11Kv Indoor Live Tank Vacuum CB Test Report: Stelmec Limited, India

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 2

11kV INdoor Live Tank Vacuum CB Test Report Page 1 of 2

Customer Bangladesh Power Development Board (BPDB)


Project 33/11 Kv Upgradation & Renovation at Shibati Substation PKG-5
Contract Contract No-10350 PKG-5
Substation Shibbati 33/11kV Substation
Location/Feeder 11kV TRIncoming Feeder (L1)

Equipment Data

Manufacturer Stelmec Limited, India


Type SPCV-36-VC53 Rated Frequency 50 Hz
Serial No. SLJ 1902 8869 Operating Sequence O-0.3s-CO-3min-CO
Mfg. Year 2019 Control Voltage 110Vdc
Rated Voltage 36kV Operating Mechanism Spring
Rated Current 1250A Motor Voltage 230Vac
Rated Short Circuit Current 26.3kA 3s Op. Counter at Charging 0047

Insulation Test

Insulation Resistance, Ω
Test Type Applied Voltage
R Y B
CB Open (R – R) 5000 346.3 G 561.3 G 504.7 G
CB Close (R – E) 5000 747.1 G 658.2 G 1100.0 G

Contact Resistance

Resistance, μΩ
Measure Location Applied Current
R Y B
CB Contact 200 A 42 38 40

Timing Test

Time, ms
Test Coil Current (A)
R Y B
CB Open 2.95 62.8 62.4 62.7
CB Close 2.94 64.1 63.8 64.1

Operation Check
Local Close (Mechanical) OK
Local Trip (Mechanical) OK
Local Close (Electrical) OK
Local Trip (Electrical) OK
Remote Close by control switch OK
Remote Trip by control switch OK
Remote Trip by Protection Relays OK

For SWPL For BPDB/NESCO Date:


26/07/2020
11kV INdoor Live Tank Vacuum CB Test Report Page 2 of 2

Customer Bangladesh Power Development Board (BPDB)


Project 33/11 Kv Upgradation & Renovation at Shibati Substation PKG-5
Contract Contract No-10350 PKG-5
Substation Shibbati 33/11kV Substation
Location/Feeder 11kV TRIncoming Feeder (L1)

Indications Lamps and Mimics OK


Healthy trip indication OK
All MCB and circuit links correct OK
Heater OK

For SWPL For BPDB/NESCO Date:


26/07/2020