TP6261 ConsiderUsingHarmonic 20061019 PDF
TP6261 ConsiderUsingHarmonic 20061019 PDF
Abstract—The terms “harmonic restraint” and “harmonic duced the idea of harmonic blocking instead of restraining [9]
blocking” are sometimes used interchangeably when talking with a relay that used only the second harmonic to block.
about transformer differential protection. This paper explores Many modern transformer differential relays employ either
the meanings of these terms and how these techniques are indi-
vidually applied in modern transformer differential relays, in-
harmonic restraint or blocking methods. These methods en-
cluding how these techniques affect the speed and security of sure relay security for a very high percentage of inrush cases.
transformer differential protection. The paper further compares However, these methods do not work in all cases, especially
these techniques using examples to show their response to several with very low harmonic content in the inrush current on one or
transformer inrush examples. two phases. Common harmonic restraint or blocking, intro-
Editorial Note—Guzman, Benmouyal, Zocholl, and Altuve duced by Einval and Linders [10], increased relay security for
prepared and presented a paper titled “Performance Analysis of
inrush but could delay operation for internal faults combined
Traditional and Improved Transformer Differential Protective
Relays” [1] that provides a thorough discussion about percentage with inrush in the nonfaulted phases.
restraint current differential relays and the history and back- Transformer overexcitation is another possible cause of dif-
ground surrounding the use of harmonics in these relays. Por- ferential relay undesired operation. Einval and Linders pro-
tions of that paper covering selected historical and fundamental posed the use of an additional fifth-harmonic restraint to pre-
background issues are used in this paper to reintroduce this sub- vent such operations [10]. Others have proposed several
ject for the reader’s convenience.
methods based on waveshape recognition to distinguish faults
from inrush and have applied these methods in transformer
I. INTRODUCTION
relays [11] [12] [13] [14]. However, these techniques gener-
Transformer differential relays are prone to undesired op- ally do not identify transformer overexcitation conditions.
eration in the presence of transformer inrush currents. Trans- Guzman, Benmouyal, Zocholl, and Altuve proposed a new
former energization is a typical cause of inrush currents, but approach for transformer differential protection using current-
any transient in the transformer circuit may generate these only inputs that combine harmonic restraint and blocking
currents. Other causes include voltage recovery after the methods with a waveshape recognition technique [1]. This
clearance of an external fault or the energization of a trans- method uses even harmonics for restraint and also blocks op-
former in parallel with a transformer that is already in service. eration using the dc component and the fifth harmonic.
Inrush currents result from transients in transformer mag-
netic flux before the flux reaches its steady-state value. Early II. TRANSFORMER DIFFERENTIAL PROTECTION
attempts to prevent differential relay operations caused by
Percentage restraint differential protective relays have been
inrush include the following:
in service for many years. Fig. 1 shows a typical differential
• Introducing an intentional time delay in the differen-
relay connection diagram. Differential relays sum the currents
tial relay [2] [3].
on each source or outlet associated with the device to deter-
• Desensitizing the relay for a given time to override the mine the difference between the current entering and leaving
inrush condition [3] [4]. the device. A substantial difference indicates a fault in the
• Adding a voltage signal to restrain [2] or to supervise device or between the current transformers (CTs) located
the differential relay [5]. around the device. A simple overcurrent relay element could
Ultimately, researchers recognized that the harmonic con- provide basic differential protection, provided the CTs could
tent of the inrush current provided information that helped be sized and connected to perfectly match the secondary cur-
differentiate internal faults from inrush conditions. Kennedy rent presented to the relay. Complexities associated with trans-
and Hayward proposed a differential relay with only harmonic former differential protection, such as tap changers, power
restraint for bus protection [6]. Hayward [7] and Mathews [8] transformer phase shift, and mismatched CT ratios, make it
further developed this method by adding percentage differen- nearly impossible to perfectly balance the CT secondary cur-
tial restraint for transformer protection. These early relays rents into the relay. For this reason, transformer differential
used all the harmonics to restrain. Sharp and Glassburn intro- relays use a percentage restraint characteristic that compares
an operating current with a restraining current. The operating
2
IOP is proportional to the fault current for internal faults and IW1 IW2
ideally approaches zero for any other operating conditions, IW1 + IW2 IRT
(Multiples
provided the “tap” settings for the relay current inputs are 2 of TAP)
properly selected to match the relative current measured by
Fig. 2. Percentage Current Differential Operate and Restraint Current Meas-
the relay on each current input for the normal, nonfault condi- urements
tion.
Equations (3) and (4) offer the advantage of being applica-
IW1 CT1 CT2 IW2 ble to differential relays with more than two restraint ele-
Power Transformer ments. The differential relay generates a tripping signal if the
operating current, IOP, is greater than a percentage, defined by
a slope setting, SLP, of the restraining current, IRT, as ex-
pressed by the following equation:
IOP > SLP ⋅ I RT (5)
Differential Relay
Another way to express this is:
IOP/ IRT > SLP
Fig. 1. Typical Differential Relay Connection Diagram
Fig. 3 shows a typical percentage restraint current differen-
Following are the most common ways to obtain the re- tial relay operating characteristic. This characteristic consists
straining current: of a straight line having a slope equal to SLP and a horizontal
r r straight line defining the relay minimum pickup current, IPU.
IRT = k IW1 − IW 2 (2)
The slope setting, SLP, is typically defined as a percentage,
IRT (r r
= k IW1 + IW 2 ) (3) which is the basis for the term “percentage restraint current
differential” relay. The minimum pickup setting, IPU, is typi-
IRT = Max ( rI
W1
r
, IW 2 ) (4) cally defined as per unit of operate current.
While the slope line typically extends to the origin, where
Where: k is a compensation factor usually taken as IOP and IRT are both zero, the minimum pickup current, IPU,
1 or 0.5. secures the relay against tripping for normal transformer exci-
More specifically, operate and restraint quantities are gen- tation current, low magnitude transformer inrush, and any CT
erated in a typical two-winding relay as shown in Fig. 2, performance differences at very low load currents. In addition,
where k = 1/2. the slope characteristic of the percentage differential relay
In Fig. 2, IWDG1 and IWDG2 are CT secondary currents provides further security for high current external faults with
measured by the relay from associated phases on the high and CT saturation. A variable-percentage or dual-slope character-
low side of the transformer. The TAP1 and TAP2 relay set- istic further increases relay security for heavy CT saturation.
tings are used to establish a per unit secondary current in the Fig. 3 shows this characteristic as a dotted line. For single- or
relay, equalized to compensate for the power transformer dual-slope characteristics, the relay operate (trip) region is
winding voltage ratio, and associated high- and low-side CT located above and to the left of the slope characteristic, and
ratios. Transformer/CT Connection Compensation provides the restraint region is below and to the right of the slope char-
the necessary angle and magnitude shift for delta- and wye- acteristic.
connected transformer windings and CTs. The resulting IOP
and IRT values are in multiples of TAP setting so they can be IOP
referenced to either current winding input. Operate Dual-Slope
Three single-phase relays with independent percentage cur- Region Characteristic
rent differential elements can be used to protect a three-phase
e2
p
Fig. 4 shows the logic used to derive the dual-slope charac- criminate inrush and overexcitation conditions from internal
teristic shown in Fig. 3. faults. However, this discrimination can be complicated by
other sources of distortion, such as CT saturation, nonlinear
IOPn + fault resistance, or system resonant conditions.
_ AND Trip
IRTn • f (SLP1, SLP2)
A. Inrush Currents
+ The study of transformer magnetization inrush phenomena
IPU _
has spanned many years. Magnetizing inrush occurs in a trans-
former whenever the polarity and magnitude of the residual
Fig. 4. Simplified Percentage Current Differential Decision Logic
flux do not agree with the polarity and magnitude of the ideal
Differential relays perform well for external faults as long instantaneous value of steady-state flux. Transformer energi-
as the CTs reproduce the primary currents correctly. When zation is a typical cause of inrush currents, but any transient in
one of the CTs saturates, or if both CTs saturate at different the transformer circuit may generate these currents. Other
levels, false operating current appears in the differential relay causes include voltage recovery after the clearance of an ex-
and could cause an undesired relay operation. Some differen- ternal fault or the energization of a transformer in parallel with
tial relays use the harmonics caused by CT saturation for a transformer that is already in service. The magnitudes and
added restraint and to avoid operations [6]. CT saturation is waveforms of inrush currents depend on a multitude of factors
only one of the causes of false operating current in differential and are almost impossible to predict [16]. The following
relays. In the case of power transformer applications, other summarizes the main characteristics of inrush currents:
possible sources of error are as follows: • Generally contain dc offset, odd harmonics, and even
• Mismatch between the CT and power transformer harmonics [15] [16].
ratios are not properly compensated by the relay TAP • Typically composed of unipolar or bipolar pulses
settings. separated by intervals of very low current values [15]
• Variable ratio of the power transformer caused by a [16].
tap changer. • Peak values of unipolar inrush current pulses decrease
• Phase shift between the power transformer primary very slowly. Their time constant is typically much
and secondary currents for delta-wye connections. greater than that of the exponentially decaying dc
• Magnetizing inrush currents created by transformer offset of fault currents.
transients because of energization, voltage recovery • Second-harmonic content starts with a low value and
after the clearance of an external fault, or energization increases as the inrush current decreases.
of a parallel transformer. • Delta currents (a delta winding is encountered in
• High exciting currents caused by transformer either the power transformer or CT connections or is
overexcitation. simulated in the relay) modify the inrush because
The relay percentage restraint characteristic typically currents of adjacent windings are subtracted, and:
solves the first two problems. Proper connection of the CTs or − DC components are subtracted.
emulation of such a connection in a digital relay (auxiliary − Fundamental components are added at 60 degrees.
CTs historically provided this function) addresses the phase- − Second harmonics are added at 120 degrees.
shift problem. A very complex problem is that of discriminat- − Third harmonics are added at 180 degrees (they
ing internal fault currents from the false differential currents cancel out), and so forth.
caused by magnetizing inrush and transformer overexcitation. Sonnemann, Wagner, and Rockefeller initially claimed that
The vast majority of percentage restraint current differential the second-harmonic content of the inrush current was never
relays employ some form of harmonic detection to discern this less than 16 percent to 17 percent of the fundamental [15].
difference. However, transformer energization with reduced voltages and
variations in point-on-wave initiation may generate inrush
III. HARMONIC SOURCES: MAGNETIZING INRUSH, currents with second-harmonic content considerably less than
OVEREXCITATION, AND CT SATURATION 10 percent, as exhibited later in this paper.
Inrush or overexcitation conditions of a power transformer
produce false differential currents that could cause undesired
relay operation. Both conditions produce distorted currents
because they are related to transformer core saturation. The
distorted waveforms provide information that helps to dis-
4
ΦT
2
ΦI
Flux and Voltage
v
ΦR 1
ΦSS
0
Magnetizing
Current
-1
Fig. 5 shows the voltage, flux, and current during a mag- following an external fault or after transformer testing proce-
netizing inrush where the transformer is energized at zero on dures, such as dc continuity tests performed on the transformer
the voltage wave. V is the voltage waveform, ΦSS is the windings. If the initial residual flux has the same relative
steady-state flux, ΦI is the initial flux at voltage energization, value as the first half cycle of energizing voltage waveform,
ΦR is the residual flux, and ΦT is the total flux (ΦI + ΦR) at the peak inrush current on that phase can be several times the
voltage energization. The associated magnetizing (exciting) full load current.
characteristic shows the nonlinear relationship between the Switching at other points on the voltage wave produces
magnetizing current and the flux in an iron-core transformer. other, less severe values of inrush current. If the point-on-
The magnetizing current increases significantly when the total wave happens to coincide with the residual flux that is correct
flux exceeds the saturation density point. for that instant under steady-state conditions, then no transient
When switching at a voltage zero, the full flux change is will occur. This nontransient condition is very rare, especially
required during the first half cycle, but with the flux initially with three-phase transformers.
zero, the maximum flux developed will be nearly twice the Three-phase transformers generally produce a mix of tran-
normal peak value (ΦI). In a linear inductor, such as an air- sient inrush conditions because the point-on-wave differs for
core inductor, twice the normal peak flux will produce twice each phase that is energized. Also, interphase coupling occurs
the normal steady-state value current. However, in nonlinear because of the common core design in most three-phase trans-
iron-core transformers where the normal peak flux is close to formers. This interphase coupling produces distortion in the
the saturation point, an increase in flux to twice the steady- current on a phase with point-on-wave energization that, by
state value causes the magnetizing (inrush) current to rise to a itself, would produce no offset. Fig. 6 shows a fairly typical
very high value, possibly even exceeding the rated full load transient inrush waveform for the energization of a three-
current value. phase transformer. As seen, IB and IC are fully offset in oppo-
When the transformer core, prior to energization, contains a site directions, and IA is more symmetrical, but definitely
relatively high residual flux (ΦR), the inrush current can in- nonsinusoidal.
crease still further. Residual (remanent) flux can be quite high
5
60
5
IA
0
40
-5
5
IB 0 0
-5
-20
5
-40
IC 0
-5 -60
0 1 2 3 4 5 6 7 0.5 1 1.5 2 2.5 3
Cycles Cycles
Secondary A
80
and Its Harmonic Components
I3(% of I1)
0
Magnetizing Current (Im)
70
60 -100
50 -200
Im(% of In) 0 0.5 1 1.5 2 2.5 3 3.5 4
Cycles
40
I5(% of I1) Harmonic Percent
30 50
40
Percentage
20 Third Harmonic
30 Fifth Harmonic
10
20
0
100 110 120 130 140 150 160 10
Voltage (Percent of Nominal Voltage) 0
0 0.5 1 1.5 2 2.5 3 3.5 4
In: Rated Current
Cycles
Im: Magnetizing Current
I1, I3, I5: Fundamental and Higher Harmonic Components of Im Fig. 9. Typical Secondary Current for Symmetrical CT Saturation and the
Harmonic Content It Contains
Fig. 8. Harmonic Content of Transformer Exciting Current as a Function of
the Applied Voltage [18]
IV. METHODS FOR DISCRIMINATING INTERNAL FAULTS FROM
C. CT Saturation INRUSH AND OVEREXCITATION CONDITIONS
CT saturation during faults and the effect of CT saturation Early transformer differential relay designs used time delay
on protective relays have received considerable attention [19] or a temporary desensitization of the relay to override the in-
[20] [21] [22] [23] [24]. In the case of transformer differential rush current. Other designs used an additional voltage signal
protection, the effect of CT saturation is double edged. For to restrain or to supervise (block) the differential relay. All of
external faults, the resulting false differential current may pro- these concepts struggled with the conflict between providing
duce relay misoperation. In some cases, the percentage re- reliable and fast internal fault detection versus providing secu-
straint in the relay addresses this false differential current, rity against tripping for external faults, magnetizing inrush,
particularly with variable-slope or dual-slope percentage re- and overexcitation.
straint characteristics. For internal faults, the harmonics result- Modern percentage current differential relays address this
ing from CT saturation could delay the operation of differen- conflict in one of two ways: using harmonics to restrain or
tial relays having harmonic restraint or blocking. block or using waveshape identification. This paper discusses
The main characteristics of CT saturation are as follows: and focuses on the harmonic-based methods.
• CTs faithfully reproduce the primary current for a We can use the harmonic content of the differential current
given time after fault inception [23]. The time to CT to restrain or block the relay, providing ways to differentiate
saturation depends on several factors but is typically between internal faults and inrush or overexcitation condi-
one cycle or longer. tions. Historically, the technical literature on this topic has not
• The worst CT saturation is produced by the dc clearly identified the differences between harmonic restraint
component of the primary current. During this dc and harmonic blocking, sometimes using the two inter-
saturation period, the secondary current may contain changeably. The purpose of this paper is to clarify the differ-
dc offset and odd and even harmonics [11] [21]. ence between the two techniques and put forth some applica-
• When the dc offset dies out, the CT has only ac tion guidelines for using the two techniques.
saturation, characterized by the presence of odd
harmonics in the secondary current [10] [11] [19]. A. Harmonic Restraint
Fig. 9 shows a typical secondary-current waveform for The original harmonic-restrained differential relays used all
computer-simulated ac symmetrical CT saturation. This figure harmonics to provide the restraint function. The resulting high
also depicts the harmonic content of this current and confirms level of harmonic restraint provided security for inrush condi-
the presence of odd harmonics and the absence of even har- tions at the expense of operating speed and dependability for
monics in the secondary current. Generally speaking, symmet- internal faults with CT saturation. This concept has been car-
rical nonsinusoidal waveforms contain predominately odd ried forward in modern relays, with subtle changes, to provide
harmonics, and asymmetrical waveforms contain predomi- restraint using selected harmonics instead of all harmonics.
nately even harmonics.
Asymmetrical CT saturation caused by dc offset is one
source of even harmonics that can adversely affect perform-
ance of percentage restraint current differential relays that use
even harmonics for harmonic blocking or harmonic restraint.
7
nt
ential restraint from the selected harmonic content of the mul-
i
tra
+ Harmonic Restraint
es
tiple winding current inputs. This concept is expressed in the
R
ic
following equation:
on
rm
Ha
I OP > I RT • f (SLP1, SLP 2) + (K h1I h1 + K h 2 I h 2 + K h 3I h 3 K + K hx I hx ) (6)
+
2)
LP
where Khx is a settable constant for each harmonic x, Ihx is the Restraint Region
,S
lOP < IRT • f (SLP1, SLP2)
measured xth harmonic content in the operate current, IOP,
P1
+ Harmonic Restraint
L
(S
keeping in mind that the operate current is the phasor sum of
•f
T
winding currents. This equation can be represented in logic
IR
=
P
form as follows:
lO
IPU
Differential relays may also use fifth-harmonic blocking to (A) Independent Harmonic Blocking (B) Common Harmonic Blocking
prevent undesired operation during overexcitation. Fig. 14 87R1
AND
87BL1
shows a logic diagram of a differential element having sec- 87BL1
87BL2 OR
ond- and fifth-harmonic blocking. A tripping signal requires 87BL3 AND TRIP
87R2
fulfillment of (6), without fulfillment of the following block- 87BL2
AND OR TRIP 87R1
87R2 OR
ing conditions (8) and (9): 87R3
TABLE II
COMPARISON OF HARMONIC RESTRAINT AND BLOCKING METHODS
Table II summarizes the results of a qualitative comparison bination of the harmonics. Although the same harmonics are
of the harmonic restraint and blocking methods for trans- available for both harmonic blocking and harmonic restraint,
former differential protection and suggests the following: the specific harmonic combination produces a different result
• All harmonic restraint and blocking techniques have in the element performance. Equation (6) shows that in the
advantages and disadvantages. harmonic restraint differential element, the harmonics are
• Although subjective, a good combination includes summed (series combination). When the harmonics are
even harmonic restraint and fifth-harmonic blocking summed, all harmonics included in the equation contribute to
to provide a good balance of security and increase the restraint quantity. This total harmonic contribu-
dependability. tion significantly enhances the security of the differential ele-
Guzman, Benmouyal, Zocholl, and Altuve established that ment.
some supplemental waveform detection techniques may be In microprocessor-based relays, the relays calculate the
required to improve security for unique combinations of fault harmonics by means of digital filters. In essence, these digital
and inrush conditions [1]. filters are integrators, summing a number of sampled current
Common harmonic blocking logic provides high security values over a specified time period. Therefore, a large numeric
but sacrifices some dependability. Energization of a faulted value remains in the digital filter for the total specified time
transformer could result in harmonics from the inrush currents period. Because the relay uses these filtered values directly in
of the nonfaulted phases, and these harmonics could delay calculating the restraint quantity, a filter that includes large
relay operation. numeric values causes delayed tripping. Depending on the
numeric value, this delayed tripping can be up to one power
A. Speed and Security system cycle.
As with all protection element evaluations, speed and secu- Fig. 14 shows that the harmonics are evaluated independ-
rity are contradictory requirements. The two factors that influ- ently in the harmonic blocking differential element, i.e., the
ence the speed and security of the harmonic elements are the values of the harmonics are not summed (parallel combina-
harmonic “combination” and the digital filtering. In this re- tion). Because the element is less secure when evaluating the
gard, harmonic combination refers to the series/parallel com- harmonics independently, the use of common harmonic block-
10
Y Y
φG 87
The waveform only exists for four cycles because the relay
in this case tripped the high-side breaker. As we will see, the
basic second-harmonic blocking technique used by the relay
was not effective in blocking operation of the percentage re-
O87P straint current differential relay.
Figs. 41, 42, and 43 show the individual phase waveform Given this analysis, we expect that independent harmonic
analysis for the final example. blocking cannot effectively prevent differential relay operation
unless the harmonic percent threshold setting is drastically
reduced to 4 percent or below. In this case, common harmonic
blocking would have been successful because both the second-
and fourth-harmonic components exceed the 12 percent har-
monic percentage threshold setting chosen for this analysis.
We next examine the harmonic restraint characteristic per-
formance to see how it performs. Figs. 44, 45, and 46 show
the modified percentage restraint current differential charac-
teristic for Phases A, B, and C using the harmonic restraint
function.
plained in the next section. If so, then some other form of se- even harmonic blocking because the harmonic restraint
curity, typically a waveform recognition technique such as function benefits from even small quantities of harmonic
proposed by Guzman, Benmouyal, Zocholl, and Altuve [1], is content. However, relays using the harmonic restraint
recommended for further security improvement. technique may operate slightly slower for internal faults
than those using harmonic blocking.
5. Common harmonic blocking increases differential relay
security but could delay relay operation for internal faults
combined with inrush currents in the nonfaulted phases.
6. Harmonic blocking and harmonic restraint techniques
may not be adequate to prevent differential element op-
eration for unique cases with very low harmonic content
in the operating current. Some form of waveshape recog-
nition may be required to ensure security for these unique
conditions without sacrificing fast and dependable opera-
tion when energizing a faulted transformer.
VII. REFERENCES
[1] A. Guzman, G. Benmouyal, S. E. Zocholl, and H. Altuve, “Performance
Analysis of Traditional and Improved Transformer Differential Protec-
Fig. 46. Harmonic Restraint Characteristic Performance on Phase C tive Relays,” 2002 Western Protective Relaying Conference, Spokane,
WA, Oct. 22–24, 2002.
C. Harmonic Sensitivity Settings [2] I. T. Monseth and P. H. Robinson, “Relay Systems: Theory and Appli-
The example cases presented in this paper used a 12 per- cations,” New York: McGraw Hill Co., 1935.
cent second- and fourth-harmonic setting to perform the [3] R. E. Cordray, “Percentage Differential Transformer Protection,” Elec-
trical Engineering, Vol. 50, May 1931, pp. 361–363.
analysis. Better security may be obtained by reducing this
[4] R. E. Cordray, “Preventing False Operation of Differential Relays,”
harmonic sensitivity setting. However, improving security Electrical World, July 25, 1931, pp. 160–161.
against misoperating on transformer inrush may decrease the [5] E. L. Harder and W. E. Marter, “Principles and Practices of Relaying in
relay’s dependability to detect internal faults. Some measure the United States,” AIEE Transactions, Vol. 67, Part II, 1948, pp. 1005–
of harmonic content can be expected for internal transformer 1023.
faults because of the nonlinear behavior of iron-core inductive [6] L. F. Kennedy and C. D. Hayward, “Harmonic-Current-Restrained
Relays for Differential Protection,” AIEE Transactions, Vol. 57, May
devices. Typical harmonic sensitivity settings in the range of 1938, pp. 262–266.
10 percent to 15 percent are considered reasonable. Settings [7] C. D. Hayward, “Harmonic-Current-Restrained Relays for Transformer
below 10 percent may jeopardize dependable operation of the Differential Protection,” AIEE Transactions, Vol. 60, 1941, pp. 377–
differential relay for internal faults. Very little experience is 382.
available in this area because of the relatively few occurrences [8] C. A. Mathews, “An Improved Transformer Differential Relay,” AIEE
of transformer faults. It seems prudent to endure the occa- Transactions, Vol. 73, Part III, June 1954, pp. 645–650.
sional differential relay operation on transformer energization, [9] R. L. Sharp and W. E. Glassburn, “A Transformer Differential Relay
With Second-Harmonic Restraint,” AIEE Transactions, Vol. 77, Part III,
or use a supplemental security measure, such as waveshape Dec. 1958, pp. 913–918.
recognition, in order to ensure fast and dependable tripping for [10] C. H. Einval and J. R. Linders, “A Three-Phase Differential Relay for
an internal fault. Transformer Protection,” IEEE Transactions PAS, Vol. PAS-94, No. 6,
Nov/Dec 1975, pp. 1971–1980.
VI. CONCLUSIONS [11] A. M. Dmitrenko, “Semiconductor Pulse-Duration Differential Restraint
Relay,” Izvestiya Vysshikh Uchebnykh Zavedenii, Elektromekhanika,
1. Most transformer differential relays use the harmonic No. 3, March 1970, pp. 335–339 (in Russian).
content of the operating current to distinguish internal [12] G. I. Atabekov, “The Relay Protection of High-Voltage Networks,”
faults from magnetizing inrush conditions using either London: Pergamon Press Ltd., 1960.
harmonic blocking or harmonic restraint techniques. [13] G. D. Rockefeller, “Fault Protection With a Digital Computer,” IEEE
Transactions PAS, Vol. PAS-98, April 1969, pp. 438–464.
2. The harmonic blocking technique uses a fixed harmonic
[14] S. B. Wilkinson, Transformer Differential Relay, U.S. Patent No
threshold, below which the differential element is free to
5627712, May 6, 1997.
operate on its normal percentage-slope characteristic.
[15] W. K. Sonnemann, C. L. Wagner, and G. D. Rockefeller, “Magnetizing
3. The harmonic restraint technique, as described in this Inrush Phenomena in Transformer Banks,” AIEE Transactions, Vol. 77,
paper, adds the harmonic component of the operate Part III, October 1958, pp. 884–892.
current to the fundamental component of the restraint cur- [16] J. Berdy, W. Kaufman, and K. Winick, “A Dissertation on Power Trans-
rent, providing dynamic restraint during transformer in- former Excitation and Inrush Characteristics,” Symposium on Trans-
former Excitation and Inrush Characteristics and Their Relationship to
rush. Transformer Protective Relaying, Houston, TX, August 5, 1976.
4. Harmonic restraint and blocking methods ensure relay [17] S. E. Zocholl, A. Guzmán, and D. Hou, “Transformer Modeling as Ap-
security for a very high percentage of transformer inrush plied to Differential Protection,” 22nd Annual Western Protective Relay
cases. Harmonic restraint tends to be more secure than Conference, Spokane, WA, October 24–26, 1995.
17
VIII. BIOGRAPHIES