BS6891 Pipework Installation
BS6891 Pipework Installation
BS 6891:2015
D
TE
BSI Standards Publication
IN
PR
Specification for the
installation and maintenance
of low pressure gasEN
H
installation pipework of up
W
to 35 mm (R11⁄4) on premises
ED
LL
O
TR
N
O
C
N
U
Gas Safe Register Licensed Subscription Copy BS 6891:2015 BRITISH STANDARD
D
Committee reference GSE/30
Draft for comment 13/30199128 DC
TE
Publication history
First published February 1988
IN
Second edition, April 1998
Third edition, April 2005
PR
Fourth (present) edition, November 2015
EN
H
W
ED
LL
O
TR
N
O
C
N
U
Gas Safe Register Licensed Subscription Copy BRITISH STANDARD BS 6891:2015
Contents
Foreword iii
1 Scope 1
2 Normative references 4
3 Terms and definitions 7
4 Competence 12
5 Design and planning 13
6 Materials and components 16
7 Jointing 18
D
8 Installation 20
9 Installation of flexible hoses, tubing, assemblies and their connections 66
TE
10 Commissioning 69
11 Maintenance 72
Annexes
IN
Annex A (informative) Guide to sizing pipework installations 73
Annex B (informative) Sulfidation of natural gas installations 81
PR
Annex C (informative) Summary and principal conclusions of the Advantica
Research Project, Gas in intermediate floors, Report Number 6699 [28] 82
Annex D (informative) Protected area 84
Annex E (normative) LPG Final stage regulator and safety devices 85
EN
Annex F (informative) Dangerous Substances and Explosive Atmospheres
Regulations [17], [18] 88
Bibliography 90
H
List of figures
W
Figure 1 – 2nd family gas installation with an internal meter 2
Figure 2 – 3rd family gas installation with cylinders 3
Figure 3 – 3rd family gas installation with bulk storage vessels 3
ED
Figure 13 – Limits for notching and drilling of solid timber floor joists 35
Figure 14 – Pipework in concrete compartment floors 38
O
walls 46
Figure 18 – Typical examples of pipework installed in timber and light
U
D
tube 75
Table A.2 – Approximate natural gas pressure loss data (mbar/m) – steel
TE
tube 76
Table A.3 – Approximate LPG (propane) pressure loss data (mbar/m) – copper
tube 77
IN
Table A.4 – Approximate LPG (propane) pressure loss data (mbar/m) – steel
tube 78
Table A.5 – Typical allowances for pressure loss of fittings 79
PR
Table A.6 – Sizing results 80
Table E.1 – Pressure characteristics of various regulators (LPG) 86
Table E.2 – Minimum proximity distances for relief valve vent tips
(millimetres) 88
EN
H
W
ED
LL
O
TR
N
O
C
N
U
Summary of pages
This document comprises a front cover, an inside front cover, pages i to iv,
pages 1 to 94, an inside back cover and a back cover.
Foreword
Publishing information
This British Standard is published by BSI Standards Limited, under licence from
The British Standards Institution, and came into effect on 30 November 2015. It
was prepared by Panel GSE/30/-/3, Domestic installation pipes, under the
authority of Technical Committee GSE/30, Gas Installations (1st, 2nd and 3rd
family gases). A list of organizations represented on this committee can be
obtained on request to its secretary.
D
NOTE 1 The standard now covers the main installation requirements for 3rd family
gas installations that were previously covered by BS 5482-1.
TE
NOTE 2 The general installation requirements for 3rd family gas installations
specified in this standard also apply to gas installations supplied with LPG/air
mixtures used in the Channel Islands or the Isle of Man, provided:
IN
• any gas equipment being installed has been appropriately converted and is
suitable for the gas being supplied; and
PR
• the requirements of the standard do not conflict with local regulations or
authorized local custom and practice.
Supersession
EN
BS 6891:2015 supersedes BS 6891:2005+A2:2008, which is withdrawn, and
partially supersedes BS 5482-1:2005, which is partially withdrawn.
H
Information about this document
W
In this revision, the layout of the standard has been modified to follow the
systematic approach adopted in other gas installation standards. The revision
provides an update of the previous edition and has been updated to reflect
ED
changes in installation practice and legislation, and align with other appropriate
standards. A number of other safety initiatives have also been included that
have not previously been covered elsewhere in detail. The opportunity has also
LL
been taken to combine the pipework requirements for 2nd and 3rd family gas
(natural gas and LPG) installations into a single standard for use by the gas
industry.
O
It has been assumed in the preparation of this British Standard that the
execution of its provisions will be entrusted to appropriately qualified and
experienced people, for whose use it has been produced.
N
Users of this British Standard are advised to consider the desirability of selecting
O
Presentational conventions
N
The provisions of this standard are presented in roman (i.e. upright) type. Its
U
D
Regulations 2004 [2];
TE
• The Gas Safety (Installation and Use) Regulations 1994, as amended and
applied by the Gas Safety (Application) (Isle of Man) Order 1996 [3];
• The Health and Safety (Gas) (Guernsey) Ordinance 2006 [4];
IN
• The Building Regulations 2010 (England and Wales), as amended [5];
•
PR
The Building Regulations (Northern Ireland) 2012 [6];
• The Building (Scotland) Regulations 2004, as amended [7];
• The Gas Safety (Management) Regulations 1996 [8];
EN
• The Gas Safety (Management) Regulations (Northern Ireland) 1997 [9].
H
W
ED
LL
O
TR
N
O
C
N
U
1 Scope
This British Standard specifies the design, installation, commissioning and
maintenance of gas installation pipework carrying 2nd and 3rd family gas of up
to 35 mm (R 11⁄4) on premises, including residential park homes (2nd
and 3rd family gas) and caravan holiday homes (2nd family gas) (see Table 1 and
examples in Figure 1 to Figure 3; see also Figure 4).
NOTE 1 The principles of the standard can also be applied to the design,
installation, commissioning and maintenance of gas installation pipework
carrying 1st family gas.
D
NOTE 2 Annex A gives a method for calculating pipe sizes. Annex B discusses the
sulfidation of natural gas installations, while Annex C summarizes the conclusions of
TE
a report on gas in intermediate floors. Guidance on determining whether an area
can be deemed a “protected area” is given in Annex D. Requirements for LPG final
stage regulator and safety devices are specified in Annex E. Annex F discusses the
IN
need for gas pipework design and installation for commercial installations to satisfy
regulatory requirements regarding explosive atmospheres.
PR
This British Standard is not applicable to:
a) service pipework and distribution systems;
b) pipework contained within an appliance;
EN
c) bulk storage vessels;
d) LPG pipework installed in leisure accommodation vehicles and for
accommodation purposes in vehicles in accordance with BS EN 1949;
H
e) boats, yachts and other vessels;
W
f) gas pipework supplying or within appliances having their own gas supply,
such as mobile heaters; or
ED
D
3rd family Downstream of: R11⁄4 steel, 37 (propane)
(LPG) •
TE
A)
the emergency control valve (ECV) located on the DN 35 28 (butane)
outside of the property where no meter is fitted;
or
IN
• the outlet of the final regulator where this is
located downstream of the ECV; or
PR
• the outlet of the final regulator where this is
located downstream of any cylinders and there is
no ECV; or
• the primary meter installation,
EN
but not downstream of the inlet of any appliance
isolation valve or the inlet of the self-sealing connector
of any flexible connection.
H
A)
Dependent upon material type.
B)
1 bar = 105 N/m2 = 100 kPa.
W
b) the diameter for carbon, stainless-steel tubing, copper and polyethylene (PE) refers to the outside
diameter.
LL
Key
1 Service pipe 7 Appliance isolation valve
2 Primary meter installation 8 Appliance
3 Installation pipework 9 Part of installation within the scope of BS 6891
4 Appliance connector R Regulator
5 Service isolation valve (where fitted) M Meter
6 Emergency control valve
D
TE
Key
IN
1 Service pipework 6 Appliance isolation valve
2 Installation pipework 7 Appliance
PR
3 Appliance connector 8 Part of installation within the scope of BS 6891
4 Cylinders R Regulator with over-pressure shut-off
5 Emergency control valve ACD Automatic changeover device
Figure 3
EN
3rd family gas installation with bulk storage vessels
H
W
ED
LL
O
TR
Key
1 Service pipework 6 Appliance isolation valve
2 Installation pipework 7 Appliance
N
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
NOTE For commercial premises less than 35 mm, IGEM/UP/2 [12] may also be utilized.
C
2 Normative references
N
document and are indispensable for its application. For dated references, only
the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
BS 21, Specification for pipe threads for tubes and fittings where pressure-tight
joints are made on the threads (metric dimensions)
BS 143 and 1256, Threaded pipe fittings in malleable cast iron and cast copper
alloy
BS 669-1, Flexible hoses, end fittings and sockets for gas burning appliances –
Part 1: Specification for strip-wound metallic flexible hoses, covers, end fittings
and sockets for domestic appliances burning 1st and 2nd family gases
BS 669-2, Flexible hoses, end fittings and sockets for gas burning appliances –
Part 2: Specification for corrugated metallic flexible hoses, covers, end fittings
and sockets for catering appliances burning 1st, 2nd and 3rd family gases
BS 864-2, Capillary and compression tube fittings of copper and copper alloy –
Part 2: Specification for capillary and compression fittings for copper tubes 1)
BS 1552, Specification for open bottomed taper plug valves for 1st, 2nd and 3rd
D
family gases up to 200 mbar
TE
BS 3016, Specification for pressure regulators for liquefied petroleum gases1)
BS 3212, Specification for flexible rubber tubing, rubber hose and rubber hose
assemblies for use in LPG vapour phase and LPG/air installations
IN
BS 4371, Specification for fibrous gland packings
BS 5114, Specification for performance requirements for joints and compression
PR
fittings for use with polyethylene pipes1)
BS 6172, Installation and maintenance of domestic gas cooking appliances
(2nd and 3rd family gases) – Specification
EN
BS 6362, Specification for stainless steel tubes suitable for screwing in
accordance with BS 21 ’Pipe threads for tubes and fittings where pressure-tight
joints are made on the threads’
H
BS 6400-1, Specification for installation, exchange, relocation and removal of gas
W
meters with a maximum capacity not exceeding 6 m3/h – Part 1: Low pressure
(2nd family gases)
BS 6400-2, Specification for installation, exchange, relocation and removal of gas
ED
meters with a maximum capacity not exceeding 6 m3/h – Part 3: Low and
medium pressure (3rd family gases) 2)
O
BS 6501-1, Metal hose assemblies – Part 1: Guidance on the construction and use
of corrugated hose assemblies
TR
BS 8537, Copper and copper alloys – Plumbing fittings – Specification for press
ends of plumbing fittings for use with metallic tubes
U
BS EN 331, Manually operated ball valves and closed bottom taper plug valves
for gas installations in buildings
BS EN 751-1, Sealing materials for metallic threaded joints in contact
with 1st, 2nd and 3rd family gases and hot water – Part 1: Anaerobic jointing
compounds
1)
Withdrawn.
2)
This standard also gives informative references to BS 6400-3:2007.
D
BS EN 1254-2, Copper and copper alloys – Plumbing fittings – Part 2: Fittings
TE
with compression ends for use with copper tubes
BS EN 1254-4, Copper and copper alloys – Plumbing fittings – Part 4: Fittings
combining other end connections with capillary or compression ends
IN
BS EN 1254-5, Copper and copper alloys – Plumbing fittings – Part 5: Fittings
with short ends for capillary brazing to copper tubes
PR
BS EN 1555-1, Plastics piping systems for the supply of gaseous fuels –
Polyethylene (PE) – Part 1: General
BS EN 1555-2, Plastics piping systems for the supply of gaseous fuels –
EN
Polyethylene (PE) – Part 2: Pipes
BS EN 1555-3, Plastics piping systems for the supply of gaseous fuels –
Polyethylene (PE) – Part 3: Fittings
H
BS EN 1775:2007, Gas supply – Gas pipework for buildings – Maximum operating
W
pressure less than or equal to 5 bar – Functional recommendation
BS EN 10216-1, Seamless steel tubes for pressure purposes – Technical delivery
conditions – Part 1: Non-alloy steel tubes with specified room temperature
ED
properties
BS EN 10216-2, Seamless steel tubes for pressure purposes – Technical delivery
conditions – Part 2: Non-alloy and alloy steel tubes with specified elevated
LL
temperature properties
BS EN 10216-5, Seamless steel tubes for pressure purposes – Technical delivery
O
BS EN 10226-1, Pipe threads where pressure tight joints are made on the
threads – Part 1: Taper external threads and parallel internal threads –
U
D
BS EN 13786, Automatic change-over valves having a maximum outlet pressure
TE
of up to and including 4 bar with a capacity of up to and including 100 kg/h,
and their associated safety devices for butane, propane or their mixtures3)
BS EN 15069, Safety gas connection valves for metal hose assemblies used for
IN
the connection of domestic appliances using gaseous fuel
BS EN 15266, Stainless steel pliable corrugated tubing kits in buildings for gas
PR
with an operating pressure up to 0,5 bar
BS EN 16129, Pressure regulators, automatic change-over devices, having a
maximum regulated pressure of 4 bar, with a maximum capacity of 150 kg/h,
EN
associated safety devices and adaptors for butane, propane, and their mixtures
BS EN 16436-1, Rubber and plastics hoses, tubing and assemblies for use with
propane and butane and their mixture in the vapour phase – Part 1: Hoses and
H
tubings
W
BS EN ISO 228-1, Pipe threads where pressure-tight joints are not made on the
threads – Part 1: Dimensions, tolerances and designation
BS EN ISO 10380, Pipework – Corrugated metal hoses and hose assemblies
ED
ISO 7-1, Pipe threads where pressure-tight joints are made on the threads –
Part 1: Dimensions, tolerances and designation
LL
For the purposes of this British Standard, the following terms and definitions
apply.
TR
3)
Current, though superseded by BS EN 16129.
3.3 basement
part of a building that is partly or wholly underground
NOTE For the purposes of this definition, a room which is built into a hillside is not
considered partially underground if at least one (outside) wall of the room is at the
same level or at a higher level than the area outside. Additionally, the area outside
should not itself be considered to be at a lower level than the wider topography.
The ultimate test should be that if an LPG leak occurred in such a room, it could
disperse safely to outside (and away) rather than build up either in the room, in
other areas of the building or in the immediate area outside the room.
D
3.4 bulk storage vessel
permanently-installed vessel for the storage of LPG under pressure, which is
TE
filled in situ
IN
transportable leisure accommodation vehicle that does not meet the
requirements for construction and use of road vehicles, that retains means for
mobility and is for temporary or seasonal occupation
PR
[SOURCE: BS EN 1949:2011+A1:2013, 3.4]
EN
floor that separates one dwelling from the rest of the building
3.9 duct
ED
enclosed space specifically designed and constructed for the passage of building
services
LL
the supply of gas in an emergency, intended for use by a gas consumer and
installed at the end of a service or service pipework
O
building
U
NOTE A roof space above the top storey of a fire compartment is included in the
compartment where the walls of that compartment extend up to the roof line.
NOTE This definition varies from that given in the Gas Safety (Installation and Use)
Regulations 1998 [1]. This term does not refer to:
• a service (pipe) or distribution main or other pipeline;
• a pipe or fitting forming part of a gas appliance;
• a pipe or fitting within a primary meter installation; or
• any valve attached to a storage container or cylinder.
Hereafter referred to as “pipework”.
D
3.15 intermediate floor
floor that separates one living space from another living space in the same
TE
dwelling
NOTE This is not a compartment floor that separates one dwelling from another
part of the building.
IN
3.16 leisure accommodation vehicle
PR
unit of living accommodation for temporary or seasonal occupation
NOTE Such vehicles might meet the requirements of the Road Vehicles
(Construction and Use) Regulations 1986, as amended [13], and include touring
caravans, motor caravans and caravan holiday homes.
installation that comprises a primary meter, valves, filter, meter regulator and
associated safety devices, pliable connector, interconnecting pipework, fittings
C
and support
N
D
3.25 over-pressure shut-off (OPSO)
TE
shut-off device, triggered by an excess outlet pressure, which causes the
complete shut-off of the flow of gas for all values of inlet pressure
NOTE This device is normally an integral part of the regulator. It may also be
IN
referred to as a “slam shut valve” or “over-pressure cut-off” (OPCO).
[SOURCE: BS 6400-3:2007, 3.25.1, modified]
PR
3.26 permanent dwelling
structure of a permanent nature used primarily for domestic purposes
EN
3.27 pliable corrugated (stainless-steel) tubing
tubing of stainless steel, capable of being bent easily by hand a limited number
of times and covered with an outer sheath by the manufacturer at the time of
H
production
NOTE The term is sometimes abbreviated to corrugated stainless-steel tubing (CSST)
W
or pliable tubing (PLT). This product should not be confused with the pliable
connectors referred to in BS 6400, which are not covered by an outer sheath and
have factory-fitted end connections.
ED
concrete floor slab to form a monolithic structure, which avoids the need for a
separate screed to provide the floor finish
O
D
appliance within a narrow range of minimum and maximum heat inputs stated
by the manufacturer to suit the actual heat requirements of the system
TE
NOTE The range between minimum and maximum heat inputs is in the region
of 3 kW.
IN
3.34 regulator
device that controls the pressure at its outlet within predetermined parameters
PR
3.35 residential park home
caravan used for permanent residence
EN
NOTE Such caravans do not meet all of the requirements of the Road Vehicles
(Construction and Use) Regulations 1986, as amended [13]. These are covered by
BS 3632. “Permanent residence” is defined in the Caravan Sites and Control of
Development Act 1960 [14] and the Caravans Sites Act 1968 [15].
H
3.36 service pipe
W
pipe for distributing gas to premises from a distribution main, being any pipe
between the distribution main and the outlet of the first emergency control
valve
ED
between the gas storage vessel and the outlet of the ECV
3.38 sleeve
O
device integral to the regulator, which causes the complete shut-off of the gas
N
3.41 void
enclosed space not specifically designed for the passage of building services
4 Competence
Persons carrying out work that will have an impact on work covered by the
scope of this standard shall ensure that they have the competence relevant for
the task such as not to compromise the requirements/recommendations of this
standard and in particular the safe installation, commissioning and operation of
gas equipment.
COMMENTARY ON CLAUSE 4
Competence requires sufficient knowledge, practical skill and experience to carry out
the job in hand safely, with due regard to good working practice. The installation
D
should also be left in a safe condition for use. Knowledge should be kept up to date
with changes in law, technology and safe working practice.
TE
It is a statutory requirement in Great Britain, the Isle of Man, Northern Ireland and
Guernsey (see Table 2) that all “gas work” be carried out by a business or
IN
self-employed person(s) that is a member of a “class of persons” registered with a
registration body which has been approved by an approval body (see Table 2) to
operate and maintain such a register.
PR
At the time of publication, the only body with approval to operate and maintain a
register of individuals/businesses who are “members of a class of persons” is the Gas
Safe Register. Thus, it is essential that all businesses or self-employed gas engineers
are registered with the Gas Safe Register.
EN
The qualifications which persons need to have to be deemed competent to carry out
gas work are given in Table 3.
H
Table 2 Approval bodies and statutory regulations by country/territory
W
Guernsey Health and Safety Executive for the Health and Safety (Gas) (Guernsey)
TR
D
accredited by Ofqual), which is aligned in
matters of gas safety
TE
National/Scottish Vocational Qualification (N/SVQ ✓ ✓ ✘
accredited by Ofqual), which is aligned under the
HSC ACoP arrangement A) as approved with the
IN
registration body
Any other scheme recognized by the gas ✓ ✓ ✓
registration body for registration purposes
PR
A)
Guidance on the individual competence required for gas work is given in IGEM/IG/1: Standards of training in gas
work [16].
EN
5 Design and planning
5.1 Exchange of information and time schedule
H
5.1.1 At the initial stages of building/installation design and planning it shall be
W
verified that the pipework will be adequate for the known requirements.
NOTE Gas pipework design and installation for commercial installations undertaken
ED
in accordance with this British Standard need to account for any requirements
imposed by DSEAR [17], [18]. Additional information can be found in Annex F.
5.1.2 All necessary information regarding the routing of pipework and positions
LL
of valves and termination points to serve the appliances shall be made available
by means of drawings, specifications and consultations, as appropriate.
O
concealed;
b) special requirements of a precautionary nature, e.g. limitations on proximity to
other services or effects of differential movement due to the building
N
construction; and
O
5.1.3 Any pipework installed shall be tested for gas tightness in accordance
with 10.2 before being buried, covered, painted or wrapped.
N
5.2 Sizing
U
5.2.1 When designing an installation, the size of all pipework shall be such that
the gas is at a suitable pressure at the inlet of any gas appliance to ensure that
it meets the required appliance heat input.
Where any sections of the pipework supply gas to multiple appliances, the heat
input of all appliances fed by that section of pipework shall be taken into
account.
NOTE Annex A gives a method for calculating pipe sizes in a system.
5.2.2 The design maximum pressure loss for all pipework shall not exceed that
specified in 5.3.2 or 5.4.2 in the following circumstances:
a) new installations;
b) pipework modification or extension to existing installations;
c) before any new appliance is fitted to a new or existing installation; and
d) increasing any appliance heat input.
NOTE The design pressure loss of existing installations that are not subject to the
modifications listed in b), c) or d) should conform to the standard that was
D
applicable at the time of installation, for example previous editions of BS 6891 for
natural gas and BS 5482-1 for LPG.
TE
5.2.3 For range-rated appliances, the installer shall use the maximum heat input
to ensure the pipework is sized to meet the requirements of 5.2.1 and 5.2.2.
IN
NOTE For combination boilers where the maximum heat input is different for the
hot water and heating modes, the higher of the two heat inputs should be used.
PR
5.2.4 For variable-rated appliances, the installer shall establish the heat input
necessary to meet the requirements of the system and shall use this value to
ensure the pipework is sized to meet the requirements of 5.2.1 and 5.2.2.
EN
NOTE For combination boilers where the maximum heat input is different for the
hot water and heating modes, the higher of the two heat inputs should be used.
5.3.2 Pipework
LL
The design pressure loss between the outlet of the primary meter installation
and the point to be connected on any appliance inlet shall not exceed 1 mbar at
O
installation
The storage vessel(s), service pipework, regulators, meter (where applicable) and
C
installation.
NOTE Further information on meter installations is given in BS 6400-3. Further
U
Figure 5 Sizing pipework – Design maximum pressure loss for typical installations
D
TE
b) Typical LPG installation incorporating a meter
IN
PR
EN
c) Typical LPG cylinder installation incorporating an automatic changeover device and ECV
H
W
ED
LL
d) Typical LPG bulk storage vessel installation with low pressure service pipework
O
TR
N
O
C
e) Typical LPG bulk storage vessel installation with medium pressure service pipework
Key
N
5.4.2 Pipework
The design pressure loss between the outlet of the primary meter installation, or
where no meter is installed, the outlet of the ECV or the outlet of the final
stage regulator when fitted after the ECV and the point to be connected on any
appliance inlet shall not exceed 2 mbar at the design installation flow rate
(see 5.2.3 and 5.2.4).
NOTE See Figure 5 for illustrative examples. For LPG/air installations the typical
operating pressure loss allowed for in the design calculations is 2 mbar.
D
Where it is not possible to purge through an appliance with an open burner,
TE
purge points shall be provided to enable the installation to be adequately
purged (see IGEM/UP/1 series of standards [21], [22], [23]).
IN
6 Materials and components
PR
COMMENTARY ON CLAUSE 6
When selecting materials for use as pipework, consideration should be given to
strength, appearance and the need for protection against corrosion. The Gas Safety
(Installation and Use) Regulations 1998 [1] prohibit the installation of lead or lead
EN
alloy pipes supplying gas. However, historically, lead pipes were used to install gas
meters, and lead alloy pipes (known as lead composition pipes) were installed as
pipework and can still be found in old housing stock. Provided this material is in
H
good condition, sound, well-supported and of adequate size, connection can be
made to steel or copper pipework using appropriate fittings (see Clause 7).
W
6.1 General
Materials used for pipework and fittings shall conform to 6.2, 6.3, 6.4,
ED
6.2 Steel
LL
• BS EN 10217-2; or
TR
• BS EN 10255.
• BS 6362;
O
• BS EN 10216-5;
•
C
BS EN 10217-7; or
• BS EN 10312.
N
• BS 7838; or
• BS EN 15266.
6.4 Copper
6.4.1 Copper tube shall conform to:
• BS EN 1057; or
D
• BS EN 13349.
TE
6.4.2 Capillary and mechanical fittings shall conform to:
• BS EN 1254-1;
IN
• BS EN 1254-2;
PR
• BS EN 1254-4; or
• BS EN 1254-5.
6.4.3 Copper and copper alloy press end connections shall conform to BS 8537,
EN
Type 2.
NOTE Sometimes referred to as “press-fit fittings”.
COMMENTARY ON 6.4
H
Brazed joints should be made in accordance with BS EN 14324, using BS EN 1044
W
filler metals.
Soft solder should conform to BS EN 29453.
ED
Sulfidation of the gas supplies can be a problem in some areas of the United
Kingdom. See Annex B for further information.
6.5 Polyethylene
LL
• BS EN 1555-1; or
• BS EN 1555-2,
TR
as appropriate.
• BS 5114; or
O
• BS EN 1555-3,
C
as appropriate.
N
NOTE Fibrous materials such as hemp conforming to BS 4371 should be used with
the appropriate jointing compound (see 7.6).
6.7 Valves
6.7.1 Valves shall conform, as appropriate, to:
• BS 1552; or
• BS EN 331; or
• PRS1/E [24]; or
D
• GIS/V7-3 [25].
TE
6.7.2 Lubricants used in valves shall be of a type suitable for use with the gas.
IN
6.8 Self-sealing sockets
PR
Only self-sealing sockets conforming to BS 669-1, BS 669-2 or BS EN 15069, as
appropriate, shall be used for gas installations. These shall be installed in
accordance with BS 6172 or BS 7624.
• BS 3212; or
EN
6.9.1 LPG hoses, tubing and assemblies shall conform to:
H
• BS 6501-1; or
W
• BS EN 16436-1; or
• BS EN ISO 10380.
ED
6.9.2 LPG hoses and tubing connections (including nozzles and adaptors) shall
conform to:
LL
• BS 3212; or
• BS EN 16129.
O
6.9.3 Natural gas hoses, tubing and assemblies shall conform to:
TR
• BS 6501-1; or
• BS EN ISO 10380.
N
7 Jointing
O
7.1 General
C
7.1.1 All joints shall be made in such a manner as to avoid undue stress on the
N
fitting.
U
7.1.2 All pipework ends shall be square-cut and deburred, as appropriate, and
finished joints shall be visually examined for defects.
7.2.2 Any flux selected for use shall only remain active during the heating
process. All flux residues shall be wiped from the pipework and fittings when
the joint has cooled.
D
purpose-made tools that form the pipework ends in accordance with BS EN 1254-1
or BS EN 1254-5.
TE
7.3 Mechanical joints
7.3.1 Any mechanical joint shall be located in a readily accessible position that
IN
allows the fitting to be tightened to make a gas-tight joint.
PR
7.3.2 Union joints shall be of the ground-faced or compression type.
EN
manufacturer’s instructions.
7.4.2 The installer shall instruct the gas consumer/responsible person to ensure
H
that the fittings are not painted with oil or solvent-based paints unless
otherwise specified in the manufacturer’s instructions.
W
NOTE The yellow colour of the bodies of press end connections should remain
visible after installation.
ED
• BS 21;
• BS 864-2;
• BS EN 1254-4;
N
• BS EN 10226-1;
O
• BS EN ISO 228-1; or
C
• ISO 7-1.
N
7.6.2 All threads shall be cleaned prior to the application of any jointing
material.
U
7.6.3 Fibrous materials such as hemp shall not be used on any threaded joint,
except in conjunction with jointing compounds for existing long screw back-nut
seals.
COMMENTARY ON 7.6
When jointing compounds are used they should only be applied to the external
threads, and any excess paste should be removed on completion of the joint.
Jointing compound should not be used in conjunction with
polytetrafluoroethylene (PTFE) materials.
It is important that any cutting oil residue is removed from the inside and outside of
the pipework.
D
When lead composition pipework is encountered and any connection joint has
to be made, then only a soldered cup joint onto copper pipework or a suitable
TE
brass union fitting shall be made. Compression fittings designed for jointing
water weight lead pipework shall not be used.
Electrofusion joints
IN
7.8
Relevant information shall be obtained from the manufacturer of the PE
PR
pipe/fittings.
NOTE Solvent welding is not acceptable (see 8.15).
EN
8 Installation
8.1 General
H
8.1.1 Where pipework is liable to mechanical damage, it shall be physically
W
protected. While installation work is in progress, precautions shall be taken to
prevent the ingress of dirt, water, etc., into pipework.
8.1.2 The bore of any pipework shall not be restricted by kinks, burrs, foreign
ED
8.1.3 Pipework shall be installed so as not to impair the structural stability, fire
LL
8.1.4 Pipework shall be situated such that, in the event of a gas escape, gas is
O
requirement to gain access to the pipe in the future, this could affect the
structural stability of the building.
N
8.1.6 For LPG installations, pipework entries to, and exits from, buildings shall
always be above ground.
O
8.1.8 Pipework and fittings that are considered to be at risk of corrosion and
degradation shall either be manufactured from materials that are inherently
U
D
8.1.12 Assembled pipework shall be tested for gas tightness in accordance
TE
with 10.2 before any additional protection against corrosion and degradation is
applied on site.
COMMENTARY ON 8.1.7 TO 8.1.12
IN
Factory-finished protected pipe should be used wherever practicable.
Factory-finished protection can take the form of pre-insulation coatings, coverings,
PR
sheathings, wrapping, dipping, galvanizing or painting.
Where possible, pre-insulation coatings, coverings, sheathings and wrapping should
be coloured yellow ochre in accordance with BS 1710:1984, O8 C 35.
EN
Where it is not practicable to use or obtain factory-finished protected pipe,
protection should be applied on site and in accordance with manufacturer’s
instructions where applicable. Where wrapping tape is to be used, the pipework
should be clean, dry and applied in accordance with the tape manufacturer’s
H
instructions. A minimum 55% overlap should be used to provide a layer of at least
double thickness.
W
Care should be taken to avoid damaging protective coatings during storage, when
bending and when installing.
ED
Some pre-insulation coatings, coverings, sheathings and wrapping tapes suffer from
colour fade and surface cracking due to the effects of ozone or when exposed to
O
direct sunlight or other ultra-violet (UV) sources. Therefore, care should be taken to
ensure a suitable material is selected.
C
Potentially corrosive environments also include coastal areas. Soot and debris in
N
Copper pipework with soft-soldered capillary joints should not be located where it is
liable to be subjected to temperatures in excess of 100 °C.
D
NOTE The use of a non-contact voltage detector (single pole) capable of indicating
voltages of 50 V or greater (see Figure 6 for an example) on all exposed metalwork
TE
in the work area assists in the detection of stray voltage that might be harmful. It
should be noted that such voltage detectors are not designed to respond to current
flow and should be used in accordance with the manufacturers’ instructions. Where
any doubt about the electrical installation exists, the advice of a competent
IN
electrician should be sought.
PR
Figure 6 Non-contact voltage detector (single pole) – Example
EN
H
W
ED
8.3.4 During any work that necessitates removal of a meter, breaking into the
gas supply, or connection or disconnection of any metal pipework, a temporary
O
continuity bond shall be fixed securely to the pipework either side of any
intended connection or disconnection point or between the pipework and any
TR
COMMENTARY ON 8.3.4
O
have a cross-sectional area of not less than 10 mm2 and be of multi-strand flexible
construction, generally in accordance with BS 6004, BS 6007 or BS 6231, and with a
N
a) Isolate the electrical connection of associated gas appliances from the electricity
supply.
b) Clip or clamp a temporary continuity bond to each side of the union, fittings or
complete section to be removed or connected, ensuring that good, secure,
metallic contact is made (see Figure 7).
c) Leave the bond in position until after the work is completed and metallic
continuity re-established. Where pipework is to be removed, ensure that both
sections of pipework left are bonded before removing the temporary electrical
continuity bonding conductors.
D
TE
IN
PR
a) At pipe
EN
H
W
ED
LL
b) At meter
Key
O
and constituting a danger (for example, when using a blowlamp) the following
precautions shall be taken.
C
to isolate the gas supply. Where a leak or let-by is found, rectify this before
proceeding.
b) Disconnect the gas supply to the installation or section of the installation.
c) Remove any meter, where fitted in the section to be worked upon, from the
installation or section of the installation.
d) Immediately seal all exposed gas ways, for example open ends on the
pipework and/or meter, with an appropriate fitting.
D
operative may choose to purge the installation of any gas. Additional guidance on
purging installations of any gas (decommissioning) can be found in IGEM/UP/1 [21],
TE
IGEM/UP/1A [22] and IGEM/UP/1B [23].
It is difficult to specify an exact set of parameters that indicate when an installation
will or will not need to be decommissioned prior to working on it due to the
IN
diversity of installations that might be encountered.
8.3.6 All open ends of the pipework shall be sealed with an appropriate fitting
PR
before any work is left unattended.
8.3.7 Where work is in progress on the pipework that exposes the gas ways, for
example open ends on the pipework, sources of ignition shall be kept away
EN
from the exposed gas ways.
8.3.8 When work has been completed, the open ends of pipework shall be
sealed with an appropriate fitting that will facilitate purging the installation, for
H
example suitably plugged or capped.
W
8.4.1 General
U
8.4.1.1 Pipework shall be located or electrically insulated such that it does not
touch metallic fitments that could promote electrolytic corrosion.
8.4.1.3 Pipework shall not be buried in floors together with electrical underfloor
heating, unless the underfloor heating has been physically and permanently
disconnected.
D
equipment, main service cut-outs or supplier (main) isolation switches, and
distribution boards or consumer units; or
TE
b) at least 25 mm away from electrical switches, sockets and electricity supply
and distribution cables.
IN
8.4.2.2 The installation pipework shall not be positioned in a manner that
prevents the operation of any electrical accessory, i.e. a switch or socket outlet.
PR
NOTE Where these spacing requirements are impracticable the pipework should
either be sheathed with an electrical insulating material rated at 230 V ac or more,
or a panel of electrical insulating material should be interposed.
EN
8.4.3.1 A gas installation within a property with an electrical supply shall have a
main protective bonding conductor connecting the pipework to the electrical
H
installation’s main earth terminal, as specified in BS 7671.
W
COMMENTARY ON 8.4.3.1
The purpose of protective bonding is to create a zone in which voltage differences
through differing earth potentials are eliminated, and therefore hazards from
ED
and
N
For internal meters, for verification purposes the bonding connection should be
within 600 mm of the meter outlet union.
For meters in outside meter boxes/compartments, the bonding connection should
preferably be inside the premises and within 600 mm of the point of entry of the
pipework into the premises.
Alternatively, the connection can be made within the box/compartment, but it is
essential that the bonding cable does not interfere with the integrity of the
box/compartment and the sealing of any sleeve (see Figure 8).
For guidance on equipotential bonding in multi-dwelling buildings see
D
IGEM/GM/5 [26].
When relocating a meter, an existing main protective bond conductor might be
TE
satisfactory as found, or it might need to be altered. Where the bonding conductor
requires altering, any alterations should be carried out by an electrically competent
person, and inspected and tested in accordance with BS 7671. The bonding
IN
connection may be considered satisfactory if the requirements of 8.4.3.1 are met.
Further guidance on the connection to installations containing pliable corrugated
PR
(stainless-steel) tube can be obtained from the product manufacturer.
Dimensions in millimetres
EN
H
W
ED
LL
O
TR
NOTE For medium-pressure fed meter installations the main protective bonding conductor should only exit the
box as detailed in BS 6400-2 and BS 6400-3.
U
8.4.3.3 When new pipework is installed, the installer of the pipework shall,
where they are competent to do so, carry out the installation of any necessary
bonding at the time of the installation.
COMMENTARY ON 8.4.3.3
Regulation 18(2) of the Gas Safety (Installation and Use) Regulations 1998 [1]
requires that any person who connects any installation pipework to a primary meter,
in any case where equipotential bonding might be necessary, has to inform the
responsible person for the premises that such bonding should be carried out by a
competent person.
A typical form of notification is a letter or card, an example of which is given in
Figure 9.
On existing installations where a main protective bonding conductor might be
D
necessary, the operative should pass such notification to the responsible person.
Figure 9 Typical notification where main protective bonding conductor is found not to be
TE
present
IN
Most electrical installations are required to be fitted with a main protective
bonding conductor, which consists of the electrical connection of the internal
PR
gas and water pipes to the installation’s main earthing terminal in accordance
with the requirements of BS 7671, Requirements for electrical installations
(IET Wiring Regulations).
The gas installation pipework fitted in your premises does not appear to have
EN
the necessary main protective bonding conductor.
I am required by The Gas Safety (Installation and Use) Regulations 1998 to tell
you that any necessary main protective equipotential bonding should be
H
carried out by a competent person.
W
I advise you to have this checked by a competent electrical operative.
If you are the tenant of this property, please bring this matter to the
attention of the owner or their agent as soon as possible.
ED
natural potential in the walls, thereby altering the mechanics of water flow.
O
Perforation of metallic pipework can occur whenever it is in contact with the fabric
of the building below the level of the titanium wire, i.e. where a conductive path
C
was provided between the two materials by the moisture in the wall. The copper
pipework might corrode preferentially because titanium is the more “noble” (resists
N
chemical action) material and because the induced voltage increases the potential
differences and could produce very rapid corrosion.
U
8.5 Valves
8.5.1 Additional emergency control valves (AECV)
8.5.1.1 An additional emergency control valve (AECV) shall be fitted where the
emergency control valve (ECV) is located remotely from the dwelling/building it
serves (see Figure 10).
D
TE
IN
PR
a) External meter to single dwelling
EN
H
W
ED
LL
O
TR
N
O
C
N
Key
1 Test point A Appliance
2 AECV M Meter
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
Key
1 Test point M Meter
2 AECV
D
e) be securely fitted with a suitable handle or other permanent means of
TE
operation; and
f) where the lever moves in the vertical plane, move to the “off” position in a
downward direction.
IN
8.5.1.3 A permanent notice shall be attached to the valve giving the following
information:
PR
a) advice that the valve is an “emergency control for gas consumers’ use”;
b) details of the parts of the installation isolated by the valve;
EN
c) the telephone number of the National Gas Emergency Call Service or the
LPG supplier Emergency Service, as appropriate; and
d) advice to the gas consumer on actions to be taken if they think they can
H
smell gas.
W
8.5.2 External pipework isolation valves
Where the pipework is taken from inside a building to supply an appliance
situated externally (see Figure 11), a valve shall be installed in an accessible
ED
8.6.1 A pressure test point shall be fitted for the purpose of gas tightness
testing. Where there is no meter installed that includes a test point, a test point
TR
shall be fitted not more than 300 mm downstream of the ECV or any AECV.
NOTE Careful consideration should be given to the positioning of the test point to
allow for ease of tightness testing.
N
8.6.2 Where a suitable test point is not provided with the appliance, a test point
O
NOTE This test point can be incorporated into the appliance isolation valve.
N
8.7 Sleeves
U
D
TE
IN
PR
Key
1 Gas supply to external location 5 EN
Pipe sleeve
H
2 House wall 6 External pipework isolation valve
3 Leisure point 7 Pipework
W
4 Barbecue
defined in 3.38.
Consideration should be given to the selection of the material for a sleeve to ensure
O
8.7.4 Any sleeve shall pass through the full width of the wall or the full
thickness of the floor. The outside of the sleeve shall be secured and sealed at
each end to the structure of the building with a suitable building material,
N
8.7.5 Any sleeve shall not impair the structural stability, fire resistance, or
thermal and sound insulation of a building. The annular space between the
C
pipework and the sleeve shall be sealed at one end to the pipework with a
flexible fire-resistant compound. Where a sleeve passes through an exterior wall,
N
the sealing of the annular space between the pipework and the sleeve shall be
on the inside of the wall. However, for a sleeve that forms part of a
U
low-pressure fed meter installation sited in a meter housing, the seal shall be
inside the housing.
NOTE The internal diameter of any sleeve should allow for an annular space
around the pipework to enable satisfactory insertion and withdrawal of the
pipework and allow adequate sealing between the pipework and the sleeve.
8.7.6 Screwed, quick-release and mechanical joints and press end connections
shall not be located on the pipework within a sleeve.
8.8.2 All pipework supports shall be suitable for the environment in which they
are installed and shall be designed to remain stable for the lifetime of the
installation, e.g. for external use corrosion resistant or UV-stabilized plastic.
8.8.3 Where pipework is installed in protected areas (see 8.19 and Annex D), all
supports shall be fire-resistant, e.g. of metallic construction.
D
8.8.4 The supports used shall be designed to prevent the pipework coming into
TE
contact with surfaces of the structure which are likely to cause corrosion.
NOTE Timber is a notable example of a material with which contact is unlikely to
cause corrosion. Other acceptable types of support include those made from metal
IN
(see BS 1494-1) and plastic materials.
PR
Table 4 Maximum interval between pipework supports
Material Nominal size Interval for vertical run Interval for horizontal run
m m
EN
Steel (rigid) Up to DN 15 (R1⁄2) 2.5 2.0
DN 20 (R3⁄4) 3.0 2.5
DN 25 (R1) 3.0 2.5
H
DN 32 (R11⁄4) 3.3 2.7
W
Copper Up to 15 mm 2.0 1.5
22 mm 2.5 2.0
28 mm 2.5 2.0
ED
35 mm 2.5 2.5
Pliable DN 15 1.2 1.2
corrugated DN 20/22 1.8 1.8
LL
compartment floors)
8.9.1 Where pipework is to be installed in joisted floors and roof spaces it shall
N
run either in the direction of the joists or at 90° to the joist direction. Diagonal
runs of pipework shall not be installed.
O
8.9.3 The flanges of timber-engineered joists and metal web joists shall not be
U
8.9.5 Where pipework is installed at 90° to metal web joists with timber flanges,
the pipework shall pass between the metal webs with pipework supported on
the wooden flanges and not in contact with the metal structure of the joist
D
(see Figure 12).
Where pipework is installed at 90° to metal web joists with metal flanges, the
TE
pipework shall pass between the metal webs with pipework supported in such a
manner that it is not in direct contact with the metal of the joist structure.
IN
NOTE Additional guidance might be available from the joist manufacturer.
8.9.6 Where pipework is laid across solid timber joists fitted with flooring, the
PR
pipework shall be located in purpose-made notches or circular holes. Notches
and holes shall conform to Figure 13.
8.9.7 Solid timber joists with a depth less than 100 mm or greater than 250 mm
EN
shall not be notched, unless this has been confirmed as acceptable by a
structural engineer.
8.9.8 Where pipework is installed within roof spaces, roof rafters, purlins,
H
trussed rafters, bracing, etc., shall only be notched, drilled or cut away with the
approval of a structural engineer.
W
accordance with 8.16.1, Table 6. For LPG and LPG/air mixtures this ventilation
shall be at the lowest point. Alternatively, the gas pipework shall be contained
within a vented duct where it passes through the void.
LL
NOTE Additional guidance on LPG gas installations under the floor of a residential
park home or dwelling manufactured to BS 3632 is given in HSE report RR945 [27].
O
TR
N
O
C
N
U
Figure 12 Notching and drilling of metal web joists and timber-engineered joists
D
TE
IN
PR
EN
H
W
Figure 13 Limits for notching and drilling of solid timber floor joists (1 of 2)
Dimensions in millimetres
D
TE
IN
PR
a) Limits for notching top of joist where drilling and notching occur
EN
H
W
ED
LL
O
b) Alternative limits for notching top of joist where drilling and notching occur
TR
N
O
C
N
U
Figure 13 Limits for notching and drilling of solid timber floor joists (2 of 2)
D
TE
IN
Key
1 Positions within which notching can occur 2 Clear span simply supported joist (not a
PR
on the bottom without a design check. trimmer, trimming joist or beam)
Minimum 100 mm between the notch
and any holes [see Figure 13a)].
NOTE 2 The notching can occur at both ends, either on top or bottom, without a design check.
EN
d) Limits for notching bottom of joist where drilling and notching occur
H
W
ED
LL
NOTE 3 The notching can occur at both ends on the bottom without a design check.
e) Alternative limits for notching: bottom of joist where drilling and notching occur
O
TR
N
O
C
N
Key
1 Drilling zone where no notching occurs
2 Holes not closer than 3 × diameter of largest hole and a maximum of 8 × 30 mm holes can be
accommodated within each drilling zone. No notching is permitted.
D
Where it is necessary during installation or retrofitting to remove a section of floor
boarding or decking, the section should be reinstated to the same standard as that
TE
before removal. Any cut edge of a floor decking should be supported by noggings
fixed between the joists.
IN
Care should be taken when fixing flooring or ceilings to prevent damage to the
pipework by nails or screws. Where possible, the flooring should be appropriately
marked to warn others. Where possible, the design should remove the need for
PR
notching solid timber joists.
Natural gas
For natural gas, research undertaken by Advantica [28] (see Annex C) on behalf of
EN
the Gas Industry Safety Group (GISG) has proved that, where gas pipework is
installed in intermediate floors in dwellings, there is sufficient adventitious
ventilation of the floor construction to safely disperse any minor leakage of gas,
i.e. natural ventilation via cracks/openings in the structure is sufficient to ensure any
H
minor escapes of gas do not present a danger.
W
Therefore, there is no requirement to install purpose-provided ventilation to floors
of this construction in conventional masonry, timber frame or light steel frame
buildings. A summary of the research project and its principal conclusions can be
ED
found in Annex C. The results and conclusions of this report should not be applied
to compartment floors between dwellings, for example in the floors which separate
one flat or apartment from another. The results and conclusions of this report apply
to natural gas installations only and should not, therefore, be applied to installations
LL
8.9.11 Pipework shall not be installed within any fire compartment floor that
O
separates one dwelling from another part of the building, except as shown in
Figure 14 and Figure 15.
TR
at least two ventilators per space, each with a free area of at least 50 cm2. For
LPG and LPG/Air mixtures, this shall be at low level; for natural gas this shall be
C
at high level.
N
8.9.13 Pipework shall not be laid below or within roof space insulation material.
U
D
TE
IN
a) Typical concrete compartment floor with suspended ceiling and topping of timber decking on
PR
battens
EN
H
W
ED
1 Pipework within vented ducting extended above floor level and sealed to floor deck with
flexible sealant
O
board
O
6 Suspended ceiling
7 Pipework with factory-finished protection laid in screed above resilient overlay A)
C
8 Screed
9 Resilient sound-proofing overlay
N
11 Floating floor
A)
Exposed metallic pipework, for example at joints, shall be further protected on site (see 8.1.7 to 8.1.12).
D
TE
IN
PR
EN
a) Typical suspended timber compartment floor
H
W
ED
LL
O
Key
1 Floor decking on battens on resilient bearers/pads
N
2 Pipework within vented ducting extended above floor level and sealed to floor deck with
flexible sealant
O
3 Structural deck
4 Timber joist
C
8.10.2 Pipework shall not be buried in structural elements of the floor, such as
concrete slabs or structural toppings. Pipework shall not be buried in
power-floated floors that form part of the structure.
8.10.3 Pipework in acoustic floors shall only be installed with the agreement of
the building designer.
D
8.10.4 Rigid stainless-steel pipework shall not be buried in floor screeds.
TE
8.10.5 Pipework that is to be buried in a solid floor shall be suitably protected
against corrosion and degradation (see 8.1.7 to 8.1.12). Galvanized or painted
pipework shall not be buried without additional onsite protection being applied
IN
(see 8.1.7 to 8.1.12).
PR
8.10.6 Pipework installed in solid floors shall be protected against failure caused
by movement.
COMMENTARY ON 8.10.6
EN
Pipework installed in solid floors should, where practical, be in one length without
any joints. Where necessary, the use of fittings should be kept to a minimum and,
where aesthetically and practicably acceptable, bends should be used in preference
to elbows.
H
Suitable methods of protection are as follows:
W
and
c) steel or copper pipework fitted with additional soft, non-permeable covering
material. The coverings should be soft and thick enough to provide movement,
LL
yet resilient enough to support the floor screed while it is setting. The covering
should be at least 5 mm thick and resistant to concrete ingress which would
O
corrosion protection.
1) conforms to 6.2.3;
C
D
4) has a factory-applied cover with a minimum thickness of 0.5 mm,
TE
manufactured from a non-chlorinated material of a synthetic polymer
or elastomer with a total chloride content not exceeding 50 ppm; or
c) laid inside a buried outer pipe conforming to 8.7.1 or a covered channel
IN
which terminates either above floor level or with suitable inspection points
which permit periodic inspection.
PR
NOTE Users of this British Standard are advised to consider the desirability of
selecting products for which independent quality assurance certification against the
appropriate product manufacture standard has been obtained.
8.10.9 All buried pipework shall be inspected for damage immediately prior to
EN
the tube being buried in the flooring material. Any damage shall be repaired in
accordance with the manufacturer’s instructions to give at least the same level
of protection that was afforded before the damage.
H
NOTE The inspection should take account of any factory-finished protection or
W
protection applied on site.
8.10.11 Pipework passing vertically through solid floors shall take the shortest
LL
8.10.13 Pipework in solid floors shall be installed in accordance with Figure 16.
TR
N
O
C
N
U
42
Figure 16 Typical examples of pipework installed in solid floors PG
•
U Dimensions in millimetres
N
C
BS 6891:2015
O
N
TR
O
TR
O
LL
ED
W
b) Suspended concrete floor
H
Key
EN
1 Chipboard or floor screed over insulation 4 Precast beam and block
2 Insulation 5 Ventilated void
3 Damp-proof membrane 6 Pipework (corrosion protected as necessary)
PR
IN
TE
43
Gas Safe Register Licensed Subscription Copy
44
Figure 16 Typical examples of pipework installed in solid floors (3 of 3)
•
U Dimensions in millimetres
N
C
BS 6891:2015
O
N
TR
O
Key
ED
1 Pipework laid in insulation layer (corrosion-protected as necessary) 5 Damp-proof membrane
2 Chipboard over insulation 6
W Concrete raft
3 Screed over insulation 7 Pipework with factory-finished protection laid in screed A)
4 Insulation H
A)
Exposed metallic pipework, for example at joints, shall be further protected on site (see 8.1.7 to 8.1.12).
EN
PR
IN
TE
D
BRITISH STANDARD
Gas Safe Register Licensed Subscription Copy BRITISH STANDARD BS 6891:2015
8.11.1.2 Any pipework installed within the building fabric of a wall shall take
the shortest practicable route, horizontally or vertically. Diagonal runs of
pipework shall not be installed.
D
8.11.1.3 Pipework in acoustic walls shall only be installed with the agreement of
TE
the building designer.
IN
corrosion and degradation (see 8.1.7 to 8.12). Galvanized or painted pipework
shall not be buried without additional onsite protection being applied
(see 8.1.7 to 8.12).
PR
8.11.1.5 Pipework installed in walls shall be protected against failure caused by
movement.
EN
8.11.1.6 All pipework shall be inspected for damage immediately prior to the
tube being encased in building material. Any damage shall be repaired in
accordance with the manufacturer’s instructions to give at least the same level
of protection that was afforded before the damage.
H
NOTE The inspection should take account of any factory finished protection or
W
protection applied on site.
Pipework shall not be placed within the cavities of cavity walls. Pipework
passing through a cavity wall shall take the shortest practicable route from one
side to the other and shall be sleeved (see 8.7).
N
8.11.3.2 Where thin wall metal pipework, for example copper and pliable
corrugated (stainless-steel) tubing, is run between battens and within 50 mm of
U
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
Key
1 Pipework set in chase 3 Pipework set into chase in plastered wall
2 Depth of chase Maximum depth of chase: T/6 horizontal; T/3 vertical
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
Key
1 Individual adhesive dabs
2 Continuous adhesive dabs to surround pipework
3 Pipework
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
NOTE The joints between the wall and studs should be sealed with mastic in order to avoid gas tracking around
U
the studs.
c) Brick and block dry lined on battens
Key
1 Timber battens
2 Pipework
3 Steel plate of min. 1 mm thickness
8.11.4.2 Pipework shall be installed such that any fixing cannot penetrate the
pipework, for example plasterboard fixings, screws or shot-fired nails which are
typically up to 50 mm long. This can be achieved by ensuring that the pipework
is installed more than 50 mm from the front face of the plasterboard.
D
If this cannot be achieved, where thin wall metal pipework, for example copper
and pliable corrugated (stainless-steel) tubing, is run within 50 mm of the
TE
decorative face of the plasterboard, it shall be protected suitably against
penetration, for example with a steel plate of minimum thickness 1 mm
(see Figure 18).
IN
8.11.4.3 If it is necessary to drill or notch the bottom plate of the wall frame
and/or the sole plate, as little timber as possible shall be removed, and not more
PR
than one third of the width of the bottom plate or sole plate shall be removed.
8.11.4.4 Where pipework is installed within timber and light steel construction
walls it shall be located in purpose-made holes conforming to Figure 19. Where
EN
holes are to be drilled to permit routing of gas pipework, they shall be as small
as possible but allow for movement. Timber-framed wall studs, rails or noggings
shall not be notched.
H
8.11.4.5 Where horizontal pipework runs are necessary, holes shall be drilled as
near as possible to the centre line of the timber member.
W
8.11.4.6 Any cut, notched or drilled surface of bottom plates or sole plates shall
be treated with an appropriate preservative to maintain the protection
ED
8.11.4.7 Where it is unavoidable to have live electrical cable in the same channel
as the gas pipework, the cable shall be routed and clipped away from the
LL
compartment (party) wall, any pipework shall rise in front of the finished
plasterboard face.
NOTE Further guidance on the fire resistance for separating or compartment walls
N
COMMENTARY ON 8.11.4
U
Figure 18 Typical examples of pipework installed in timber and light steel-framed construction walls
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
NOTE The joints between the studs should be sealed with mastic in order to avoid gas tracking around the
studs.
a) Pipework passing through timber-frame wall
Key
1 Timber stud 5 Pipework
2 Pipework 6 Plasterboard
3 Timber stud blocking piece 7 Steel plate of min. 1 mm thickness
4 Timber stud 8 Vapour barrier
Figure 18 Typical examples of pipework installed in timber and light steel-framed construction walls
D
TE
IN
PR
EN
H
W
NOTE The joints between the studs should be sealed with mastic in order to avoid gas tracking around the
studs.
ED
2 Pipework
3 Steel plate of min. 1 mm thickness
O
TR
N
O
C
N
U
Figure 18 Typical examples of pipework installed in timber and light steel-framed construction walls
Dimensions in millimetres
D
TE
IN
PR
EN
H
W
ED
NOTE Pipework to be located in a channel formed by timber studs of the same depth as the timber frame [the
LL
principles for which are shown in Figure 18a) and b)]. Timber studs should be sealed with mastic.
c) Pipework entering a timber-framed/light steel-framed building from a meter box
O
Key
TR
of min. 1 mm thickness as necessary) 13 Pipework from meter notched through sole plate
C
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
Key
1 Allowable zones for drilling. Maximum 2 Notching NOT acceptable in wall studding
diameter of hole = T × 0.25
D
NOTE Where copper pipework is exposed to external weather conditions, it does
not normally require further protection unless subjected to an additional corrosive
TE
source.
IN
8.13.1 Buried external pipework shall be inherently resistant to, or otherwise
adequately protected against, corrosion and degradation (see 8.1.7 to 8.1.12).
PR
Steel tubes conforming to 6.2.1 and 6.2.2 shall not be buried.
8.13.2 When routing pipework, consideration shall be given to the soil type in
which it is to be laid and its likely corrosion impact over time.
EN
8.13.3 Whatever material is chosen, the design shall make allowance for any
additional loading or constraint imposed by backfill or location.
H
8.13.4 Buried metallic pipework (other than proprietary systems intended for
underground use) shall only be installed when appropriate and where:
W
consumer.
to prevent the accumulation of water in the outer pipe or duct, while still
U
8.13.6 Exposed metallic pipe, for example at joints, shall be further protected on
site (see 8.1.7 to 8.1.12).
8.13.7 All buried pipework shall be inspected for damage immediately prior to
backfilling. Any damage shall be repaired in accordance with the manufacturer’s
instructions to give at least the same level of protection that was afforded
before the damage.
NOTE The inspection should take account of any factory-finished protection or
protection applied on site.
8.13.9 Unless of a type specifically designed for direct burial, mechanical joints
D
shall not be directly buried below ground. Press end connections shall not be
TE
directly buried below ground.
8.13.10 Unless of a type specifically designed for direct burial, mechanical joints
in underground pipework shall be readily accessible for inspection, e.g. in an
IN
appropriate inspection chamber. Press end connections shall not be installed in
underground pipework.
PR
8.13.11 Routes shall be chosen that minimize the length of pipework required
and create minimal disturbance of other underground services, e.g. existing
pipework or cables.
EN
8.13.12 Pipework shall have a minimum depth of cover as given in Table 5.
specified depth of cover, additional mechanical protection shall be provided above the
pipe, such as burying concrete slabs below ground level at approximately 100 mm
TR
8.13.13 The trench shall be excavated to firm ground at least 75 mm below the
N
8.13.15 The trench can be backfilled prior to tightness testing, but all joints and
connections shall be left exposed until a satisfactory test is completed.
U
8.13.16 The backfill shall be carried out progressively in layers from one end of
the pipework installation and carefully consolidated to provide firm lateral
support between the pipework and the trench.
8.13.17 The backfill at the sides and immediately above the pipework shall be
the same as that used for the bedding. A minimum of 75 mm of cohesive or
granular material shall be backfilled above the pipework.
8.13.18 The use of wet clay shall be avoided immediately adjacent to the
pipework. Fill such as hard chalk shall not be used as backfill material.
Dimensions in millimetres
D
TE
IN
PR
EN
H
W
Key
1 Minimum spade width (allow wider for 3 Gas marker tape 100 mm to 300 mm above pipe
ED
COMMENTARY ON 8.13
U
External buried pipework should, where practical, be in one length without any
joints. Where necessary, the use of fittings should be kept to a minimum and, where
aesthetically and practicably acceptable, bends should be used in preference to
elbows.
Reference should also be made to:
a) HSG47, Avoiding danger from underground services [31]; and
b) National Joint Utilities Group Guidelines On The Positioning of Utilities
Apparatus For New Development Sites [32].
D
NOTE Where employed, it is preferential for the indicator tapes for polyethylene
pipework to incorporate a metallic core wire to permit the pipework route to be
TE
identified by a suitable instrument.
IN
polyethylene (PE) pipework
PR
NOTE The requirements of this subclause are additional to those of
8.12, 8.13 and 8.14.
8.15.1 PE pipework and fittings shall only be used for external pipework.
EN
8.15.2 PE pipework and fittings shall not be subjected to prolonged exposure to
sunlight or other ultraviolet (UV) sources.
8.15.3 PE pipework and fittings shall not be used above ground, except to rise
H
vertically to allow the transition to metallic pipework, which shall be as close as
practicable to the external ground level.
W
8.15.4 PE pipework and fittings above ground level shall be shrouded from
sunlight and other ultraviolet (UV) sources and mechanical damage. Where PE
ED
pipework and fittings are installed above ground, provision shall be made to
protect the pipe from such sources, for example by enclosing the pipe in a
glass-reinforced plastic sleeve, a steel sleeve or another sleeve manufactured
LL
COMMENTARY ON 8.15
TR
It is preferable to use metal gas pipework entries into buildings. The Gas Safety
(Installation and Use) Regulations [1] require that where PE pipework is used to
C
enter the building, that part of it within the building is placed within a metal sheath
which is constructed and installed so as to prevent, as far as practicable, gas escaping
N
It is essential that care be taken to ensure that pipework designed for carrying water
is not used for gas installations. Also, plastics pipes designed to distribute water in
both domestic hot/cold water and central heating systems, whether or not they
contain a metallic barrier, are not suitable for use for gas installations.
8.16.1.2 Any ventilation opening shall be located such that air movement can
occur within the duct.
D
8.16.1.3 Any ventilation opening shall lead to a safe place, preferably to outside
air.
TE
8.16.1.4 Ducts shall be sealed from any cavity, wall or floor void through which
they pass.
IN
COMMENTARY ON 8.16.1
The duct can run freely through a number of storeys or take the form of an
PR
enclosure at each storey level. Where ducts are continuous, ventilation can normally
be achieved by the provision of openings sized in accordance with Table 6
[see Figure 22a)].
A duct, or an isolated section of duct contained solely within a room or space,
EN
can be ventilated within that room or space, provided the room or space is
ventilated to normal occupational standards.
H
Table 6 Free area of ventilation openings
W
Cross-sectional area Minimum free area of each opening A)
m2 m2
Not exceeding 0.01 0
ED
A)
For vertical shafts and ducts the required openings should be provided at both high
and low level. For horizontal ducts and ceiling voids the required openings should be
provided at either end.
O
Ducts having a small cross-sectional area and volume (i.e. 0.01 m2 or less with a total
volume of less than 0.1 m3) are considered to be adequately ventilated by
adventitious means and no additional openings are required.
N
The level of ventilation is not intended to clear a major gas escape arising from
O
The fire resistance of any duct containing pipework shall have a fire rating equal
U
D
TE
IN
NOTE Cross-sectional area of duct is measured perpendicular to its longest length:
0.075 m × 0.195 m = 0.0146 m2
PR
8.17 Multi-occupancy buildings
Where pipework passes through an individual dwelling/commercial unit other
EN
than the one it supplies, it shall be located in a purpose-provided duct designed
and constructed to prevent damage to the pipework [see Figure 22b)].
NOTE The Building Regulations [5], [6] and [7] also contain provisions for the
H
design and construction of such ducts.
W
8.18 Fire stopping
For buildings containing flats and/or maisonettes, pipework shall be fire-stopped
as it passes from one floor to another, unless it is installed in its own protected
ED
shaft that is ventilated top and bottom to outside air. When pipework from a
protected shaft enters a flat or maisonette, it shall be fire-stopped at the point
of entry [see Figure 22a)].
LL
COMMENTARY ON 8.18
When pipework passes through the protecting structure (i.e. compartment walls or
O
floors) all openings should be kept as small, and as few in number, as practicable,
and should be suitably fire-stopped in such a manner as to allow thermal movement
TR
of the pipework and ensure the fire resistance is not impaired. To prevent
displacement, materials used for fire stopping should be supported by, or reinforced
with, materials of limited combustibility. Any proprietary fire stopping should, when
N
tested in accordance with the applicable part of BS 476, achieve the relevant periods
of fire resistance for the structure in respect of load bearing capacity, integrity and
O
insulation.
C
N
U
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
a) Ventilated duct
Key 1 Ventilation 6 Flat 1 ECV Emergency control valve
2 Appliance 7 Meter room AECV Additional emergency control valve
3 Fire stop 8 Meter room ventilation IIV Inlet isolation valve
4 Flat 3 9 Ground level M Gas meter
5 Flat 2 10 Gas service TP Test point
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
NOTE Vents are to communicate with an area that is ventilated in accordance with the Building
Regulations [5], [6], [7].
D
manufactured to withstand fire test A of BS EN 1775:2007, Annex A.
TE
NOTE See Figure 23. Pliable corrugated (stainless-steel) tubing manufactured to
BS 7838 meets fire test A. For pliable corrugated tubing manufactured to
BS EN 15266 the manufacturer should be consulted.
IN
Figure 23 Copper and steel pipe in a protected area
PR
EN
H
W
ED
LL
O
TR
N
O
C
Key
N
2 Pipe not conforming to 8.19.1, e.g. jointed copper gas installation pipe, within its own fire-rated
duct which is ventilated in accordance with 8.19.
3 Pipe conforming to 8.19.1, e.g. steel pipe with screwed joints.
8.19.2 Other than the exceptions described in 8.19.3 to 8.19.5, a protected area
containing pipework shall be ventilated at high and low levels direct to the
outside air. Sizes of ventilation openings shall be in accordance with Table 6.
Mechanical ventilation shall not be used to achieve the required ventilation
levels.
D
building designer or the local building control body.
Further guidance on protected areas is given in the appropriate Building
TE
Regulations [5], [6], [7] and other applicable building standards.
Subclauses 8.19.1 and 8.19.2 do not normally apply to one or two storey domestic
dwellings.
IN
8.19.3 Pipework within a protected corridor/lobby, including any suspended
PR
ceiling void above the protected area, can be contained within a duct which is
vented to outside air either directly or indirectly via another ventilated area.
Any ducting shall be of fire-resisting construction to the level of the fire
resistance of the protected area it passes through or of an alternative material
EN
with fire stopping where the duct passes through the compartment walls/floors.
or common lobbies.
which does not form part of the required fire/acoustic performance of the
compartment floor can be vented into the corridor via vents inserted through
TR
the ceiling, provided the corridor is ventilated direct to outside air. These vents
shall be sized and installed in accordance with 8.16.1 and Table 6.
8.19.6 If the gas pipework is within a duct and any inspection hatch or door
N
opens from that duct into a protected area, that hatch or door shall be of at
O
least the same fire rating as the protected area in which it is fitted and suitably
sealed on all edges to contain any gas escape within the duct.
C
NOTE The seals to be used should enable the hatch or door to be opened without
compromising the integrity of the seal when the hatch or door is closed.
N
U
8.20.2 Where installing pipework through a vapour control layer (VCL), any hole
cut in the VCL shall be as small as possible to accommodate the pipework/sleeve.
D
Where the VCL is a polythene membrane, the hole in the VCL shall be 10 mm
TE
smaller than the pipework/sleeve so that it makes a tight interference fit
around. Any perforations of the VCL shall be made good with an adhesive tape.
8.20.3 The plasterboard shall be made good with plaster or flexible fire-resistant
IN
compound so that there is no route for air movement into the inner leaf
framework.
PR
8.20.4 When forming channels in previously constructed walls the channel shall
be re-instated so that the insulation, VCL and plasterboard are to the same
standard as the rest of the wall.
EN
8.20.5 Provision shall be made for pipework to accommodate any normal
differential movement or shrinkage of the building, with special attention being
given to buildings of multi-storey construction.
H
COMMENTARY ON 8.20
W
Additional guidance on differential movement or shrinkage in timber-framed and
light steel-framed buildings can be found in IGEM/UP/7 [30] and IGEM/G/5 [34].
A suitable method of accommodating movement for gas pipework passing through
ED
D
TE
IN
PR
a) As installed: before movement of timber
EN
H
W
ED
LL
1 Timber frame
TR
5 Flexible sealant on one end of sleeve only, preferably external side to prevent water ingress
6 Rigid pipe
O
9.1 General
D
9.1.1 Flexible hoses, tubing and associated assemblies shall only be used for:
TE
a) LPG cylinder-mounted regulator connections – the connection between a
cylinder-mounted regulator and the fixed pipework installation; and
b) residential park home and caravan holiday home connections – the
IN
connection between an ECV, AECV, meter or a regulator/changeover device
sited remotely from a residential park home or caravan holiday home on a
PR
standpipe/upstand and the fixed pipework installation.
NOTE For details on the requirements for the installation of high-pressure hoses,
tubing, assemblies and their connections between a cylinder vapour valve and a
regulator/changeover device, see BS 5482-1, BS 5482-2 or UKLPG Code of
EN
Practice 24 [35]. For details on the requirements for the installation of
standpipe/upstands, see IGEM/G/6 [36].
prevent excessive strain on it or its end connections and to allow smooth swept
bends without kinking (see 9.2 and 9.3).
ED
9.1.4 Flexible pipework connections shall not be used if, when inspected, they
show any signs of any physical damage, environmental deterioration or service
LL
failure.
NOTE Examples include:
O
connections;
• environmental deterioration, such as stiffening, cracking, delamination of outer
N
• service failure, such as blistering, soft spots, rupture and, for preassembled end
fittings, corrosion or loosening of swaged fittings attaching hose.
C
9.1.5 Where flexible pipework connections are used, electrical continuity shall be
N
9.1.6 Flexible pipework connections shall not be used where they could be
subjected to temperatures in excess of 50 °C, unless specifically designed for that
application.
9.1.7 Flexible pipework connections shall not pass through walls, floors, ceilings
or other partitions.
Figure 25 Identification of hoses, tubing and assemblies for use with LPG
D
TE
IN
PR
EN
a) Typical BS 3212 hose type identification H
W
ED
LL
O
TR
9.1.9 Flexible tubing conforming to BS EN 16436-1 shall not be used after the
N
COMMENTARY ON 9.1.9
Whilst no expiry date, specific service life or exchange interval is specified for flexible
C
the service life would exceed 10 years, so replacement at this age is recommended.
Requirements relating to expiry date for these class 2 and 3 hoses will be given in
BS EN 16436-2 (when published).
9.1.12 Flexible hose or tubing with an internal diameter of less than 8 mm and
hose operated at a pressure exceeding 50 mbar shall always be secured by crimp
clips or swaged fittings. Worm drive clips shall not be used.
D
For installations other than those specified in 9.3, the length of the flexible
TE
pipework connection between the cylinder regulator and the fixed pipework
shall be limited to a maximum length of 500 mm.
IN
9.3
PR
ECV, AECV, meter or regulator/changeover device and the fixed pipework
installation shall only be made once the residential park home or caravan
holiday home has been fully sited.
EN
9.3.2 Movement of the residential park home or caravan holiday home due to
settlement, thermal expansion, structural flexing or wind loading, and its
potential effects on the gas pipework and attached equipment, shall be
accommodated by installing an appropriate flexible pipework connection with a
H
minimum length 300 mm between any standpipe/upstand installation and the
fixed pipework installation. The length of the flexible pipework connection shall
W
be limited to the minimum possible exceeding 300 mm, with a maximum length
that shall not exceed 2 m (see the exception in 9.3.5).
ED
further than 1 m from, the residential park home and caravan holiday home it
serves. See IGEM/G/6 [36].
O
9.3.3 Flexible pipework connections shall not be used with the intention to
increase the distance of a residential park home or caravan holiday home from
TR
9.3.6 Where the residential park home or caravan holiday home is not
sufficiently anchored, any uncontrolled release of gas caused by movement or
overturning through high winds or flooding shall be limited by including a quick
release, self-sealing coupling with an integral anchored release sleeve.
NOTE The length of pipework and number of fittings between any quick release
coupling and the flexible connection should be minimized. IGEM/UP/2 [12] contains
the detail of an acceptable coupling for this purpose.
10 Commissioning
10.1 General
Where the appliance input is range or variable-rated, the installer shall
permanently mark on the appliance the actual heat input at which the
appliance is to be set.
D
accordance with the appropriate standard.
TE
NOTE For the majority of installations the appropriate standard is IGEM/UP/1B [23],
but alternatively IGEM/UP/1 [21] or IGEM/UP/1A [22], as appropriate, can be utilized.
IN
10.3.1 Natural gas meter installations shall be installed and commissioned in
PR
accordance with BS 6400-1 and BS 6400-2, IGEM/GM/6 [10] or IGE/GM/8 [11], as
appropriate.
EN
10.3.3 On LPG installations that do not incorporate a meter immediately
downstream of the regulator, the regulator shall be installed in accordance with
H
Annex E and commissioned in accordance with a) and b).
NOTE 1 Many LPG regulators and associated safety devices are factory-preset to
W
deliver the required pressures and operate within specific tolerances. They should
not require further adjustment during their service life on site. Adjustments of such
regulators and associated safety devices might affect their safe operation and
ED
flow rate is obtained. Where appliances have already been installed and
commissioned, this can be achieved by operating all appliances at full gas flow
TR
rate. Where no appliances are installed and commissioned, this can be achieved
by using a device that allows a flow rate of at least 0.5 m3/h.
At low flow rates the operating pressure can tend towards the higher values in
N
Table 7 and at high flow rates operating pressure can tend towards the lower
values.
O
b) The installer shall ensure that the regulator locks up at a pressure not
C
exceeding the values given in Table 7, with no flow through the installation.
N
U
D
Butane 28 23 33 +10
TE
Propane 37 32 42 +15
BS 3016 – Final (second) stage regulator
set pressures (low pressure):
IN
Propane 37 32 42 +10
BS 3016 – Cylinder automatic changeover
device set pressures (low pressure):
PR
Propane 37 32 42 +15
BS EN 12864 or BS EN 16129 – Cylinder
single stage regulator set pressures:
EN
Butane 29 22 35 40
Propane 37 27 A) 45 50
BS EN 13785 or BS EN 16129 – Final stage
H
regulator set pressures (low pressure):
Propane 37 32 B) 45 50
W
Butane 29 22 35 40
Propane 37 27 A) 45 50
A)
Value is the minimum outlet pressure specified in the regulator standard to align with BS EN 437. However, it is
LL
recommended that for the UK market the minimum operating pressure for propane regulators is 32 mbar.
B)
Due to the UK-agreed UPSO range the minimum outlet pressure for regulators manufactured for the UK market
is taken as 32 mbar NOT the 27 mbar declared in BS EN 13785 or BS EN 16129.
O
COMMENTARY ON 10.3.4
O
The operational set pressures for the relief valve, the UPSO and the OPSO, are
factory-preset and tested by the manufacturer in accordance with the appropriate
C
10.3.5 If any of the checks or tests in 10.3.4 or 10.3.6 are outside the acceptable
range and/or are unsuccessful:
a) if the regulator and associated safety devices are of a type that can be
adjusted, they shall be adjusted by a person authorized by the LPG supplier
in accordance with manufacturer’s instructions; or
b) if the regulator and associated safety devices are of a type that cannot be
adjusted, the complete regulator and/or associated safety devices shall be
replaced.
COMMENTARY ON 10.3.5
D
Regulation 14(6)(b) of the Gas Safety (Installation and Use) Regulations 1998 [1]
TE
requires that no person except the LPG supplier, or a person authorized to act on
the supplier’s behalf, is to break a seal on a regulator controlling the pressure of gas
from a gas storage vessel.
IN
See also 10.3.3.
10.3.6 The installer shall ensure that the regulator and safety device(s) are sealed
PR
to prevent their settings from being interfered with without the seal being
broken.
EN
When appliances are connected, it shall be confirmed that the pipework is
adequate to ensure that all appliances connected operate at their required heat
input in accordance with the appliance manufacturers’ instructions.
H
COMMENTARY ON 10.4
W
Where there is a concern that there might be an excessive pressure loss, the
operating pressure at the primary meter outlet or, where no meter is fitted, the
regulator outlet should be checked to confirm that this is within acceptable
LL
tolerances. Where a meter is installed, a check should then be carried out to confirm
that the individual appliance(s) heat input is in accordance with the appliance
manufacturer’s specification. Where multiple appliances are installed, this check
O
should be repeated with all appliances in operation to confirm the total of all
appliance heat inputs is achieved. Where no meter is installed on an LPG installation,
TR
In addition to confirming the appliance operating pressure or heat input or, where
O
4)
www.gassaferegister.co.uk [viewed: 28 October 2015].
11 Maintenance
COMMENTARY ON CLAUSE 11
The maintenance of the pipework after commissioning is the duty of the responsible
person.
11.1 The maintenance of pipework, including safety devices, shall ensure the
continued safety of the installation.
D
and sealed at each end with an appropriate fitting.
TE
11.3 Where filters have been installed on the pipework, these shall be
periodically checked and cleaned (see also Annex B).
IN
11.4 Where flexible pipework connections have been installed, they shall be
periodically checked and replaced as necessary (see 9.1.2, 9.1.8 and 9.1.9).
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
D
pipework installation, such as changes in pipework manufacture standards over
the years and the changes to pipework bores, etc., it is impossible to cover every
TE
possible scenario. Therefore, a number of reasonable assumptions have been
made in these tables, which are also provided for information only.
IN
Operatives should obtain accurate pressure loss data from the pipework
manufacturer when undertaking the design process specified by 5.2.
PR
A.2 Theories and other reasonable assumptions utilized in
formulating Tables A.1, A.2, A.3 and A.4
The following formula has been used in calculating the values in Tables A.1, A.2,
EN
A.3 and A.4.
Q 5 57.1×10−5[pd5(sLf)21]0.5 (A.1)
H
where:
W
where:
D
• 38.9 MJ/m3 for natural gas; and
•
TE
93.1 MJ/m3 for LPG.
The ratio of gross:net heat input is approximately 1.11:1 for natural gas,
1.09:1 for propane and 1.08:1 for butane. Whilst the conversion of rated input
IN
between gross and net values strictly depends on the calorific value of gas used,
in practical terms a common factor 1.1 has been used.
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
Table A.1 Approximate natural gas pressure loss data (mbar/m) – copper tube (1 of 4)
0.25 2.70 2.46 0.2675 0.0710 0.0255 0.0077 0.0014 0.0004 0.0001
0.50 5.40 4.91 0.8348 0.2188 0.0777 0.0231 0.0040 0.0011 0.0004
0.75 8.10 7.37 – 0.4285 0.1514 0.0447 0.0077 0.0022 0.0007
1.00 10.81 9.82 – 0.6940 0.2444 0.0719 0.0123 0.0035 0.0011
D
1.25 13.51 12.28 – – 0.3553 0.1042 0.0178 0.0050 0.0016
1.50 16.21 14.73 – – 0.4833 0.1414 0.0240 0.0067 0.0021
TE
1.75 18.91 17.19 – – 0.6276 0.1832 0.0311 0.0086 0.0027
2.00 21.61 19.65 – – 0.7877 0.2296 0.0388 0.0108 0.0034
IN
2.25 24.31 22.10 – – 0.9630 0.2804 0.0473 0.0131 0.0042
2.50 27.01 24.56 – – – 0.3353 0.0565 0.0156 0.0049
2.75 29.72 27.01 – – – 0.3945 0.0663 0.0183 0.0058
PR
3.00 32.42 29.47 – – – 0.4577 0.0769 0.0212 0.0067
3.25 35.12 31.93 – – – 0.5249 0.0880 0.0243 0.0077
3.50 37.82 34.38 – – – 0.5960 0.0998 0.0275 0.0087
EN
3.75 40.52 36.84 – – – 0.6709 0.1123 0.0309 0.0097
4.00 43.22 39.29 – – – 0.7496 0.1253 0.0345 0.0108
4.25 45.92 41.75 – – – 0.8321 0.1390 0.0382 0.0120
H
4.50 48.63 44.20 – – – 0.9182 0.1533 0.0421 0.0132
4.75 51.33 46.66 – – – – 0.1681 0.0462 0.0145
W
Table A.2 Approximate natural gas pressure loss data (mbar/m) – steel tube (2 of 4)
Flow Heat input Nominal pipe size (mm/R) A)
rate Gross Net 8/R1/4 10/R3/8 15/R1/2 20/R3/4 25/R1 32/R11/4
3
(m /h) (kW) (kW) (8.6) (12.1) (15.8) (21.3) (26.9) (35.6)
D
1.25 13.51 12.28 0.8792 0.1777 0.0512 0.0128 0.0043 0.0012
1.50 16.21 14.73 – 0.2414 0.0693 0.0172 0.0058 0.0016
TE
1.75 18.91 17.19 – 0.3130 0.0897 0.0222 0.0075 0.0020
2.00 21.61 19.65 – 0.3924 0.1123 0.0278 0.0094 0.0025
IN
2.25 24.31 22.10 – 0.4793 0.1370 0.0338 0.0114 0.0031
2.50 27.01 24.56 – 0.5735 0.1637 0.0404 0.0136 0.0037
2.75 29.72 27.01 – 0.6748 0.1924 0.0474 0.0159 0.0043
PR
3.00 32.42 29.47 – 0.7831 0.2230 0.0549 0.0184 0.0050
3.25 35.12 31.93 – 0.8982 0.2556 0.0628 0.0210 0.0057
3.50 37.82 34.38 – – 0.2901 0.0712 0.0238 0.0064
EN
3.75 40.52 36.84 – – 0.3264 0.0801 0.0268 0.0072
4.00 43.22 39.29 – – 0.3645 0.0893 0.0299 0.0080
4.25 45.92 41.75 – – 0.4044 0.0991 0.0331 0.0089
H
4.50 48.63 44.20 – – 0.4461 0.1092 0.0364 0.0098
4.75 51.33 46.66 – – 0.4896 0.1198 0.0400 0.0107
W
Table A.3 Approximate LPG (propane) pressure loss data (mbar/m) – copper tube (3 of 4)
0.25 6.47 5.88 0.4413 0.1148 0.0405 0.0119 0.0021 0.0006 0.0002
0.50 12.93 11.76 1.4367 0.3705 0.1298 0.0379 0.0064 0.0018 0.0006
0.75 19.40 17.63 – 0.7421 0.2590 0.0753 0.0127 0.0035 0.0011
1.00 25.86 23.51 – 1.2194 0.4246 0.1231 0.0206 0.0057 0.0018
D
1.25 32.33 29.39 – 1.7959 0.6243 0.1807 0.0302 0.0083 0.0026
1.50 38.79 35.27 – – 0.8565 0.2474 0.0412 0.0113 0.0035
TE
1.75 45.26 41.14 – – 1.1200 0.3231 0.0537 0.0147 0.0046
2.00 51.72 47.02 – – 1.4137 0.4074 0.0676 0.0185 0.0058
IN
2.25 58.19 52.90 – – 1.7369 0.5001 0.0829 0.0227 0.0071
2.50 64.65 58.78 – – – 0.6009 0.0995 0.0272 0.0085
2.75 71.12 64.65 – – – 0.7097 0.1174 0.0320 0.0100
PR
3.00 77.58 70.53 – – – 0.8264 0.1365 0.0372 0.0116
3.25 84.05 76.41 – – – 0.9508 0.1569 0.0428 0.0133
3.50 90.51 82.29 – – – 1.0827 0.1786 0.0486 0.0151
EN
3.75 96.98 88.16 – – – 1.2222 0.2014 0.0548 0.0170
4.00 103.44 94.04 – – – 1.3690 0.2254 0.0613 0.0191
4.25 109.91 99.92 – – – 1.5230 0.2506 0.0682 0.0212
H
4.50 116.38 105.80 – – – 1.6843 0.2770 0.0753 0.0234
4.75 122.84 111.67 – – – 1.8527 0.3045 0.0827 0.0257
W
Table A.4 Approximate LPG (propane) pressure loss data (mbar/m) – steel tube (4 of 4)
Flow Heat input Nominal pipe size (mm/R) A)
rate Gross Net 8/R1/4 10/R3/8 15/R1/2 20/R3/4 25/R1 32/R11/4
3
(m /h) (kW) (kW) (8.6) (12.1) (15.8) (21.3) (26.9) (35.6)
D
1.25 32.33 29.39 1.5558 0.3094 0.0878 0.0215 0.0072 0.0019
1.50 38.79 35.27 – 0.4239 0.1201 0.0294 0.0098 0.0026
TE
1.75 45.26 41.14 – 0.5538 0.1567 0.0382 0.0127 0.0034
2.00 51.72 47.02 – 0.6985 0.1974 0.0481 0.0160 0.0043
IN
2.25 58.19 52.90 – 0.8575 0.2421 0.0589 0.0196 0.0052
2.50 64.65 58.78 – 1.0307 0.2908 0.0707 0.0235 0.0063
2.75 71.12 64.65 – 1.2176 0.3432 0.0834 0.0277 0.0074
PR
3.00 77.58 70.53 – 1.4180 0.3994 0.0970 0.0321 0.0086
3.25 84.05 76.41 – 1.6317 0.4594 0.1114 0.0369 0.0098
3.50 90.51 82.29 – 1.8584 0.5229 0.1267 0.0420 0.0112
EN
3.75 96.98 88.16 – – 0.5900 0.1429 0.0473 0.0126
4.00 103.44 94.04 – – 0.6606 0.1599 0.0529 0.0140
4.25 109.91 99.92 – – 0.7347 0.1778 0.0588 0.0156
H
4.50 116.38 105.80 – – 0.8123 0.1965 0.0649 0.0172
4.75 122.84 111.67 – – 0.8933 0.2159 0.0713 0.0189
W
Bends Fittings
Steel Copper 45° 90° 90° Tee A) Tee A)
elbow (flow entering (flow exiting into
from a branch) a branch)
D
≤15 mm ≤R1⁄2 ≤15 mm 0.15 0.20 0.40 0.75 1.20
20 mm R ⁄4
3 22 mm 0.20 0.30 0.60 1.20 1.80
TE
25 mm R1 28 mm 0.25 0.40 0.80 1.50 2.30
32 mm R11⁄4 35 mm 0.30 0.50 1.00 2.00 3.00
A)
Use the largest connection size on the fitting that is not necessarily the branch size.
IN
NOTE For pressure losses associated with press end fittings, pliable corrugated (stainless-steel) tubing fittings,
flexible connections, secondary meters, check valves, regulators, etc., reference needs to be made to the
PR
manufacturer’s data.
EN
Figure A.1 gives an example of a typical natural gas copper tube installation
showing the lengths of pipework and the heat input of the appliances. The
pipework has been sized using Table A.1 and Table A.5. The results of the design
exercise are shown in Table A.6.
H
Figure A.1 – Example natural gas installation
W
ED
LL
O
TR
N
O
C
Key
N
80
Table A.6 Sizing results
•
Pipework
U
Maximum heat Maximum Estimated Pipe
Fittings allowance B)
Adjusted Pressure Pressure loss C)
section input A)
N flow rate A) pipe size length Equivalent length loss/metre
Type
length
kW m3/h mm/DN m m m mbar/m mbar
C
BS 6891:2015
O Elbow × 1 0.80
A–B 50 (net) – 28 1 Tee 3.3 0.0548 0.19
1.50
N (Enter) × 1
90°
B–C 5 (net) – 15 1 0.40 1.4 0.0447 0.07
Bend × 2
B–D 45 (net) – 28 3 N/A 0 3.0 0.0462 0.14
TR
Tee
2.30
(Exit) × 1
D–E 30 (net) – 22
O 1
Elbow × 1 0.60
3.9 0.0880 0.35
D
of the pipework installation. Where the exact heat input/flow rate is not
TE
documented, the next heat input/flow rate upwards should be utilized.
When the design pressure loss for each section of this pipework installation has
been calculated, the total pressure loss between the meter outlet and the point
IN
to be connected on each appliance inlet should be determined. The total
pressure loss at each point to be connected on each appliance inlet should not
in this example exceed 1 mbar.
PR
If the design pressure loss at any of the appliance inlets exceeds the maximum
allowed, in this case 1 mbar, then it is necessary to re-estimate the proposed
pipework size(s) for one or more of the sections that supply any affected
EN
appliance(s). The design process should then be repeated for all of the sections
affected by the revision to the proposed pipework size, and the results
re-evaluated. This process should be repeated until the design pressure loss at all
of the appliance inlets does not exceed the maximum allowed.
H
W
hydrogensulfide (H2S) in gas and domestic copper pipework. The thin, shiny,
black flakes of copper sulfide (Cu2S) break off to be carried along the pipework
and into gas appliances, where they accumulate in valves, filters and injectors.
LL
In some gas installations, sulfidation forms a black film on the inner surface of
copper gas supply pipework. The thickness of the coating depends on the
amount of H2S in the gas and the thicker the coating, the less stable it becomes,
O
often flaking off and breaking down to form black dust. The maximum amount
of H2S concentration permitted in gas throughout the United Kingdom (UK) is
TR
appearance of small platelets with a metallic sheen. The platelets are quite
brittle and easily break down to become dust, particularly in a fast moving gas
O
stream, where it builds up in and blocks gas valves, filters and injectors. This can
result in gas valves failing to operate and reductions in appliance performance.
C
In some extreme cases the build-up can completely block the gas pipework.
N
D
NOTE The results and conclusions of this report apply to natural gas installations
only and should not, therefore, be applied to installations supplied with LPG or
TE
LPG/air gas mixtures.
C.1 Introduction
IN
Regulation 19(6) of the Gas Safety (Installation and Use) Regulations [1] requires
adequate ventilation to be present when pipework is located within voids,
PR
shafts and ducts.
With the general use of board materials (chipboard, oriented strand board,
plywood) as the decking there was concern regarding the level of potential gas
EN
build-up within the voids between joists of intermediate floors associated with
minor gas leaks.
advised that minor gas leakage is “that which would remain undetected by
normal soundness testing techniques” and further “the level of ventilation
is not intended to clear a major gas escape arising from damage or failure
N
of a gas pipe.”
O
d) IGE/UP/1 [39], IGE/UP/1A [40] and IGEM/UP/1B [38] explained that, “A gas
tightness test is a test undertaken to ensure that the leakage rate of an
C
e) IGEM/UP/1B [38] allowed a pressure drop for a domestic gas installation with
U
D
Industry Safety Group (GISG), to make gas concentration measurements within,
above and below this representative 3 m2 floor cassette with typical openings
TE
for plumbing and electrical services. The tests were performed using a fixed
orifice opening and a range of gas supply pressures to vary the gas leak rate.
IN
C.4 Conclusions
The experimental study reached the following conclusions.
PR
a) In the event of a gas leak from pipework in the floor void, a modern floor
construction allows passage of gas across joists and the voids created as a
consequence of the installation of electrical and plumbing services.
EN
b) The profiles for gas build-up and decay within the floor compartments and
the upper and lower volumes (constructed to represent habitable spaces
above and below the floor void) were consistent with theoretical
H
approaches.
c) Adding floor covering above the floor and painting the ceiling under the
W
floor alters the characteristics of the gas concentration build-up within the
floor. The more sealed nature of the test results in higher gas concentrations
within the floor assembly.
ED
d) The trends in gas concentration across the test floor were always in the
order F1 > F2 > F3, F4 and F5. This was expected as the gas leak was in
compartment F1 and F2 is the next compartment in the sequence.
LL
allow transfer of air and gas from one compartment into adjacent
compartments. These compartments were assigned designations F1, F2, F3,
TR
plumbing and electrical services penetrating into the floor void. Increased
ventilation and leakage were thus possible from these three compartments.
O
However, in the most sealed floor condition F3 was greater that F4 and F5.
C
f) Measured gas concentrations in the upper (i.e. above the test floor) and
lower (i.e. below the test floor) polythene shrouded volumes were typically
N
lower than those in the floor cassette assembly, reflecting the increased
volume of the enclosure and potentially increased ventilation rates through
U
the tape sealed joints. The measured values were often around the
threshold levels for odorant detection.
NOTE 2 The polythene shrouded volumes above and below the test floor were
to simulate the location of the floor within a home.
g) The measured gas concentration in the lower volume was greater than the
upper for all test cases except where the floor had the saw-cut and skirting
added.
h) For a gas leak rate of 19mL/min the build-up of gas within the test floor did
not produce a gas concentration greater than 2.5% gas in air, irrespective of
floor condition, i.e. the degree of ventilation of the floor void.
i) As anticipated, for gas leakage rates considerably in excess of
(e.g. 30 mL/min) a minor gas leak, the build-up of gas within the test floor
did produce increased gas in air concentrations within the floor void. These
concentrations were also affected by the degree of ventilation of the floor
void.
A copy of the full report may be obtained from Advantica, Ashby Road,
Loughborough, Leicestershire LE11 3GR; Telephone 01509 282000;
Facsimile 01509 283131, quoting Advantica Report Number 6699 “GAS PIPES IN
D
INTERMEDIATE FLOORS”. Any questions on the research project and its
TE
conclusions should be addressed to Advantica.
IN
(informative)
For the purposes of this standard the term “protected area” is used in relation
to fire safety, and is a ventilated space containing gas pipework and isolated
PR
from other parts of the building within fire-resisting construction.
NOTE Fire resistance is the ability of a component or construction of a building to
satisfy for a stated period of time some or all of the appropriate criteria specified in
EN
the relevant part of BS 476.
The Building Regulations (England and Wales) 2010, as amended [5], the Scottish
Building Standards Technical Handbook 2 [41] and Northern Ireland Technical
H
Booklet E [42] provide the following definitions in relation to fire protected
areas.
W
England
a) Protected corridor/lobby. A corridor or lobby which is adequately protected
ED
height above ground level, the availability of escape windows and its fire
separation from the common stair from which it is accessed, there might be a
TR
need under the Building Regulations [5], [6], [7] to provide a protected entrance
hall/landing within the flat. In such cases the doors and walls between the
entrance hall/landing and the rooms that it serves (normally excluding
bathrooms and WCs) would need to be fire resisting. In most circumstances this
N
could be achieved with FD20 fire doors and 30-minute fire-resisting partitions.
O
maintain the required fire protection. The building control body should be
consulted for further advice.
U
Scotland
a) Compartment. A part of a building (which might contain one or more
rooms, spaces or storeys and includes, where relevant, the space above the
top storey of the compartment) constructed so as to prevent the spread of
fire to or from another part of the same building, and “compartmented”
and “compartmentation” should be construed accordingly.
b) Compartment wall. A wall with the fire resistance required to ensure
compartmentation.
c) Compartment floor. A floor with the fire resistance required to ensure
D
compartmentation.
TE
d) Protected enclosure in a dwelling means a circulation area constructed to
resist fire in adjoining accommodation. It includes a hall, landing or private
stair or ramp but not a room.
IN
e) Protected lobby. A lobby within a protected zone but separated from the
remainder of the protected zone so as to resist the movement of smoke
from the adjoining accommodation to the remainder of the protected zone.
PR
f) Protected zone. That part of an escape route which is within a building, but
not within a room, and to which access is only by way of a protected door
and from which there is an exit directly to a place of safety.
Annex E
(normative) EN
LPG Final stage regulator and safety devices
H
E.1 General
W
COMMENTARY ON E.1.1
The purpose of the OPSO and limited relief valve is to prevent the installation
TR
pipework and gas fittings downstream of the regulator from being subjected to a
pressure greater than that for which they were designed, for example if the
regulator fails.
N
The regulator design capacity is the rated capacity of the regulator declared by the
manufacturer.
O
When specifying a regulator it is necessary to confirm that the limited relief valve
C
has a maximum capacity of not greater than 5% of the regulator design capacity.
N
The purpose of the UPSO is to prevent the installation pipework and gas fittings
downstream of the regulator from being subjected to a pressure less than that for
U
which they were designed, protecting the installation if the gas supply pressure falls
to a dangerously low level, for example because the LPG storage vessel has become
empty.
E.1.2 Pressure regulators shall be installed in accordance with the regulator
manufacturer’s instructions.
E.1.3 The design of the installation shall ensure a nominal operating pressure at
the outlet of the final stage regulator is in accordance with Table E.1.
E.1.4 The regulator and safety devices shall be preset to conform to Table E.1.
86
Table E.1 Pressure characteristics of various regulators (LPG)
•
Fuel
U Nominal
outlet
Minimum
outlet
Maximum
outlet
Maximum lock-up
pressure
Relief valve
operating
UPSO
operating
OPSO
operating
N pressure pressure pressure (above set pressure) range range range
C mbar mbar mbar mbar mbar A) mbar mbar A)
BS 6891:2015
E.2 Location
E.2.1 Regulators and automatic changeover devices shall not be sited:
a) in close proximity to any source of heat or where they might be subjected
to extremes of temperature;
b) where they might be exposed to accidental damage;
c) where they might cause an obstruction;
d) where they might be affected by a corrosive atmosphere;
D
e) where they will constitute a danger to any person;
f) any nearer to electrical wiring, switchgear, etc., than the distances specified
TE
in 8.4.2;
g) in a basement or cellar; or
IN
h) at such a low level that there is a significant risk of them being submerged
in the event of flooding.
PR
E.2.2 Regulators incorporating a limited relief valve shall not be sited in a
covered passageway or car port except where the passageway or car port has at
least two open and unobstructed sides to ensure the area is ventilated.
EN
E.2.3 Regulators and automatic changeover devices connected to cylinders shall
be located so that the inlet to the regulator is at or above the level of the
cylinder outlet valve connection. They shall not be sited in a covered passageway
or car port.
H
E.2.4 Where there is a regulator downstream of an ECV/AECV, the inlet of the
W
regulator and its safety devices shall be connected as near as practicable to the
outlet of that ECV/AECV.
E.2.5 The regulator and limited relief valve vent tip shall be located away from
ED
any source of ignition, and in a location and manner not subject to fouling,
blockage, water ingress or interference by unauthorized persons.
E.2.6 Diaphragm vent holes and limited relief valves in regulators shall be
LL
E.2.7 Regulators incorporating a limited relief valve shall not be located within a
building.
TR
E.2.8 Regulators incorporating a limited relief valve shall be located so that the
limited relief valve vent is terminated in accordance with Table E.2.
N
order to terminate in a safe location in accordance with Table E.2. The tip of any
vent pipe shall be securely fixed so it protrudes out of the enclosure by at
C
NOTE Where the minimum clearances from a limited relief valve tip that is integral
to the regulator cannot be achieved, the limited relief can be piped in order to
U
Table E.2 Minimum proximity distances for relief valve vent tips (millimetres)
Semi-concealed Meter housing other Meter housing to Vent tip to Vent tip to electrical
meter box to than semi-concealed to electrical opening D) equipment E)
opening A) opening B) equipment C)
1 000 180 330 570 850
A)
This is the distance from the meter box to any un-trapped drain, gully, balanced flue terminal or low-level
opening into the building, such as doors or air bricks which are below 250 mm from ground level.
B)
This is the distance from the meter housing to any opening into the building, such as opening windows, doors, air
bricks and balanced flue terminals.
D
C)
This is the distance from any meter housing to any electrical equipment.
D)
This is the distance from any relief valve vent tip to any opening into the property or un-trapped drain or gully.
TE
E)
This is the distance from the relief valve vent tip to any electrical equipment.
NOTE 1 The limited relief valve has a capacity of not greater than 5% of the regulator design capacity.
IN
NOTE 2 Minimum proximity distances are aligned with those in BS 6400-2 for 2nd family gases and have been
confirmed by Calor Gas Limited in accordance with BS EN 60079-10.
PR
E.2.10 The internal diameter of any vent pipe shall not change the performance
of the regulator and shall be of sufficient size to vent at the maximum relief
valve discharge capacity of the regulator.
NOTE A long vent pipe might require a larger diameter in order to maintain the
EN
maximum relief valve discharge capacity and avoid undue back-pressure on the
pressure control and protection system.
H
Annex F Dangerous Substances and Explosive
W
(informative)
Atmospheres Regulations [17], [18]
Gas pipework design and installation for commercial installation undertaken in
ED
accordance with this standard has to account for any requirements imposed by
DSEAR [17], [18]. However, it is acknowledged that a DSEAR risk assessment
might be undertaken by others some time later on the completed installation.
LL
Such an assessment could identify issues with the gas installation, which could
have arisen as a result of subsequent work undertaken by others on the site
after completion of the gas installation or of site-specific risks subsequently
O
DSEAR principally concerns risks to the safety of workers, rather than risks to
property, equipment or business continuation.
N
and
c) the dangerous substance presents a risk to human safety.
N
The very wide definition of “workplace” covers any premises or part of premises
U
used for work. “Premises” includes all industrial and commercial premises,
land-based and offshore installations, as well as vehicles and vessels. Common
parts of shared buildings, private roads and paths on industrial estates, and
business parks are also “premises”, as are schools, hospitals, restaurants, houses
and other domestic dwellings. Basically, if there is a work activity in “premises”
as defined then it is a workplace for DSEAR purposes.
D
The Energy Institute has prepared the following guidance on interpreting
TE
DSEAR: EI IP-MCSP-P15 [47].
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
Bibliography
Standards publications
For dated references, only the edition cited applies. For undated references, the
latest edition of the referenced document (including any amendments) applies.
BS 476 (all parts), Fire tests on building materials and structures
BS 1494-1, Specification for fixing accessories for building purposes – Part 1:
Fixings for sheet, roof and wall coverings
D
BS 1710:1984, Specification for identification of pipelines and services
BS 3632, Residential park homes – Specification
TE
BS 4250, Specification for commercial butane and commercial propane
BS 5482-1:2005, Domestic butane- and propane- gas-burning installations –
IN
Part 1: Installations at permanent dwellings, residential park homes and
commercial premises, with installation pipework sizes not exceeding DN 25 for
PR
steel and DN 28 for corrugated stainless steel or copper 5)
BS 5482-2, Domestic butane- and propane- gas-burning installations –
Part 2: Installations in caravans and non-permanent dwellings
EN
BS 6004, Electric cables – PVC insulated, non-armoured cables for voltages up to
and including 450/750 V, for electric power, lighting and internal wiring
BS 6007, Electric cables – Single core unsheathed heat resisting cables for
H
voltages up to and including 450/750 V, for internal wiring
BS 6173, Specification for installation of gas-fired catering appliances for use in
W
wiring
BS 7967, Guide for the use of electronic portable combustion gas analysers for
the measurement of carbon monoxide in dwellings and the combustion
LL
phase – Part 1: Requirements for rubber and plastics tubing and hoses 6)
O
5)
Partially withdrawn
6)
Withdrawn.
Other publications
[1] GREAT BRITAIN. Gas Safety (Installation and Use) Regulations 1998. London:
The Stationery Office.
[2] GREAT BRITAIN. The Gas Safety (Installation and Use) Regulations (Northern
Ireland) 2004. London: The Stationery Office.
[3] GREAT BRITAIN. The Gas Safety (Installation and Use) Regulations 1994, as
amended and applied by the Gas Safety (Application) (Isle of Man)
Order 1996. London: The Stationery Office.
[4] GUERNSEY. The Health and Safety (Gas) (Guernsey) Ordinance 2006.
D
[5] ENGLAND AND WALES. The Building Regulations 2010 (England and Wales),
TE
as amended. London: The Stationery Office.
[6] NORTHERN IRELAND. The Building Regulations (Northern Ireland) 2012.
London: The Stationery Office.
IN
[7] SCOTLAND. The Building (Scotland) Regulations 2004, as amended.
Edinburgh: The Stationery Office.
PR
[8] GREAT BRITAIN. The Gas Safety (Management) Regulations 1996. London:
HMSO.
[9] NORTHERN IRELAND. The Gas Safety (Management) Regulations (Northern
EN
Ireland) 1997. London: HMSO.
[10] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGEM/GM/6 Edition 2:
Non-domestic meter installations. Standard designs. Kegworth:
H
IGEM. 2011. 7) http://shop.igem.org.uk/download/document/
W
Pages%20from%20IGEM-GM-6%20Edition%202.pdf [viewed: 28 October
2015].
[11] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGE/GM/8: Non-domestic
ED
meter installations. Flow rate exceeding 6 m3h-1 and inlet pressure not
exceeding 38 bar. Kegworth: IGEM. 2005.6)
[12] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGEM/UP/2 Edition 2:
LL
[13] GREAT BRITAIN. Road Vehicles (Construction and Use) Regulations 1986, as
amended. London: HMSO.
TR
[14] GREAT BRITAIN. Caravan Sites and Control of Development Act 1960.
London: The Stationery Office.
N
[15] GREAT BRITAIN. Caravans Sites Act 1968. London: The Stationery Office.
[16] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGEM/IG/1: Standards of
O
training in gas work: Criteria and guidance in the development and delivery
of training programmes in gas work. Kegworth: IGEM. 2014.7)
C
7)
Published and available from the Institution of Gas Engineers and Managers, IGEM
House, High Street, Kegworth, Derbyshire, DE74 2DA.
[20] UKLPG. Code of Practice 22: Design, Installation and Testing of LPG Piping
Systems. Kenilworth: UKLPG. 2011.
[21] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGE/UP/1 Edition 2:
Strength testing, tightness testing and direct purging of industrial and
commercial gas installations. Kegworth: IGEM. 2005. 8)
[22] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGE/UP/1A Edition 2:
Strength and tightness testing and direct purging of small low pressure
industrial and commercial Natural Gas installations. Kegworth: IGEM. 2005.8)
[23] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGEM/UP/1B Edition 3:
D
Tightness testing and direct purging of small Liquefied Petroleum Gas/Air,
Natural Gas and Liquefied Petroleum Gas installations. Kegworth:
TE
IGEM. 2012.8)
[24] ADVANTICA TECHNOLOGIES LTD. PRS/1E: Brass and copper fittings
(Issue 3). Loughborough: Advantica. 2002. (Available from IGEM
IN
publications.)
[25] NATIONAL GRID. Gas Industry Standard. GIS/V7-3:2008. Specification for
PR
distribution valves – Part 3: Brass bodied manually operated ball and taper
plug valves not exceeding 5 bar maximum operating pressures. National
Grid. 2008. https://www.nationalgrid.com/NR/rdonlyres/
312F5EB2-3313-4B49-A283-1D87B04EA549/30936/V7pt3DEC08.pdf [viewed:
EN
28 October 2015].
[26] INSTITUTION OF GAS ENGINEERS AND MANAGERS. IGEM/GM/5 Edition 3:
Electronic gas meter volume conversion systems. Kegworth: IGEM. 2008.8)
H
[27] HEALTH AND SAFETY EXECUTIVE. Research Report RR945: Potential for leaks
W
of LPG from underground pipes into caravans and park homes. Buxton: HSE
Books. 2012. http://www.hse.gov.uk/research/rrpdf/rr945.pdf [viewed:
28 October 2015].
ED
PE and steel gas services and service pipework. Kegworth: IGEM. 2007.8)
U
8)
Published and available from the Institution of Gas Engineers and Managers, IGEM
House, High Street, Kegworth, Derbyshire, DE74 2DA.
D
[40] INSTITUTION OF GAS ENGINEERS AND MANAGERS: IGE/UP/1A, Soundness
testing and direct purging of small low pressure industrial and commercial
TE
Natural Gas installations. Kegworth: IGEM. 1998.9)
[41] SCOTTISH GOVERNMENT. Scottish Technical Handbooks 2015: Fire.
http://www.gov.scot/Topics/Built-Environment/Building/Building-standards/
IN
publications/pubtech [viewed: 28 October 2015].
[42] DEPARTMENT OF FINANCE AND PERSONNEL NORTHERN IRELAND (DFPNI).
PR
Technical Bulletin E: Fire safety. 2005.
https://www.dfpni.gov.uk/sites/default/files/publications/dfp/
DFP%20Technical%20Booklet%20E%202005%20-%20Fire%20safety.pdf
[viewed: 28 October 2015].
EN
[43] HEALTH AND SAFETY EXECUTIVE. Dangerous Substances and Explosive
Atmospheres Regulations 2002. Approved Code of Practice and guidance.
Dangerous substances and Explosive Atmospheres. L138 (Second edition).
H
2013. http://www.hse.gov.uk/pubns/priced/l138.pdf [viewed: 28 October
W
2015].
[44] HEALTH AND SAFETY EXECUTIVE. A brief guide to the Dangerous
Substances and Explosive Atmospheres Regulations. INDG370(rev1). 2013.
ED
9)
Published and available from the Institution of Gas Engineers and Managers, IGEM
House, High Street, Kegworth, Derbyshire, DE74 2DA.
D
TE
IN
PR
EN
H
W
ED
LL
O
TR
N
O
C
N
U
94 • © The British Standards Institution 2015 This page deliberately left blank
Gas Safe Register Licensed Subscription Copy
U
N
C
O
N
TR
O
LL
ED
W
H
EN
PR
IN
TE
D
D
products are published by BSI Standards Limited.
TE
IN
About us Revisions
We bring together business, industry, government, consumers, innovators Our British Standards and other publications are updated by amendment or revision.
and others to shape their combined experience and expertise into standards We continually improve the quality of our products and services to benefit your
PR
-based solutions. business. If you find an inaccuracy or ambiguity within a British Standard or other
The knowledge embodied in our standards has been carefully assembled in BSI publication please inform the Knowledge Centre.
a dependable format and refined through our open consultation process.
Organizations of all sizes and across all sectors choose standards to help Copyright
them achieve their goals. All the data, software and documentation set out in all British Standards and
EN
other BSI publications are the property of and copyrighted by BSI, or some person
Information on standards or entity that owns copyright in the information used (such as the international
We can provide you with the knowledge that your organization needs standardization bodies) and has formally licensed such information to BSI for
to succeed. Find out more about British Standards by visiting our website at commercial publication and use. Except as permitted under the Copyright, Designs
bsigroup.com/standards or contacting our Customer Services team or and Patents Act 1988 no extract may be reproduced, stored in a retrieval system
H
Knowledge Centre. or transmitted in any form or by any means – electronic, photocopying, recording
or otherwise – without prior written permission from BSI. Details and advice can
W
Buying standards be obtained from the Copyright & Licensing Department.
You can buy and download PDF versions of BSI publications, including British
and adopted European and international standards, through our website at Useful Contacts:
bsigroup.com/shop, where hard copies can also be purchased. Customer Services
ED
If you need international and foreign standards from other Standards Development Tel: +44 845 086 9001
Organizations, hard copies can be ordered from our Customer Services team. Email (orders): [email protected]
Email (enquiries): [email protected]
Subscriptions
LL
Subscriptions
Our range of subscription services are designed to make using standards
Tel: +44 845 086 9001
easier for you. For further information on our subscription products go to
Email: [email protected]
bsigroup.com/subscriptions.
O
With British Standards Online (BSOL) you’ll have instant access to over 55,000 Knowledge Centre
British and adopted European and international standards from your desktop. Tel: +44 20 8996 7004
TR
It’s available 24/7 and is refreshed daily so you’ll always be up to date. Email: [email protected]
You can keep in touch with standards developments and receive substantial
Copyright & Licensing
discounts on the purchase price of standards, both in single copy and subscription
format, by becoming a BSI Subscribing Member. Tel: +44 20 8996 7070
Email: [email protected]
N
To find out more about becoming a BSI Subscribing Member and the benefits
of membership, please visit bsigroup.com/shop.
C
With a Multi-User Network Licence (MUNL) you are able to host standards
publications on your intranet. Licences can cover as few or as many users as you
N
wish. With updates supplied as soon as they’re available, you can be sure your
documentation is current. For further information, email [email protected].
U