Miniature Circuit Breaker S 200 MT UC For DC and AC Applications in The Traction Industry
Miniature Circuit Breaker S 200 MT UC For DC and AC Applications in The Traction Industry
Miniature Circuit Breaker S 200 MT UC For DC and AC Applications in The Traction Industry
2CDC021009S0014
2CDC021012S0014
The miniature circuit breaker S 200 MT UC Standards and approvals
extends the established ABB System Standards
IEC/EN 60947-2
pro M compact® product range with an UL 1077
MCB for DC and AC applications for CSA 22.2. No.235
General Data
Standards IEC/EN 60947-2, UL1077, CSA 22.2 No. 235
Poles 1P, 2P, 3P, 4P
Rated current In 0.2 - 63 A
Rated frequency f 0/50/60 Hz
Rated insulation voltage Ui 253 V AC (phase to ground), 440 V AC (phase to phase)
Overvoltage Category III
Pollution Degree 2
IEC/EN 60947-2
Tripping Characteristics B, C, K, Z
Rated operational voltage U e 1P: 253 V AC, 220 V DC
2...4P: 440 V AC, 440 V DC
Max. power frequency recovery voltage U max 1P: 266 V AC, 250 V DC
2...4P: 462 V AC, 500 V DC
Min. operating voltage 12 V AC – 12 V DC
Rated ultimate short-circuit breaking capacity Icu ≤40 A: 10 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
Rated service short-circuit breaking capacity I cs ≤40 A: 7.5 kA (AC); 10 kA (DC)
>40 A: 6 kA (AC); 10 kA (DC)
Rated impulse withstand voltage U imp (1.2/50µs) 4 kV (test voltage 6.2 kV at sea level; 5 kV at 2,000 m)
Dielectric test voltage 2.0 kV (50/60 Hz, 1 min)
Reference temperature for tripping characteristics B, C 55 °C
K, Z 20 °C
Electrical endurance I n ≤ 25 A: 20,000 ops. (AC), In > 25 A: 10,000 ops. (AC); 1,500 ops. (DC)
UL1077 / CSA 22.2 No. 235
Tripping Characteristics K, Z
Rated voltage 1P: 277 V AC, 250 V DC
2...4P: 480 V AC, 500 V DC
Rated interrupting capacity 6 kA (AC); 10 kA (DC)
Application Suppl. prot., for general use
Reference temperature for tripping characteristics 25 °C
Electrical endurance 6,000 ops., 1 cycle (1s.-ON, 9s.-OFF)
Mechanical data
Housing Insulation group I, RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Real CPI (green OFF / red ON)
Protection degree acc. to DIN EN 60529 IP20, IP40 in enclosure with cover
Mechanical endurance 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5 g - 20 cycles at 5 ... 150 ... 5 Hz at 0.8 In
Environmental conditions (damp heat cyclic) 28 cycles with 55 °C/90-96 % and 25 °C/95-100 %
acc. to IEC/EN 60068-2-30
Ambient temperature -25 ... +55 °C
Storage temperature -40 ... +70 °C
2 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Technical data
Installation
Terminal Failsafe bi-directional cylinder-lift terminal
Cross-section of conductors (top/bottom) solid, stranded: 35 mm² / 35 mm²
flexible: 25 mm2 / 25 mm2
14 – 4 AWG (Cu only)
Cross-section of busbars (top/bottom) 10 mm² / 10 mm²
14 – 8 AWG
Torque IEC 2.8 Nm
UL 18 in-Ibs.
Screw driver No. 2 Pozidrive
Mounting on DIN rail 35 mm, acc. to EN 60715 by fast clip
Mounting position any
Supply Please note polarity of device
Dimensions and weight
Mounting dimensions acc. to DIN 43880 1
Pole dimensions (H x D x W) 85 x 69 x 17.5
Pole weight approx. 125 g
Combination with auxiliary elements
Auxiliary contact Yes
Signal contact Yes
Shunt trip Yes
Undervoltage release Yes
Motor operating device Yes
2CDC002175D0201 - 3
Miniature Circuit Breaker S 200 MT UC
Tripping characteristics
B characteristic C characteristic
2CDC022015F0214
2CDC022017F0214
K characteristic Z characteristic
2CDC022060F0211
2CDC022010F0211
4 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Derating
For installations of miniature circuit breakers at other temperatures than the reference value and installations of several minia-
ture circuit breakers directly side by side, derating factors have to be considered.
2CDC002175D0201 - 5
Miniature Circuit Breaker S 200 MT UC
Accessories and dimensional drawings
Accessory* overview
2CDC092028F0214
H-R Auxiliary contact S2C-H6-...R H-L Auxiliary contact to be mounted on the left S2C-H...L
S/H Signal/Auxiliary contact S2C-S/H6R H-BF Auxiliary contact for bottom fitting
Dimensional drawing
2CDC022007F0010
6 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Use of MCBs in direct current circuits
S 200 MT UC MCBs can be used in the one-pole version at For DC incoming supply from above
220 V DC, and in the 2-pole or 4-pole version with series S 200 MT UC MCBs have, in the area of arc chutes, perma-
connection of two poles up to 440 V DC. nent magnets. It is therefore necessary to take into account
the polarity during the installation process.
S 200 MT UC differs from the standard S 200 type as it is Doing so ensures that in the case of a short circuit the ma-
fitted with permanent magnets, which assists in the forced gnetic field of the permanent magnets corresponds with the
extinguishing of the arc. electromagnetic field of the short-circuit current, therefore
safely leading the short circuit into the arc chute.
If voltages to earth exceeding 220 V DC may occur, 2-pole Incorrect polarities may cause damage to the MCB. This is
S 200 MT UC is to be used for one-pole disconnection, and why – in the case of top-fed devices – terminal 1 must be
four-pole S 200 MT UC for all-pole disconnection. connected to (-) and terminal 3 to (+).
Example for permissible voltages between the conductors depending on the number of poles and circuit layout:
voltage U n
between 220 V– 440 V– 440 V– 440 V– 440 V–
conductors (voltage reversal)
voltage U n
between 220 V– 220 V– 440 V– 220 V– 220 V–
conductor and earth
MCB 1-pole 2-pole 2-pole 2-pole 4-pole
S 201 MT UC S 202 MT UC S 202 MT UC S 202 MT UC S 204 MT UC
supply
from below
SK 0114 Z 94
supply
from above
SK 0115 Z 94
Examples for different voltage levels betweeen conductor and earth in the case of identical voltage between conductors:
voltage U n
between 440 V– 440 V– 440 V–
conductors all-pole disconnection 1-pole disconnection all-pole disconnection
voltage U n 440 V– 440 V–
between 220 V– circuit circuit unearthed or
conductor and earth circuit symmetrically earthed unsymmetrically earthed unsymmetrically earthed
MCB 2-pole 2-pole 4-pole
S 202 MT UC S 202 MT UC S 204 MT UC
SK 0196 Z 98
➀ in the circuit diagram, the negative pole is earthed. ➁ in the circuit diagram, the positive pole is earthed.
2CDC002175D0201 - 7
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic B
8 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic C
2CDC002175D0201 - 9
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic C
A pc. kg
4 0.5 S204MT-C0.5UC 2CDS274065R0984 4447563 1 0.500
1 S204MT-C1UC 2CDS274065R0014 4446948 1 0.500
1.6 S204MT-C1.6UC 2CDS274065R0974 4447556 1 0.500
2 S204MT-C2UC 2CDS274065R0024 4446955 1 0.500
3 S204MT-C3UC 2CDS274065R0034 4446962 1 0.500
4 S204MT-C4UC 2CDS274065R0044 4446979 1 0.500
6 S204MT-C6UC 2CDS274065R0064 4446986 1 0.500
8 S204MT-C8UC 2CDS274065R0084 4446993 1 0.500
10 S204MT-C10UC 2CDS274065R0104 4447013 1 0.500
13 S204MT-C13UC 2CDS274065R0134 4447037 1 0.500
16 S204MT-C16UC 2CDS274065R0164 4447068 1 0.500
20 S204MT-C20UC 2CDS274065R0204 4447082 1 0.500
25 S204MT-C25UC 2CDS274065R0254 4447112 1 0.500
32 S204MT-C32UC 2CDS274065R0324 4447181 1 0.500
40 S204MT-C40UC 2CDS274065R0404 4447259 1 0.500
50 S204MT-C50UC 2CDS274065R0504 4447389 1 0.500
63 S204MT-C63UC 2CDS274065R0634 4447549 1 0.500
10 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic K
A pc. kg
1 0.2 S201MT-K0.2UC 2CDS271065R0087 4448270 10 0.125
0.3 S201MT-K0.3UC 2CDS271065R0117 4448294 10 0.125
0.5 S201MT-K0.5UC 2CDS271065R0157 4448317 10 0.125
0.75 S201MT-K0.75UC 2CDS271065R0187 4448348 10 0.125
1 S201MT-K1UC 2CDS271065R0217 4448362 10 0.125
1.6 S201MT-K1.6UC 2CDS271065R0257 4448393 10 0.125
2 S201MT-K2UC 2CDS271065R0277 4448416 10 0.125
3 S201MT-K3UC 2CDS271065R0317 4448430 10 0.125
4 S201MT-K4UC 2CDS271065R0337 4448461 10 0.125
2CDC021030S0013
2CDC002175D0201 - 11
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic K
A pc. kg
3 0.2 S203MT-K0.2UC 2CDS273065R0087 4447662 1 0.375
0.3 S203MT-K0.3UC 2CDS273065R0117 4447686 1 0.375
0.5 S203MT-K0.5UC 2CDS273065R0157 4447709 1 0.375
0.75 S203MT-K0.75UC 2CDS273065R0187 4447730 1 0.375
1 S203MT-K1UC 2CDS273065R0217 4447754 1 0.375
1.6 S203MT-K1.6UC 2CDS273065R0257 4447785 1 0.375
2 S203MT-K2UC 2CDS273065R0277 4447808 1 0.375
3 S203MT-K3UC 2CDS273065R0317 4447822 1 0.375
4 S203MT-K4UC 2CDS273065R0337 4447853 1 0.375
2CDC021032S0013
12 - 2CDC002175D0201
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic Z
A pc. kg
1 0.5 S201MT-Z0.5UC 2CDS271065R0158 4448324 10 0.125
1 S201MT-Z1UC 2CDS271065R0218 4448379 10 0.125
1.6 S201MT-Z1.6UC 2CDS271065R0258 4448409 10 0.125
2 S201MT-Z2UC 2CDS271065R0278 4448423 10 0.125
3 S201MT-Z3UC 2CDS271065R0318 4448447 10 0.125
4 S201MT-Z4UC 2CDS271065R0338 4448478 10 0.125
5 S201MT-Z5UC 2CDS271065R0358 4448492 10 0.125
6 S201MT-Z6UC 2CDS271065R0378 4448515 10 0.125
8 S201MT-Z8UC 2CDS271065R0408 4448546 10 0.125
2CDC021030S0013
2CDC002175D0201 - 13
Miniature Circuit Breaker S 200 MT UC
Ordering data characteristic Z
In
A pc. kg
3 0.5 S203MT-Z0.5UC 2CDS273065R0158 4447716 1 0.375
1 S203MT-Z1UC 2CDS273065R0218 4447761 1 0.375
1.6 S203MT-Z1.6UC 2CDS273065R0258 4447792 1 0.375
2 S203MT-Z2UC 2CDS273065R0278 4447815 1 0.375
3 S203MT-Z3UC 2CDS273065R0318 4447839 1 0.375
4 S203MT-Z4UC 2CDS273065R0338 4447860 1 0.375
5 S203MT-Z5UC 2CDS273065R0358 4447884 1 0.375
6 S203MT-Z6UC 2CDS273065R0378 4447907 1 0.375
2CDC021032S0013
14 - 2CDC002175D0201
Miniature
For Your Notes
Circuit Breaker S 200 MT UC
2CDC002175D0201 - 15
Contact us
You can find the address of your We reserve all rights in this document and in
local sales organization on the the subject matter and illustrations contained
ABB home page therein. Any reproduction, disclosure to third
http://www.abb.com/contacts parties or utilization of its contents – in whole
-> Low Voltage Products and Systems or in parts – is forbidden without prior written
consent of ABB AG.