Victaulic Balancing Valves TA Series 786H/787H/788/789 and Series 78KH

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

Victaulic Balancing Valves

TA Series 786H/787H/788/789 and Series 78KH 08.16

1.0 PRODUCT DESCRIPTION


Available Sizes
• ½ – 16"/DN15 – DN400
Maximum Working Pressure
• Series 786H, 787H and 78KH: 400 psi/2758 kPa/27.6 bar
• Series 788: 250 psi/1724 kPa/17.2 bar
• Series 789: 350 psi/2413 kPa/24 bar
Operating Temperature
• –4°F to +248°F/–20°C to +120°C
Application
• Heating (not including steam) and cooling systems
Function
• Balancing
• Pre-Setting
• Measuring
• Shut-Off
• Draining (depending on valve type) or optional drain kit (Series 786H only)

2.0 CERTIFICATION/LISTINGS


ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION, MAINTENANCE OR SUPPORT.

System No. Location Spec Section Paragraph

Submitted By Date Approved Date

victaulic.com
08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.
1
victaulic.com

3.0 SPECIFICATIONS – MATERIAL


TA Series 786H & 787H and Series 78KH
Valve Body and Bonnet: AMETAL® dezincification resistant (DZR) brass alloy
Sealing (Body/Bonnet): EPDM O-ring
Valve Plug: AMETAL®
Seat Seal: EPDM O-ring
Spindle: AMETAL®
Slip Washer: Polytetrafluoroethylene (PTFE)
Spindle Seal: EPDM O-ring
Spring: Stainless steel
Hand Wheel: Polyamide and TPE
Measuring Points: AMETAL®
Measuring Point Seals: EPDM
Measuring Point Caps: Polyamide and TPE
Drain Kit Body: AMETAL®
Drain Kit Seals: EPDM
Drain Kit Gasket: Fiber-based aramid

TA Series 788 & 789


Body: Ductile iron conforming to ASTM A536 Grade 60-40-18 (BS Grade 400/15)
Body Coating: 2 ½ – 8" – Epoxy painted; 10 – 16" – Painted
Trim (Bonnet, Stem and Restriction Cone)
• Bonnet: 2 ½ – 6" – AMETAL®; 8 – 16" – Ductile iron
• 2 ½ – 6" Stem & Restriction Cone: AMETAL®
• 8 – 16" Cone – Ductile iron; 8 – 16" Spindle – AMETAL®
Seat: Ductile iron
Seat Seal: EPDM
Stem Seal: EPDM
Probe Seal: EPDM
Handwheel: 2 ½ – 6" – Red polyamide plastic; 8 – 16" – Aluminum
Optional Equipment: 2 ½ – 6" Series 789 only – Insulation kit, polyurethane
Allen Wrench Sizes
• ½ – 2" Series 786, 787H and 78KH: 3 mm memory
• 2 ½ – 12" Series 788 & 2 ½ – 6" Series 789: 5 mm memory
• 8 – 16" Series 789: 8 mm memory
NOTE
• AMETAL® is the dezincification-resistant brass alloy of IMI TA

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 2
victaulic.com

4.0 DIMENSIONS
TA Series 786H Solder End
TA Series 787H Female NPT Threaded End

A A

B
B

TA Series 786H TA Series 787H


½ – 2"/DN15 – DN50 ½ – 2"/DN15 – DN50

TA Series 786H Solder End TA Series 787H Female NPT Threaded End
Size (400 psi/2758 kPa) (400 psi/2758 kPa)
Actual Approx. Approx.
Outside A B Weight A B Weight
Nominal Diameter End to End Center to Top (Each) End to End Center to Top (Each)
inches inches inches inches lb inches inches lb
DN mm mm mm kg mm mm kg
½ 0.840 3.54 3.94 1.4 3.31 4.00 1.5
DN15 21.3 90 100 0.6 84 102 0.7
¾ 1.050 3.82 3.94 1.4 3.70 4.00 1.6
DN20 26.9 97 100 0.6 94 102 0.7
1 1.315 4.33 4.13 1.9 4.13 4.13 2.0
DN25 33.7 110 105 0.9 105 105 0.9
1¼ 1.660 4.88 4.13 2.4 4.76 4.13 2.6
DN32 42.4 124 105 1.1 121 105 1.2
1½ 1.900 5.12 4.72 3.1 4.96 4.75 3.3
DN40 48.3 130 120 1.4 126 121 1.5
2 2.375 6.08 4.72 4.5 6.10 4.75 5.0
DN50 60.3 154 120 2.0 155 121 2.3

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 3
victaulic.com

4.1 DIMENSIONS
Series 78KH Male NPT Union x Female NPT
A

Series 78KH
½ – 2"/DN15 – DN50

Size Series 78KH Male NPT Union x Female NPT (400 psi/2758 kPa)
Nominal Actual Outside Diameter Approx.
inches inches A B Weight
mm mm End to End Center to Top (Each)
inches inches lb
MPT Union FPT Valve MPT Union FPT Valve mm mm kg
½ x ½ 0.840 x 0.840 5.56 4.00 1.7
DN15 DN15 21.3 21.3 141 102 0.8
¾ 1.050 5.83 4.00 1.8
DN20 26.9 148 102 0.8
1 1.315 6.09 4.13 2.7
   
DN25 33.7 155 105 1.2
1¼ 1.660 7.25 4.13 4.1
DN32 42.4 184 105 1.9
¾ ¾ 1.050 1.050 5.88 4.00 2.3
x x
DN20 DN20 26.9 26.9 149 102 1.0
1 1.315 6.63 4.13 2.2
DN25 33.7 168 105 1.0
1¼ 1.660 7.50 4.13 4.3
   
DN32 42.4 190 105 1.9
1½ 1.900 7.50 4.75 5.0
DN40 48.3 190 121 2.3
1 x 1 1.315 x 1.315 7.52 4.13 4.02
DN25 DN25 33.7 33.7 191 105 1.8
1¼ 1.660 7.65 4.13 2.8
DN32 42.4 194 105 1.3
1½ 1.900 7.50 4.75 5.2
   
DN40 48.3 190 121 2.4
2 2.375 8.88 4.75 7.3
DN50 60.3 226 121 3.3
1¼ 1¼ 1.660 1.660 8.06 4.13 5.52
x x
DN32 DN32 42.4 42.4 205 105 2.5
1½ 1.900 8.04 4.75 3.6
DN40 48.3 204 121 1.6
2 2.375 8.88 4.75 7.5
DN50 60.3 226 121 3.4
1½ 1½ 1.900 1.900 8.83 4.75 7.16
x x
DN40 DN40 48.3 48.3 224 121 3.2
2 2.375 8.99 4.75 5.3
DN50 60.3 228 121 2.4
2 2 2.375 2.375 8.86 4.75 7.19
x x
DN50 DN50 60.3 60.3 225 121 3.3
NOTE
• Optional tailpiece options are available. See accessory table on pg. 5 for more information.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 4
victaulic.com

4.2 OPTIONAL PARTS


Series 78KH Union Tailpieces (Optional)

Female Tailpiece Sweat Tailpiece Male Tailpiece

Size Victaulic Part Code


Nominal1
inches Female Tailpiece Sweat Tailpiece Male Tailpiece
½ x ½ P00478Y304 P00478Y504 P00478U404
¾ x ½ P00678Y304 P00678Y504 P00678U404
¾ P00678Y306 P00678Y506 P00678U406
1 x ½ P00678Y304 P00678Y504 P00678U404
¾ P00678Y306 P00678Y506 P00678U406
1 P00678Y310 P00678Y510 P00678U410
1¼ x ½ – – P01278U404
¾ P01278Y306 P01278Y506 P01278U406
1 P01278Y310 P01278Y510 P01278U410
1¼ P01278Y312 P01278Y512 P01278U412
1½ x ½ – – P01278U404
¾ P01278Y306 P01278Y506 P01278U406
1 P01278Y310 P01278Y510 P01278U410
1¼ P91278Y312 P01278Y512 P01278U412
1½ P01278Y314 P01278Y514 P01278U414
2 x 1 – – P02078U410
1¼ P02078Y312 P01278Y512 P02078U412
1½ P02078Y314 P01278Y514 P02078U414
2 P02078Y320 P02078Y520 P02078U420

1 This table is for nominal valve size by outlet or inlet union size. For example: A 3/4 x ½" tailpiece is used to enlarge from a ½" valve to a 3/4" valve or to reduce an
outlet from a 3/4" valve to a ½" outlet. They are common components with other Victaulic valve families.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 5
victaulic.com

4.3 DIMENSIONS
TA Series 788 Flanged End
(Class 150 RF, ASME/ANSI B16.42)
TA Series 789 Grooved End

A
A

B
B

TA Series 788 TA Series 789


2 ½ – 16"/73.0 mm – DN400 2 ½ – 12"/73.0 mm – DN300

TA Series 788 Flanged End TA Series 789 Grooved End


Size (250 psi/1724 kPa) (350 psi/2413 kPa)
Actual Approx. Approx.
Outside A B D Weight A B Weight
Nominal Diameter End to End Center to Top (Each) End to End Center to Top (Each)
inches inches inches inches inches lb inches inches lb
DN mm mm mm mm kg mm mm kg
2½ 2.875 11.42 8.07 7.09 24.0 11.38 8.00 14.0
73.0 290 205 180 10.9 289 203 6.4
3 3.500 12.20 8.66 7.48 31.0 12.25 8.63 20.0
DN80 88.9 310 220 190 14.1 311 219 9.1
4 4.500 13.78 9.45 9.06 43.0 13.75 9.44 31.0
DN100 114.3 350 240 230 19.6 350 240 14.1
5 5.563 15.75 10.83 10.04 62.0 15.75 10.88 50.0
DN125 141.3 425 275 255 28.5 400 276 22.7
6 6.625 18.90 11.22 11.02 82.0 18.88 11.25 69.0
DN150 168.3 480 285 280 37.5 480 286 31.3
8 8.625 23.62 16.93 13.58 168.0 23.63 17.00 140.0
DN200 219.1 600 430 345 76.5 600 432 63.7
10 10.750 28.74 16.54 15.98 270.0 28.75 17.75 202.0
DN250 273.0 730 420 406 122.9 730 451 91.9
12 12.750 33.46 18.90 19.02 360.0 33.50 19.00 280.0
DN300 323.9 850 480 483 163.9 851 483 127.4
14 14.000 38.58 23.03 20.98 655.0
– – –
DN350 355.6 982 585 533 297.0
16 16.000 43.31 25.20 23.50 895.0
– – –
DN400 406.4 1100 640 597 406.0

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 6
victaulic.com

5.0 PERFORMANCE
Valve Selection Guide – TA Series 786H & 787H and Series 78KH
Size Flow Data for TA Series 786H & 787H and Series 78KH
Actual
Nominal Outside Diameter Absolute Min. Flow Nominal Range of Flow Absolute Max. Flow
inches inches GPM GPM GPM
DN mm LPM LPM LPM
½ 0.840 0.1 0.6 – 2.8 8.6
DN15 21.3 0.5 2.3 – 10.6 32.6
2.0 – 6.0
¾ 1.050 0.4 20.0
DN20 26.9 1.5 7.6 – 22.7 76.0
1 1.315 0.5 3.9 – 10.0 30.0
DN25 33.7 1.7 14.8 – 37.9 114.0
1¼ 1.660 0.9 5.0 – 15.0 48.0
DN32 42.4 3.3 18.9 – 56.8 182.0
1½ 1.900 1.3 6.6 – 20.0 66.0
DN40 48.3 4.9 25.0 – 75.7 250.0
2 2.375 2.0 12.6 – 36.0 110.0
DN50 60.3 7.6 47.7 – 136.0 416.0

Important Notes
Balancing valves should be sized in accordance with the GPM/LPM flows (and not in relation to pipeline size). Sizing
balancing valves based on the minimum or maximum flow rates is not recommended. Valves should be sized using
the nominal flow rate only. The Minimum Flow is calculated from the minimum open setting of the valve and a
minimum pressure drop 1 Ft. WG (= 3 kPa). The Nominal Flow is calculated from the maximum open setting of the
valve and the minimum recommended pressure drop, 2 Ft. WG (= 6 kPa). The Maximum Flow is calculated from the
maximum open setting of the valve and the maximum pressure drop, 20 Ft. WG (= 60 kPa). A computer program,
TA-Select, is available for calculation of valve handwheel pre-set position and other applications.
NOTE
• For information regarding Allen Wrench sizes see section 3.0 Material Specifications.

Measuring Accuracy
The hand wheel zero position is calibrated and must not be changed. Valves have an accuracy of flow measurement
of 2% to 3% when used within their recommended flow range and installed in accordance with the figure below.
NOTE
• For the most accurate results, a Series 734 TA SCOPE or Series 73M CMI should be used. However, any differential pressure meter may be used.

Pump

2D 5D 2D 10 D

The illustration relates to the accuracy of differential pressure


measurement and is not an installation requirement.

Valve may be installed in one of six possible orientations,


provided the above placement criteria are met.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 7
victaulic.com

5.1 PERFORMANCE
CV Values for Various Handle Settings
TA Series 786H
The values below may be used when calculating and sizing a piping system.

TA Series 786H

CV Values for Sizes listed below1


No. of Turns ½" ¾" 1" 1 ¼" 1 ½" 2"
0.50 0.157 0.616 0.693 1.38 2.19 3.03
1.00 0.261 0.903 1.19 2.42 3.93 4.74
1.50 0.401 1.41 2.46 3.88 5.48 7.82
2.00 0.714 2.25 4.21 6.03 7.23 13.2
2.50 1.08 3.13 6.08 8.98 10.6 18.3
3.00 1.69 4.29 7.69 11.4 14.8 24.9
3.50 2.39 5.21 9.01 13.8 18.7 31.2
4.002 2.96 6.23 9.93 16.4 22.3 37.3
1 CV = GPM at a ΔP of 1 psi/7 kPa) through the valve at any given setting.
1 psi = 2.31 ft. of H2O
2 Full open valve.

TA Series 787H and Series 78KH


The values below may be used when calculating and sizing a piping system.
A
A

B
B

TA Series 787H TA Series 78KH

CV Values for Sizes listed below1


No. of Turns ½" ¾" 1" 1 ¼" 1 ½" 2"
0.50 0.157 0.616 0.693 1.38 2.19 3.03
1.00 0.261 0.903 1.19 2.42 3.93 4.74
1.50 0.401 1.41 2.46 3.88 5.48 7.82
2.00 0.714 2.25 4.21 6.03 7.23 13.2
2.50 1.08 3.13 6.08 8.98 10.6 18.3
3.00 1.69 4.29 7.69 11.4 14.8 24.9
3.50 2.39 5.21 9.01 13.8 18.7 31.2
4.002 2.96 6.23 9.93 16.4 22.3 37.3
1 CV = GPM at a ΔP of 1 psi/7 kPa) through the valve at any given setting.
1 psi = 2.31 ft. of H2O
2 Full open valve.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 8
victaulic.com

5.2 PERFORMANCE
Valve Selection Guide – TA Series 788 & 789
Size Flow Data for TA Series 788 & 789
Actual
Nominal Outside Diameter Absolute Min. Flow Nominal Range of Flow Absolute Max. Flow
inches inches GPM GPM GPM
DN mm LPM LPM LPM
2½ 2.875 1.4 38.0 – 100.0 290.0
73.0 5.3 144.0 – 379.0 1097.7
31.0 – 130.0
3 3.500 1.5 410.0
DN80 88.9 5.7 117.0 – 493.0 1551.9
4 4.500 1.9 68.0 – 200.0 650.0
DN100 114.3 7.2 257.0 – 757.0 2460.3
5 5.563 4.2 90.0 – 320.0 1020.0
DN125 141.3 15.9 341.0 – 1211.0 3860.7
6 6.625 5.0 182.0 – 450.0 1430.0
DN150 168.3 18.9 689.0 – 1703.0 5412.6
8 8.625 30.0 367.0 – 820.0 2600.0
DN200 219.1 113.6 1389.0 – 3104.0 9841.0
10 10.750 70.0 540.0 – 1300.0 4040.0
DN250 273.0 265.0 2044.0 – 4921.0 15291.4
12 12.750 115.0 960.0 – 1500.0 4950.0
DN300 323.9 435.3 3634.0 – 5678.0 18735.8
143 14.000 83.0 1020.0 – 2700.0 7414.0
DN350 355.6 314.0 3861.0 – 10220.0 28062.0
163 16.000 95.0 1330.0 – 3400.0 9371.0
DN400 406.4 360.0 5034.0 – 12869.0 35469.0
3 Only the TA Series 788 Flanged End Balancing Valves is available in 14 – 16"/DN350 – DN400 sizes.

Important Notes
Balancing valves should be sized in accordance with the GPM/LPM flows (and not in relation to pipeline size). Sizing
balancing valves based on the minimum or maximum flow rates is not recommended. Valves should be sized using
the nominal flow rate only. The Minimum Flow is calculated from the minimum open setting of the valve and a
minimum pressure drop 1 Ft. WG (= 3 kPa). The Nominal Flow is calculated from the maximum open setting of the
valve and the minimum recommended pressure drop, 2 Ft. WG (= 6 kPa). The Maximum Flow is calculated from the
maximum open setting of the valve and the maximum pressure drop, 20 Ft. WG (= 60 kPa).A computer program, TA-
Select, is available for calculation of valve handwheel pre-set position and other applications.
NOTES
• For information regarding Allen Wrench sizes, see section 3.0 Material Specifications.
• For the most accurate results, a Series 734 TA SCOPE or Series 73M CMI should be used. However, any differential pressure meter may be used.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 9
victaulic.com

5.3 PERFORMANCE
CV Values for Various Handle Settings
TA Series 788 & 789
The values below may be used when calculating and sizing a piping system.
A
A

B
B

TA Series 788 TA Series 789

CV Values for Sizes listed below4


No. of Turns 2 ½" 3" 4" 5" 6" 8" 10" 12" 14" 5 16" 5
0.50 2.09 2.32 2.90 6.38 7.54 – – – – –
1.00 3.94 4.64 6.96 12.20 13.90 – – – – –
1.50 5.68 6.96 10.40 18 25.50 – – – – –
2.00 7.54 9.28 13.30 24.90 46.40 46.40 104 – – –
2.50 10.80 12.80 18.60 31.30 75.40 58 128 – – –
3.00 18.90 16.20 30.20 41.80 116 75.40 162 174 126 145
3.50 29.70 22.60 51 63.80 157 104 226 267 150 172
4.00 40.90 33.60 73.10 96.30 196 139 296 348 172 198
4.50 51.60 47.60 92.80 132 240 191 371 429 197 241
5.00 60.30 63.80 114 164 281 261 447 522 240 306
5.50 70.20 78.90 133 194 324 331 516 621 295 378
6.00 78.90 92.80 153 229 362 394 580 719 350 448
6.50 84.70 107 168 255 394 464 632 800 408 521
7.00 89.30 119 184 289 426 505 684 870 469 597
7.50 93.40 131 203 320 454 545 766 945 546 684
8.00 98.60 6 1396 2206 3486 4876 597 841 1032 645 789
9.00 – – – – – 690 951 1125 909 1037
10.00 – – – – – 754 1090 1206 1110 1322
11.00 – – – – – 824 1218 1299 1276 1450
12.00 – – – – – 8876 13756 1392 1462 1624
13.00 – – – – – – – 1531 1647 1810
14.00 – – – – – – – 1589 1868 2007
15.00 – – – – – – – 1624 2042 2250
16.00 – – – – – – – 16826 2169 2482
17.00 – – – – – – – – 2274 2645
18.00 – – – – – – – – 2366 2796
19.00 – – – – – – – – 2471 2935
20.00 – – – – – – – – 25526 3051
21.00 – – – – – – – – – 3144
22.00 – – – – – – – – – 32256
4 CV = GPM at a ΔP of 1 psi/7 kPa) through the valve at any given setting.
1 psi = 2.31 ft. of H2O
5 Only the TA Series 788 Flanged End Balancing Valve is available in 14 – 16"/DN350 – DN400 sizes.
6 Full open valve.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 10
victaulic.com

5.4 PERFORMANCE
Correction Factors
For liquids other than water, the flow values from the balancing wheel can be adjusted as follows:
Divide the flow rate (as indicated by the balancing wheel) by the square root of the specific gravity.
qCalculated
Actual Flow =
SG

This applies to liquids having, on the whole, the same viscosity as water, i.e. most water/glycol mixtures and water/
brine solutions at room temperature. At low temperatures, the viscosity increases and laminar flow may occur in
certain valves. The risk increases with small valves, low settings and low differential pressures.
A computer program, HySelect, is available for calculation of pre-setting values and other applications. When the
flow setting is verified or changed to the final setting, the memory stop should be set. Also, the TA Scope can
automatically make this conversion by programming the properties of the fluid being used. Contact Victaulic for
further information.
Correction Factors
When Δp and the design flow rate are known, use the formula shown to calculate the CV value or use the graphs on
page 17 – 19. The Tour & Andersson balancing wheel can also be used.

A computer program, HySelect, is available from Victaulic for calculation of pre-setting values and other applications.
When measuring pressure drop across the Series 788 or 789 valves installed in the vertical position, the measured value
should be adjusted by the static head created by the distance between the PT ports.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 11
victaulic.com

5.5 PERFORMANCE
Accessories
Drain Kit
Series 786-DK

• A separate drain kit with a 3/4"/20 mm connection is available for Series 786H valves.
• Kit must be field mounted
• Kit comes complete with 2 gaskets and a hexnut.
• Partcode= K-000-786-CBV
NOTE
• If a drain is needed for a Series 787H or a Series 78KH, be sure to choose the valve assembly with the factory installed option. Standard Series 787H or
Series 78KH valves cannot be field retrofitted.

Probe Port

Size L
inches inches
Series mm mm Part Code
L ½–2 1.75
786H/787H/78KH K-000-740-003
15 – 50 45
2 ½ – 16 1.19
788/789 K-000-740-002
65 – 400 30
L 3.50
2 ½ – 16
788/789 K-000-740-001
65 – 400 89

TA Series 786H/787H/788/789 TA Series 788/789

Universal Gauge Meter Conversion Kit


• This kit is required to measure TA valves with third party differential pressure meters. It includes 2 probes, the
necessary fittings, a flow wheel, and an instructions sheet.
• Partcode= K-000-738-100
PT Extension
Size L
inches inches
mm mm Part Code
½– 2 2.8
P0007862PT
15 – 50 71.1

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 12
victaulic.com

5.5 PERFORMANCE (CONTINUED)

Hand Wheels
Digital Digital
Read out 0 Lock Feature/ Read out 0 Lock Feature/
Memory Stop Memory Stop
0 0

STAD 2½ STAD 2½

Valve Type Valve Type


and Size and Size

TA Series 786/787H TA Series 788/789 TA Series 788/789


Plastic Plastic Aluminum
½ – 2" 2 ½ – 6" 8 – 16"

Part Code Part Code Part Code


P-004-784-001 P-024-784-001 P-080-784-001

Prefab Insulation
TA Series 786H & TA Series 787H H

D L
B

Dimensions
Valve Size Part Code H D B L
inches inches inches inches inches inches
mm mm mm mm mm mm
½&¾ 5.31 3.54 4.06 5.51
K-004-784-INS
15 & 20 135 90 103 140
1 5.59 3.70 4.06 6.30
K-010-784-INS
25 142 94 103 160
1¼ 6.14 4.17 4.06 7.09
K-012-784-INS
32 156 106 103 180
1½ 6.65 4.25 4.45 8.43
K-014-784-INS
40 169 108 113 214
2 7.01 4.25 4.49 9.65
K-020-784-INS
50 178 108 114 245

Prefab Insulation
TA Series 788 & TA Series 789

L D

C Min.

Dimensions
Valve Size Part Code L D C Min
inches inches inches inches inches
mm mm mm mm mm
2½ 17.75 10.63 10.63
K-024-784-INS
65 451 270 270
3 19.00 11.44 11.44
K-030-784-INS
80 483 291 291
4 20.50 12.63 12.63
K-040-784-INS
100 521 321 321
5 22.50 13.75 13.75
K-050-784-INS
125 572 349 349
6 26.00 15.00 15.00
K-060-784-INS
150 660 381 381

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 13
victaulic.com

5.6 PERFORMANCE
TA Series 734 Scope

The TA Series 734 SCOPE is a wireless, handheld device for the swift and accurate measurement of differential
pressure, flow, temperature and power.
An independent sensor communicates with the TA SCOPE to deliver data quickly, thereby enabling contractors to
balance a system, troubleshoot hydronic problems and log system performance.
The TA Series 734 SCOPE Premium is a more robust case compared to the TA Series 734 SCOPE. See page 15 of
this publication for additional details on the TA SCOPE and TA SCOPE Premium.
Differential pressure
• TA SCOPE: 0-29 psi/0-200 kPa
• TA SCOPE (High Pressure): 0-145 psi/0-1000 kPa

TA Series 736 Differential Pressure Sensor

Provides connection between a building’s heating/cooling system and building monitoring system (BMS).
• Continuously measures the flow and differential pressure through and across the IMI TA balancing valves.
• Measurement probes provided for direct connection to the measurement points on all TA Series 786H, 787H,
788, and 789 balancing valves.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 14
victaulic.com

5.6 PERFORMANCE (CONTINUED)


TA Series 734 Scope/Scope Premium
The TA Series 734 Scope contains a reduced set of
accessories compared to the TA Series 734 Scope
Premium. All parts marked with an asterisk (*) in the
list below are included in both the Scope and the Scope
Premium kits. All other parts are only available in the
Scope Premium kit.
1. *Handheld unit (Hh)
2. *Dp Sensor unit (DpS)
3. *Digital Temperature Sensor (DTS)
4. *Measuring hoses, 20 in. red/blue
5. Safety pressure and temperature probe (SPTP)
6. Safety pressure probes (SPP)
7. Measuring hoses with twin needle, 5.9 in x4

8. Flashlight
9. Mirror
10. Chucks for older valves, red/blue
11. *Allen keys 3mm/5mm
12. Spanner for measuring points on older valves
13. *Presetting tool TA Series TC/TCM/TCP
14. *Spare filters (4 pcs) 21 22

15. Chain for mounting


16. Neckstrap
17. *USB cables for connection: Hh - DpS and Hh - PC
18. *Multi-charger for handheld, Dp sensor(s) and
TA Series 734 Scope Relays
19. *DC cable (2 PCS) 23 24 25 26 27

20. *AC cable (EU, UK, US or AU.NZ)


21. Cable wrapping
22. *Case
23. HySelect Software
24. User manual
25. *Calibration certificates for DpS, DTS, and SPTP
26. *Quick Guide
27. SPTP/SPP instruction
28. SPTP/SPP stickers

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 15
victaulic.com

6.0 NOTIFICATIONS

WARNING

• Read and understand all instructions before attempting to install, remove, adjust, or maintain any Victaulic
piping products.
• Depressurize and drain the piping system before attempting to install, remove, adjust, or maintain any
Victaulic piping products.
• Wear safety glasses, hardhat, and foot protection.
Failure to follow these instructions could result in death or serious personal injury and property damage.

7.0 REFERENCE MATERIALS


08.29: Victaulic Differential Pressure Controller - TA Series 793/794
08.30: Victaulic KOIL-KIT Coil Pack
08.34; Victaulic Automatic Balancing Valves - Series 76T, 76B, 76K, 76V & 76G
08.37: Victaulic Compact Pressure Independent Balancing and Control Valve (Compact P) - TA Series 7CP
08.38: Victaulic TBV Terminal Balancing and Control Valves - Series TC & Series TCM
08.46: Victaulic Differential pressure Controller - TA Series 7PR
08.47 Victaulic Compact Differential Pressure Control TA Series 7DA
08.55: Victaulic Pressure Independent Balancing and Modulating Control Valve - TA Series 7MP
08.57 Victaulic Differential Pressure Relief Valve TA Series 782

User Responsibility for Product Selection and Suitability Note


Each user bears final responsibility for making a determination as to the suitability of Victaulic This product shall be manufactured by Victaulic or to Victaulic specifications. Victaulic
products for a particular end-use application, in accordance with industry standards and recommends all products to be installed in accordance with current IMI TA installation/
project specifications, and the applicable building codes and related regulations as well as assembly instructions. Victaulic and IMI TA reserve the right to change product specifications,
Victaulic performance, maintenance, safety, and warning instructions. Nothing in this or any designs and standard equipment without notice and without incurring obligations.
other document, nor any verbal recommendation, advice, or opinion from any Victaulic Installation
employee, shall be deemed to alter, vary, supersede, or waive any provision of Victaulic Reference should always be made to the current IMI TA installation/assembly instructions for
Company's standard conditions of sale, installation guide, or this disclaimer. the product you are installing. For coupling and strainer installation, reference should always
Intellectual Property Rights be made to the I-100 Victaulic Filed Installation Handbook for the product you are installing.
No statement contained herein concerning a possible or suggested use of any material, Handbooks are included with each shipment of Victaulic products for complete installation
product, service, or design is intended, or should be constructed, to grant any license and assembly data, and are available in PDF format on our website at www.victaulic.com
under any patent or other intellectual property right of Victaulic or any of its subsidiaries or Warranty
affiliates covering such use or design, or as a recommendation for the use of such material, Refer to the Warranty section of the current Price List or contact Victaulic for details.
product, service, or design in the infringement of any patent or other intellectual property
right. The terms “Patented” or “Patent Pending” refer to design or utility patents or patent Trademarks
applications for articles and/or methods of use in the United States and/or other countries. Victaulic and all other Victaulic marks are the trademarks or registered trademarks of
Victaulic Company, and/or its affiliated entities, in the U.S. and/or other countries.

08.16 0930 Rev T Updated 02/2020 © 2020 Victaulic Company. All rights reserved.

victaulic.com 16

You might also like