0% found this document useful (0 votes)
242 views13 pages

Visual and Technical Checking of Instrumentation and Control System

This document outlines the requirements and procedures for visually inspecting and testing instrumentation and control systems during commissioning of new plants or after modifications. It describes inspecting the physical installation of instruments and wiring, as well as verifying the calibration, logic, displays and proper operation of instrumentation, controls, and auxiliary systems. The intent is to ensure all aspects of the control system are installed correctly and functioning as intended before being put into operation.

Uploaded by

zhangyili
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
242 views13 pages

Visual and Technical Checking of Instrumentation and Control System

This document outlines the requirements and procedures for visually inspecting and testing instrumentation and control systems during commissioning of new plants or after modifications. It describes inspecting the physical installation of instruments and wiring, as well as verifying the calibration, logic, displays and proper operation of instrumentation, controls, and auxiliary systems. The intent is to ensure all aspects of the control system are installed correctly and functioning as intended before being put into operation.

Uploaded by

zhangyili
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 13

Visual and Technical Checking of Instrumentation and Control

System

BY · PUBLISHED · UPDATED

This article defines the minimum requirements for initial inspection,

loop check, and commissioning of control systems during new plant

construction, as well as those inspections, loop checks, and

commissioning that might be necessary following major

revisions/modifications or repair.

This document outlines specific steps that need to be taken in the course

of commissioning. The document is organized so that key sections may

be extracted to be used as instructions for that identified task, these tasks

shall be coordinated by Process Controls Engineering.

This standard applies globally to all control systems undergoing initial

inspection, loop checking, and commissioning.

Documents used in Commissioning and Loop checking

Application and Use of Instrumented Systems in Process Plants

Initial Instrumented Protection System Validation


Initial Validation Testing of Instrumented Protection Functions and

Systems

Glossary – Process Control Definitions

 Alarm and Trip Summary

Programmable Electronic System (PES) Staging Requirements

The tasks to be performed to fully commission an entire control/safety

and independent safety system are outlined in Figure 1, Task Flow

Diagram. All steps will be clarified with references to other standards

when the content falls outside the scope of this standard.

The intent of this standard is to provide the minimum requirements for

initial inspection, loop check, and commissioning of a control system.

The objectives of this standard are as follows:

 Verify the proper physical installation (wiring, grounding, labels,

tags, pressure ratings, area classification) of instruments.

 Ensure wiring is landed on the proper termination and verify

overall wiring loop integrity.

 Verify proper calibration range, engineering units, tag name, and

diagnostics.

 Verify PES input range.


 Verify all logic including the interlock system

 Verify pre-alarms, bad quality, maintenance bypass switches, and

proper configuration of HMI displays.

 Verify and confirm proper operation of the instrument and sensor

according to supplier and Air Products specifications.

 Verify proper installation, power and grounding, backup power,

network communications, system diagnostics, and operational

functionality of the PES.

 Verify auxiliary systems (Foreign Device Interfaces, Historians,

and Billing Systems).

 Verify remote access and remote control if applicable.

The following documents shall be available on site and shall be the latest

revision:

 PES Procurement Specification.

 Supplier Control System Manufacturing Drawings (if applicable).

 Control System Design Objectives and Control and Optimization

Strategy Document (if applicable).

 HMI Console Configuration Guidelines/Control System Design

Basis Paper (if applicable).

 Instrument Specifications.

 Alarm and Trip Summary.


 Electrical Schematics (both Air Products- and supplier-furnished).

 Hazardous area classification drawings.

 Relevant calculations and process data (for example, heat and

material balance, sequence data, compressor curves, compressor

surge lines, motor data sheets, and flow element calculations).

 Any relevant data needed for interface to supplier skids and

equipment.

 Applicable configuration standards.

 P&ID.

 FAT report and punch list.


Test Equipment

Other than for purposes of rectification, repair, or replacement, no test

equipment shall be moved from the job site for the duration of the

contract.

All calibration test equipment supplied by a contractor shall be certified

for accuracy by an independent testing laboratory before use.


Each item of calibration test equipment supplied by a contractor shall

exhibit a permanently fixed validation label indicating the serial number,

name of certifier, and the date and duration of certification. Copies of

relevant test certificates will be kept on file by the supplier of the test

equipment and shall be made available for inspection by Air Products at

any time.

Equipment that shall be considered calibration test equipment shall

comprise, but not be limited to, the following:  Hart Communicators,

hand pumps, precision test gauges, portable potentiometers, deadweight

tester (pneumatic only), manometers, constant temperature generator,

thermocouple calibrator, RTD calibrator, transmitter simulators,

pneumatic calibrators, signal generator and counter, portable

oscilloscope, leak detection unit, and instrument manufacturer’s specially

designed portable test sets.

Visual inspection of devices

Typically, physical inspection is the first task to be performed once an

instrument is turned over from construction. Physical inspections do not

have to be done in conjunction with loop checking but depending on

manpower and instrument location, physical inspections and loop

checking may be done at the same time. At a minimum, physical


inspections must be documented to provide evidence of what was

checked and whether the device passed or failed. It is recommended that

field inspection reports be filled out for every piece of instrumentation.

Failed devices shall be corrected before proceeding to loop check.

General Inspection Checks:

 Transmitter support stands installed

 Proper wiring, glanding, and conduit connection such as low point

drains, grounding, shielding and terminations, and bottom cabinet

entry

 Verify proper labeling of all tags, warning signs, pressure ratings,

etc…

 Confirm all covers, screws, fittings, etc. are installed and properly

tightened

 Look for signs of moisture and/or corrosion in electrical conduit

and process impulse line

 Wire terminations are tightened

Pressure Transmitters Checking:

 Verify sensing line size, material, slope, tap orientation, adequate

supports, etc.

 Proper installation of all compression fitting.


 Root valves installation and location.

 Manifold valve selection and proper installation.

 Verify sufficient impulse line length for heat transfer.

 Verify loop seals where required.

 Verify configuration according to specification sheet.

 Instrument accessible for routine maintenance and correctly

supported

 Environment acceptable, vibration, heat, splash, etc.

 Heat traced if necessary.

 Verify proper electrical connections.

DP (level and flow) Transmitters and orifice plate Checking:

 Verify beta ratio and flow direction for orifice plates directly from

the handle or nameplate.

 Verify sensing line size, material, slope, tap location, adequate

supports, etc.

 Verify HI/LO pressure tap location relative to gas or liquid

measurement.

 Proper installation of all compression fitting.

 Root valves installation and location.

 Manifold valve selection and proper installation.


 Inspect and confirm all sealed capillary sensing systems used for

level measurement against instrument specification.

 Verify sufficient impulse line length for heat transfer.

 Verify loop seals where required.

 Verify configuration according to specification sheet.

 Instrument accessible for routine maintenance.

 Instrument correctly supported.

 Environment acceptable, vibration, heat, splash, etc.

 Heat traced if necessary.

 Verify proper electrical connections.

Temperature Element/ Transmitters Checking:

 Verify insertion length within process pipe and ensure firm contact

with bottom of well.

 Verify that either RTD or T/C elements are connected and properly

terminated to the transmitter

 Verify T/C element type and extension wire type according to

specification

 Verify proper grounding and shielding according to specification

and electrical installation drawings

 Confirm that all threaded connections are tight (for example,

nipple-union-nipple, head cover and gasket)


 Verify transmitter configuration according to specification sheet

 Instrument accessible for routine maintenance

 Instrument correctly supported

 Environment acceptable, vibration, heat, splash, etc.

 Heat traced if necessary

 Verify proper electrical connections

Control Valves Checking:

 Verify control valve flow direction.

 Ensure proper installation of all tubing, fittings, and solenoid

valves.

 Verify positioner and solenoid wiring for proper connections and

tagging.

 Inspect overall installation of valve body and actuator. Look for

signs of overstressed piping or improper actuator installation

causing unnecessary stress.

 For rotary valves, ensure actuator rotation is indexed correctly with

valve rotation.

 Verify installation of bug screens or other means of preventing

water ingress for all vented openings.

 Check fail action.

 Verify start-up flush kit has been removed where applicable.


 Verify all other ancillary valve equipment functions properly.

 Verify configuration according to specification sheet.

 Instrument accessible for routine maintenance, actuator removal,

bonnet and plug removal, hand wheel operation, positioner

maintenance, and solenoid maintenance.

 Valve stroke is within specified time

 Proper support.

 Correct packing for application.

 Packing gland properly tightened.

 Verify all covers, screws, fittings, etc., are installed and properly

tightened.

Field Switches Checking :

 Verify installation location, confirm against P&ID

 Verify wiring: NO/ NC contacts

 Verify wiring labeling

 Instrument accessible for routine maintenanc

  Verify all covers, screws, fittings, etc., are installed and properly
tightened

Note: Field Inspection Reports (Appendix A) are included to provide

guidance. There is a unique report template for each type of instrument

and a generic form for special devices.

You might also like