T14 Control Charts PDF
T14 Control Charts PDF
TURBINE METER
K-FACTOR CONTROL CHARTS
1.1 CRITERIA
1.2 REPEATABILITY
1.3 ACCURACY OF CALIBRATION
1.4 SENSITIVITY TO FLOW RATE
1.5 SENSITIVITY TO FLUID
1.6 STABILITY OVER TIME
2.1 TECHNIQUES
2.2 PERFORMANCE CURVES
2.3 CONTROL CHARTS
2.4 NORMALISATION
3.1 DATA
3.2 ANALYSIS
4.1 INTERPRETATION
4.2 COMPARISON
1.1 CRITERIA
It can be demonstrated that the accuracy of a turbine flow meter is critically dependant upon
the accuracy of the meter K-factor.
a) Repeatability
b) Accuracy of calibration
c) Sensitivity to flow rate
d) Sensitivity to fluid
e) Stability over time
1.2 REPEATABILITY
Repeatability, that is the quality of the flow meter to return a consistent K-factor at specified
conditions, is essential for a fiscal flow meter.
The ideal turbine flow meter would have a constant K-factor at all flow rates and at all fluid
conditions. The real turbine meter is subject to K-factor variation due to changes in:
a) The flowrate
b) The fluid conditions, especially viscosity
c) Wear and tear
d) Mechanical inconsistencies
Item (a) above, a random scatter of K-factor is the normally accepted definition of
non-repeatability and cannot be accepted in a fiscal flow meter.
The accuracy of the turbine meter calibration is critical to the overall accuracy of
measurement.
A turbine meters K-factor will change with flow rate. The quantative shift will vary with
flow meter design and between the products of different manufacturers.
Turbine flow meters are sensitive to fluid conditions. There is a degree of sensitivity to the
direct effect of the fluid temperature, density and pressure, but the most significant effect is
the sensitivity to fluid VISCOSITY.
The fluid viscosity cannot be readily measured but viscosity is a function to temperature,
density and pressure.
A focal problem with operating a turbine meter is in differentiating between random K-factor
shifts (non-repeatability) and viscosity related K-factor shifts.
Stability over a time period can be classified in a similar manner to repeatability (section 1.2
above):
Item (a) exhibits non-repeatability and would result in the rejection of the turbine meter.
Item (b) could be considered as “bedding-in” of the meter and can be accommodated by
routine meter proving.
Item (c) must be investigated. There may be circumstances where the meter was rejected
and there may be circumstances where the meter could continue in use.
2.1 TECHNIQUES
There are two techniques commonly applied to monitoring the performance of turbine flow
meters:
a) Performance curves
b) Statistical control charts
When a new meter has been installed a series of meter proving runs must be carried out to
determine the meter K-factor over a range of flow rates (20% to 100% of maximum flow
rate).
If the fluid viscosity is subject to change then more than one performance curve will be
required for each meter. Performance curves at representative fluid conditions are required.
When the performance curve has been established action limits at + 0.1% and -0.1% must
be set up.
Each time the flow meter has been proved the operator should check the K-factor obtained
against the corresponding flowrate on the performance curve.
If the K-factor is within the action limit of the performance curve then the K-factor may be
accepted.
If the K-factor is outwith the limit then the meter proof should be repeated. If after three
full meter proofs have been carried out and the K-factor can be confirmed to have shifted
the operator must take action as specified for the particular meter station.
The control chart is a chart of meter K-factor against consecutive meter proofs (time).
Statistical analysis is applied to the meter proof results to set up warning and action limits.
Meter K-factor control charts provide a convenient graphical means for monitoring the
performance of turbine meters and the meter system as a whole. The control chart can be
used to assist in deciding whether an observed change in meter factor is acceptable, based on
the statistical analysis of past performance data, or whether there is some "assignable cause"
influencing the change.
In the latter case the control chart cannot indicate where the problem lies. If the change falls
outside acceptable limit of random variation then it may have been the result of damage or
wear to the meter; leaking valves; incorrect data in the flow computer etc. An investigation
will be necessary.
A meter K-factor control chart should therefore be maintained for each meter in service and
should be used to check the validity of new K-factors determined after each reproof.
2.4 NORMALISATION
Ideally the meter K-factor should be normalised to counteract the effect of flowrate and
viscosity sensitivity.
Without normalisation the K-factor will exhibit changes which could be due to any of the
following:
a) Flowrate variation
b) Viscosity variation
c) Damage to the meter
d) Meter wear and deterioration
Normalisation would remove the effects of items (a) and (b), which are normal, and
highlight the fault conditions (c) and (d). Graphical techniques and regression analysis have
been proposed.
3.1 DATA
Meter factor control charts should be set up as soon as possible after the meter system has
been started up or a new meter has been installed. Repeated meter proving sequences
should be carried out until sufficient data has been gathered to calculate meaningful control
limits. Ideally at least 15 proving sequences should be carried out but the feasibility of this
will depend on operating conditions. In any case the results of not less than 10 proving
sequences should be acquired.
If the system is known to operate under different operating condition regimes it may be
necessary to construct a number of control charts to accommodate the different operating
conditions. Where operating conditions are reasonably constant a control chart reflecting
average operating conditions can be used to test the validity of subsequent K-factor
determinations.
3.2 ANALYSIS
Having gathered the initial K-factor data it can be processed statistically in the following
way.
K=
(K1 + K 2 + K3 .... + K n )
n
Where:
3.2.2 The next step is to calculate the standard deviation of the K-factor
determinations K1, K2 etc. This is done using the following formula.
∑ (K - K)
2
σ = i
n -1
Where
The term
∑ (K - K)
2
i
means
(K 1 - K ) + (K 2 - K ) + (K 3 - K ) .... + (K n - K )
2 2 2 2
4.1 INTERPRETATION
In order for the control chart to provide useful information it must be kept up to date at all
times.
If K-factors drift outside or repeatedly fall outside the control limits then the system must be
investigated to find an assignable cause. The control chart can give no indication of the
likely cause of the shift and a number of possibilities need to be considered before it is
concluded that the problem lies with the meter itself. A typical list of possible causes is
given below.
4.2 COMPARISON
Where the meter system comprises a number of parallel runs a check on the K-factors of
other meters may assist in determining whether the problem, if it is a meter system problem,
lies with the meter or with the prover.
Note to Rev 3, October 1999: The DTI (OGO) are investigating the preparation of
guidelines to set common standards for monitoring and accepting meter K-factors
Control charts or trend charts can be used to monitor the performance of many different
types of instrument.
Turbine meter control charts can be applied to positive displacement meters and can be
adapted to apply to Coriolis mass flow meters.
Trend charts and deviation charts can be applied to monitor density meters.
FIG. 1
K-Factor
Determination K-Factor
Run Number Pulses/m³ K −K (K − K )2
K = 6002.44
∑ (K - K ) = 12.48
2
i
12.48
σ =
(5 - 1)
F = ± 1.77 pulses/m³
2F = ±3.54 pulses/m³
3F = ±5.31 pulses/m³