
p29240 Select Referencing Mode 0 4 1 - I16 IM T
Description: Selects referencing mode.
• 0: referencing with external signal REF
• 1: referencing with external reference cam (signal REF)
• 2: referencing with zero mark only
• 3: referencing with external reference cam (CCWL) and zero mark
• 4: referencing with external reference cam (CWL) and zero mark
p29241 Motion Mode 0 3 0 - U16 IM T
Description: Moves mode set for IPos:
• 0: means relative moving
• 1: means abs moving
• 2: POS Mod
• 3: NEG Mod
p29242 CLR Pulse Mode 0 2 0 - U16 IM T
Description: Select clear pulse mode
• 0: disabled
• 1: means clear pulse on high level
• 2: means clear pulse on rising edge
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29243 Positioning tracking acti- 0 1 0 - I16 IM T
vate
Description: Activation of position tracking.
• 0: deactivated
• 1: activated
p29244 Absolute encoder virtual 0 4096 0 - U32 IM T
rotary revolutions
Description: Sets the number of rotations that can be resolved for an encoder with activated position tracking
function (p29243 = 1).
p29245 Axis mode state 0 1 0 - U32 IM T
Description: Linear/modulo mode
• 0: linear axis
• 1: modulo axis
p29246 * EPOS modulo correction 1 214748264 360000 LU U32 IM T
module range 7
Description: Sets the modulo range for axes with modulo correction.
p29247 * Mechanical gear: pulse 1 214748364 10000 - U32 IM T
per revolution 7
Description: LU per load revolution
p29248 * Mechanical gear: numer- 1 1048576 1 - U32 IM T
ator
Description: (Load/Motor) Load revolutions
p29249 * Mechanical gear: denom- 1 1048576 1 - U32 IM T
inator
Description: (Load/Motor) Motor revolutions
p29250 PTI Absolute Position 0 1 0 - U32 RE T
Mode Enable
Description: Absolute Position Mode Enable.
• =1 Enable Absolute Mode
• =0 Disable Absolute Mode
p29300 Digital Input Forced Sig- 0 127 0 - U32 IM T, U
nals
Description: Input signals are forced to be high. 7 bits in total.
• Bit 0: SON
• Bit 1: CWL
• Bit 2: CCWL
• Bit 3: TLIM1
• Bit 4: SPD1
• Bit 5: TSET
• Bit 6: EMGS
If one or more bits are set to be high, the corresponding input signals are forced to be logical high signals.
Note: The drive unit displays the value in hex format. To know the logic (high/low) assignment to each bit, you
must convert the hex number to the binary number, for example, FF (hex) = 11111111 (bin).
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29301[0.. Digital Input 1 Assign- 0 28 1 - I16 IM T
.3] ment
Description: Defines the function of digital input signal DI1 (PTI mode)
• SON 1
• RESET 2
• CWL 3
• CCWL 4
• G-CHANGE 5
• P-TRG 6
• CLR 7
• EGEAR1 8
• EGEAR2 9
• TLIMT1 10
• TLIMT2 11
• CWE 12
• CCWE 13
• ZSCLAMP 14
• SPD1 15
• SPD2 16
• SPD3 17
• TSET 18
• SLIMT1 19
• SLIMT2 20
• POS1 21
• POS2 22
• POS3 23
• REF 24
• SREF 25
• STEPF 26
• STEPB 27
• STEPH 28
Index:
• [0]: DI1 for Control mode 0
• [1]: DI1 for Control mode 1
• [2]: DI1 for Control mode 2
• [3]: DI1 for Control mode 3
p29302[0.. Digital Input 2 Assign- 0 28 2 - I16 IM T
.3] ment
Description: Defines the function of digital input signal DI2
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
Index:
• [0]: DI2 for Control mode 0
• [1]: DI2 for Control mode 1
• [2]: DI2 for Control mode 2
• [3]: DI2 for Control mode 3
p29303[0.. Digital Input 3 Assign- 0 28 3 - I16 IM T
.3] ment
Description: Defines the function of digital input signal DI3
Index:
• [0]: DI3 for Control mode 0
• [1]: DI3 for Control mode 1
• [2]: DI3 for Control mode 2
• [3]: DI3 for Control mode 3
p29304[0.. Digital Input 4 Assign- 0 28 4 - I16 IM T
.3] ment
Description: Defines the function of digital input signal DI4
Index:
• [0]: DI4 for Control mode 0
• [1]: DI4 for Control mode 1
• [2]: DI4 for Control mode 2
• [3]: DI4 for Control mode 3
p29305[0.. Digital Input 5 Assign- 0 28 [0] 5; [1] - I16 IM T
.3] ment 5; [2]
12; [3]
12
Description: Defines the function of digital input signal DI5
Index:
• [0]: DI5 for Control mode 0
• [1]: DI5 for Control mode 1
• [2]: DI5 for Control mode 2
• [3]: DI5 for Control mode 3
p29306[0.. Digital Input 6 Assign- 0 28 [0] 6; [1] - I16 IM T
.3] ment 6; [2]
13; [3]
13
Description: Defines the function of digital input signal DI6
Index:
• [0]: DI6 for Control mode 0
• [1]: DI6 for Control mode 1
• [2]: DI6 for Control mode 2
• [3]: DI6 for Control mode 3
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29307[0.. Digital Input 7 Assign- 0 28 [0] 7; [1] - I16 IM T
.3] ment 21; [2]
15; [3]
18
Description: Defines the function of digital input signal DI7
Index:
• [0]: DI7 for Control mode 0
• [1]: DI7 for Control mode 1
• [2]: DI7 for Control mode 2
• [3]: DI7 for Control mode 3
p29308[0.. Digital Input 8 Assign- 0 28 [0] 10; - I16 IM T
.3] ment [1] 22;
[2] 16;
[3] 19
Description: Defines the function of digital input signal DI8
Index:
• [0]: DI8 for Control mode 0
• [1]: DI8 for Control mode 1
• [2]: DI8 for Control mode 2
• [3]: DI8 for Control mode 3
p29330 Digital Output 1 Assign- 1 14 1 - I16 IM T
ment
Description: Defines the function of digital output signal DO1
• 1: RDY
• 2: FAULT
• 3: INP
• 4: ZSP
• 5: SPDR
• 6: TLR
• 7: SPLR
• 8: MBR
• 9: OLL
• 10: WARNING1
• 11: WARNING2
• 12: REFOK
• 13: CM_STA
• 14: RDY_ON
p29331 Digital Output 2 Assign- 1 14 2 - I16 IM T
ment
Description: Defines the function of digital output signal DO2
p29332 Digital Output 3 Assign- 1 14 3 - I16 IM T
ment
Description: Defines the function of digital output signal DO3
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29333 Digital Output 4 Assign- 1 14 5 - I16 IM T
ment
Description: Defines the function of digital output signal DO4
p29334 Digital Output 5 Assign- 1 14 6 - I16 IM T
ment
Description: Defines the function of digital output signal DO5
p29335 Digital Output 6 Assign- 1 14 8 - I16 IM T
ment
Description: Defines the function of digital output signal DO6
p29340 Warning 1 Assigned for 1 6 1 - U16 IM T
Digital Output
Description: Defines conditions for WRN1.
• 1: Motor overload protection warning: 85% of overload threshold has been reached.
• 2: Holding brake power overload warning: 85% of overload threshold has been reached.
• 3: Fan warning: fan has stopped for more than 1 s.
• 4: Encoder warning
• 5: Motor overtemperature warning: 85% of overtemperature threshold has been reached.
• 6: Capacitor service life warning: The capacitor has reached its expiry, so replace it.
p29341 Warning 2 Assigned for 1 6 2 - U16 IM T
Digital Output
Description: Defines conditions for WARNING2.
• 1: Motor overload protection warning: 85% of overload threshold has been reached.
• 2: Holding brake power overload warning: 85% of overload threshold has been reached.
• 3: Fan warning: life time of fan expired (40000 hours), replacement of fan needed.
• 4: Encoder warning
• 5: Motor overtemperature warning: 85% of overtemperature threshold has been reached.
• 6: Capacitor service life warning: The capacitor has reached its expiry, so replace it.
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p29350 Select sources for analog 0 12 0 - U16 IM T
output 1
Description: Selects signal source for analog output 1.
• 0: Actual speed (reference p29060)
• 1: Actual torque (reference 3 × r0333)
• 2: Speed setpoint (reference p29060)
• 3: Torque setpoint (reference 3 × r0333)
• 4: DC bus voltage (reference 1000 V)
• 5: Pulse input frequency (reference 1k)
• 6: Pulse input frequency (reference 10k)
• 7: Pulse input frequency (reference 100k)
• 8: Pulse input frequency (reference 1000k)
• 9: Remaining number of pulses (reference 1k)
• 10: Remaining number of pulses (reference 10k)
• 11: Remaining number of pulses (reference 100k)
• 12: Remaining number of pulses (reference 1000k)
p29351 Select Signal Source for 0 12 1 - U16 IM T
Analog 2
Description: Selects signals for analog output 2.
• 0: Actual speed (reference p29060)
• 1: Actual torque (reference 3 × r0333)
• 2: Speed setpoint (reference p29060)
• 3: Torque setpoint (reference 3 × r0333)
• 4: DC bus voltage (reference 1000 V)
• 5: Pulse input frequency (reference 1k)
• 6: Pulse input frequency (reference 10k)
• 7: Pulse input frequency (reference 100k)
• 8: Pulse input frequency (reference 1000k)
• 9: Remaining number of pulses (reference 1k)
• 10: Remaining number of pulses (reference 10k)
• 11: Remaining number of pulses (reference 100k)
• 12: Remaining number of pulses (reference 1000k)
p31581 VIBSUP: Filter type 0 1 0 - I16 IM T
Description: Sets the filter type for VIBSUP. Depending on the selected filter type, the VIBSUP filter results in
motion sequences that take somewhat longer.
• 0: The rugged VIBSUP filter has a lower sensitivity to frequency offsets compared with the sensitive filter
type, but results in a higher delay of the motion sequence. The total motion sequence is extended by the
time period Td (Td = 1/fd).
• 1: The sensitive VIBSUP filter has a higher sensitivity to frequency offsets compared with the rugged filter
type, but results in a lower delay of the motion sequence. The total motion sequence is extended by half
the time period Td/2 (Td = 1/fd).
Par. No. Name Min Max Factory Unit Data Effective Can be
Setting type changed
p31585 VIBSUP: Filter frequency 0.5 62.5 1 Hz Float 32 IM T
fd
Description: Sets the frequency of the damped natural vibration of the mechanical system. This frequency can
be determined by making the appropriate measurements.
Note: The maximum frequency that can be set depends on the filter sampling time.
p31586 VIBSUP: Filter damping 0.00 0.99 0.03 - Float 32 IM T
Description: Sets the value for the damping of the natural mechanical vibration to be filtered. Typically, the
damping value is about 0.03, and can be optimized by performing the appropriate positioning tests.
Read-only parameters
NOTICE
Faults have higher display priority than alarms
In the case that both faults and alarms occur, only faults are displayed until they have been
acknowledged.
● Alarms
● Alarms
Note
• If you do not eliminate the cause(s) of the fault, it can appear again after no button
operation for five seconds. Make sure that you have eliminated the cause(s) of the fault.
• You can acknowledge faults using RESET signal. For details of the signal, refer to DIs
(Page 92).
• You can acknowledge faults on the SINAMICS V-ASSISTANT. For details, refer to
SINAMICS V-ASSISTANT Online Help.
Two LED status indicators (RDY and COM) are available to indicate drive status. Both LEDs
are dual color (green/red).
You can find detailed information about the status indications in the table below:
Fault list
v = (p29244 * 29247)/p29246
F7443: Reference point coor- The reference point coordinate received Set the reference point coordinate to a lower
dinate not in the permissible when adjusting the encoder via connector value than specified in the fault value.
range input p2599 lies outside the half of the See also: p2599 (EPOS reference point coor-
Reaction: OFF1 (OFF2, encoder range and cannot be set as actual dinate value.
OFF3) axis position.
For a motor with an absolute encoder, the
Acknowledgement: maximum permissible encoder range is calcu-
IMMEDIATELY lated by the formula (4096xp29247)/2.
F7450: Standstill monitoring After the standstill monitoring time expired, Check the causes and resolve.
has responded the drive left the standstill window.
Reaction: OFF1 • Position loop gain too low.
Acknowledgement: • Position loop gain too high (instabil-
IMMEDIATELY ity/oscillation).
• Mechanical overload.
• Connecting cable, motor/drive convert-
er incorrect (phase missing, inter-
change).
Alarm list
Ball screw
Belt transmission
Rack and pinion and/or gear
2. Determine the operation pattern including such parameters as acceleration time (ta),
constant motion time (tu), deceleration time (td), stopping time (ts), cycle time (tc), and
travel distance (L).
Torque
● Summit torque: It refers to the maximum torque required by a motor in operation, which is
generally less than 80% of the motor’s maximum torque. When the torque is a negative
value, regenerative resistors may be needed.
● Moving torque and hold torque in standstill: It refers to the torque required by a motor in
long-term operation, which is generally less than 80% of the motor’s rated torque. When
the torque is a negative value, regenerative resistors may be needed.
Torque calculation methods of two major mechanism types:
● Effective torque: It refers to the continuous effective load torque converted into the
equivalent value on the servo motor shaft, which is generally less than 80% of the motor’s
rated torque.
Ta: Acceleration torque [N·m] ta: Acceleration time [s] tc: Cycle time [s]
Tm: Moving torque [N·m] tu: Constant motion time [s]
Td: Deceleration torque [N·m] td: Deceleration time [s]
Speed
Maximum speed: It refers to the motor's maximum speed in operation, which is generally
lower than the rated speed. When a motor operating at the maximum speed, pay attention to
its torque and temperature rise.
One-button auto tuning with resonance suppression Direction and stop, 209
(p29023.1=1), 261 External analog torque setpoint, 208
Real-time auto tuning with resonance suppression External speed limit, 179
(p29024.6=1), 262 Internal speed limit, 179
Response time, 243 Offset adjustment, 208
Risk analysis, 234 Torque control with fixed setpoint, 209
Risk reduction, 236 Torque setpoint, 208
Torque limit, 179
External torque limit, 181
S Internal torque limit, 180
Overall torque limit, 180
Safe Torque Off
Torque limit reached (TLR), 182
functional features, 243
Transmitting sequence for the absolute position
response time, 245
data, 225
selecting/deselecting STO, 245
Tuning
Safety Integrated function, 240
Configuration of dynamic factor, 252, 256
Safety of machinery in Europe, 228
Manual tuning, 259
Save parameters in the servo drive, 155
Real-time auto tuning, 255
Search a parameter in "P ALL" menu, 152
Servo gains, 248
Selection of control mode
Tuning methods, 249
Control mode change for a compound control
Tuning with SINAMICS V-ASSISTANT, 250
mode, 161
Control modes, 161
Selection of a basic control mode, 161
U
Servo ON signal, 162
Relevant parameter settings, 163 Update firmware, 157
Set parameter set to default, 155 Usage of the shielding plate, 85
Set zero position, 160 USS
Speed control mode Telegram format, 210
Direction and stop, 204
External speed setpoint, 202
Offset adjustment, 203 W
Parameter settings for fixed speed setpoint, 203
Wiring and connecting
Ramp-function generator, 205
Adjusting cable orientations, 86
Speed setpoint, 201
Wiring and connection
Zero speed clamp, 204
Connecting the motor holding brake - X7, 129
Speed limit, 178
Overall speed limit, 178
Standards for implementing safety-related
controllers, 230
Stopping method at servo OFF, 169
Coast-down, 170
Emergency stop, 170
Ramp-down (OFF1), 170
System connection, 81
T
Technical data
Cables, 66
Torque control mode
300% overload capacity, 207