Manual: Simrad IS20 Graphic Multifunction Display
Manual: Simrad IS20 Graphic Multifunction Display
Manual: Simrad IS20 Graphic Multifunction Display
General information
The IS20 Graphic is a multifunction instrument that
displays speed, depth, heading, position, wind and
environmental data measured by sensors and other
equipment connected to the system.
Navigational data, engine/battery status and vessel
parameters as e.g. accumulated log and rudder angle
may also be displayed.
The instrument calculates speed trim, wind head/lift,
trip distance and time, average speed, set and drift
parameters. A race timer is also included in the IS20.
Instrument layout
The IS20 has a 130 * 104 pixels LCD. The display may
be set to red or white illumination color, and the contrast
and light level are adjustable.
The instrument is equipped with 2 SimNet connectors,
and with one NMEA0183 input connector.
Keys
The instrument is operated by 6 keys. These are used to
adjust the light, scroll between data pages, to operate
the menu and to set parameter values.
OK
Cancel
Press and holding the Left key will always return the
display to normal operation and the last active page!
Enabling a page
2 windows 3 windows
Press and hold the Left key to leave the menu and return
to normal operation when all windows are defined.
For a list of all available data groups and data items,
refer to Data groups and data items.
Remote operation
BACKLIGHT = 1
DAMPING = 1
COCKPIT
BACKLIGHT = 2
Demo mode
The IS20 includes a demo mode, useful for
demonstrations and on show.
The race timer will continue to run until the Stop softkey
is pressed even if the race timer page is replaced by
another page!
- accumulated total
distance since the
instrument was installed
or from a factory reset
- distance and time since
the trip log was started/
reset
Speed logging
The speed log display shows:
- Current speed
General
The wind alarm can be set for high and low wind speeds.
The wind shift alarm will monitor the wind angle. The
reference angle is set when the alarm is turned on,
and reset to present wind angle when an alarm is
acknowledged.
Alarm indication
The alarm system in IS20 Graphic is activated if any
alarm settings are exceeded. Refer to Alarm setup,
page 34.
When an alarm is notified, the
alarm will be indicated with an
alarm text and with an audible
alarm.
The different alarm indications are
shown in the table below.
Reminder
Alarm type Sound Light
interval
Vital alarm 10s
Switching
Important Alternating on/off 20s
alarm between 2
tones
Standard 40s
alarm
Warning Single beep 60s
Light warning Single beep
Alarm codes
If the alarm is received from other units connected to
SimNet, the alarm text may not be displayed. The alarm
condition will then be indicated in a code.
A description for available codes is listed in the table on
the next page.
Mechanical installation
Panel mounting
The mounting surface must be flat and even to within 0.5
mm.
1 Drill the 4 mounting holes and make a panel cut-
out according to the drilling template included in
the package
2 Use the supplied 19 mm selftapping screws to
secure the control unit to the panel
3 Apply the front panel corners
SimNet/ SimNet/
NMEA2000 NMEA2000
NMEA0183 In
SimNet
The SimNet cable system with very small plugs in both
ends makes it easy to run the cables. Only 10 mm (3/8”)
holes are required through panels and bulkheads.
The SimNet accessory program contains the necessary
items to make a successful installation. Refer to SimNet
cables and accessories.
SimNet cables
A SimNet unit has one or two yellow SimNet connectors.
There are no dedicated “in” or “out” connectors.
Route the SimNet cables with the figures on page 51, 52
and 53 as a guideline. Select cables and accessories from
the SimNet accessory program.
Connect products with two SimNet connectors in a daisy
chain and use drop cables and T-joiners when required.
For cable extension in-line cable joiners are available.
Boat speed
The hull shape or the location of the speed sensor
may cause incorrect speed readings, and calibration is
required to ensure that correct speed and log readings
are displayed.
Compass
The compass calibration and the heading offset function
affects the compass that is selected as heading source.
If more than one compass is connected to the system,
each compass have to be manually selected as compass
source (sensor) and calibrated separately. Refer to
Manual source selection, page 38.
Magnitude of local
field in % of earth’s
magnetic field.
Direction of local field
with respect to lubber
line. it can also be on
the reciprocal.
Rudder
The rudder calibration is used to compensate for any
non-linearity in the transmission between the rudder and
the rudder feedback unit.
General maintenance
The IS20 instruments are “repair by replacement” units,
and the operator is therefore required to perform only a
very limited amount of preventive maintenance.
If the unit requires any form of cleaning, use fresh water
and a mild soap solution (not a detergent). It is important
to avoid using chemical cleaners and hydrocarbons such
as diesel, petrol etc.
Make sure that all open SimNet connectors are fitted
with a protection cap (part no. 24006355).
Always put on the weather cover when the unit is not in
use.
Service information
SimNet status
System data
Technical specifications
Weight:.......................................................... 0.3 kg (1.1 lbs)
Power consumption:...................................................... 1.3 W
SimNet Network Load (NL):............................................. 2 NL
Color:........................................................................... Black
Display:
Type:..........................................Backlit LCD matrix display
Resolution:.............................................. 130 x 104 pixels
Illumination (Red or white):................ Adjustable in 10 steps
Environmental protection:
Front:....................................................................... IP56
Back:....................................................................... IP43
Safe distance to compass:..................................0.3 m (1.0 ft.)
Temperature:
Operating:............................. 0 to +55 °C (+32 to +130 °F)
Storage:............................. –30 to +70 °C (–22 to +158 °F)