0% found this document useful (0 votes)
59 views13 pages

Example2 Gauss Seidel Details

This document describes using the Gauss-Seidel method to solve a power flow problem for a three-bus system. It involves determining the bus types, converting impedances to admittances, setting up the bus power injections, iteratively calculating the voltages and reactive power at buses 2 and 3 until reaching an acceptable tolerance, then calculating line currents, line flows, and losses.

Uploaded by

Nor Hanaros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views13 pages

Example2 Gauss Seidel Details

This document describes using the Gauss-Seidel method to solve a power flow problem for a three-bus system. It involves determining the bus types, converting impedances to admittances, setting up the bus power injections, iteratively calculating the voltages and reactive power at buses 2 and 3 until reaching an acceptable tolerance, then calculating line currents, line flows, and losses.

Uploaded by

Nor Hanaros
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

GAUSS

SEIDEL
EXAMPLE 2 (SLACK
BUS AND PV BUS)

Example 2 Gauss Seidel|


AziahKhamisV1_2020
EXAMPLE
The Figure shows the one-line diagram of a simple three-
2 bus power system with generators at buses 1 and 3. The
magnitude of voltage at bus 1 is adjusted to 1.05 pu.
Voltage magnitude at bus 3 is fixed at 1.04 pu with a real
power generation of 200 MW. A load consisting of 400
MW and 250 Mvar is taken from bus 2. Line impedances
are marked in per unit on a 100 MVA base, and the line
charging susceptances are neglected. Obtain the power
flow solution by the Gauss-Seidel method including line
flows and line losses.

Example 2 Gauss Seidel| AziahKhamisV1_2020


STEP1: TYPE OF BUS
B1 B2 B3 NEXT STEP
Voltage, |V | ✓ ✓
Phase angle, δ ✓
S
Real power, P ✓ ✓
Reactive power, Q ✓ PV
BUS

FROM THE TABLE AND THE QUESTION:


V1= SLACK BUS
SO WE NEED TO FIND V2 AND Q3. (USING GAUSS
SEIDEL METHOD)

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 2: IMPEDANCE TO ADMITTANCE

yij IMPEDANCE ADMITTANCE


y12 0.02+j0.04
y13 0.01+j0.03
y23 0.0125+j0.025

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 3: S IN PER UNIT
P Q
S2 400 j250 NOTE THAT SBASE
S3 200 GIVEN IN QUESTION IS
100MVA.

NEXT

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 4: CALCULATE Vi
Assume initial V for V(2)(0) = 1+j0; GIVEN THAT V(3)(0) =1.04+j0; V(1) =1.05 Recall
information

S2sch,
S3sch

Example 2 Gauss Seidel| V(2)(2)


V(3)(2)
AziahKhamisV1_2020
STEP 5: CALCULATE Q3
Evaluate Q(3)(1) value from base on the calculation of V(2)(1)
V(2)(1)

S2sch,
S3sch

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 7: CONTINUE CALCULATE Q3 Vi
Continue solving V(2)(2) and Q3)(2) by taking V(2)(1) and V(3)(1) value from the calculation

V(2)(1)

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 7: CHECK ACCURACY
Continue solving V(2)(3) and Q(3)(3) by taking V(2)(2) and Q(3)(2) value from the calculation and repeat until error = 5x10-5

Therefore,

LINE
CURRENT

Example 2 Gauss Seidel|


AziahKhamisV1_2020
STEP 8: CALCULATE S AT SLACK BUS
Recall
information

Example 2 Gauss Seidel|


AziahKhamisV1 2020
STEP 9: CALCULATE LINE CURRENT
I12=y12(V1-V2)
V2
I21=- I12 V3
I13=y13(V1-V3)
I31=- I13
I23=y23(V2-V3)
I32=- I23

DRAW
Example 2 Gauss Seidel|
AziahKhamisV2 2020
STEP 10: CALCULATE LINE FLOW

DRAW
Example 2 Gauss Seidel|
AziahKhamisV1_2020
STEP 9: DRAW DIAGRAM

LINE FLOW
LOSSES

Example 2 Gauss Seidel|


AziahKhamisV1_2020