DIN-rail Programmable Transducers: Applications Features

DPT are DIN-rail programmable transducers that measure electrical parameters like power, current, voltage, and frequency. They generate analog and digital output signals and have options for Modbus communication, up to 4 analog outputs, and 2 digital outputs. DPTs are configurable via ConfigView software to measure single or three phase systems and comply with IEC standards with accuracy classes of 0.5 or 0.2. They are suitable for applications like instrumentation panels, control systems, and SCADA systems.

Uploaded by

RAHAT KHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
59 views

DIN-rail Programmable Transducers: Applications Features

DPT are DIN-rail programmable transducers that measure electrical parameters like power, current, voltage, and frequency. They generate analog and digital output signals and have options for Modbus communication, up to 4 analog outputs, and 2 digital outputs. DPTs are configurable via ConfigView software to measure single or three phase systems and comply with IEC standards with accuracy classes of 0.5 or 0.2. They are suitable for applications like instrumentation panels, control systems, and SCADA systems.

Uploaded by

RAHAT KHAN
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

DPT

DIN-rail Programmable Transducers

Our family of DIN-rail programmable transducers (DPT) measure


a wide range of electrical parameters and generate equivalent
analogue output signals suitable for interfacing with
instrumentation and control systems. DPTs are available with
up to four analogue outputs, up to two digital outputs and
Modbus communication functionality. All the outputs are
galvanically isolated and can be programmed with easy-to-use
ConfigView software. Any of the measured parameters can be
assigned to the analogue outputs and can be read out via the
optional Modbus connection. ConfigView can also be used to
configure the connection to the measured circuit for single-
phase, three-phase three-wire, three-phase four-wire, balanced
or unbalanced load. DPTs comply with IEC 60688 and are
available in accuracy classes 0.5 and 0.2. DPT support wide
range of voltage, current and auxiliary supply.

Applications Features
Ÿ Instrumentation panels Ÿ Fully programmable inputs & outputs
Ÿ Control systems Ÿ Accuracy class 0.5 or 0.2
Ÿ Electrical distribution panels Ÿ True root mean squared (RMS) measurement
Ÿ Transmission systems and generators Ÿ Up to 4 analogue outputs (voltage or current signals)
Ÿ SCADA systems Ÿ Up to 2 digital outputs only for energy parameters
Ÿ Optional Modbus communications via RS-485 port
Ÿ DIN-rail mounting
Ÿ USB Mini port for local programming
Ÿ Meter cover and terminal cover open detection
Benefits Ÿ RS232 port compatible with meter-powered modem
Ÿ Each DPT covers the entire range of common electrical
parameters
Ÿ DPT decal (rating plate) configurable and printable through
software
Ÿ Better response time
Ÿ THD measurement
Ÿ Offered product suitable for stocking at Distributor/OEMs
end
Ÿ User friendly Configuration & Reading through Configview
software
Ÿ Easy to install and configure
DPT
ordering information

Product Ordering Configuration

D P T 0 0 0 - 0 0 0
D for DIN -rail mounting Analogue output variants
P for Programmable 00 - No analogue output variant
T for Transducer 01 - 20 mA upper range
02 - 5 mA upper range
Class Accuracy
03 - 2 mA upper range
2 - 0.2 Accuracy
10 - 10 V upper range
5 - 0.5 Accuracy
11 - 2 V upper range
Digital Outputs
0 - No output No. of Analogue outputs
2 - Two outputs 0- No output
1- 1 output
Rs485 Communication 2- 2 outputs
0 - No communication 3- 3 outputs
1 - Rs485 modbus 4- 4 outputs

Note: This ordering key represents the overall portfolio of DPT. Please confirm the availability of desired item number with our sales representative.

ConfigView Software Functions


Configuration
All parameters associated with transducer functionality can be programmed, such as connection type, transformer ratios,
curves for analogue outputs, modbus id and baud rate.

Reading
The continuously updated measured parameters can be read out and stored in a time-stamped file. The DPT configuration
can also be read out.

Remote Control
Analogue outputs can be set to a particular value and digital outputs can be set on or off using a remote control function.

Note: USB cable and software to be ordered separately.


DPT
measured quantities

Quantity By phase Total Unit

Active power Yes Yes W

Reactive power Yes Yes var

Apparent power Yes Yes VA

Active power factor P/S Yes Yes

Reactive power factor Q/S Yes Yes

LF factor SgnQ (1 -[PF]) Yes Yes

Frequency Not applicable Yes Hz

Current Yes Yes A

Phase voltage Yes Yes V

Phase to phase voltage Yes Yes V

Current with sign Yes Yes A

Phase angle Yes Yes Rad

Phase angle voltage (phase to neutral) Yes Not applicable Rad

Phase angle voltage (phase to phase) Yes Not applicable Rad

Phase angle current Yes Not applicable Rad

THD current Yes Not applicable %

THD voltage Yes Not applicable %

Average current Yes Yes A

MD* current Yes Yes A

Average active power Yes Yes W

MD* active power Yes Yes W

Average reactive power Yes Yes var

MD* reactive power Yes Yes var

Average apparent power Yes Yes VA

MD* apparent power Yes Yes VA

*MD: This is a periodic interval value not linked with date and time stamping.
DPT
DIN-rail Programmable Transducers

Technical specifications

General measurement
Accuracy Class 0.2, Class 0.5 (Frequency ± 0.01 Hz, Power Factor ± 0.1°)
Mains frequency 50 or 60 Hz (45-65 Hz)
Measurement True root-mean squared (RMS)

Voltage Circuit
Nominal measuring voltage (UN) 3 x 100-693 V (three-wire system)
3 x 57.7/100 V to 3 x 400/693 V (four-wire system)
Measuring range 0% - 120% UN
Burden ≤V2/400 k ± 3% (W) per phase
Maximum overload voltage 1.2 x UN continuously
1.5 x UN for 10 s with up to 10 repetitions at 10 s intervals
2 x UN for 1 s with to 10 repetitions at 10 s intervals
Starting voltage 0.25 V

Current Circuit
Nominal measuring voltage (IN) 1-5 A
Measuring range 0% - 200% IN
Burden ≤I2x0.01 (W) per phase
Maximum overload current 2 x IN continuously
20 x IN for 1 s with up to 10 repetitions at 100 s intervals
40 x IN for 1 s with to 5 repetitions at 300 s intervals
Starting current 4 mA

Auxiliary Supply
Voltage range 40-276 V AC or DC (AC frequency 45-65 Hz)
Maximum burden < 12 VA / 7 W

Analogue Outputs
Type Current/voltage bi-polar
Maximum voltage (open output) ±20 V
Range/load (current output) ±20 mA / ≤ 750
±5 mA / ≤ 3 k
±2 mA / ≤ 7.5 k
Range/load (voltage output) ±10 V / ≥ 2 k
±2 V / ≥ 400
Programmable response time (t99) 300 ms default (provision for better or higher response time)

Digital Outputs
Accuracy 0.5 s
Pulse length 10 ms to 1 s, RON 8 Ω (max.)

Temperature Range
Operating temperature -10 °C to +50 °C
Storage temperature -20 °C to +80 °C

Environmental
Specifications are subject to change without prior notice

Protection class II (double insulation) EN 61010-1


Pollution degree 2
Installation category CATIII (refer to measuring and auxiliary inputs ≤ 300 V AC versus earth)
CATII (refer to measuring inputs ≤ 600 V AC versus earth)
Ingress protection Protection housing IP 40 | Terminals IP 20

Physical
Dimensions (W x H x D) 102 x 71 x 114 mm
Weight 0.5 kg (approx.)
Mounting DIN rail (DIN EN 50022)