0% found this document useful (0 votes)
911 views3 pages

NH40 Chint Reversora Manual

The document discusses NH40 series changeover switches. 1. NH40 changeover switches are fully enclosed switches used in distributing and motor circuits to provide safety isolation and overcurrent protection. 2. They are available in various pole configurations and current ratings from 125A to 630A for 400V AC and 800V insulation. 3. The switches have a unique rolling insert contact system and can be ordered in lateral or front operation styles with extended or direct rotary handles.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
911 views3 pages

NH40 Chint Reversora Manual

The document discusses NH40 series changeover switches. 1. NH40 changeover switches are fully enclosed switches used in distributing and motor circuits to provide safety isolation and overcurrent protection. 2. They are available in various pole configurations and current ratings from 125A to 630A for 400V AC and 800V insulation. 3. The switches have a unique rolling insert contact system and can be ordered in lateral or front operation styles with extended or direct rotary handles.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Changeover Switch

Ukrain

NH40S Changeover Switch

1. General
1.1 Application
Mainly used in the distributing and motor circuit which has high
short-circuit current, and acted as main switch or master switch
infrequently operated by hand, it is particularly suitable in the
relative high class with drawable low voltage complete equipment.
They provide safety isolation and protection against overcurrent
for any low voltage electrical circuit.
1.2 Standard: IEC/EN 60947-3.
1.3 General characteristic
Full-enclosed structure
Unique rolling insert type contact system.

2. Changeover switch
2.1 Ordering information

Nh40 - □ / □ C S □

W: extended rotary handle


Blank: direct rotary handle
S: Changeover switch
C: lateral operation
Blank: front operation
No. of poles: 3,4
Conventional thermal current
Series No.

2.2 Property

Conventional thermal current 125 160 200 250 315 400 630
Rated current of fuse(A) 125 160 200 250 315 400 630
Rated insulation voltage(V) 800
400V AC21 125 160 200 250 315 400 630
690V AC21 125 160 160 200 315 400 500
Rated current (A)
230V DC21 125 160 160 250 315 400 630
440V DC21 125 160 160 200 315 400 500
Operation force (N) 40~60 65~100 75~120

Conventional thermal current 1000 1250 1600 2000 2500 3150


Rated current of fuse(A) 1000 1250 2×800 2×1000 2×1250
Rated insulation voltage(V) 800
400V AC20 1000 1250 1600 2000 2500 3150
690V AC20 1000 1250 1600 2000 2500 3150
Rated current (A)
230V DC20 1000 1250 1600 2000 2500 3150
440V DC20 1000 1250 1600 2000 2500 3150
Operation force (N) 200~300

.30.
Changeover Switch

Mounting dimensions of NH40-125~1600/C and NH40-125~1600/CS

A
A1 Y1
J J1 Y

R φX
L
U
B


G
V P P P N C1 20

125A~1600A/CS
Lateral double-throw operation

28
4φ6

125A~1600A/CSW
50

Lateral double-throw
64

operation outside the switchgear


65X65板
50

φ31
Z±1
4φ4.5 50 D1

Gate hole Minim length of extended connecting stick


125-630A: Z+27±1
1000-1600 A: Z+35±1

Mounting dimension of NH40 lateral operation and NH40 changeover switch disconnector

Specification NH40-XX/C NH40-XX/CS Overall and mounting dimensions (mm)


Current A A1 B C C1 D1 J K L N P R U V X Y Y1 Z
125A/3 267 196 135 152 212 60 120 95 7 29.5 36 20 115 20 9 55 120 232
160A/3 267 196 135 152 212 60 120 95 7 29.5 36 20 115 20 9 55 120 232
125A/4 297 296 135 152 212 60 150 95 7 29.5 36 20 115 20 9 55 120 232
160A/4 297 296 135 152 212 60 150 95 7 29.5 36 20 115 20 9 55 120 232
200A/3 307 236 170 147 229 60 160 115 7 29.5 50 25 140 27 11 65 145 249
250A/3 307 236 170 147 229 60 160 115 7 29.5 50 25 140 27 11 65 145 249
200A/4 357 286 170 147 229 60 210 115 7 29.5 50 25 140 27 11 65 145 249
250A/4 357 286 170 147 229 60 210 115 7 29.5 50 25 140 27 11 65 145 249
315A/3 372 301 240 184 297 60 210 180 9 45 65 32 205 37.5 11 84 198 317
400A/3 372 301 240 184 297 60 210 180 9 45 65 32 205 37.5 11 84 198 317
630A/3 372 301 260 184 297 60 210 180 9 45 65 32 205 37.5 13 84 198 317
315A/4 432 361 240 184 297 60 270 180 9 45 65 32 205 37.5 11 84 198 317
400A/4 432 361 240 184 297 60 270 180 9 45 65 32 205 37.5 11 84 198 317
630A/4 432 361 260 184 297 60 270 180 9 45 65 32 205 37.5 13 84 198 317
1000A/3 621 472 310 230 374 81 353 220 11 51.5 120 60 250 60.5 13 108 253 374
1250A/3 621 472 360 230 374 81 353 220 11 51.5 120 80 250 60.5 13 108 253 374
1600A/3 621 472 360 230 374 81 353 220 11 51.5 120 80 250 60.5 13 108 253 374
1000A/4 741 592 310 230 374 81 473 220 11 51.5 120 60 250 60.5 13 108 253 374
1250A/4 741 592 360 230 374 81 473 220 11 51.5 120 80 250 60.5 13 108 253 374
1600A/4 741 592 360 230 374 81 473 220 11 51.5 120 80 250 60.5 13 108 253 374

.31.
Mounting dimensions of NH40-2000~3150/C and NH40-2000~3150/CS

A Y3
A1 Y2
J Y1
Y T T
''3-7
1-5 '' 1-5 3-7
11

7-7' 5-5' 3-3' 1-1'


K
B

I I

8-8' 6-6' 4-4' 2-2'

''2-6
4-8 '' 4-8 2-6
12.5 V P 51.5 C

2000A~3150A/CS

Terminal

50
φ13
20 40
65X65

40 20
50

80

4φ4.5 φ30

φ13
Without extended connecting stick
50

81
100

Minim length of extended connecting stick Z+35:1


25

50 35

Mounting dimension of NH40 changeover switch disconnect

Specification NH40-XX/C NH40-XX/CS Overall and mounting dimensions (mm)


Current A A1 B C C1 J K P V Y Y1 Y2 Y3 Z
2000A/3 576 472 450 603 374 353 220 120 60 80 230 420 465 603
2500A/3 576 472 450 603 374 353 220 120 60 80 230 420 465 603
3150A/3 576 472 450 603 374 353 220 120 60 80 230 420 465 603
2000A/4 696 592 510 603 374 473 220 120 60 80 230 420 465 603
2500A/4 696 592 510 603 374 473 220 120 60 80 230 420 465 603
3150A/4 696 592 510 603 374 473 220 120 60 80 230 420 465 603

.32.