PVC-Insulated Cables: 450/750V Single-Core PVC Insulated, Non-Sheathed Cable

This document summarizes the specifications of PVC-insulated single-core cables with voltage ratings of 450/750V. The cables can be used in light fittings and switching equipment installed in conduits, trunking, or on cable trays. The cable consists of plain annealed copper conductors insulated with PVC. Conductor sizes range from 1.5 to 630 mm2. Insulation thickness and overall cable diameters vary with conductor size. Color coding of the insulation is also specified.

Uploaded by

Than Zaw Htay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
147 views1 page

PVC-Insulated Cables: 450/750V Single-Core PVC Insulated, Non-Sheathed Cable

This document summarizes the specifications of PVC-insulated single-core cables with voltage ratings of 450/750V. The cables can be used in light fittings and switching equipment installed in conduits, trunking, or on cable trays. The cable consists of plain annealed copper conductors insulated with PVC. Conductor sizes range from 1.5 to 630 mm2. Insulation thickness and overall cable diameters vary with conductor size. Color coding of the insulation is also specified.

Uploaded by

Than Zaw Htay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

PVC-Insulated Cables

tel (65) 6367 0107 fax (65) 6365 2963


450/750V Single-Core www.keystone-cable.com
PVC Insulated, Non-Sheathed Cable
CU/PVC

Application : This cable is used in light fitting, and in switching


and control equipment. It can be installed in
conduit, in cable trunking and on cable trays.
Voltage rating : 450/750V
Construction : Plain annealed copper, PVC insulated cable
Brown, Black, Grey, Blue, Green/Yellow or as per
Insulation colour :
order
Specification : SS358-3, BS6004, IEC60227-3

Conductor Insulation Approx.


Approx. Weight
Nominal Area No./Dia. of Strand Approx. Dia. Thickness Overall Dia.

mm2 No./mm mm mm mm kg/km

1.5 1/1.38 1.38 0.7 2.9 20

1.5 7/0.53 1.59 0.7 3.1 22

2.5 1/1.78 1.78 0.8 3.4 32

2.5 7/0.67 2.01 0.8 3.7 34

4 7/0.85 2.55 0.8 4.3 50

6 7/1.04 3.12 0.8 4.8 70

10 7/1.35 4.05 1.0 6.0 120

16 7/1.70 5.10 1.0 7.0 180

25 7/2.14 6.42 1.2 9.0 280

35 19/1.53 7.65 1.2 10.0 380

50 19/1.78 8.90 1.4 12.0 500

70 19/2.14 10.70 1.4 13.7 715

95 19/2.52 12.60 1.6 16.0 990

120 37/2.03 14.21 1.6 17.5 1,220

150 37/2.25 15.75 1.8 19.5 1,500

185 37/2.52 17.64 2.0 22.0 1,890

240 61/2.25 20.25 2.2 25.0 2,460


PVC-Insulated Cables

300 61/2.52 22.68 2.4 28.0 3,080

400 61/2.85 25.65 2.6 31.5 3,920

500 61/3.20 28.80 2.8 35.0 4,920

630 127/2.52 32.76 2.8 39.0 6,260


For current rating and voltage drop please refer to Tables 10 & 11 (Page 54)