DIN-rail Programmable Transducers: Applications Features
DIN-rail Programmable Transducers: Applications Features
Applications Features
Ÿ Instrumentation panels Ÿ Fully programmable inputs & outputs
Ÿ Control systems Ÿ Accuracy class 0.5 or 0.2
Ÿ Electrical distribution panels Ÿ True root mean squared (RMS) measurement
Ÿ Transmission systems and generators Ÿ Up to 4 analogue outputs (voltage or current signals)
Ÿ SCADA systems Ÿ Up to 2 digital outputs only for energy parameters
Ÿ Optional Modbus communications via RS-485 port
Ÿ DIN-rail mounting
Ÿ USB Mini port for local programming
Ÿ Meter cover and terminal cover open detection
Benefits Ÿ RS232 port compatible with meter-powered modem
Ÿ Each DPT covers the entire range of common electrical
parameters
Ÿ DPT decal (rating plate) configurable and printable through
software
Ÿ Better response time
Ÿ THD measurement
Ÿ Offered product suitable for stocking at Distributor/OEMs
end
Ÿ User friendly Configuration & Reading through Configview
software
Ÿ Easy to install and configure
DPT
ordering information
D P T 0 0 0 - 0 0 0
D for DIN -rail mounting Analogue output variants
P for Programmable 00 - No analogue output variant
T for Transducer 01 - 20 mA upper range
02 - 5 mA upper range
Class Accuracy
03 - 2 mA upper range
2 - 0.2 Accuracy
10 - 10 V upper range
5 - 0.5 Accuracy
11 - 2 V upper range
Digital Outputs
0 - No output No. of Analogue outputs
2 - Two outputs 0- No output
1- 1 output
Rs485 Communication 2- 2 outputs
0 - No communication 3- 3 outputs
1 - Rs485 modbus 4- 4 outputs
Note: This ordering key represents the overall portfolio of DPT. Please confirm the availability of desired item number with our sales representative.
Reading
The continuously updated measured parameters can be read out and stored in a time-stamped file. The DPT configuration
can also be read out.
Remote Control
Analogue outputs can be set to a particular value and digital outputs can be set on or off using a remote control function.
*MD: This is a periodic interval value not linked with date and time stamping.
DPT
DIN-rail Programmable Transducers
Technical specifications
General measurement
Accuracy Class 0.2, Class 0.5 (Frequency ± 0.01 Hz, Power Factor ± 0.1°)
Mains frequency 50 or 60 Hz (45-65 Hz)
Measurement True root-mean squared (RMS)
Voltage Circuit
Nominal measuring voltage (UN) 3 x 100-693 V (three-wire system)
3 x 57.7/100 V to 3 x 400/693 V (four-wire system)
Measuring range 0% - 120% UN
Burden ≤V2/400 k ± 3% (W) per phase
Maximum overload voltage 1.2 x UN continuously
1.5 x UN for 10 s with up to 10 repetitions at 10 s intervals
2 x UN for 1 s with to 10 repetitions at 10 s intervals
Starting voltage 0.25 V
Current Circuit
Nominal measuring voltage (IN) 1-5 A
Measuring range 0% - 200% IN
Burden ≤I2x0.01 (W) per phase
Maximum overload current 2 x IN continuously
20 x IN for 1 s with up to 10 repetitions at 100 s intervals
40 x IN for 1 s with to 5 repetitions at 300 s intervals
Starting current 4 mA
Auxiliary Supply
Voltage range 40-276 V AC or DC (AC frequency 45-65 Hz)
Maximum burden < 12 VA / 7 W
Analogue Outputs
Type Current/voltage bi-polar
Maximum voltage (open output) ±20 V
Range/load (current output) ±20 mA / ≤ 750
±5 mA / ≤ 3 k
±2 mA / ≤ 7.5 k
Range/load (voltage output) ±10 V / ≥ 2 k
±2 V / ≥ 400
Programmable response time (t99) 300 ms default (provision for better or higher response time)
Digital Outputs
Accuracy 0.5 s
Pulse length 10 ms to 1 s, RON 8 Ω (max.)
Temperature Range
Operating temperature -10 °C to +50 °C
Storage temperature -20 °C to +80 °C
Environmental
Specifications are subject to change without prior notice
Physical
Dimensions (W x H x D) 102 x 71 x 114 mm
Weight 0.5 kg (approx.)
Mounting DIN rail (DIN EN 50022)
www.cewesecure.se
01-18/Ver 1.0/skv