OOH740, OOHC740 Automatic Fire Detectors: Technical Manual
OOH740, OOHC740 Automatic Fire Detectors: Technical Manual
OOH740, OOHC740 Automatic Fire Detectors: Technical Manual
Imprint
Technical specifications and availability subject to change without notice.
Issued by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2019-08-12
Document ID: A6V10305793_r_en_--
2 | 118 A6V10305793_r_en_--
Table of contents
1 About this document................................................................................. 7
1.1 Applicable documents .............................................................................. 9
1.2 Download center....................................................................................... 9
1.3 Technical terms ........................................................................................ 10
1.4 History of changes.................................................................................... 10
2 Safety ....................................................................................................... 13
2.1 Intended use............................................................................................. 13
2.2 Safety notes.............................................................................................. 13
2.3 Safety regulations for the method of operation......................................... 15
2.4 Standards and directives complied with ................................................... 17
2.5 Release Notes .......................................................................................... 17
A6V10305793_r_en_-- 3 | 118
3.5.5 Sounder base DBS720 ............................................................... 51
3.5.6 Designation plate FDBZ291........................................................ 52
3.5.7 Detector base seal RS720 .......................................................... 52
3.5.8 Base attachment BA720 ............................................................ 52
3.5.9 Base attachment wet BA721 ...................................................... 53
3.5.10 Designation plate DBZ1193A ..................................................... 53
3.5.11 Detector heating unit FDBH291 .................................................. 53
3.5.12 Protective cage DBZ1194 ........................................................... 54
3.5.13 Detector locking device LP720 ................................................... 54
3.5.14 Micro terminal DBZ1190-AA ....................................................... 54
3.5.15 Connection terminal DBZ1190-AB.............................................. 55
3.5.16 Parameter set resistor 33 kΩ PSR720-1 .................................... 55
3.5.17 Parameter set resistance 68 kΩ PSR720-2................................ 55
4 Planning.................................................................................................... 56
4.1 Compatibility ............................................................................................. 56
4.2 Fire detection............................................................................................ 57
4.2.1 Ambient features......................................................................... 57
4.2.2 Parameter sets: Sensor mode 0 'Neural fire detector' ................ 58
4.2.2.1 Description ........................................................................ 58
4.2.2.2 Use.................................................................................... 60
4.2.2.3 Specification...................................................................... 61
4.2.3 Parameter sets: Sensor mode 1 'Heat detector' ......................... 62
4.2.4 Parameter sets: Sensor mode 2 'Smoke detector' ..................... 63
4.2.4.1 Description ........................................................................ 63
4.2.4.2 Use.................................................................................... 64
4.2.4.3 Specification...................................................................... 64
4.2.5 Parameter sets for collective operation ...................................... 65
4.2.5.1 Description ........................................................................ 65
4.2.5.2 Use.................................................................................... 65
4.2.5.3 Specification...................................................................... 66
4.2.6 Default settings for operating on the C-NET ............................... 67
4.2.7 Setting the parameter set in collective operation........................ 68
4.2.8 Sample applications for OOH740 ............................................... 69
4.2.9 Sample applications for OOHC740............................................. 70
4.3 Technical CO alarm.................................................................................. 71
4.3.1 Parameter sets for the 'Technical CO Alarm'.............................. 71
4.3.1.1 Description ........................................................................ 71
4.3.1.2 Use.................................................................................... 72
4.3.1.3 Specification...................................................................... 73
4.3.1.4 Default settings ................................................................. 74
4.3.1.5 Application examples ........................................................ 74
4.3.2 Ambient features......................................................................... 75
4.4 Technical Ambient Supervision Message................................................. 76
4.4.1 Ambient features......................................................................... 76
4.4.1.1 Temperature monitoring.................................................... 78
4.4.1.2 CO monitoring ................................................................... 78
4.4.2 Configuration .............................................................................. 79
4.4.3 Default settings ........................................................................... 79
5 Mounting / Installation............................................................................... 80
5.1 Required space ........................................................................................ 80
5.2 Detector base DB72x and detector base (collective) DB110 ................... 81
5.3 Sounder base DBS720............................................................................. 83
5.4 Detector base seal RS720........................................................................ 84
4 | 118 A6V10305793_r_en_--
5.5 Base attachment BA720........................................................................... 85
5.6 Base attachment wet BA721 .................................................................... 87
5.7 Detector locking device LP720 ................................................................. 89
5.8 Designation plate FDBZ291 ..................................................................... 90
5.9 Cable entry ............................................................................................... 91
5.9.1 Auxiliary terminals DBZ1190-AA/-AB ......................................... 92
5.10 Detector lines............................................................................................ 93
5.10.1 Connection diagram, addressed ................................................. 93
5.10.2 Connection diagram, collective ................................................... 95
5.11 Detector dust cap ..................................................................................... 97
5.12 Detector heating unit FDBH291................................................................ 98
5.12.1 Installation of the detector heating unit ....................................... 98
5.12.2 Connection of the detector heating unit ...................................... 99
5.13 Migration from collective detector line to addressed detector line............ 100
5.13.1 Removing the diode unit ............................................................. 101
Index................................................................................................................... 113
A6V10305793_r_en_-- 5 | 118
6 | 118 A6V10305793_r_en_--
About this document
1
Target groups
The information in this document is intended for the following target groups:
Target group Activity Qualification
Product Manager ● Is responsible for information ● Has obtained suitable specialist
passing between the manufacturer training for the function and for the
and regional company. products.
● Coordinates the flow of information ● Has attended the training courses
between the individual groups of for Product Managers.
people involved in a project.
Project Manager ● Coordinates the deployment of all ● Has obtained suitable specialist
persons and resources involved in training for the function and for the
the project according to schedule. products.
● Provides the information required to ● Has attended the training courses
run the project. for Project Managers.
Project engineer ● Sets parameters for product ● Has obtained suitable specialist
depending on specific national and/ training for the function and for the
or customer requirements. products.
● Checks operability and approves ● Has attended the training courses
the product for commissioning at for Product Engineer.
the place of installation.
● Is responsible for troubleshooting.
Installation personnel ● Assembles and installs the product ● Has received specialist training in
components at the place of the area of building installation
installation. technology or electrical installations.
● Carries out a function check
following installation.
Maintenance personnel ● Carries out all maintenance work. ● Has obtained suitable specialist
● Checks that the products are in training for the function and for the
perfect working order. products.
● Searches for and corrects
malfunctions.
Document identification
The document ID is structured as follows:
ID code Examples
ID_ModificationIndex_Language_COUNTRY A6V10215123_a_de_DE
-- = multilingual or international A6V10215123_a_en_--
A6V10315123_a_--_--
A6V10305793_r_en_-- 7 | 118
About this document
1
Date format
The date format in the document corresponds to the recommendation of
international standard ISO 8601 (format YYYY-MM-DD).
The 'i' symbol identifies supplementary information and tips for an easier way of
working.
8 | 118 A6V10305793_r_en_--
About this document
Applicable documents
1
Please also observe the documentation for your fire detection system.
You will also find information about search variants and links to mobile
applications (apps) for various systems on the home page.
A6V10305793_r_en_-- 9 | 118
About this document
1 Technical terms
The first edition of a language version or a country variant may, for example, be
version 'd' instead of 'a' if the reference document is already this version.
10 | 118 A6V10305793_r_en_--
About this document
Technical terms
1
A6V10305793_r_en_-- 11 | 118
About this document
1 Technical terms
12 | 118 A6V10305793_r_en_--
Safety
Intended use
2
2 Safety
Battery Heat
Signal word
The signal word classifies the hazard as defined in the following table:
Signal word Danger level
DANGER 'DANGER' identifies a dangerous situation, that results directly in death or serious
injuries, if you do not avoid this situation.
WARNING 'WARNING' identifies a dangerous situation, that can result in death or serious
injuries, if you do not avoid this situation.
CAUTION 'CAUTION' identifies a dangerous situation, that can result in minor or moderate
injuries, if you do not avoid this situation.
Note 'NOTE' identifies a possible situation that may cause damage if not observed.
'NOTE' does not reference possible injury.
A6V10305793_r_en_-- 13 | 118
Safety
2 Intended use
WARNING
Type and source of hazard
Consequences in the event the hazard occurs
● Measures/prohibitions to prevent the hazard
NOTICE
Type and source of hazard
Consequences in the event the hazard occurs
● Measures/prohibitions to prevent the hazard
14 | 118 A6V10305793_r_en_--
Safety
Safety regulations for the method of operation
2
Electrical installations
WARNING
Electrical voltage
Electric shock
● Work on electrical installations may only be carried out by qualified
electricians or by instructed persons working under the guidance and
supervision of a qualified electrician, in accordance with the electrotechnical
regulations.
● Wherever possible disconnect products from the power supply when carrying
out commissioning, maintenance or repair work on them.
● Lock volt-free areas to prevent them being switched back on again by mistake.
● Label the connection terminals with external voltage using a
'DANGER External voltage' sign.
● Route mains connections to products separately and fuse them with their own,
clearly marked fuse.
● Fit an easily accessible disconnecting device in accordance with IEC 60950‑1
outside the installation.
● Produce earthing as stated in local safety regulations.
CAUTION
Noncompliance with the following safety regulations
Risk of injury to persons and damage to property
● Compliance with the following regulations is required.
A6V10305793_r_en_-- 15 | 118
Safety
2 Safety regulations for the method of operation
16 | 118 A6V10305793_r_en_--
Safety
Standards and directives complied with
2
WARNING
Limited or non-existent fire detection
Personal injury and damage to property in the event of a fire.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
NOTICE
Incorrect planning and/or configuration
Important standards and specifications are not satisfied.
Fire detection installation is not accepted for commissioning.
Additional expense resulting from necessary new planning and/or configuration.
● Read the 'Release Notes' before you plan and/or configure a fire detection
installation.
● Read the 'Release Notes' before you carry out a firmware update to a fire
detection installation.
A6V10305793_r_en_-- 17 | 118
Structure and function
3 Overview
3.1 Overview
In this document the following point detectors are referred to collectively using the
term 'Automatic fire detectors':
● Multi-sensor smoke detector, ASA OOH740
● Neural fire detector OOHC740
Multi-sensor smoke detector, ASA Neural fire detector
OOH740 OOHC740
Can be used addressed in the C-NET Can be used addressed on the C-NET
and in collective mode
Detection behavior can be selected
18 | 118 A6V10305793_r_en_--
Structure and function
Overview
3
Properties
● Communication via C-NET (addressed detector line)
● Address automatically issued during commissioning
● Can also be used on collective detector lines in conjunction with the detector
bases DB721D and DB110
● Built-in line separator
● Signal processing with ASAtechnology and optional detection behavior
(application-specific ASA parameter sets)
● Software can be used to set as:
– Neural fire detector
– Wide-spectrum smoke detector
– Heat detector
● Red LED as alarm indicator
● The following functions are also included from point detector
product version [➙ 26] ES ≥20:
– 'Technical Ambient Supervision Message' mode can be selected
– Extended flashing behavior of the internal alarm indicator
– Additional 'Super Sensitive' and 'Ultra Sensitive' parameter sets
Check the version of your FS720 or FC360 control panel. Some features are only
available as of certain versions. You will find details in the 'List of compatibility'.
A6V10305793_r_en_-- 19 | 118
Structure and function
3 Overview
Properties
● Communication via C-NET (addressed detector line)
● Address automatically issued during commissioning
● Built-in line separator
● Signal processing with ASAtechnology and optional detection behavior
(application-specific ASA parameter sets)
● Software can be used to set as:
– Neural fire detector
– Neural CO-supported fire detector
– Wide-spectrum smoke detector
– Heat detector
● Detection behavior of the 'Technical CO Alarm' can be set regardless of the
ASA parameter sets for fire detection. Can be set using software.
● 'Technical CO Alarm': Detection of carbon monoxide (CO) at concentrations of
5 ppm CO or more (MAK value=30 ppm CO)
● 'Technical Ambient Supervision Message': Adjustable hysteresis-induced
ambient monitoring of temperature or carbon monoxide. Can be set using
software.
● From point detector product version [➙ 26] ES ≥20: Extended flashing
behavior of the internal alarm indicator
● Red LED as alarm indicator
Check the version of your FS720 or FC360 control panel. Some features are only
available as of certain versions. You will find details in the 'List of compatibility'.
See also
2 Applicable documents [➙ 9]
20 | 118 A6V10305793_r_en_--
Structure and function
Overview
3
Environment
Evaluation of the Dynamic influence
situation of parameter
Danger
level
C
Sensory
The signals captured by the sensory are transmitted to the algorithm. The
algorithms are set by selecting the parameter set.
Algorithms
The individual parameters in the selected parameter set can be adapted with
ASAtechnology. A real time interpretation of the situation leads to a dynamic
influence on the algorithm. This results in the parameter set's and therefore the
point detector's application range broadening. The detector reacts more sensitively
in the event of fire, and more robustly in the event of deceptive phenomena.
A6V10305793_r_en_-- 21 | 118
Structure and function
3 Overview
In addition to selecting the parameter set, the point detectors with ASAtechnology
enable time- or process-controlled switching over of the parameter sets (Manned/
Unmanned switchover). Thanks to this function, the detector can be used in places
where the situation changes regularly and frequently (e.g. kitchens, production
halls).
22 | 118 A6V10305793_r_en_--
Structure and function
Overview
3
The 'Technical CO Alarm' mode can only be selected on the point detector
OOHC740.
Alongside its fire detection functionality, the point detector also has a CO detection
functionality with the following features:
● Static or dynamic alarm profiles
● Real time interpretation of the situation
● Process- and time-controlled switchover of the parameter sets for CO
Signal processing by the 'Technical CO Alarm' is undertaken regardless of CO
signal processing for the fire detection functionality with the 'Suppression CO' and
'Balanced CO' parameter sets.
The signal processing feature of the 'Technical CO Alarm' enables optimum
calculation of the CO concentration. The electro-chemical cell allows the best
possible level of accuracy to be obtained depending on the ambient conditions.
The point detector's CO detection is characterized by the ability for parameters to
be set and a relatively low cross-sensitivity to other gases, e.g. ethanol or
hydrogen (H2).
Environment:
CO and other
gases
CO
Warning level
CO Technical CO alarm
°C t
Sensory
The signals captured by the CO sensor are corrected with regard to CO exposure,
sensor sensitivity, temperature, and aging and supplied to the algorithm. The
algorithms are set by selecting the parameter set.
Algorithms
The parameter set can be used to select static and dynamic algorithms. A real time
interpretation of the ambient conditions results in improved measurement
accuracy.
The alarm limits correspond to the specified or proposed limits in the respective
standards.
A6V10305793_r_en_-- 23 | 118
Structure and function
3 Overview
The point detector allows for the time-or process-controlled independent changing
over of the parameter set for CO (Manned / Unmanned changeover). This function
allows the detector to be used in places where the situation changes significantly
on a regular basis.
NOTICE
Functionality of the 'Technical CO Alarm'
There is a risk of undetected CO exposure if the 'Technical CO Alarm' is not
configured on the control panel
● Use the documentation provided for the fire control panel to ensure that the
parameters you want to set for the 'Technical CO Alarm' are supported by the
control panel.
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
● The signals for CO detection alone must not be used to control fire detection
equipment in accordance with EN 54-2.
24 | 118 A6V10305793_r_en_--
Structure and function
Overview
3
‘Technical Ambient Supervision Message' mode can only be selected for point
detector OOH740 from product version ES ≥20.
The evaluation of the CO concentration in 'Technical Ambient Supervision
Message' mode can only be selected for point detector OOHC740.
In 'Technical Ambient Supervision Message' mode, the point detector can detect
an increase in temperature or CO concentration above a specified trigger threshold
caused by hysteresis.
The control panel is used to configure the parameters.
Environment:
CO or
temperature
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
● The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN 54-2.
A6V10305793_r_en_-- 25 | 118
Structure and function
3 Overview
ES
Figure 6: Example of a packaging label with details of the product version
04
ES
Figure 7: Example of a product label with details of the product version
Depending on the product and various approvals, the product labels may differ in
terms of the information type and layout.
Look for your device's order number on the product label.
You will find the product version after the order number.
26 | 118 A6V10305793_r_en_--
Structure and function
Setup
3
3.2 Setup
A6V10305793_r_en_-- 27 | 118
Structure and function
3 Setup
28 | 118 A6V10305793_r_en_--
Structure and function
Setup
3
Fire detection
The point detector's high-quality opto-electronic measuring chamber houses the
following components:
● Two optical transmitters
● One optical receiver
● Two thermal sensors
● One CO sensor
The transmitters illuminate the smoke particles from different angles. One sensor
acts as forward scatterer, the other as backward scatterer. The scattered light then
hits the receiver (photodiode) and generates a measurable electric signal.
The combination of forward scatterers and backward scatterers allows for optimum
detection of and distinction between light and dark particles and particle sizes. The
distinction between light and dark particles firstly results in a homogeneous
response behavior and secondly enables better differentiation between wanted
signals and deceptive phenomena.
In addition, the heat sensors make it possible to detect fires without smoke
generation.
The CO sensor enables faster detection of fires with incomplete combustion and
fires with the development of a lot of CO.
The combination of optical, thermal and CO sensor signals optimizes detection
reliability for all types of fire, regardless of whether they generate dark or light
smoke, or none at all.
You can set the following response behaviors on the neural fire detector
OOHC740:
● Combined optical and thermal
● Combined optical, thermal and CO
A6V10305793_r_en_-- 29 | 118
Structure and function
3 Setup
NOTICE
Functionality of sensor modes
Danger of alarm activation as a result of deceptive phenomena
● Depending on the configuration software used for the fire control panel,
sensor modes 1 and 2 may not be available.
If the deceptive phenomena occurring (e.g. if the operator suspects that both
CO and smoke-like deceptive phenomena are present at the same time)
mean that only one heat detector can be operated, the OOHC740 may not be
used in such environments.
Technical CO alarm
The point detector has a high-quality CO sensor which is based on the
measurement principle of the electro-chemical cell.
Instances of the specified CO concentration being exceeded can be detected by
the CO sensor. The limit values vary depending on the parameters set.
You can set the following CO response behaviors on the neural fire detector
OOHC740:
● Static CO alarm thresholds
● Dynamic CO alarm thresholds
The response behavior is configured with the 'Cerberus-Engineering-Tool'
software.
30 | 118 A6V10305793_r_en_--
Structure and function
Setup
3
See also
2 Parameter sets [➙ 32]
A6V10305793_r_en_-- 31 | 118
Structure and function
3 Function
3.3 Function
On a C-NET detector line, the parameter set must always be set explicitly.
See also
2 Parameter set resistor 33 kΩ PSR720-1 [➙ 55]
2 Parameter set resistance 68 kΩ PSR720-2 [➙ 55]
2 Connection diagram, collective [➙ 95]
2 Applicable documents [➙ 9]
32 | 118 A6V10305793_r_en_--
Structure and function
Function
3
Always use the suitable parameter set for fire detection for the corresponding
application.
The default device parameter set is not always the suitable parameter set.
A6V10305793_r_en_-- 33 | 118
Structure and function
3 Function
The 'High Suppression', 'High Sensitive Fast', and 'Super Sensitive' parameter
sets are only suited for special applications.
The 'Ultra Sensitive' parameter set does not meet the criteria of standard
EN 54-7.
34 | 118 A6V10305793_r_en_--
Structure and function
Function
3
If there is still a flashing signal on a point detector OOH740 more than 3 minutes
after the detector line was started up, there is a fault. You will find more
information in chapter 'Internal alarm indicator in the case of ES <20 [➙ 40]'.
The point detector OOH740 is always operated in sensor mode 0 'Neural fire
detector' on a collective detector line.
See also
2 Parameter sets: Sensor mode 0 'Neural fire detector' [➙
58]
2 Parameter sets: Sensor mode 1 'Heat detector' [➙ 62]
2 Parameter sets: Sensor mode 2 'Smoke detector' [➙ 63]
2 Parameter sets for collective operation [➙ 65]
2 Internal alarm indicator in the case of ES <20 [➙ 40]
A6V10305793_r_en_-- 35 | 118
Structure and function
3 Function
See also
2 Parameter sets for the 'Technical CO Alarm' [➙ 71]
2 Configuration [➙ 79]
36 | 118 A6V10305793_r_en_--
Structure and function
Function
3
The evaluation of the danger level and the decisions to be taken (e.g. activation of
remote transmission) are configured in the fire detection system.
A6V10305793_r_en_-- 37 | 118
Structure and function
3 Function
The functions described in this section are only available on the OOHC740.
Measured values above a response threshold depending on the parameter set for
CO are not the only basis for reaching a warning level for CO. The CO progression
is also observed over a longer period of time and evaluated using algorithms.
Neural fire detector OOHC740 can convey the following warning levels to the
control panel in the form of a technical message:
Warning level Meaning Comment
for the Technical CO
Alarm
0 No danger Normal condition
1 Advance warning Increased CO concentration (MAK value = 30 ppm CO
level 1/ exceeded)
CO loading
2 Warning High CO concentration
3 Alarm, evacuation The CO concentration has reached dangerous levels.
This warning level requires parameters to first be set for the CO
evaluation.
The warning level is not available in degraded mode operation
or on devices that have not been commissioned or localized.
The evaluation of the warning level and the decisions to be taken (e.g. activation
of remote transmission) are configured in the fire detection system.
The evaluation of the danger level and the decisions to be taken are configured in
the fire detection system.
38 | 118 A6V10305793_r_en_--
Structure and function
Function
3
The CO sensor can only be monitored for failure. For a functional test, the CO
sensor must be tested with test gas.
Once the cause of a short-circuit has been remedied on the C-NET, an open line
separator does not close automatically. Reset the detector line on the control
panel.
A6V10305793_r_en_-- 39 | 118
Structure and function
3 Function
Information about the product version of your device can be found in the
'Product version ES [➙ 26]' chapter.
Addressed mode
The point detectors have an internal alarm indicator. The internal alarm indicator
shows the point detector's operating conditions in addressed mode.
Operating condition Flashing mode of alarm indicator
Normal Al off
Alarm AI flashes every second
Test mode Al off
Alarm in test mode AI flashes every second
The flashing behavior of the point detectors in addressed mode for higher product
versions is described in the
'Extended flashing behavior of the alarm indicators in the case of ES ≥20 [➙ 42]'
chapter.
Collective mode
The flashing behavior of the OOH740 in collective mode is independent from the
product version!
The following additional displays are possible when operating the point detector
OOH740 in collective mode:
Operating condition Flashing mode of alarm indicator
Normal Off
Alarm Flashing every 1 s
Fault Two flashes every 4 s
1
'Standard Plus' parameter Flash every 6 s
set is set
1
'Suppression'parameter set Two flashes every 6 s
is set
1
'High Sensitive Fast' Three flashes every 8 s
parameter set is set
1
Only during the first three minutes of operation after the detector line being started up or reset.
See also
2 Setting the parameter set in collective operation [➙ 68]
40 | 118 A6V10305793_r_en_--
Structure and function
Function
3
The flashing behavior of the external alarm indicators in addressed mode for
higher point detector product versions is described in the
'Extended flashing behavior of the alarm indicators in the case of ES ≥20 [➙ 42]'
chapter.
A6V10305793_r_en_-- 41 | 118
Structure and function
3 Function
Several flashing patterns are available for normal operation. The flashing pattern
is selected using the 'Cerberus-Engineering-Tool' software.
1
Or 'Configuration 1' mode active.
The display priority ensures that important messages are prioritized in the flashing
behavior. Highest display priority: 1.
Example: If a detector is displaying 'Fault' and then an alarm is detected, the
flashing mode will change from 'Fault' to 'Alarm'.
Not all fire control panels support the flashing patterns described.
A steady-on flashing mode for the alarm and an alternative flashing mode for
normal operation can be set using the 'Cerberus-Engineering-Tool' software.
42 | 118 A6V10305793_r_en_--
Structure and function
Function
3
The above graphics are not valid in countries in which the alarm is indicated by an
alarm indicator that lights up permanently. For more information, please contact
your regional company.
Please also observe the documentation for your fire detection system.
1
Fault EAI off
Display priority: 2 t
0 1 2 3 4 5 6 7 8 9 10 11 12 [s]
1
Or 'Configuration 1' mode active.
The display priority ensures that important messages are prioritized in the flashing
behavior. Highest display priority: 1.
Example: If a detector is displaying 'Fault' and then an alarm is detected, the
flashing mode will change from 'Fault' to 'Alarm'.
Information about the product version of your point detector can be found in the
'Product version ES [➙ 26]' chapter.
A6V10305793_r_en_-- 43 | 118
Structure and function
3 Function
See also
2 Sounder base DBS720 [➙ 51]
2 Connection diagram, addressed [➙ 93]
2 Connection diagram, collective [➙ 95]
44 | 118 A6V10305793_r_en_--
Structure and function
Function
3
Physical testing:
● The optical function part on the neural fire detector can also be tested with the
detector tester RE8ST and the test gas REF8 or REF8‑S.
● The heat sensors of the neural fire detector can be tested with the following
accessories:
– Hot air fan
– RE7T Solo461 heat detector tester kit
● The CO sensor can be tested with the detector tester RE8STCO and the test
gas REF8‑C.
See also
2 Internal alarm indicator in the case of ES <20 [➙ 40]
2 Setting the parameter set in collective operation [➙ 68]
2 Testing the point detector [➙ 103]
A6V10305793_r_en_-- 45 | 118
Structure and function
3 Function
In degraded mode operation, the OOHC740 only supports the 'Fire' alarm class. If
the 'CO' alarm class is also to be supported in degraded mode operation, please
contact technical customer support.
Degraded mode operation on the C-NET is not supported in the same way by all
control panels. The information in the 'List of compatibility' and in the corresponding
control panel documentation must be taken into account during project planning.
See also
2 Applicable documents [➙ 9]
46 | 118 A6V10305793_r_en_--
Structure and function
Mechanical setup
3
Properties
● Quick installation and secure contact
● The centered alarm indicator makes an alignment of the detector base
superfluous
● Space for up to 4 auxiliary terminals
Accessories are available for a variety of different applications and can be
combined to suit the particular application in question.
See also
2 Detector base with loop contact DB721 [➙ 48]
2 Detector base DB721D [➙ 50]
2 Detector base (collective) DB110 [➙ 51]
2 Sounder base DBS720 [➙ 51]
A6V10305793_r_en_-- 47 | 118
Structure and function
3 Accessories
3.5 Accessories
See also
2 Detector base DB72x and detector base (collective) DB110
[➙ 81]
2 Cable entry [➙ 91]
48 | 118 A6V10305793_r_en_--
Structure and function
Accessories
3
See also
2 Detector base DB72x and detector base (collective) DB110
[➙ 81]
2 Cable entry [➙ 91]
A6V10305793_r_en_-- 49 | 118
Structure and function
3 Accessories
See also
2 Detector base DB72x and detector base (collective) DB110
[➙ 81]
2 Cable entry [➙ 91]
50 | 118 A6V10305793_r_en_--
Structure and function
Accessories
3
See also
2 Detector base DB72x and detector base (collective) DB110
[➙ 81]
2 Cable entry [➙ 91]
See also
2 Sounder base DBS720 [➙ 83]
2 Cable entry [➙ 91]
A6V10305793_r_en_-- 51 | 118
Structure and function
3 Accessories
See also
2 Designation plate FDBZ291 [➙ 90]
See also
2 Detector base seal RS720 [➙ 84]
See also
2 Base attachment BA720 [➙ 85]
52 | 118 A6V10305793_r_en_--
Structure and function
Accessories
3
See also
2 Base attachment wet BA721 [➙ 87]
See also
2 Base attachment wet BA721 [➙ 87]
See also
2 Detector heating unit FDBH291 [➙ 98]
A6V10305793_r_en_-- 53 | 118
Structure and function
3 Accessories
See also
2 Base attachment wet BA721 [➙ 87]
See also
2 Detector locking device LP720 [➙ 89]
54 | 118 A6V10305793_r_en_--
Structure and function
Accessories
3
See also
2 Connection diagram, collective [➙ 95]
See also
2 Connection diagram, collective [➙ 95]
A6V10305793_r_en_-- 55 | 118
Planning
4 Compatibility
4 Planning
4.1 Compatibility
Compatible with control panels that support the C-NET detector line.
The point detector OOH740 is also compatible with control panels which support
collective mode.
You will find detailed information in the 'List of compatibility'.
The table below shows the compatibility of the devices with various product lines:
Detector Control panels
line
FC20xx FC10 FC12x FC72x SIGMASYS AlgoRex XC10 FC361-xx
C-NET – – – X – – – X
1) 1) 1) 2) 1) 1) 2)
Collective – X X X – – X X
X = compatible
– = not compatible
1)
OOH740 only
2)
Connection only possible via suitable line devices, e.g., input/output module (transponder)
FDCIO223 or zone module FDCI723
56 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
Value concentration
Irreplaceable cultural assets are often on display in museums. Computer centers
house servers with large data volumes. The concentration of valuable items is
rather high. In a normal hotel room the concentration of valuable items must be
classified as low.
Room geometry
High ceilings, complex room shapes or well-ventilated rooms have a complex room
geometry. This aggravates early fire detection, as it is difficult for the fire
phenomenon to reach the fire detector. An office room with normal ceiling height
has a simple room geometry.
Deceptive phenomena
Deceptive phenomena can deceive a fire detector and bring about a false alarm.
The deceptive phenomena differ depending on the fire detector. Deceptive
phenomena include
● Steam
● Cigarette smoke
● Dust
● Dry ice in discotheques
● Exhaust fumes
● Aerosols produced when welding
● Sources of heat such as radiant heaters or hot engines
In a small hotel room with a rather low ceiling where vapor from the bathroom may
penetrate the room, or in operating facilities where a lot of dust is generated, many
deceptive phenomena must be taken into consideration. In a clean room where
electronic modules are fabricated the risk of deceptive phenomena is rather low.
Risk of fire
In production facilities where highly combustible materials such as flammable
liquids, cotton, paper etc. are processed and where electrical machines are
operated, the fire risk is very high. Minor overheating or sparks may cause a fire. In
a storehouse where steel is stored and where no electrical installation is provided
with the exception of lighting, the fire risk is very low.
A6V10305793_r_en_-- 57 | 118
Planning
4 Fire detection
4.2.2.1 Description
(Parameter set numbers in brackets)
Suppression (5):
Thanks to its very robust behavior, the 'Suppression (5)' parameter set is
particularly suitable for rooms where deceptive phenomena such as vapor, very
dense cigarette smoke or exhaust fumes can be expected. It reacts in a very
robust way to the deceptive phenomenon vapor.
Suppression CO (12):
Thanks to its very robust behavior, this parameter set is particularly suited for
rooms where deceptive phenomena such as vapor, cigarette smoke or exhaust
fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor. In the event of smoldering fires or fires in rooms where
cleaning products are stored, the parameter set reacts quicker than the
'Suppression (5)' parameter set as it takes the CO concentration into account.
Robust (2):
The priority of the 'Robust (2)' parameter set is on robust response. The sensitivity
is the same as with the 'Suppression (5)' parameter set; however, deceptive
phenomena are not explicitly analyzed and suppressed. It is thus particularly suited
to application in rooms where deceptive phenomena such as cigarette smoke or
dust can be expected. The 'Robust (2)' parameter set is suitable for higher rooms
in comparison to the 'Suppression (5)' parameter set.
Balanced (4):
The 'Balanced (4)' parameter set displays a balanced response behavior in its
response to fires and robustness to deceptive phenomena. It reacts faster with
open fires. It reacts slower with vapor, cigarette smoke or smoldering fires.
58 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
Balanced CO (10):
This parameter set displays a balanced response behavior in its response to fires
and robustness to deceptive phenomena. It reacts faster with open fires. It reacts
slower with vapor and cigarette smoke. In the event of smoldering fires or fires in
cleaning rooms, the parameter set reacts quicker than the 'Balanced (4)' parameter
set as it takes the CO concentration into account.
Thanks to the fact that three criteria are evaluated (smoke, heat and CO
concentration), this gives particular robustness to deceptive phenomena when
compared with more sensitive parameter sets.
All parameter sets except for 8 comply with standards EN 54-7 and CEA 4021.
Parameter sets 'Balanced CO' and 'Suppression CO' do not have LPCB approval.
A6V10305793_r_en_-- 59 | 118
Planning
4 Fire detection
4.2.2.2 Use
No. Name Risk of damage Concentration Room geometry Deceptive Risk of fire Critical fire size
to persons of valuable phenomena
items
8 'High Suppression'
5 'Suppression'
12 'Suppression CO'
7 'High Compensation'
2 'Robust'
4 'Balanced'
10 'Balanced CO'
6 'Fast Response'
11 'Super Sensitive'
The 'High Suppression', 'High Sensitive Fast', and 'Super Sensitive' parameter
sets are only suited for special applications.
60 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
4.2.2.3 Specification
The following table shows the characteristics and fields of application of the
parameter sets of the point detectors OOH740 and OOHC740.
No. Name Optical Thermal
15
1
The CO signal helps to speed up alarm activation in the event of smoldering fires but cannot
trigger fire alarms on its own.
2
Only for OOHC740: If the 'Suppression (5)' parameter set is needed, 'Suppression CO (12)' should
be used for new applications.
3
Depends on CO proportion.
4
In the case of open fires, the proportion of CO in the fire gas make-up is low. With high proportions
of CO, the sensitivity could theoretically increase by up to 0.9 %/m with open fires (i.e. instead of
2.3 %/m to 1.4…2.3 %/m, for example).
5
Only in the OOH740 from ES ≥20
The following table shows which product version ES meets which standard for the
parameter sets.
No. Name ES <30 ES ≥30
8 'High Suppression' – –
5 'Suppression' EN 54-7 EN 54‑7, EN 54‑29
12 'Suppression CO' EN 54-7 EN 54‑7, EN 54‑29
7 'High Compensation' EN 54-7 EN 54‑7, EN 54‑29
0 'High Compensation' EN 54-7 EN 54‑7, EN 54‑29
2 'Robust' EN 54-7 EN 54‑7, EN 54‑29
4 'Balanced' EN 54-7 EN 54‑7, EN 54‑29
10 'Balanced CO' EN 54-7 EN 54‑7, EN 54‑29
6 'Fast Response' EN 54-7 EN 54‑7, EN 54‑29
9 'High Sensitive Fast' EN 54-7 EN 54‑7, EN 54‑29
11 'Super Sensitive' EN 54-7 EN 54-7
14 Application-specific parameter set – –
A6V10305793_r_en_-- 61 | 118
Planning
4 Fire detection
62 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
4.2.4.1 Description
Select sensor mode 2 when fast temperature changes may occur which are not
caused by fire (e.g. radiant heaters, hot engines). In this sensor mode the detector
only reacts optically; this is comparable with a wide-spectrum smoke detector.
However, because it has a second optical sensor, it reveals an optimized response
behavior in relation to the different types of fire.
(Parameter set numbers in brackets)
Robust (2):
This parameter set responds to aerosols in a similar way as the neural fire detector
in sensor mode 0 with the 'Robust' parameter set, without taking into account the
temperature.
Universal (1):
With 'Universal' the sensitivity and response time to aerosols are between 'Robust'
and 'Sensitive'.
Sensitive (3):
With regard to aerosols, this parameter set reacts in a way that is comparable to
'Fast Response' in sensor mode 0 without temperature influence.
With the exception of '6', all parameter sets meet the criteria of standard EN 54-7.
A6V10305793_r_en_-- 63 | 118
Planning
4 Fire detection
4.2.4.2 Use
No. Name Risk of damage to Concentration of Room geometry Deceptive Risk of fire Critical fire size
persons valuable items phenomena
2 'Robust'
1 'Universal'
3 'Sensitive'
5 'Super Sensitive'
6 'Ultra Sensitive'
4.2.4.3 Specification
The table below shows the parameter sets' characteristics and fields of application:
No. Name Response time Sensitivity
[s] open fire/smoldering fire
[%/m]
2 'Robust' 80 2.3 / 8
1 'Universal' 50 2.3 / 8
0 'Universal' 50 2.3 / 8
3 'Sensitive' 30 1.6 / 5.6
1
5 'Super Sensitive' 12 1.0 / 1.5
1
6 'Ultra Sensitive' 12 0.35 / 0.5
1
Only in the OOH740 from ES ≥20
64 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
4.2.5.1 Description
Standard Plus:
This parameter set is fast and highly sensitive. It is thus especially suited to rooms
without deceptive phenomena, where the priority is on early fire detection.
Suppression:
Thanks to its very robust behavior, the 'Suppression' parameter set is particularly
suitable for rooms where deceptive phenomena such as cigarette smoke or
exhaust fumes can be expected. It reacts in a very robust way to the deceptive
phenomenon vapor.
4.2.5.2 Use
Name Risk of damage Concentration Room Deceptive Risk of fire Critical fire size
to persons of valuable geometry phenomena
items
'Standard Plus'
'Suppression'
'High Sensitive
Fast'
A6V10305793_r_en_-- 65 | 118
Planning
4 Fire detection
4.2.5.3 Specification
Name Optical Thermal
1
Typ. Response Sensitivity, open Sensitivity, Static activation Differential activation temperature
time fire smoldering fire temperature
from - typ. - to
1
Applicable with fast temperature increases >10 K/min.
66 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
After the commissioning of the control panel, the fire detectors are automatically
set to their country-specific basic setting.
You can select and set the parameter sets as follows:
● Using the 'Cerberus-Engineering-Tool' software
● Directly on your fire detection system (only within the same sensor mode)
You will find a description of the exact procedure for selecting and setting the
parameters in the relevant documentation.
See also
2 Applicable documents [➙ 9]
A6V10305793_r_en_-- 67 | 118
Planning
4 Fire detection
If no resistor is installed in the detector base, the 'Standard Plus' parameter set is
set.
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
See also
2 Internal alarm indicator in the case of ES <20 [➙ 40]
2 Parameter set resistor 33 kΩ PSR720-1 [➙ 55]
2 Parameter set resistance 68 kΩ PSR720-2 [➙ 55]
68 | 118 A6V10305793_r_en_--
Planning
Fire detection
4
Hospital room, museum Quick response needed, no deceptive 'Fast 'Standard Plus'
phenomena expected Response (6)'
Clean room Fast and very sensitive reaction 'High Sensitive 'High Sensitive
required Fast (9)' Fast'
A6V10305793_r_en_-- 69 | 118
Planning
4 Fire detection
70 | 118 A6V10305793_r_en_--
Planning
Technical CO alarm
4
The 'Technical CO Alarm' mode can only be selected on the neural fire detector
OOHC740.
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
● The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN 54-2.
4.3.1.1 Description
(Parameter set numbers in brackets)
Static 40 (4):
This parameter set has a static alarm threshold of 40 ppm CO. The parameter set
has a small compensation range.
Static 50 (5):
This parameter set has a static alarm threshold of 50 ppm CO. The parameter set
has a small compensation range.
Static 60 (6):
This parameter set has a static alarm threshold of 60 ppm CO. The parameter set
has a small compensation range.
A6V10305793_r_en_-- 71 | 118
Planning
4 Technical CO alarm
4.3.1.2 Use
No. Name Risk of increased CO concentration Room geometry Deceptive Compensation
concentration of CO phenomena range
(risk of damage to
persons)
0 'Robust EU1'
1
1 'Balanced EU2'
4 'Static 40'
5 'Static 50'
6 'Static 60'
1
7 'Balanced US1'
1
Time-dependent
72 | 118 A6V10305793_r_en_--
Planning
Technical CO alarm
4
4.3.1.3 Specification
The table below shows the characteristics and fields of application of the
parameter sets for CO of the point detector.
No. Name Response thresholds of warning levels 1 to 3 'Technical CO Alarm' Alarming
[ppm CO] according to
standard
1 2 3
Static Concentration-dependent
[ppm CO] response time [min]
1
0 'Robust EU1' 30 60 – - –
4 'Static 40' 30 35 40 - –
5 'Static 50' 30 40 50 - –
6 'Static 60' 30 45 60 - –
1
Warning level 3 is not output in the default device parameter set.
Example for parameter set 1 'Balanced EU2' @ 55 ±5 ppm CO:
At 50 ppm CO, alarming must take place after between 60 and 90 minutes.
The point detector may only be used in continuous operation within the specified
temperatures!
A6V10305793_r_en_-- 73 | 118
Planning
4 Technical CO alarm
See also
2 Applicable documents [➙ 9]
74 | 118 A6V10305793_r_en_--
Planning
Technical CO alarm
4
A6V10305793_r_en_-- 75 | 118
Planning
4 Technical Ambient Supervision Message
‘Technical Ambient Supervision Message' mode can only be selected for point
detector OOH740 from product version ES ≥20.
The evaluation of the CO concentration in 'Technical Ambient Supervision
Message' mode can only be selected for point detector OOHC740.
NOTICE
The system is not controlled as laid down in EN 54-2
Infringement of the EN 54-2 standard
● The signals for CO detection or temperature recording must not be used to
control fire detection equipment in accordance with EN 54-2.
76 | 118 A6V10305793_r_en_--
Planning
Technical Ambient Supervision Message
4
35
2
30
25
1
20 t
4
2
0 t
Figure 10: Ambient supervision output signal when the operating temperature threshold value of 35 °C
is exceeded and a hysteresis range of 5 °C is selected. The diagram below shows the progression of
the output signal.
A6V10305793_r_en_-- 77 | 118
Planning
4 Technical Ambient Supervision Message
Hysteresis ranges
You can set two hysteresis ranges:
● Normal hysteresis range with a range of 1 °C.
● Large hysteresis range with a range of 5 °C.
See also
2 Technical data for OOH740 [➙ 107]
2 Technical data for OOHC740 [➙ 110]
4.4.1.2 CO monitoring
CO monitoring compares the current measured CO concentration with a preset
threshold value.
Alarming takes place when the current measured CO concentration temperature
exceeds the set threshold value.
You can set the CO concentration threshold value in stages of 5 ppm between
20 and 600 ppm.
78 | 118 A6V10305793_r_en_--
Planning
Technical Ambient Supervision Message
4
4.4.2 Configuration
You can configure the point detector using the 'Cerberus-Engineering-Tool'
software as follows:
A6V10305793_r_en_-- 79 | 118
Mounting / Installation
5 Required space
5 Mounting / Installation
* * *
* = min. 2 cm
1
80 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector base DB72x and detector base (collective) DB110
5
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
● The cable loops must be placed flat in the base bottom.
● The bare length of the cables is approximately 8…10 mm.
Please note the limitations when using the detector base DB721D.
See chapter 'Connection diagram, collective [➙ 95]'.
In the case of the detector bases DB721 and DB722, the C-NET detector line is
not interrupted even if a point detector is not used.
A6V10305793_r_en_-- 81 | 118
Mounting / Installation
5 Detector base DB72x and detector base (collective) DB110
Connection terminals
The following detector bases have screw terminals:
● DB721
● DB721D
● DB720
● DB110
The following detector bases have spring clips:
● DB722
DB721
DB721D
DB720
DB110
DB722
You will find information on connecting the detector bases in the chapters
'Cable entry [➙ 91]' and 'Detector lines [➙ 93]'.
82 | 118 A6V10305793_r_en_--
Mounting / Installation
Sounder base DBS720
5
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
● The cable loops must be placed flat in the base bottom.
● The bare length of the cables is approximately 8…10 mm.
In the case of the sounder base DBS720, the C‑NET detector line is not
interrupted even if a point detector is not used.
A6V10305793_r_en_-- 83 | 118
Mounting / Installation
5 Detector base seal RS720
84 | 118 A6V10305793_r_en_--
Mounting / Installation
Base attachment BA720
5
A6V10305793_r_en_-- 85 | 118
Mounting / Installation
5 Base attachment BA720
2
Figure 14: Surface-mounted cable entry with base attachment BA720
86 | 118 A6V10305793_r_en_--
Mounting / Installation
Base attachment wet BA721
5
Note the dimensions of the protective cages (Fig. 3) before installing base
attachment wet BA721!
You will find information on connecting detector heating unit FDBH291 in the
'Connection of the detector heating unit' chapter.
122 13
13
A
122
122
1x A
Click
13
13 122
Click
Fig. 2
5
4.
1x A
7.
5
DB72x
4x
Fig. 1
2x
DBZ1193A
160
13 13
FDBZ294
Fig. 3 Fig. 4
DBZ1194
Figure 15: Mounting and removal of protective cages and designation plates on base attachment wet
BA721
A6V10305793_r_en_-- 87 | 118
Mounting / Installation
5 Base attachment wet BA721
WARNING
Danger of falling
Danger of injury
● When installing, use a secured ladder or work platform.
● Only use detector exchanger DX791 as a mounting tool.
See also
2 Protective cage DBZ1194 [➙ 54]
2 Detector heating unit FDBH291 [➙ 53]
88 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector locking device LP720
5
1.
2.
B
Figure 16: Installing the detector locking device LP720
A6V10305793_r_en_-- 89 | 118
Mounting / Installation
5 Designation plate FDBZ291
If the detector base seal RS720 is being used, it is not possible to install the
designation plate FDBZ291.
90 | 118 A6V10305793_r_en_--
Mounting / Installation
Cable entry
5
The resistor for selecting the parameter set must be mounted between connections
'5' and '1a'.
NOTICE
Incorrect laying of cables
Damage to cables and difficulties when installing the point detector
● The cable loops must be placed flat in the base bottom.
● The bare length of the cables is approximately 8…10 mm.
A6V10305793_r_en_-- 91 | 118
Mounting / Installation
5 Cable entry
Figure 18: Detector base with connection terminals and micro terminals
92 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector lines
5
A6V10305793_r_en_-- 93 | 118
Mounting / Installation
5 Detector lines
1 7
8
5 6 5 6 5 6
+ + –
3
– –
5 6
– +
4
2 2
1a 1b 1a 1b
5 6
5 6 5 6
3 3
4
The alarm indicator connected will continue to function correctly in the event of a
short-circuit occurring at position '7' on the connection diagram. The alarm indicator
is triggered by cable –EAI6.
If the short-circuit occurs at position '8' on the connection diagram, the alarm
indicator will no longer be triggered.
As an option, the alarm indicator may also be connected using cable -EAI5.
In this case, the alarm indicator will correctly indicate an alarm even if a short-
circuit occurs at position '8'.
This ensures that the alarm indicator is always functioning correctly.
94 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector lines
5
You will find more detailed information in the fire detection system documentation.
Use of the detector base DB721D makes it easier to subsequently migrate the fire
detection installation from a collective detector line to an addressed detector line.
The detector bases no longer need to be replaced.
A6V10305793_r_en_-- 95 | 118
Mounting / Installation
5 Detector lines
Connection diagram
Check that the cables are installed correctly by performing an appropriate function
test.
See also
2 Parameter sets for fire detection [➙ 33]
2 Parameter set resistor 33 kΩ PSR720-1 [➙ 55]
2 Parameter set resistance 68 kΩ PSR720-2 [➙ 55]
96 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector dust cap
5
A detector dust cap is provided as part of the scope of supply for each point
detector.
A6V10305793_r_en_-- 97 | 118
Mounting / Installation
5 Detector heating unit FDBH291
Optimum function of the detector heating unit is only guaranteed with base
attachment wet BA721.
98 | 118 A6V10305793_r_en_--
Mounting / Installation
Detector heating unit FDBH291
5
NOTICE
Risk of icing
Malfunction
● To ensure smooth operation, the detector must be checked regularly for icing.
DB721 DB721
1a 1b 1a 1b +
DBZ1190-AA DBZ1190-AA
5 6 5 6
- + - +
-
1 +
FDBH291 FDBH291
LINE
2 +
-
Figure 22: Connection diagram for detector heating unit FDBH291
A6V10305793_r_en_-- 99 | 118
Mounting / Installation
5 Migration from collective detector line to addressed detector line
Because the resistor is no longer needed, e.g. the connection wires of the resistor
can be cut using a wire cutter or another cutting tool.
If there are a lot of collective point detectors on one stub, it is often the case that
not all of the detectors are detected when the detector line is first started up. In
this instance, restart the detector line. Repeat this process until all of the
detectors are detected by the control panel.
See also
2 Connection diagram, collective [➙ 95]
2 Removing the diode unit [➙ 101]
WARNING
Falling diode unit
Risk of eye damage
● Wear safety goggles when removing the diode unit!
6 Commissioning
7 Maintenance / Repair
Recommendation:
● Check the devices every year.
● Replace heavily soiled or damaged devices.
● All point detectors should be replaced after 6 to 8 years of service, depending
on the ambient conditions.
● The CO sensor used in the OOHC740 has a maximum service life of 5 years.
When CO-supported parameter sets are activated, a critical warning is
triggered once this period has lapsed.
It can continue to be used as an OOHC fire detector depending on the fire
control panel following reconfiguration to non-CO-supported parameter sets
until the recommended replacement interval of 6 to 8 years is reached.
Collective operation
In collective operation, the point detector OOH740 has a reduced response time for
a period of 3 minutes following the detector line being started up or reset. In this
time, the point detector responds faster to test gas or a hot air fan than in normal
operation.
Once an alarm is triggered on a point detector, the detector line must be restarted.
Only then can the next point detector be tested.
You will find more detailed information in the fire detection system documentation.
See also
2 Test mode on the control panel [➙ 104]
Collective operation
Collective control panels can be switched to test mode too. In this instance,
however, only the output of a real alarm is prevented. With collective control
panels, test mode has no influence over point detectors' response times.
The detector must be disconnected from the power supply on a collective detector
line such that it switches to test mode.
You can do the following to disconnect the power supply:
● Restart the detector line
● Remove from the detector base for at least 5 s the detector to be tested first in
a detector line and then reinsert it
The point detectors then have a reduced response time for 3 minutes.
See also
2 Testing the point detector [➙ 103]
If the point detector is working in test mode, the following must be noted:
In test mode, the point detector responds according to the sensor mode selected.
This means when the point detector is operated as a heat detector (sensor
mode 1), it must be thermally checked as well.
Selecting test mode for the fire zone on the fire control panel does not deactivate
evaluation of the functionality of the 'CO Technical Alarm' and 'Ambient
Supervision Technical Alarm'.
When the detector is in alarm condition, the internal alarm indicator flashes. For
information on the flashing modes, observe the notices in chapters
'Internal alarm indicator in the case of ES <20 [➙ 40]' and
'Extended flashing behavior of the alarm indicators in the case of ES ≥20 [➙ 42]'.
If the point detector OOHC740 is working in test mode, the following must be
noted:
Because the fire detection functionality is not automatically deactivated during test
mode for CO, the documentation provided for the control panel must be consulted
for details of how to proceed.
If using CO test gases which haven't been approved, a fire alarm may be
triggered during testing if additional setting of test mode is not undertaken on the
fire control panel.
8 Specifications
Unless otherwise mentioned, the following data applies:
Temperature = 25 °C
Air pressure = 1000 hPa (750 Torr)
8.3 Dimensions
OOH740 OOHC740
106 106
43
43
27
27
117 117
49
49
8.4 Environmental compatibility
This equipment is manufactured using materials and procedures which
comply with current environmental protection standards as best as
possible. More specifically, the following measures have been
undertaken:
● Use of reusable materials
● Use of halogen-free plastics
● Electronic parts and synthetic materials can be separated
Larger plastic parts are labeled according to ISO 11469 and ISO 1043.
The plastics can be separated and recycled on this basis.
Index
A
Ambient supervision ......................................... 20
Application as heat detector
Sensor mode 1 ............................................ 30
Application as neural fire detector
Sensor mode 0 ............................................ 30
Application as smoke detector
Sensor mode 2 ............................................ 30
Approvals ............................................... 107, 110
ASAtechnology................................................. 21
Auxiliary terminals
Connection terminal .................................... 92
Micro terminal.............................................. 92
C
Cables .............................................................. 93
Carbon monoxide
CO ............................................................... 20
CE marking............................................. 107, 110
CO
Carbon monoxide ........................................ 20
CO concentration ....................................... 30, 78
Average ....................................................... 78
Average over 15 minutes ............................ 78
CO sensor
Detection of carbon monoxide .................... 29
Collective behavior
Degraded mode operation .......................... 46
Collective mode
Internal alarm indicator................................ 40
Product version and flashing modes ........... 40
Setting for parameter sets ........................... 32
Compatibility............................................... 56, 95
Compatibility with control panels ...................... 56
Connection diagram ......................................... 93
External alarm indicators............................. 93
Connection terminal ......................................... 92
Control panel .................................................. 102
H R
Hot air fan Recycling........................................................ 112
Test device .................................................. 45 Renovation mode
Hysteresis................................................... 28, 30 Major renovation work ................................. 44
Hysteresis range .................................. 30, 76, 78 Required space ................................................ 80
Resistance
I
PSR720-1.............................................. 55, 95
Internal alarm indicator..................................... 40
PSR720-2.............................................. 55, 95
Alarm ........................................................... 40
Collective mode........................................... 40 S
Test mode ................................................... 40 Screw terminals
Assignment ................................................. 91
L
Sensor mode 0
Line separator
Application as neural fire detector ............... 30
Function ...................................................... 39
Sensor mode 1
List of compatibility ..... 9, 20, 46, 56, 95, 107, 110
Application as heat detector ........................ 30
Loop ................................................................. 93
Sensor mode 2
M Application as smoke detector .................... 30
Maintenance intervals .................................... 103 Short-circuit
Major renovation work Line separator ............................................. 39
Renovation mode ........................................ 44 Reset the detector line ................................ 39
Micro terminal................................................... 92 Signal processing of the point detector
Danger level ................................................ 37
O Warning level .............................................. 38
Order number ................................................... 25
Sounder base ............................................. 44, 47
Original language ............................................... 7
Source language ................................................ 7
T
Temperature exceeded .................................... 78
Temperature increase ................................ 28, 30
Temperature undershot.................................... 78
Test device
Detector tester RE6T .................................. 45
Detector tester RE8ST ................................ 45
Detector tester RE8STCO........................... 45
Heat detector tester kit RE7T Solo461........ 45
Hot air fan.................................................... 45
Test gases REF8, REF8-S.......................... 45
Test gases REF8, REF8-S
Test device .................................................. 45
Test mode
Addressable detector ................................ 104
Collective detector..................................... 104
Threshold value................................................ 78
Topology........................................................... 93
Type plate
Product version ........................................... 26
W
Warning level
Signal processing of the point detector ....... 38
A6V10305793_r_en_--