Current Transformer - 110kV
Current Transformer - 110kV
ABB
Data schedule: Current Transformer
General Data
Item 40
Quantity 4
Type IMB 123
Design Outdoor
Insulation Oil/paper
Manufacturer, country ABB, Sweden
Insulation levels
Lightning Impulse Withstand Level (LIWL) 1,2/50 µs kV peak 550
Switching Impulse Withstand Level (SIWL) 250/2500 µs kV peak 0
Power Frequency Withstand, dry kV r.m.s. 230
Power Frequency Withstand, wet kV r.m.s. 230
Current ratings
Rated primary current (Ipn) A 200
Primary rating factor (Rf) 1.2
Max continuous thermal current A r.m.s. 240
Rated short time current (Ith) kA r.m.s./s 31.5 / 3
Rated dynamic current (Idyn) kA peak 80
Reconnection −
Core No 1,2 200 : 1 A
Accuracy ratings
Core No at ratio Accuracy Rct75 Note
1 200:1 30VA 0.2 Fs5
2 200:1 30VA 5P20
Product data
Dimension drawing 1HSE210003−320
Insulator type/color Porcelain / Brown
Minimum creepage/protected distance mm 3625 / 1370
Minimum flashover distance mm 1120
Capacitive voltage tap Yes Inside secondary box
Al pad D=14 (4x) 40−50
Primary terminal type
T=20
Max force on primary terminal (Stat/Dyn)N 3000/4200
Secondary terminal box 1HSE 24102−M
Extra equipment in secondary terminal box Without accessories
Earth terminal type Standard, 1 Brass clamp
Dia 8−15mm
Weight incl. oil kg 450
Weight oil kg 50
Packing 3−pack Vertical
Shipping weight kg/unit 505
Shipping volume m3/unit 1.2
Catalogue 1HSM 954342−00en
© ABB AB 2008. All rights to this document and its information are reserved. Any form of reproduction,
use, or disclosure to third parties or unauthorised persons without our prior written consent is strictly forbidden.
Data is based on calculation number: 79024