Heating and Ventilating Systems 33

Steam heating systems work by boiling water into steam in a boiler and transporting the steam through pipes to heat exchangers where it condenses back into water. Some air gets absorbed into the steam from the water and collects in the heat exchangers, requiring venting. There are three types of steam traps - thermostatic traps that sense temperature differences, mechanical traps that use floats, and thermodynamic traps that use discs or orifices to release condensate. Hot water heating systems circulate heated water through pipes to heating units and then return it to the boiler to be reheated, providing more consistent heat than steam systems.

Uploaded by

rohit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views2 pages

Heating and Ventilating Systems 33

Steam heating systems work by boiling water into steam in a boiler and transporting the steam through pipes to heat exchangers where it condenses back into water. Some air gets absorbed into the steam from the water and collects in the heat exchangers, requiring venting. There are three types of steam traps - thermostatic traps that sense temperature differences, mechanical traps that use floats, and thermodynamic traps that use discs or orifices to release condensate. Hot water heating systems circulate heated water through pipes to heating units and then return it to the boiler to be reheated, providing more consistent heat than steam systems.

Uploaded by

rohit
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Heating and Ventilating Systems 33

up of air in the system which reduces the heat transfer efficiency


of the system and may cause air binding in the heat exchanger. In
a steam heating system, water enters a heat conversion unit (a
heat exchanger, the boiler, etc.) and is changed into steam. When
the water is boiled, some air in the water is also released into the
steam and is moved along with the steam to the heat exchanger.
As the heat is released at the heat exchangers (and through pipe
radiation losses), the steam is changed into condensate water.
Some of the air in the piping system is absorbed back into the
water. However, much of the air collects in the heat exchanger
and must be vented.
Steam traps are classified as thermostatic, mechanical or
thermodynamic. Thermostatic traps sense the temperature differ-
ence between the steam and the condensate using an expanding
bellows or bimetal strip to operate a valve mechanism. Mechani-
cal traps use a float to determine the condensate level in the trap
and then operate a discharge valve to release the accumulated
condensate. Some thermodynamic traps use a disc which closes to
the high velocity steam and opens to the low velocity condensate.
Other types will use an orifice which flashes the hot condensate
into steam as the condensate passes through the orifice.

HOT WATER HEATING SYSTEMS

Hot water heating systems (Figure 3-4) transport heat by


circulating heated water to a designated area. Heat is released
from the water as it flows through the heating unit (coil, termi-
nal). After heat is released, the water returns to the boiler to be
reheated and recirculated. Low temperature hot water boilers are
≤ 250°F. High temperature hot water boilers are >250°F.

ADVANTAGES OF HOT WATER


HEATING OVER STEAM HEATING

Hot water heating systems produce heat more consistently


than steam heating systems. The water in a hot water heating
34
HVAC Fundamentals
Figure 3-4. Hot Water Heating System