1008S Quick User Guide
1008S Quick User Guide
Flow Indicator Totaliser -1008S 90%) RELAY CONTACT 250VAC/5Amps TERMINAL input/output terminals. Not
RESOLUTION 16 bit RATING isolated from 24Vdc supply
POLARITY Not provided (Transmitter power supply)
PROTECTION and internal circuit.
Communication Specification
MEMORY BACKUP EEPROM 24V DC SUPPLY Not isolated from the
PROTOCOL Modbus RTU serial FOR measured input terminal &
Loop Power Supply Specification TRANSMITTER
STANDARD EIA RS-485 internal circuit, isolated
MAX. 1200 mtrs. (For 9600 from other input/output
LOOP POWER 24VDC ± 5% @ 50mA COMMUNICATION bps RS 485) terminals.
SUPPLY DISTANCE RETRANSMISSION Isolated from other
COMMUNICATION 2 wire half duplex (RS OUTPUT
Retransmission Output input/output terminals and
METHOD 485) TERMINAL internal circuit.
DATA FRAME N, 8, 1
NUMBER OF OUTPUTS 1 COMMUNICATION 9600, 19200 bps CONTACT INPUT Isolated from other
OUTPUT SIGNALS 4 to 20 mA DC RATE TERMINAL input/output terminals and
1008S Flow Indicator Totaliser
MAX. CONNECTABLE 32 internal circuit.
LOAD RESISTANCE 500Ω or less CONTROLLERS/ RELAY CONTACT Isolated from other input
Input Type Range
INDICATOR O/P TERMINAL /output terminals and
OUTPUT ACCURACY ± 0.25% of full scale +1
0 to 20 mA ADDRESS RANGE 1 to 99 (DIGITAL INPUT) internal circuit.
count
4 to 20 mA RESOLUTION 12 bits (5uA) RS-485 Isolated from other
0 to Display Unit Specification COMMUNICATION input/output terminals and
0 to 5 V 3000 0 TERMINAL
Contact Input (Digital input) internal circuit.
PROCESS VALUE 0.56” 5 digit 7-
1 to 5 V POWER SUPPLY Isolated from other input /
DISPLAY segment red display
*Pulse Input NO OF INPUTS 4 TERMINAL output terminals and
INTEGRATED TOTAL 0.40” 8 digit 7-
Integrated/ 0 to USAGE Input 1 : Stop Batch DISPLAY segment red display internal circuit.
Batch Total 9999 99 Input 2 : Integration total PARAMETER DISPLAY Same integrated total GROUND Isolated from other input/
Table 1.1 zero(Therefore Batch total display TERMINAL output terminals and
and roll count will be zero) STATUS INDICATING Red LED’s internal circuit.
SPECIFICATIONS Input 3 : Start Batch LAMP
Input 4 : Batch total zero Environmental Specification
NUMBER OF INPUTS 1 with Optional 2 & 3 INPUT TYPE Non- voltage contact input Power Supply Specification
ACCURACY ± 0.25% of full scale ± 1 or transistor open collector OPERATING 0 to 55C
Count , input POWER SUPPLY 110 to 230 VAC, 50Hz ; TEMPERATURE
**0.45 % - for INPUT CONTACT 12VDC,10mA or more (for 24VDC(optional) STORAGE 0 to 70C
Integrated/ Batch Total CAPACITY non – voltage contact input) POWER <10Va
TEMPERATURE
BURN OUT Available for 1 to 5VDC, ON/ OFF For non-voltage CONSUMPTION
DETECTION 4 to 20 mA, 0 to 10 KHz. DETERMINATION contact input HUMIDITY 30 to 90% RH
WITHSTANDING Between primary terminal
INPUT RESISTANCE 250 Ohms Internal ON = contact VOLTAGE and secondary terminal : (Noncondensing)
for current Input resistance of 1KΩ or 1500VAC(For 1 min) WARM UP TIME >10 Minute
320K Ohms for less, Between primary terminal EFFECT OF For Voltage Input:
Voltage Input OFF = contact and ground terminal : AMBIENT 0.005% of FS/ C or less
ALLOWABE SIGNAL DC input voltage: 1KΩ or resistance of 20KΩ 500VDC(for 1 min) TEMPERATURE For analog output:
SOURCE less. Effect from or more Between ground terminal 0.010% of FS/ C or less
RESISTANCE allowable signal source For transistor contact and Secondary terminal:
Resistance: 0.031 % / input 500V AC (for 1 minute). Alarm Specification
100Ω or less ON = 2V or less (Primary terminal:
ALLOWABLE INPUT DC voltage: ±20V DC OFF = leak current Power supply, relay ALARM TYPES Flow high limit, Flow low limit
VOLTAGE of 100µA or less BATCHING Pre warn and set point
output)
NOISE REJECTION Common Mode: > MINIMUM About 1 Second ALARM
(Secondary terminal:
RATIO 100db RETENTION TIME SETTING Flow (PV) Alarms:
Normal mode: > 40db Analog input/output signal
FOR STATUS RANGES FOR Min = Zero of individual I/P type
RESPONSE TIME Input to relay o/p: < 1 terminals, contact input
DETECTION PROCESS Max = Span of individual I/P
second. terminal)
VALUE type
Input to Analog o/p: < Contact Outputs ALARMS
1 second or less, 63 % Signal Isolation Specifications
(10 - 90%) (Time NUMBER OF OUTPUTS 4 (2 Flow alarm relays,
required for o/p to reach 2 Batch relays) ISOLATION Between power supply
63% of the maximum USAGE Flow alarm / Batch relay RESISTANCE terminal and ground
excursion when PV terminal: 500 VDC, 50MΩ
RELAY CONTACT 3(Common, NO, NC)
Doc.Ref. No. m18A/QG/101 Issue No.:00 Page 1 of 2
Display Specification 1. It will increment value of digit
selected or constant selected. Rear Panel Diagram Of 1008S With Mass Flow Batch total:
PV DISPLAY 5 digit red 7 segment display STOP OR 2. It will stop batch, if pressed, when This is an eight digit totalized value, displayed
for flow rate INCREMENT BT/IT are being displayed. as Batch total. As per the selected time base,
INTEGRATED 8 digit red 7 segment display 3. For Pause batch press stop key for Zero and Full-scale settings, this total is
TOTAL for integrated total 1 second. updated continuously, proportional to input.
PARAMETER Same 8 digit red 7 segment 4. If we press stop key for 3 second When New Batch Starts or Integration total is
DISPLAY display integrated total then batch becomes zero. reset this value also gets initialized to 0.
STATUS Red LEDs (for alarm & Batch) 1. It will escape to previous
DISPLAY status, with reference to its current Integration total:
ESCAPE status. This is an eight digit totalized value, displayed
Other Specification Sequence of status: as integrated total. As per the selected time
IT MENU SUB-MENU base, Zero and Full-scale settings, this total is
SQUARE ROOT Applicable Parameter’s Value updated continuously, proportional to input.
EXTRACTION Escape sequence
DIGITAL FILTER Applicable When Esc key is pressed in Menu, Relay-mode:
TIME BASE UNIT Second, minute, hour, the instrument will come in RUN In ‘Relay-mode’ (relay nod), if set to ‘normal
day Mode. If user wants to go in EDIT ‘mode then alarm relays and LEDs will work
CONVERSION 0.00 to 99.99 mode, he will have to enter the according to alarm values.
FACTOR correct password again. i.e. Relays on, LEDs on
FIVE POINT Applicable 2. When Esc key is pressed in RUN Relays off, LEDs off
LINEARIZATION Mode, it will directly enter in to the
PULSE OUT PUT Maximum pulse: 20 set point menu. This function is But if set to ‘Failsafe’ Mode then alarm relays
pulses/Sec. only applicable when type of and LEDs will operate reversibly.
Excitation Voltage: instrument is totaliser. i.e. Relays on, LEDs off
Terminal Details of 1008S Standard Relays off, LEDs on
<24Vdc with maximum When Respective Relay LED Lits (In
10 mAdc RL1, RL2 Red) OR When Channel is
LOW FLOW CUT OFF Applicable Cut Off(Low Flow Cut Off):
RL3,RL4 OPEN(Channel no. is corresponding
Cut off could be set to 0000 to 0100.
to Relay no.)
Cut off will display the % value.
MOUNTING DETAILS
When Communication on, two LEDs
Rx/Tx
(In Red) blink.
Structure: Front fascia IP54 complied(not
certified), Enclosure GP (IP20) Cutoff value = Cutoff parameter (in %)*Full
Body construction: Polycarbonate plastic. scale value
Case color: Dark grey BACK PLATE CONNECTION DETAIL If full scale value is 10000 and cut off is 5%
Weight: 0.45Kg Then cut off value will be calculated as
Rear Panel Diagram of 1008S Standard = (5/100)*10000 = 500.
Instrument Dimension: 96 W* 96H*125D max
So, if the displayed flow rate (displayed at
behind panel with terminal (all in mm)
upper window) is less then 500, it will not be
Mounting Method: Panel mounting added in integration.
Panel cut-out: 92W* 92H (all in mm)
Terminal Details of 1008S with Mass Flow
Wiring: 2.5sq.mm
Standard Accessories: 2 mounting clamp
Name of
Function
Part
1. It will allow user to enter in EDIT
mode, when instrument is in RUN
SET OR mode.
SHIFT 2. It will scroll menu and submenu
When it is enabled.
3. It will save edited data. For operation manual please visit www.masibus.com
Specifications are subject to change without notice due to
1. It will enter into the submenu,
continuous improvements.
when main menu is enabled and Masibus Automation And Instrumentation Pvt. Ltd.
shows submenu’s value. B-30, GIDC Electronics Estate, Sector-25, Gandhinagar-
START OR 2. It will select the digit to modify, 382044, Gujarat, India.
SHIFT when value is edited. Tel: +91 79 23287275-79 Fax: +91 79 23287281
3. It will start batch, if pressed, Web:www.masibus.com Email:[email protected]
when IT & BT are being displayed
Doc.Ref. No. m18A/QG/101 Issue No.:00 Page 2 of 2