NYCWY Power Cables

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Eland Cables’ Datasheet Electrical Cable | Product Group Fixed Wiring

NYCWY Power Cable


Eland Product Group A9N www.eland.co.uk

Dimensions
Resistance Values (ohms per kilometre)
Application Eland Part Numbers No. of Cores x Nominal Conductor Type Nominal Overall Nominal Weight
For use where increased electrical and mechanical Cross Sectional Area Diameter kg/Km
# x mm² mm
protection is required, preferably for underground
laying, especially in subscriber networks, NYCWY Cable - 2 Cores
power stations as well as control cables for the A9NYCWY02010/10 2 x 10.0 re / 10.0 19.0 650.0
transmission of control impulses and test data. A9NYCWY02016/16 2 x 16.0 re / 16.0 21.5 850.0
A9NYCWY02025/25 2 x 25.0 rm / 25.0 24.5 1210.0
Standards
NYCWY Cable - 3 Cores
VDE0276 part 603, CENELEC HD603 S1,
A9NYCWY03010/10 3 x 10.0 re / 10.0 19.5 730.0
IEC 60502
A9NYCWY03016/16 3 x 16.0 re / 16.0 22.0 1000.0
Conductor A9NYCWY03025/16 3 x 25.0 rm / 16.0 26.0 1550.0
rm conductor: Class 1 solid plain copper to A9NYCWY03025/25 3 x 25.0 rm / 25.0 26.0 1600.0
BS EN 60228:2005 (previously BS6360), A9NYCWY03035/35 3 x 35.0 sm / 35.0 27.5 1850.0
VDE0295, IEC 60228, CENELEC HD383
A9NYCWY03035/16 3 x 35.0 sm / 16.0 27.0 1750.0
rm conductor: Class 2 stranded, round plain
copper conductor, multi wire to BS EN A9NYCWY03050/50 3 x 50.0 sm / 50.0 29.5 2450.0

60228:2005 (previously BS6360), VDE0295, A9NYCWY03050/25 3 x 50.0 sm / 25.0 29.0 2250.0


IEC 60228, CENELEC HD383 A9NYCWY03070/70 3 x 70.0 sm / 70.0 34.0 3350.0
sm conductor: Class 2 stranded, sectorial plain A9NYCWY03070/35 3 x 70.0 sm / 35.0 33.0 2950.0
copper conductor to BS EN 60228:2005
A9NYCWY03095/95 3 x 95.0 sm / 95.0 38.5 4550.0
(previously BS6360), VDE0295, IEC 60228,
A9NYCWY03095/50 3 x 95.0 sm / 50.0 38.0 4100.0
CENELEC HD383
A9NYCWY03120/70 3 x 120.0 sm / 70.0 41.0 5050.0
Insulation A9NYCWY03120/120 3 x 120.0 sm / 120.0 42.0 5550.0
PVC (Polyvinyl Chloride) DIV4 to HD 603.1 A9NYCWY03150/70 3 x 150.0 sm / 70.0 45.0 6000.0
A9NYCWY03150/150 3 x 150.0 sm / 150.0 46.0 6900.0
Bedding
A9NYCWY03185/95 3 x 185.0 sm / 95.0 50.0 7550.0
PVC (Polyvinyl Chloride)
A9NYCWY03185/185 3 x 185.0 sm / 185.0 51.0 8500.0

Concentric Conductor A9NYCWY03240/120 3 x 240.0 sm / 120.0 57.0 9950.0


Waveconal outer conductor – copper wires NYCWY Cable - 4 Cores
and contrahelical copper tape (reverse lay A9NYCWY04010/10 4 x 10.0 re / 10.0 20.5 890.0
copper tape)
A9NYCWY04016/16 4 x 16.0 re / 16.0 23.5 1250.0
A9NYCWY04025/16 4 x 25.0 rm / 16.0 28.0 1800.0
Sheath
PVC (Polyvinyl Chloride) DMV5 to HD 603.1 A9NYCWY04035/16 4 x 35.0 sm / 16.0 29.0 2050.0
A9NYCWY04050/25 4 x 50.0 sm / 25.0 33.0 2700.0
Sheath Colour A9NYCWY04070/35 4 x 70.0 sm / 35.0 37.0 3750.0
Black A9NYCWY04095/50 4 x 95.0 sm / 50.0 43.5 5000.0
A9NYCWY04120/70 4 x 120.0 sm / 70.0 47.0 6350.0
Voltage Rating
600/1000V A9NYCWY04150/70 4 x 150.0 sm / 70.0 51.0 7650.0
A9NYCWY04185/95 4 x 185.0 sm / 95.0 56.0 9350.0
Temperature Rating A9NYCWY04240/120 4 x 240.0 sm / 120.0 62.5 11600.0
Fixed: -30°C to +70°C
Flexing: -5°C to +50°C re = round conductor, rm = stranded conductor, sm = sectional conductor

Minimum Bending Radius


Single Core: 15 x overall diameter
Conductors
Multi-Core: 12 x overall diameter
Class 1 solid conductors for Single Core and Multi-Core cables
Core Identification 1 2

Up to and including 5 cores: Nominal Cross Sectional Area Maximum Resistance of Conductor at 20ºC
mm2
colour coded or number coded Circular, Annealed Copper Conductors
Plain
ohms/Km
10.00 1.8300
16.00 1.1500

Table in accordance with BS EN 60228:2005 (previously BS6360)

Datasheet Continues »
Issue_02_0608
Eland Cables’ Datasheet NYCWY Power Cable [Continued]

Class 2 stranded conductors for Single Core and Multi-Core cables


1 2 4 6 8
Nominal Cross Minimum Number of Wires in the Conductor Maximum Resistance of Conductor at 20ºC
Sectional Area
Circular Circular Shaped Annealed Copper Conductor
mm2
Compacted
Cu Cu Cu Plain Wires ohms/Km
25.0 7 6 6 0.7270
35.0 7 6 6 0.5240
50.0 19 6 6 0.3870
70.0 19 12 12 0.2680
95.0 19 15 15 0.1930
120.0 37 18 18 0.1530
150.0 37 18 18 0.1240
185.0 37 30 30 0.0991
240.0 37 34 34 0.0754

Table in accordance with BS EN 60228:2005 (previously BS6360)

Electrical Characteristics
Current Carrying Capacity (amperes), laying in ground (20°C)
Nominal Cross-sectional Area Multicore cables
mm² A

10.0 79
16.0 102
25.0 133
35.0 160
50.0 190
70.0 234
95.0 280
120.0 319
150.0 357
185.0 402
240.0 463

Current Carrying Capacity (amperes), laying in air (30°C)


Nominal Cross-sectional Area Multicore cables
mm² A

10.0 60
16.0 80
25.0 108
35.0 132
50.0 160
70.0 202
95.0 249
120.0 289
150.0 329
185.0 377
240.0 443

Conversion factors for multicore cable (≥5 cores)


The conversion factors are to be used for laying cables in ground or in sir, to values given in above tables.
Number of loaded cores Laying in Ground Laying in air
n f f

5 0.70 0.75
7 0.60 0.65
10 0.50 0.55
14 0.45 0.50
19 0.40 0.45
24 0.35 0.40
40 0.30 0.35
61 0.25 0.30

Note: valid for cross-section 1.5 to 10mm²

The information contained within this datasheet is for guidance only. When selecting accessories such as cleats, glands, etc please note that actual cable
dimensions may vary due to manufacturing tolerances.

For all your cable needs [email protected] www.eland.co.uk tel +44 (0)207 241 8787 fax +44 (0)207 241 8700

You might also like