Information For Replacement of The FR-S500 (S500E) Series by The FR-D700 Series
Information For Replacement of The FR-S500 (S500E) Series by The FR-D700 Series
Information For Replacement of The FR-S500 (S500E) Series by The FR-D700 Series
Size, connection, and parameter concerning replacement are stated from the next page.
1/19 BCN-C21002-106
1. Size
The installation size of the FR-S500 (S500E) series and of the FR-D700 series is the same.
For details of size, refer to the outline dimension drawings on the next page and later.
Power Supply
Installed Inverter Replacing Inverter Installation Size
Voltage
FR-S540(E)-0.4K FR-D740-0.4K Same size
FR-S540(E)-0.75K FR-D740-0.75K Same size
Three phase
FR-S540(E)-1.5K FR-D740-1.5K Same size
400V
FR-S540(E)-2.2K FR-D740-2.2K Same size
FR-S540(E)-3.7K FR-D740-3.7K Same size
*The installation size of the FR-S500E series is the same as the FR-S500 series.
2/19 BCN-C21002-106
Outline dimension drawing (Unit: mm)
2-Φ5hole
2-Φ5hole
Cooling fan
3/19 BCN-C21002-106
2. Connection
Since terminal names are the same, connect according to the names.
Refer to page 5, 6 for terminal size.
circuit/input RM RM RM
signal RL RL RL
SD SD SD Isolated from terminals 5 and SE.
PC PC PC
10 10 10
Frequency
2 2 2
setting
A, B, C A, B, C A, B, C
Control circuit
output signal SE SE SE Isolated from terminals 5 and SD.
Pulse
FM FM FM
4/19 BCN-C21002-106
Terminal Size
5/19 BCN-C21002-106
[Control circuit terminal]
FR-S500, S500E FR-D700
Control circuit Control circuit
Except for A, B, C A, B, C
M2 insertion type M3 insertion type Spring clamp terminal
flathead screw flathead screw
terminal terminal
(Note 1) In case when using bar terminals of Phoenix Contact Co., Ltd. introduced for the FR-S500, S500E, they are not compatible with the
FR-D700 since it does not match with the spring clamp terminal block. (Depends on the size difference of a bar terminal, some other bar
terminal may not be wired to the FR-D700.)
In such a case, cut the bar terminal and strip off the wire to make it a bare wire, or use bar terminals introduced below. Also check for the
applicable wire size.
Table. FR-D700 control terminal block applicable wire size (bare wire)
Wire Stripping Size Applicable Bare Wire Size
Single wire (mm2)
6/19
Table. FR-D700 control terminal block applicable wire size (bar terminal)
Bar Terminal Type (Phoenix Contact Co., Ltd.)
Applicable Wire Size (mm2)
With insulation sleeve Without insulation sleeve
AI 0.5-10WH - 0.3 to 0.5
AI 0.75-10GY AI 0.75-10 0.75
AI 1-10RD A 1-10 1
AI 1.5-10BK AI 1.5-10 1.25, 1.5
BCN-C21002-106
6/19 BCN-C21002-106
3. Parameter
Although most parameter numbers are the same, some setting values differ. Refer to the following table and set the parameter.
List of FR-D700 series parameters compatible with the FR-S500 and S500E series
The following shows parameter settings when replacing the FR-S500 and S500E series by the FR-D700 series.
When the FR-S500 and FR-S500E series settings are changed from factory settings, set parameters of the FR-D700 series according to the following table.
When the FR-S500 and S500E series settings are factory settings, it is unnecessary to change parameters of the FR-D700 series.
Numbers of parameters differ from that of the Setting ◎: Set the same value as FR-S500 and S500E
FR-S500 and S500E series.
△: Setting needs to be changed from FR-S500
and S500E
X: Adjust and set on the FR-D700
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
0 Torque boost 0 to 15% Except for the 0 Torque boost 0 to 30% 0.75K or less: 6% △ If the setting of the S500 is the factory setting,
following: 6% 1.5K to 3.7K: 4% setting change is not required for D700.
S540-1.5K, 2.2K: 5.5K to 7.5K: 3% If there is a setting change, set an percentage ratio
5% of factory setting.
S540E-1.5K, 2.2K: (Example)
5% When the FR-S540-1.5K setting is 6%,
S540-3.7K: 4% set (6/5) x 4 = 4.8% for the FR-D740-1.5K.
S540E-3.7K: 4%
1 Maximum frequency 0 to 120Hz 60Hz 1 Maximum frequency 0 to 120Hz 120Hz ◎ Factory setting was changed.
7/19
28 Stall prevention operation 0 to 120Hz 60Hz 66 Stall prevention operation 0 to 400Hz 60Hz ◎
reduction starting frequency reduction starting frequency
29 Acceleration/deceleration 0, 1, 2 0 29 Acceleration/deceleration 0, 1, 2 0 ◎
pattern pattern selection
30 Extended function display 0, 1 0 160 Extended function display 0, 9999 9999 △ Set 0 to select extended mode.
selection selection
31 Frequency jump 1A 0 to 120Hz, --- --- 31 Frequency jump 1A 0 to 400Hz, 9999 9999 ◎
32 Frequency jump 1B 0 to 120Hz, --- --- 32 Frequency jump 1B 0 to 400Hz, 9999 9999 ◎
33 Frequency jump 2A 0 to 120Hz, --- --- 33 Frequency jump 2A 0 to 400Hz, 9999 9999 ◎
34 Frequency jump 2B 0 to 120Hz, --- --- 34 Frequency jump 2B 0 to 400Hz, 9999 9999 ◎
35 Frequency jump 3A 0 to 120Hz, --- --- 35 Frequency jump 3A 0 to 400Hz, 9999 9999 ◎
36 Frequency jump 3B 0 to 120Hz, --- --- 36 Frequency jump 3B 0 to 400Hz, 9999 9999 ◎
37 Speed display 0, 0.1 to 999 0 37 Speed display 0, 0.01 to 9998 0 ◎
BCN-C21002-106
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
38 Frequency setting voltage 1 to 120Hz 60Hz 125 Terminal 2 frequency setting 0 to 400Hz 60Hz △ Frequency at 5V(10V) input for the FR-S500, and
gain frequency gain frequency frequency to the voltage set with C4 for the
FR-D700. If frequencies do not match, calibrate
again.
39 Frequency setting current 1 to 120Hz 60Hz 126 Terminal 4 frequency setting 0 to 400Hz 60Hz △ Frequency at 20mA input for the FR-S500 and
gain frequency gain frequency frequency to the current set with C7 for the
FR-D700. If frequencies do not match, calibrate
again.
11) 11)
84 Multi-speed setting (speed 0 to 120Hz, --- --- 236 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
12) 12)
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
85 Multi-speed setting (speed 0 to 120Hz, --- --- 237 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
13) 13)
86 Multi-speed setting (speed 0 to 120Hz, --- --- 238 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
14) 14)
87 Multi-speed setting (speed 0 to 120Hz, --- --- 239 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
15) 15)
88 PID action selection 20, 21 20 128 PID action selection 0, 20, 21, 40 to 43 0 △ Set same value as S500.
89 PID proportional band 0.1 to 999%, --- 100% 129 PID proportional band 0.1 to 1000%, 9999 100% ◎
90 PID integral time 0.1 to 999s, --- 1s 130 PID integral time 0.1 to 3600s, 9999 1 ◎
91 PID upper limit 0 to 100%, --- --- 131 PID upper limit 0 to 100%, 9999 9999 ◎
92 PID lower limit 0 to 100%, --- --- 132 PID lower limit 0 to 100%, 9999 9999 ◎
93 PID action set point for PU 0 to 100% 0% 133 PID action set point 0 to 100%, 9999 9999 △ When using terminal 2 of D700 as set point, set
operation 9999. Note that, if a value other than 9999 is set for
D700, the value is used as the set point including
other operation mode.
94 PID differential time 0.01 to 10s, --- --- 134 PID differential time 0.01 to 10s, 9999 9999 ◎
95 Rated motor slip 0 to 50%, --- --- 245 Rated slip 0 to 50%, 9999 9999 ◎
96 Slip compensation time 0.01s to 10s 0.5s 246 Slip compensation time 0.01 to 10s 0 ◎
constant constant
97 Constant power range slip 0, --- --- 247 Constant-power range slip 0, 9999 9999 ◎
compensation selection compensation selection
98 Automatic torque boost 0.1 to 3.7kW --- 80 Motor capacity 0.1 to 7.5kW, 9999 9999 ◎ Use general-purpose magnetic flux vector control
selection for D700 if automatic torque boost is selected for
(Motor capacity) S500.
82 Motor excitation current 0 to 500A, 9999 9999 Set the same value as S500 in Pr. 80, and perform
11/19
×
83 Rated motor voltage 0 to 1000V 200/400V × auto tuning with setting Pr. 71, 83, and 84.
84 Rated motor frequency 10 to 120Hz 60Hz ×
99 Motor primary resistance 0 to 50Ω , --- --- 90 Motor constant (R1) 0 to 50Ω , 9999 9999 ×
96 Auto tuning setting/status 0, 11, 21 0 ×
C1 FM terminal calibration - - 900 FM terminal calibration - - ◎
(900)
C2 Frequency setting voltage 0 to 60Hz 0Hz 902 Terminal 2 frequency 0Hz △
0 to 400Hz Different calibration method
(902) bias frequency setting bias frequency
C3 Frequency setting voltage 0 to 300% 0% 902 Terminal 2 frequency 0% △
0 to 300% Different calibration method
(902) bias setting bias
903 Terminal 2 frequency 60Hz △
0 to 400Hz Different calibration method
setting gain frequency
C4 Frequency setting voltage 0 to 300% 96% 903 Terminal 2 frequency 0 to 300% 100% △ Different calibration method
(903) gain setting gain
C5 Frequency setting current 0 to 60Hz 0Hz 904 Terminal 4 frequency 0Hz △ Different calibration method
0 to 400Hz
(904) bias frequency setting bias frequency
C6 Frequency setting current 0 to 300% 20% 904 Terminal 4 frequency 0 to 300% 20% △ Different calibration method
(904) bias setting bias
905 Terminal 4 frequency 0 to 400Hz 60Hz △ Different calibration method
setting gain frequency
C7 Frequency setting current 0 to 300% 100% 905 Terminal 4 frequency 0 to 300% 100% △ Different calibration method
(905) gain setting gain
BCN-C21002-106
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
(The following parameters are available for FR-S500E)
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
H1(503) Maintenance timer 0 to 999 0 503 Maintenance timer 0 to 9998 0 - Read only
H2(504) Maintenance timer alarm 0 to 999, --- 36 504 Maintenance timer alarm 0 to 10s 0 △ To make the same setting as S500E, set a value of
output set time output set time 10 times of the S500.
H3(555) Current average time 0.1 to 1s 1s 555 Current average time 0.1 to 1s 1s ◎
H4(556) Data output mask time 0 to 20s 0s 556 Data output mask time 0 to 20s 0s ◎
H5(557) Current average value 0.1 to 999A 1A 557 Current average value 0 to 500A Rated inverter △ Set same value as S500E.
monitor signal output monitor signal output current
reference current reference current
H6(162) Automatic restart after 0, 1, 10 1 162 Automatic restart after 0, 1, 10, 11 1 ◎
instantaneous power failure instantaneous power failure
selection selection
H7(559) Second electronic thermal 0 to 50A, --- --- 51 Second electronic thermal 0 to 500A, 9999 9999 ◎
O/L relay O/L relay
b 1(560) Regenerative function 0, 1 0 30 Regenerative function 0, 1, 2 0 ◎
selection selection
b 2(561) Special regenerative brake 0 to 30% 0% 70 Special regenerative brake 0 to 30% 0% ◎
duty duty
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
(The following parameters are available for FR-S500-□k-R, FR-S500E)
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
n1(331) Communication station 0 to 31 0 117 PU communication station 0 to 31 0 ◎
number number
12/19
n2(332) Communication speed 48, 96, 192 192 118 PU communication speed 48, 96, 192, 384 192 ◎
n3(333) Stop bit length 0, 1, 10, 11 1 119 PU communication stop bit 0, 1, 10, 11 1 ◎
length
n4(334) Parity check 0, 1, 2 2 120 PU communication parity 0, 1, 2 2 ◎
presence/absence check
n5(335) Number of communication 0 to 10, --- 1 121 Number of PU 0 to 10, 9999 1 ◎
retries communication retries
n6(336) Communication check time 0 to 999s --- 122 PU communication check 0 to 999.8s, 9999 0 ◎
interval time interval
n7(337) Waiting time setting 0 to 150ms, --- --- 123 PU communication waiting 0 to 150ms, 9999 9999 △
time setting
n8(338) Operation command source 0, 1 0 338 Communication operation 0, 1 0 ◎
command source
n9(339) Speed command source 0, 1 0 339 Communication speed 0, 1, 2 0 ◎
command source
n10 Link startup mode selection 0, 1 0 340 Communication startup 0, 1, 10 0 ◎
(340) mode selection
n11 CR/LF selection 0, 1, 2 1 124 PU communication CR/LF 0, 1, 2 1 ◎
(341) selection
n12 EEPROM write selection 0, 1 0 342 Communication E2PROM 0, 1 0 ◎
(342) write selection
n13 PU display language 0 to 7 0 145 PU display language 0 to 7 0 ◎
(145) selection selection
n14 PU buzzer control 0, 1 1 990 PU buzzer control 0, 1 1 ◎
BCN-C21002-106
(990)
n15 PU contrast adjustment 0 to 63 58 991 PU contrast adjustment 0 to 63 58 ◎
(991)
n16 PU main display screen 0, 100 0 Set by Pr. 52
(992) data selection
n17 Disconnected PU 0, 1, 10 0 75 Reset selection 0 to 3, 14 to 17 14 △ Set 14 when a setting value of S500 and S500E is
(993) detection/PU setting lock /disconnected PU detection 0, 10, or set 16 when a setting value of S500 and
/PU stop selection S500E is 1.
4. Option
The following shows the compatibility of options used with the FR-S500 (S500E) series on the
FR-D700 series.
Option Type
Name
FR-S500, S500E FR-D700
There are some restrictions, such as parameter
Parameter unit FR-PU04
copy is invalid, etc.
Parameter unit
FR-CB201, 203, 205 Compatible
connection cable
MRS□□, MYS□□ Compatible
Brake resistor
FR-ABR-(H)□□K Compatible
BU-1500 to 15K, H7.5K,
Brake unit Compatible
H15K
Discharging
GZG□□, GRZG□□ Compatible
resistor
Power factor improving
FR-BAL-(H)□□K Compatible
Stand-alone
AC reactor
Power factor improving
FR-BEL-(H)□□K Compatible
DC reactor
Capacitor type filter FR-BIF-(H) Compatible
Common mode filter FR-BSF01、FR-BLF Compatible
FR-CV type power
regeneration common FR-CV-(H)7.5K(-AT) Compatible
converter
Dedicated,
standalone FR-CVL-(H)7.5K Compatible
reactor
FR-HC type high power
FR-HC-(H)7.5K Compatible
factor converter
Surge voltage
FR-ASF-H□□K Compatible
suppression filter
Manual controller FR-AX Compatible
Manual controller/speed
potentiometer
Frequency meter YM206NRI 1mA Compatible
Calibration resistor RV24YN 10kΩ Compatible
Not compatible.
Inverter setup software FR-SW1-SETUP-WJ
(compatible with the FR-SW3-SETUP-WJ)
13/19 BCN-C21002-106
5. Main differences with the FR-S500, S500E series
1) Main specification comparison and differences
Item FR-S500, S500E FR-D700
Three-phase FR-S520(E)-0.1K to 3.7K
(To be released)
200V class (seven models)
Three-phase FR-S540(E)-0.4K to 3.7K FR-D740-0.4K to 15K (nine models)
400V class (five models) (11K and 15K will be released)
Model
Single phase FR-S520S(E)-0.1K to 1.5K
(To be released)
200V class (five models)
Single phase FR-S510W (E)-0.1K to 0.75K
(To be released)
100V class (four models)
Soft-PWM control/high carrier frequency PWM
Soft-PWM control/high carrier
control
frequency PWM control
(V/F control, general-purpose magnetic flux vector
Control method (V/F control, or automatic torque
control, optimum excitation control can be selected)
boost control can be selected)
Long wiring mode became unnecessary and was
Long wiring mode
deleted.
150% 60s, 200% 0.5s
Overload capacity 150% 60s, 200% 0.5s (inverse-time characteristics)
(inverse-time characteristics)
Terminal 2: 0 to 10V, 0 to 5V can Terminal 2: 0 to 10V, 0 to 5V can be selected
Frequency Analog input be selected Terminal 4: 0 to 10V, 0 to 5V, 4 to 20mA can be
setting Terminal 4: 4 to 20mA selected
signal Input using the setting dial of the Input using the setting dial of the operation panel or
Digital input
operation panel or parameter unit parameter unit
<Additional function>
Inverter operation enable (X10),
PU operation external interlock (X12),
Terminal
Magnetic flux vector/V/F switchover (X18),
function
PU-NET operation switchover (X65),
Input signal External-NET operation switchover (X66),
Command source switchover (X67)
Terminal
Pr.60 to Pr.63 (input terminal
function Addition of Pr.178 (STF)
function selection)
selection
<Additional function>
Regeneration brake pre-alarm (RBP), electronic
thermal pre-alarm (THP), brake opening request
(BOF), fan failure (FAN), heatsink overheat
Terminal With current average value pre-alarm (FIN), deceleration at an instantaneous
function monitor (Y93) power failure (Y46), PID control activated (PID),
during retry (Y46), PID output interruption (SLEEP),
life alarm (Y90), current average value monitor
(Y93)
*Negative logic is added to all terminal functions
Output
signal
<Additional function>
Output voltage, frequency setting value, converter
output voltage, regenerative brake duty, electronic
thermal relay function load factor, output current
Output signal Output frequency and output
peak value, converter output voltage peak value,
for indicator voltage only
output power, reference voltage output, motor load
factor, cumulative power, PID set point, PID
measured value, PID deviation, motor thermal load
factor, inverter thermal load factor
<Additional function>
Input phase loss, brake transistor alarm, output
phase loss, output current detection value excess,
inrush resistor overheat, communication alarm,
Protective/warning function With brake transistor alarm
analog input alarm, PTC thermistor operation, safety
circuit alarm, regeneration brake pre-alarm,
electronic thermal pre-alarm, maintenance output,
operation panel lock, password locked, safety input
14/19 BCN-C21002-106
Item FR-S500, S500E FR-D700
Outline dimension Compatible
Installation size Compatible
Main circuit terminal block Compatible (screw type terminal block)
Fixed insertion terminal block Refer to
Control circuit terminal block Flathead screw M3: ABC terminal Spring clamp terminal
and screw size Flathead screw M2: except for ABC 1. Size
terminal
Control terminal cable size 2 2
0.3 to 0.75mm 0.3 to 1.5mm
when bar terminal is used
For all capacities, fans are
placed on top of the inverter.
Cooling fan position Placed below the inverter Clearance is necessary in
the above for replacement of
the cooling fan.
Operation panel Integrated to the body, not removable. Integrated to the body, not removable.
Compatible with the conventional models (some functions were partially changed or
Parameter (function)
deleted)
FR-PU07 Compatible Compatible
FR-PU04 Compatible Compatible (partially restricted)
Parameter FR-PU03
unit /FR-ARW03
Not compatible Not compatible
FR-DU01
FR-PU02/FR-ARW
PU FR-CB2□□ Compatible Compatible
connection Not compatible Not compatible
cable FR-CBL□□
Plug-in option Not compatible Not compatible
Provided with all capacity
Inrush current limit circuit Provided with all capacity
Cooling fan 2 to 3 years 10 years
Design life Electrolytic
5 years 10 years
capacitor
Stand-alone option Compatible
Refer to 4. Option
(noise filter, reactor, etc.)
15/19 BCN-C21002-106
2) Parameter comparison description and main difference
Main differences with the
FR-S500 and S500E
Parameter
Item
Parameter
Comparison Remarks
Function
function
number
change
change
change
Added
Name
Description
16/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item
Parameter
Comparison Remarks
Function
function
number
change
change
change
Added
Name
Description
17/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item
Parameter
Comparison Remarks
Function
function
number
change
change
change
Added
Name
Description
18/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item
Parameter
Comparison Remarks
Function
function
number
change
change
change
Added
Name
Description
19/19 BCN-C21002-106