Data Sheet: Communication Unit 560CMU02

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

RTU560 product line

Communication Unit 560CMU02


Data sheet

E1 E2 CP1, CP2
RS232C or
10/100 MB LAN 10/100 MB LAN
RS485

Ethernet Ethernet
USART
Controller Controller

Processor bus

MPU RAM/Flash
ELAN520 Memory

RAM

Application
SLC
The 560CMU02 communication unit is one of the CMU modules
of the RTU560 product line.

The essential tasks are:


SPB
– Managing and controlling of the I/O modules via the inter-
face to the serial I/O bus.
– Reading Process events from the input modules. Figure 1: Block diagram 560CMU02
– Send commands to the output modules.
– Communicating with control systems and local HMI sys-
tems via the serial interfaces (RS232) and the Ethernet Characteristics
10/100BaseT interfaces.
– Communication with Sub-RTU’s, IED’s or multimeter de- The two microprocessors are the essential hardware parts of
vices via the interfaces (RS485) and the Ethernet interfaces. the module, which share themselves in the tasks:
– Managing the time base for the RTU560 station and syn- – MPU: 32 Bit Main Processing Unit
chronizing the I/O modules. – SLC: 8 Bit Serial Line Controller
– Handling the dialog between RTU560 and Web-Browser via
the LAN interfaces. One task of the SLC is to work as master for the SPB I/O bus
(serial peripheral bus). In addition the SLC is the time base for
Within the RTU560 racks the board occupies one slot. The com- the I/O modules and does the periodical time synchronization
munication unit is able to handle Ethernet-, UART- and non UART of the I/O modules. Depending on the configuration also serial
character based communication protocols. protocols can be handled via the SLC.

The MPU is responsible for the other tasks. The MPU handles
the absolute time and date for the RTU. The real time clock
560RTC0x can be used for the time reference or the time may
be set and synchronized from the central system via the serial
lines or via the Ethernet LAN interface. RTU560 synchronizes it-
self to the time references supplied by 560RTC0x. The time in-
formation of the 560RTC0x is provided to the 560CMU02 on the
backplane of the sub-rack.

System relevant configuration files are stored in the non-volatile


flash memory card in order to guarantee a valid system configu-
ration after Power on Reset (PoR).

The communication unit provides the following interfaces:


– Communication Port 1 and 2 (CP1 & CP2): serial interfaces
according RS232C or RS485 with RJ45 connectors.
– Ethernet Interface 1 and 2 (E1 & E2) Ethernet interface
10/100BaseT with RJ45 connector.
– The SPB I/O bus is directly connected to the backplane
connector.

2 | 1KGT 150 717 V003 1 - Communication Unit 560CMU02


Technical data Signaling by LEDs

ERR (red) ON: RTU in error state


In addition to the RTU500 series general technical data, the fol- Flashing: RTU in warning state
lowing applies:
For more details see RTU500 series
Function Description
Main Processing Unit MPU
Tx (green) Transmit data on serial communica-
CPU ELAN520 @ 133 MHz tion ports CP
(incorporating an Intel® 586TM class
Rx (green) Receive data on serial communication
32 bit processor)
ports CP
RAM 64 MByte
A (green) Activity on Ethernet interface E

L (green) Link up on Ethernet interface E


Serial Line Controller SLC

CPU 80C251
Mechanical layout
RAM 32 kByte
Dimensions 160 mm x 100 mm, 3HE euro card
Dual ported RAM 16 kByte format
4R (20 mm) front panel

CompactFlash card Housing type Printed circuit board

Connector CompactFlash card slot Mounting for mounting in RTU560 racks

Type CF-Typ I (36,4 mm × 42,8 mm × 3,3 Weight 0.3 kg


mm)

Capacity 128 MByte Connection type

RTU560 backplane connector 48 pole type F DIN 41612


Serial interfaces CP1 and CP2

Connector RJ45 Immunity test


Type RS232C or RS485 Electrostatic discharge 8 kV air (level 3) / 4 kV contact (level 2)

RS232C: IEC 61000-4-2 Performance criteria A

Bit rate 50 bit/s - 38.4 kbit/s Radiated Radio-Frequency Electro- 10 V/m (level 3)
magnetic Field Performance criteria A
Signal lines GND E2/102
IEC 61000-4-3
TxD D1/103
RxD D2/104 Electrical Fast Transient / Burst 2 kV (level 3)
IEC 61000-4-4 Performance criteria A
RTS S2/105
CTS M2/106 Surge 2 kV (level 3)
DTR S1.2/108 IEC 61000-4-5 Performance criteria A
DCD M5/109
Conducted Disturbances, induced by 10 V (level 3)
Level typical: ± 6V Radio-Frequency Fields Performance criteria A
IEC 61000-4-6
RS485:

Bit rate 50 bit/s - 38.4 kbit/s

Level typical: ± 6V Environmental conditions

Nominal operating temperature range: -25°C... 70°C


Ethernet interface E1 and E2 EN 60068-2-1, -2-2, -2-14
Connector RJ45
Relative humidity 5 ... 95 %
Type IEEE 802.3, 10/100BaseT EN 60068-2-30 (non condensing)

Current consumption for power supplied via RTU560 backplane Ordering information

5 V DC 1080 mA 560CMU02 R0002 1KGT012600R0002

24 V DC

Communication Unit 560CMU02 - 1KGT 150 717 V003 1 | 3


ABB AG Note:
Power Systems Division The specifications, data, design or other information contained in this document
P.O. Box 10 03 51 (the “Brochure”) - together: the “Information” - shall only be for information pur-

68128 Mannheim, Germany poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-

www.abb.com/substationautomation serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.

This product is designed to be connected to and to communicate information


and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall es-
tablish and maintain any appropriate measures (such as but not limited to the in-
stallation of firewalls, application of authentication measures, encryption of da-
ta, installation of anti-virus programs, etc) to protect the product, the network,
its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB
AG is not liable for any damages and/or losses related to such security breaches,
any unauthorized access, interference, intrusion, leakage and/or theft of data or
information.

ABB AG shall be under no warranty whatsoever whether express or implied and


assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in con-
nection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be exclud-
ed. In particular ABB AG shall in no event be liable for any indirect, consequen-
tial or special damages, such as – but not limited to – loss of profit, loss of pro-
duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-
ital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in ac-
cordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).

ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.

© Copyright ABB 2014


All rights reserved

4 | 1KGT 150 717 V003 1 - Communication Unit 560CMU02

You might also like