Load Resistance Report - 8-12-6 DGU - 4.2 KPa (Comments)
Load Resistance Report - 8-12-6 DGU - 4.2 KPa (Comments)
Load Resistance Report - 8-12-6 DGU - 4.2 KPa (Comments)
Hence, load resistance of proposed glass combination 8-12-6 DGU is 7.14 Kpa
and it can resist a wind load of 3 4.20 Kpa
Deflection Check
Aspect Ratio – L/B 1.20 1.33
Area of glass panel – L x B 2.70 4.32 Sqm Load share factor
Maximum wind load acting on outer glass 2.94 2.1 Kpa 0.7
Maximum wind load acting on Inner glass 1.26 0.9 Kpa 0.3
Load x Area2 (for Outer glass) 39.19 21.43 kN . M2
Deflection on the outer glass 16.5 mm As per deflection chart of ASTM E 1300
Deflection on the Inner glass 14.5 mm As per deflection chart of ASTM E 1300
Allowable Deflection limit for 4-sided support – 19mm or L /60 25.00 whichever is lower (L= Shortest Span)
Conclusion
Glass combination of 8-12-6 DGU, is passing the load resistance check and deflection is within the allowable limit and hence glass design is
safe.
Note - Allowable deflection criteria is considered as per Indian Building Code. For Deflection Criteria in any country apart from
India, local guidelines shall prevail if any.
Please note that Guardian does its best to ensure the accuracy of the results of the glass thickness evaluations. However, Guardian
disclaims all liability whatsoever arising from any inaccuracy in or omission from this analysis and all the consequences of relying
on it.