Introduction For Etabs Report

This report summarizes the structural analysis and design of a residential building using the ETABS 2018 software. The building is modeled with frame elements for beams and columns and area elements for slabs and roofs. The 2.5 story building is located in Ramdhuni-3, Sunsari and has RCC special moment resisting frame structure. Key parameters of the building like plan, structural system, soil properties, and loading are defined according to Indian codes like IS 456, IS 1893, and IS 875. The design is based on dead and live loads calculated according to the code specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
160 views

Introduction For Etabs Report

This report summarizes the structural analysis and design of a residential building using the ETABS 2018 software. The building is modeled with frame elements for beams and columns and area elements for slabs and roofs. The 2.5 story building is located in Ramdhuni-3, Sunsari and has RCC special moment resisting frame structure. Key parameters of the building like plan, structural system, soil properties, and loading are defined according to Indian codes like IS 456, IS 1893, and IS 875. The design is based on dead and live loads calculated according to the code specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

1.

Introduction
1.1 About this Report
This report deals with methodology of the structural analysis and design of a Residental
Building and its result. This report includes different parameters for the analysis and design of
the structure. The design resut are shown in a very convenient tabular format in the report.

1.2 Analysis Procedure

The structure has been modelled, analysed and designed in a computer software "ETABS 2018
ADVANCED VERSION". The software has very good analysis and design capability which are
verified in the verification problems included in the pakage. It is a Finite Element Method
(FEM) based software and requires modelling of the structure by finite-elements. Beams and
Columns are modelled with the line(or frame) elements, while the slabs and roofs are modelled
with area elements.

2. Detailed Parameters of the building


2.1 Plan of the Building
2.2 General Parameters
Building Type : R.C.C Frame Structure
Building Use : Residental Building
Location : Ramdhuni-3, Sunsari
Owner Name : Hari bdr. Rayamajhi
No. of Blocks : 1
Plot Area : 997(1ka)
Plinth Area : 676 sq.ft
Ground Coverage : 30.97%
No.of Storey : 2.5
Floor Height : 10'-00"
Wall : 10"& 5" thick brick wall

2.3 Structural Parameters


Foundation Type : Isolated Footing with connecting Beam System
Column : Rectangular 12"x12" & 9"x9"
Beams : 10"x15"
Tie Beam : 9"x12"
Slab : Two-way 5"
walls : Non-load bearing brick wall
Structural System : RCC Special Moment Resistng Frame (SMRF)
Soil Type : ii
Bearing Capacity : 120(Assumed as medium type soil)
Soil Report : N/A

2.4 Design Basis


The building is designed following the standard codes and norms. The different codes used for
the structural design are
i. IS 456:2000 [Code of practice for plain and reinforced concrete] for Design of Concrete
Structures.
ii. IS1893:2002 [Criteria for earthquake resistant design of structure] for earthquake load
calculation.
iii. IS875:1987 [Code of practice for design loads (other than earthquake) for building and
structures.
iv. SP16:1980 [Design aids for reinforced concrete to IS456:1978] for detailing of structural
members.
v. IS13920:1993 [Ductile detailing of reinforced concrete structures subjected to seismic
forces] for Ductile Detailing of the structure.

4. Loading
All loading are derived based on different parts of IS875. Earthquake load is calculated based on
IS1893:2002.
4.1 Dead Loads (DL)
These are the permanent load which is not supposed to change during the structure's design life.
The dead load included in design are :
1 10" thick wall and 10' height wall with both side plaster(with 0% opening) : 12.4 Kn/m
2 5" thick wall and 10' height wall with both side plaster(with 0% opening) : 6.2 Kn/m
3 5" partition wall : 2.2 Kn/m
4 Floor Finish : 1.1 Kn/m

4.2 Live Loads (LL)


These are the loads that may vary its intensity and/or position during design life. Live loads for
different rooms and roofs are calculated as per the functional requirements as specified in IS875
code.
1 Live load for all accessible floor : 2Kn/m
2 Live load for Staircase and Balcony : 3Kn/m