APD550P
APD550P
APD550P
550KVA / 440KW
POWERED by PERKINS
MODEL APD550P
kVA 550
Standby
Power kW 440
Pf. 0.8 kVA 500
Prime
kW 400
Standby: Continuous running at variable load for duration of an emergency. No overload is permitted on these ratings. In accordance with ISO 3046 .
Prime: Continuous running at variable load for unlimited periods with 10% overload available for 1 hour in any 12 hour period. In accordance with ISO 8528,ISO 3046.
Manufacturer reserves the right to make changes in model, technical specifications, color, equipment and accessories without prior notice.
www.aksapowergen.com
ENGINE
PERKINS
Model 2506A-E15TAG2
Engine Power Output kWm 495
at rated rpm HP 664
Aspiration and Cooling turbocharged, air-to-air charge cooling
Total Displacement Litre 15,2
No. of Cylinders and Build 6; vertical in-line
Engine Speed rpm 1500
Bore and Stroke mmxmm 137×171
Compression Ratio 16:1
Governor Electronic
Fuel Consumption at full load L/hr 106
Fuel Tank Capacity Litre 850
Oil Capacity Litre 62
Coolant Capacity Litre 58
Radiator Cooling Air m³/min 722
Air Intake – Engine m³/min 36.6
Exhaust Gas Flow m³/min 98
Heavy duty Perkins diesel engine Cooling radiator and fan
Four stroke, water cooled, turbocharged and air charge cooled Starter battery (with lead acid) including Rack and Cables
Direct injection fuel system Flexible fuel connection hoses and manual oil sump drain valve
Electronic Governor system Industrial capacity exhaust silencer and steel bellows
12/24 V D.C. starter and charge alternator Jacket water heater(at automatic models)
Replaceable fuel filter, oil filter and dry element air filter Operation manuals and circuit diagram documents
ALTERNATOR
Design Brushless single bearing, revolving field
Stator 2/3 pitch
Rotor Single bearing, flexible disc
Insulation System Class H
Standard Temperature Rise 105 - 130°C Continuous
Exciter Type Self Excited
Phase Rotation A (U), B (V), C (W)
Alternator Cooling Direct drive centrifugal blower fan
AC Waveform Total Harmonic Distortion No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) <50 per NEMA MG1-22.43
Telephone Harmonic Factor (THF) <2%
Brushless, single bearing system, flexible disc, 4 poles Impregnation with tropicalised epoxy varnish
Insulation class H Solid state Automatic Voltage Regulator
Standard degree of protection IP21 (*IP22/IP23 is available.) Stator winding with 2/3 pitch for improved harmonics
Self-exciting and self-regulating
www.aksapowergen.com
CONTROL SYSTEM
Control supervision and protection panel is mounted on the genset base frame.
The control panel is equipped as follows:
OPTIONAL EQUIPMENTS
www.aksapowergen.com
CHASSIS
The complete gen-set is mounted as whole on a heavy-duty fabricated, steel base frame
Anti-vibration pads are fixed between the engine/ alternator feet and the base frame
Base frame design incorporates an integral fuel tank (Up to 1000 kVA)
The generating set can be lifted or carefully pushed / pulled by the base frame
Dial type fuel gauge and drain plug on the fuel tank
Forklift pockets within base frame (up to 500kVA)
DIMENSIONS
OPEN TYPE
DIMENSIONS (LxWxH) mm 3449x1550x2105
DRY WEIGHT kg 3650
CANOPY
All canopy parts are designed with modular principles Exhaust silencer is protected against environment influences
Without welding assembly Thermally insulated engine exhaust system
Doors on each side Emergency stop push button is installed outside of the canopy
All metal canopy parts are painted by electrostatic Easy lifting and moving
polyester powder paint Easy maintenance and operation