Differential Relay: Power System Protection

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Differential Relay

Power system protection


Introduction:

 The relays used in power system


protection are of different types. Among
them differential relay is very
commonly used relay for protecting
transformers and generators from
localized faults.
 Differential relays are very sensitive to
the faults occurred within the zone of
protection but they are least sensitive to
the faults that occur outside the protected
zone.
Fig. 1:Diffrantial relay schemes.
Definition of differential relay:

 Most of the relays operate when any


quantity exceeds beyond a
predetermined value for example over
current relay operates when current
through it exceeds predetermined value.
 The principle of differential relay is
somewhat different. It operates
depending upon the difference between
Fig. 2:Diffrantial relay schemes with fault.
two or more similar electrical quantities.
Principle of work:

 The differential relay is one that operates


when there is a difference between two
or more similar electrical quantities
exceeds a predetermined value.
 In the differential relay scheme circuit,
there are two currents come from two
parts of an electrical power circuit. These
two currents meet at a junction point
where a relay coil is connected.
According to Kirchhoff Current Law, the
resultant current flowing through the
relay coil is nothing but the summation
Fig. 3:Diffrantial relay schemes circuit.
of two currents, coming from two
different parts of the electrical power
circuit.
Principle of work:

 there are two sets of current transformer each connected to either side of the equipment
protected by differential relay. The ratio of the current transformers are so chosen, the
secondary currents of both current transformers matches each other in magnitude.
 The polarities of current transformers are such that the secondary current of these CTs
opposes each other. From the circuit in the previous slide is clear that only if any nonzero
difference is created between this to secondary currents, then only this differential current
will flow through the operating coil of the relay. If this difference is more than the peak up
value of the relay, it will operate to open the circuit breakers to isolate the protected
equipment from the system.
Types of Differential Relay:

1. Current Balance Differential Relay.

2. Voltage Balance Differential Relay.


1. Current Balance Differential Relay

 In current differential relay two current


transformers are fitted on the either side
of the equipment to be protected. The
secondary circuits of CTs are connected
in series
 The operating coil of the over current
relay is connected across the CT
secondary circuit. This differential relay
compares the current at the two ends of
the alternator winding.
 Under normal operating conditions,
suppose the alternator winding carries a
Fig. 4: CT Differential relay under normal condition.
normal current of 1000 A. Then the
currents in the two secondaries of CT’s
are equal [See Fig. 4].
1. Current Balance Differential Relay

 If a ground fault occurs on the alternator


winding as shown in [Fig. 5] the two
secondary currents will not be equal and
the current flows through the operating
coil of the relay, causing the relay to
operate. The amount of current flow
through the relay will depend upon the
way the fault is being fed.
 If some current (500 A in this case) flows
out of one side while a larger current
(2000 A) enters the other side as shown Fig. 5: CT Differential relay under fault.
in Fig, 5 then the difference of the CT
secondary currents i.e. 10 – 2 5 = 7.5 A
will flow through the relay.
1. Current Balance Differential Relay

 If current flows to the fault from both


sides as shown in Fig. then sum of CT
secondary currents i.e. 10 + 5 = 15 A will
flow through the relay.

 The current is double from in way fault. Fig. 6:CT Differential relay under fault from booth side.
2. Voltage Balance Differential Relay
 Fig. 7 shows the arrangement of voltage balance protection. two similar current transformers
are connected at either end of the element to be protected by means of pilot wires. The
secondaries of current transformers are connected in series with a relay in such way that under
normal conditions, their induced e.m.f.s’ are in opposition.

Fig. 7:VT Differential relay

 Under healthy conditions, equal currents II = I2) flow in both primary windings. Therefore, the
secondary voltages of the two transformers are balanced against each other and no current will
flow through the relay operating coil. When a fault occurs in the protected zone, the currents
in the two primaries will differ from one another (i.e. I1 ≠ I2) and their secondary voltages will
no longer be in balance. This voltage difference will cause a current to flow through the
operating coil of the relay which closes the trip circuit.
Applications:

 current-differential relays for protection of a transformer.


 current-differential relays for delta-wye transformer protection.
 The relay typically trips fault interrupting devices on both sides of the transformer.
 zone of protection
 bus differential relays to a primary-selective system.
Done by:
Abdallah Husain Sulieman Daldoom.
31502020130

Eng. Esra’a Al-hindi.

You might also like