MDB Specs PDF
MDB Specs PDF
MDB Specs PDF
All of the major type tests shall have been certified at an independent authority with the tests
carried outside the country of manufacture.
6. Quality
When requested by the customer, the supplier shall provide proof that he applies a quality
procedure in compliance with the standard, namely:
- Use of a quality manual approved and signed by a top management representative,
- Periodic updating of the manual so that it reflects the quality control procedures in
effect,
- ISO 9001 certification.
SECTION 16425
(TYPE TESTED)
LOW VOLTAGE SWITCHGEAR ASSEMBLIES
MAIN DISTRIBUTION BOARD
PART 1 - GENERAL
1.4 SUBMITTALS
A. Product Data: Submit manufacturer's data for switchgears, including size,
enclosures, and electrical ratings and characteristics.
PART 2 - PRODUCTS
2.1 GENERAL
A. The switchgears shall be 660 V class 3PH, 50HZ completely wired and type tested
at the factory, ready for installation on the site. Sectionalizing shall be
accomplished and bracing provided for access of the equipment into the building.
B. Switchgears shall be designed and manufactured to comply with IEC - 439, VDE
660 Part 500, UTE 63 - 410 .
C. The Electrical installation has been designed to give load balance across the
phases as far as possible but it is the contractor's responsibility to maintain or
improve the balance when making connections to bars etc.
When the final commissioning is to be completed the contractor shall allow in his
tender for checking loads and altering connections in order to achieve as even a
balance over the phases as possible.
2.2 CONSTRUCTION
A. The switchgears shall be of the totally enclosed, front and rear. accessible, indoor
type, of size, rating and arrangement as indicated on the Drawings. The complete
assembly shall be floor mounted, free standing, with matching cases, to form a
continuous integral structure.
B. Switchgears shall consist of the required number of compartmented formed and
welded sheet enclosures required to mount circuit- breakers and other specified
equipment or as shown on the Drawings.
C. Switchgears shall be completely enclosed with hinged front covers and removable
steel plates of not less than 2 mm gauge on sides, top and rear.
D. All fastenings between structural members shall be bolted, not welded, to provide
flexibility during installation.
E. The arrangement shall permit the busbars and/or cables to enter from the top or
bottom of the enclosures as shown on the Drawings and connect at their respective
terminals without interference.
F A modular arrangement shall be used to permit interchanging differently sized
device cover plates without additional drilling of structure.
G. Structures and busses shall be arranged to permit future sections to be added. A
suitable cover plate shall be provided for temporary protection.
H. Switchgears shall be dust, vermin and rodent proof IP43 according to IEC 529.
All compartments shall be suitably ventilated where required.
I The switchboard busses shall be braced for a short-circuit duty as indicated on the
drawings.
J. All bolted and plug-in connections shall be Electro-silver plated to a minimum
thickness of 0.0125 mm.
K. A spare position shall be fully equipped cell ready to receive a circuit-breaker.
A. All copper bus bars, switching devices and connections shall be of sufficient sizes
o
and silver plated at contact to limit the temperature rise to 25 C over an average
o
ambient temperature of 45 C outside the enclosure.
All bus bars and connections shall be accessible for inspection and maintenance
purposes.
C. Bus bars are to be of high conductivity copper and rigidly supported to withstand
the mechanical stress of a rated short- time withstand current of 85KA (rms) in
accordance with IEC recommendation No. 439-1
D. Main bus shall be of continuous construction. Main bus joints and all top
connections shall be silver plated and tightly bolted to insure maximum
conductivity.
E. Bus bars shall be clearly marked with their respective phase colors and shall be
furnished for future extensions.
F. Clearance to earth and to other live metal are to be in accordance with the
standards.
G. The main set of bus bars shall be housed in segregated chamber at the top. Bus
bar top covers shall be capable of supporting a man weight without deflection.
H. Incoming and outgoing supplies to switchgears shall be either busways or cables
as indicated on drawings.
I. A full length ground copper bus shall be provided. The ground bus shall be
bounded to the metal enclosure of each compartment and to metering and
relaying, transformers secondary windings. Lugs shall be provided one at each
end of the ground bus and one in each cubicle for the user's copper ground cables.
J. The cross sectional area of neutral bus bars shall not be less than that of the
associated phase bars.
K. Access to bus bars and bus bar connections shall be possible only after the
removal of covers secured by bolts or studs. Such covers shall be identified
externally by engraved laminated labels bearing the inscription "BUSBARS
DANGER 380 VOLTS" in 30mm high black lettering on a yellow background.
2.7 EARTHING
A. Each assembly shall be provided with a continuous copper earth bar running the
whole length sized in accordance with DIN/VDE standards for the prospective
short-circuit current.
B. Discrete terminals shall be provided for connection to all the protective conductors.
Each individual section of the assembly shall be separately bonded to the main
earth bar.
2.8 COMPONENTS
A. All components shall be installed in accordance with the instructions of their
manufacturers. This requirement does not negate the requirement for type and
routine testing as specified elsewhere in this Specification.
B. Adjusting and resetting devices shall be easily accessible.
C. All actuators for emergency switching devices shall be mounted between 0.8m and
1.6m above the base of the assembly.
D. All components shall be installed and wired such that their function is not impaired
by interaction such as heat, arcs, vibration, and fields of energy present in normal
operation.
E. Barriers for manual switching devices shall be designed such that arcs caused by
switching under normal operation or the interruption or making of a fault current
shall not present a danger to the operator.
F. All removable and withdrawable components shall be installed and designed such
that they can be safely disconnected or connected to supply circuits while the
associated conductors are live.
(Or)
(ii) rated power does not exceed 1.6KVA with a rated secondary voltage of
less than 110V, and whose relative short-circuit voltage is not less than
4%.
G. Works tests shall include inspection of all wiring and a complete electrical
functioning test.
H. Protection relays shall be tested by primary current injection with currents equal to
overload, short-circuit and earth fault conditions.
I. Works tests shall be done in the presence of Owner consultant.
A. ASSEMBLIES
All assemblies shall be subjected to the routine tests as defined in IEC, DIN/VDE
standards. after installation on site. Test Certificates shall be provided.
C. PROTECTION CIRCUITS
All protection circuits in with relays used shall be tested for correct operation by
secondary injection of test currents. This shall be carried out at currents equivalent
to overload, short-circuit and earth fault conditions.
D. CURRENT TRANSFORMERS
Where specified in the schedules, protection circuits using current transformer
(CT) operated relays shall be tested by primary injection of current to prove the
transformer ratio.
2.13 COMMISSIONING
A. Following the satisfactory conclusion of inspections and tests on completed
sections of the Works, each switchgear assembly shall be duly commissioned and
left in full working order. The term "Commissioning" shall be deemed to include:
(i) The energizing of functional device circuits and equipment which have
previously been inspected, tested, found to be satisfactory and capable of
being energized with compete safety.
(ii) The starting up of all electrically powered plant and equipment, including
that supplied and installed under other contracts, and as specified in the
schedules.
(iii) The verification of the performance of each switchgear assembly relative
to all such plant and equipment by the carrying out, where required, of
further tests and the making of all necessary adjustments so as to obtain
optimum performance.
(iv) The proving of all interlock operations in all possible combinations and the
operation of all control systems, metering and indications to meet the
performance requirements specified.
PART 3 - EXECUTION
3.1 INSPECTION
A. Examine conditions under which switchgears are to be installed, and notify in
writing of conditions detrimental to proper completion of work. Do not proceed with
work until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A. Install switchgears as indicated, in accordance with manufacturer's written
instructions, requirements of applicable Standards, and in accordance with
recognized industry practices to ensure that installation complies with
requirements and serves intended function.
B. Coordinate as necessary to interface installation of switchgears with other work.
C. Tighten connectors and terminals, including screws and bolts and equipment
grounding connections, in accordance with equipment manufacturer's published
torque tightening values for equipment connectors.
SECTION 16430
PART 1 - GENERAL