Over Voltages and Insulation Requirements
Over Voltages and Insulation Requirements
The voltage stress caused by over voltage can damage the lines and equipment’s connected to
the system.
Transient over voltages can be generated at high frequency (load switching and lightning),
medium frequency (capacitor energizing), or low frequency.
Over voltage due to external causes: This cause of over voltage in power system is the
lightning strokes in the cloud. When electric charges get accumulated in clouds due to
thunder Strom caused due to some bad atmosphere process. This type of over voltages
originates from atmospheric disturbances, mainly due to lightning. This takes the form of a
surge and has no direct relationship with the operating voltage of the line.
Electric current reaches 20-150 kA. An abnormally high voltage generated by direct lightning
discharge applied to electric power cables or communication cables at that instance is called
‘direct lightning surge’.
Also, when lightning strikes a lightning rod and the ground potential rises, instruments’
grounding potential becomes also high. This causes an abnormally great potential difference
between the cables and the ground, which is called ‘lightning surge caused by increased
ground potential’.
Overvoltage may be of transient or persistent nature. There are two categories, internal and
external. This overvoltage can source destruction to insulators and substation gear. Thus, it is
required to provide facilities to protect insulators and other gear from the damaging of
overvoltage. The process of protecting the electrical system from the destruction that may be
triggered by overvoltage. The use of devices such as bent sirens close to the transmission line
and Zener diodes for electronic circuits. There are dissimilar methods can be used for
overvoltage protection, with its specific characteristics. Performance, cost, difficulty and
functioning mode all need to be considered when defining the method to use.
SCR Crowbar
Figure shows the crowbar circuit that seats a short circuit across the output if an overvoltage
situation is practiced. Characteristically thyristors for example SCRs are used for as they can
switch great currents and continue pending any charge has isolated. Often the thyristor is
related back to a fuse that isolates the regulator from needing any more voltage located upon
it
Insulation Coordination
Voltage surges maybe caused by a lightning strike at a conductor, flashover from an air
terminal, or switching operation such as opening and closing of a circuit breaker. The surge
propagates from the point of disturbance and travels along a transmission line. As the surge
propagates past a junction between two components such as transmission lines with different
impedances, some part of the surge will refract or pass through the junction called the
transmitted wave and the rest will reflect as shown in Figure.
The reflection and refraction of the surge propagation at the junction between two different
transmission lines.
Where e,i is the voltage and current of the surge propagation. e' ,i' is the voltage and current
of the reflected wave. e" ,i" is the voltage and current of the transmitted wave. Zl is the
impedance of the transmission line 1. Zk is the impedance of the transmission line 2.
From the Thevenin equivalent circuit in Figure, the surge voltage e" travelling past the
junction, and the reflected voltage e’ can be obtained in (1) and (2) respectively.
e “ = 2Zk/ Z1 + Zk .e …………………………………..(1)
e’ = e” – e …………………………………………….(2)
If a junction comprises several different transmission lines as shown in Figure , the refracted
voltage surge e" is given by
e “ = 2Zt/ Z1 + Zt e ………………………………………………………………….(3)
Zt = Z2 Z3 Z4 / Z2 Z3 + Z2 Z4 + Z3 Z4
Analysis of a surge propagation moving past a surge arrester installation point uses the same
principle as the case of several different conductors connected to the junction. When no surge
is presented, the impedance of an arrester is ideally infinite as shown in Figure (b). The
voltage across the surge arrester is surge voltage ( e" e ) and the reflected voltage is zero ( e'
0 ). When a surge arrives at the arrester, and the arrester starts conducting, its impedance is
ideally zero as shown in Figure (c). The voltage across the surge arrester is zero ( e" 0 ) and
the reflected voltage is the opposite of the of surge voltage ( e' e ). In practice however,
there exist some voltage across the surge arrester during its operation because the resistance
of the surge arrester is non-linear. Accordingly, the voltage across the surge arrester will be
tested and provided by the manufacturer.
Consider a line connected to a source of constant voltage v at one end and open circuited at
the other, as shown in Fig. . Let αs and αL be the reflection coefficients at the sending end
and the load end respectively, and t, the time taken by the wave to travel from one end to the
other end.
When time t= 0 s, the voltage v is connected to the source end (s) and starts travelling along
the line reaching the load end in time t s with the same magnitude.
Since the load end is an open circuit, the wave reflected back with a magnitude of αLv =v
(because αL= 1 for an open-ended line) at time t + s, reaches source end in time 2t with a
magnitude of v.
The reflected wave is reflected back once again with a magnitude of sv from the source end
after reaching the source end at time 2t + and this process is continued indefinitely.
The same procedure can be implemented for current waves also. This procedure is illustrated
in the Lattice diagram shown in Fig.(b)
When time t 0 s, the voltage V is connected to the source end (s) and starts travelling along
the line, and reaching the load end in time t s with the same magnitude.
After reaching the junction, the wave is split into two parts, one part of the wave is
transmitted and the other is reflected back with a magnitude of αL=V at time t + it travels
towards source and reaches the source end in time 2t with a magnitude of αLV. The wave,
which has reached the source end, splits into two parts once again.
One part is transmitted and the other is reflected back with a magnitude of αsαLV from
source end at time 2t +. This process is continued indefinitely.
The same procedure can be implemented for current waves also. This procedure is illustrated
in the Lattice diagram shown in Fig
References:
Power System Analysis and Design Book by J. Duncan Glover and Mulukutla S
Sarma