SIL DECLARATION OF CONFORMITY Model ST100 SERIES

We, Fluid Components International LLC, located at 1755 La Costa Meadows Drive, San Marcos, California 92078-
5115 USA, declare as manufacturer, that the ST100 Series of products is suitable for use in a safety instrumented
system for SIL 1, flow, temperature and pressure measurement.

The ST100 Series has been classified as Type B subsystem according to IEC 61508-1 Chapter 7.4.4.1.3 with a
Hardware tolerance (HFT) of 0.

The Failure Modes, Effects and Diagnostic Analysis (FMEDA) report carried out by exida, resulted in following
failure ratings:

SIL (Safety Integrity Level) : 1 - As a single device


HFT (Hardware Fault Tolerance) : 0
Subsystem type : B

Failure rates according to IEC 61508-1


Function SFF PFD (AVG) λDU λDD λSU λSD
-2
Single Probe AC supply 79.8 % 1.21 x 10 567 FIT 1927 FIT 314 FIT 0
Single Probe DC supply 79.9 % 1.22 x 10 -2 570 FIT 1946 FIT 317 FIT 0
-2
Dual Probe AC supply 88.9% 1.00 x 10 415 FIT 2918 FIT 404 FIT 0
Dual Probe DC supply 88.9% 1.01 x 10 -2 418 FIT 2937 FIT 407 FIT 0

Terminology:
SFF = Safe Failure fraction
PFD = Probability of failure on demand
λDU = failure rate dangerous undetected faults
λDD = failure rate dangerous detected faults
λSU = failure rate safe undetected faults
λSD = failure rate safe detected faults
FIT = Failure Rate in 10-9 /hour

Above analysis is based on assuming:


 The HART protocol is used for setup, calibration and diagnostics purposes, not for safety critical function.
 Materials are compatible with process conditions.
 The device is installed per manufacturer’s instructions.
 External power supply failure rates are not included.
 Worst-case internal fault detection time is 1 hour.
 The device is configured for fault detection per NAMUR NE43 or the logic solver is configured to interpret
output fault conditions.
 Proof test interval of 1 year.
Issued at San Marcos, California USA
20, May 2012
Eric Wible
2012.06.28 15:47:50 -07'00'
______________________________________
Eric Wible, Engineering Manager

Flow/Liquid Level/Temperature Instrumentation


Visit FCI on the Worldwide Web: www.fluidcomponents.com
1755 La Costa Meadows Drive, San Marcos, California 92078 USA 760-744-6950  800-854-1993  760-736-6250
European Office: Persephonestraat 3-01 5047 TTTilburg – The Netherlands – Phone 31-13-5159989  Fax 31-13-5799036

Doc no. 23EN000025-