Information For Replacement of The FR-S500 (S500E) Series by The FR-D700 Series

Download as pdf or txt
Download as pdf or txt
You are on page 1of 19

Information for Replacement of the FR-S500

(S500E) Series by the FR-D700 Series

Size, connection, and parameter concerning replacement are stated from the next page.

1/19 BCN-C21002-106
1. Size
The installation size of the FR-S500 (S500E) series and of the FR-D700 series is the same.
For details of size, refer to the outline dimension drawings on the next page and later.

Power Supply
Installed Inverter Replacing Inverter Installation Size
Voltage
FR-S540(E)-0.4K FR-D740-0.4K Same size
FR-S540(E)-0.75K FR-D740-0.75K Same size
Three phase
FR-S540(E)-1.5K FR-D740-1.5K Same size
400V
FR-S540(E)-2.2K FR-D740-2.2K Same size
FR-S540(E)-3.7K FR-D740-3.7K Same size
*The installation size of the FR-S500E series is the same as the FR-S500 series.

2/19 BCN-C21002-106
Outline dimension drawing (Unit: mm)

FR-S540(E)-0.4K to 3.7K FR-D740-0.4K to 3.7K

2-Φ5hole
2-Φ5hole

Cooling fan

Inverter Type D D1 D2 D3 Inverter Type D D1


FR-S540(E)-0.4K FR-D740-0.4K
129.5 59 52 5 129.5 54
FR-S540(E)-0.75K FR-D740-0.75K
FR-S540(E)-1.5K 135.5 65 52 8 FR-D740-1.5K 135.5 60
FR-S540(E)-2.2K 155.5 65 72 8 FR-D740-2.2K 155.5 60
FR-S540(E)-3.7K 165.5 65 82 8 FR-D740-3.7K 165.5 60
(Note) The 0.4K and the 0.75K do not have a (Note) The 0.4K and the 0.75K do not have
cooling fan. a cooling fan.

3/19 BCN-C21002-106
2. Connection
Since terminal names are the same, connect according to the names.
Refer to page 5, 6 for terminal size.

[Standard type inverter]


FR-S500 FR-S500E FR-D700
Type Terminal Terminal Compatible Remarks
Name Name Terminal Name
R, S, T R, S, T R/L1, S/L2, T/L3
U, V, W U, V, W U, V, W
FR-S500 does not have PR
terminal.
P/+, PR P/+, PR For the FR-S500E, only
Main Circuit FR-S520E-0.4K to 3.7K has PR
terminal.
FR-S520E-0.1K to 0.75K do not
P, N P/+, N/- P/+, N/-
have N/- terminal.
P, P1 P/+, P1 P/+, P1

STF STF STF


STR STR STR
Control RH RH RH
Contact

circuit/input RM RM RM
signal RL RL RL
SD SD SD Isolated from terminals 5 and SE.
PC PC PC
10 10 10
Frequency

2 2 2
setting

Analog 5 5 5 Isolated from terminals SD and


SE.
4 4 4
Contact

A, B, C A, B, C A, B, C

RUN RUN RUN


collector
Open

Control circuit
output signal SE SE SE Isolated from terminals 5 and SD.
Pulse

FM FM FM

For the FR-S500, FR-S500-□K-R


RS-485

PU connector PU and FR-S500E have PU


Communication PU connector connector.
(-R type only) connector

4/19 BCN-C21002-106
Terminal Size

[Main circuit terminal]


FR-S500 FR-S500E FR-D700
Voltage R/L1,
Capacity U, V, R, S, U, V, P/+, N/-*1 P/+, N/-
Class R, S, T P, N, P1 S/L2, U, V, W
W T W P1, PR*2 P1, PR
T/L3
Three
0.4K to
phase M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4
3.7K
400V
*1 FR-S520E-0.1K to 0.75K do not have N/- terminal.
*2 Only FR-S520E-0.4K to 3.7K have PR terminal.
5/19
BCN-C21002-106

5/19 BCN-C21002-106
[Control circuit terminal]
FR-S500, S500E FR-D700
Control circuit Control circuit
Except for A, B, C A, B, C
M2 insertion type M3 insertion type Spring clamp terminal
flathead screw flathead screw
terminal terminal

(Note 1) In case when using bar terminals of Phoenix Contact Co., Ltd. introduced for the FR-S500, S500E, they are not compatible with the
FR-D700 since it does not match with the spring clamp terminal block. (Depends on the size difference of a bar terminal, some other bar
terminal may not be wired to the FR-D700.)
In such a case, cut the bar terminal and strip off the wire to make it a bare wire, or use bar terminals introduced below. Also check for the
applicable wire size.

Table. FR-D700 control terminal block applicable wire size (bare wire)
Wire Stripping Size Applicable Bare Wire Size
Single wire (mm2)
6/19

Wire the stripped cable after twisting


it to prevent it from becoming loose.
10mm
In addition, do not solder it. 0.3 to 0.75

Table. FR-D700 control terminal block applicable wire size (bar terminal)
Bar Terminal Type (Phoenix Contact Co., Ltd.)
Applicable Wire Size (mm2)
With insulation sleeve Without insulation sleeve
AI 0.5-10WH - 0.3 to 0.5
AI 0.75-10GY AI 0.75-10 0.75
AI 1-10RD A 1-10 1
AI 1.5-10BK AI 1.5-10 1.25, 1.5
BCN-C21002-106

AI-TWIN 2×0.75-GY - 0.75 (for two wires)


*The bar terminal length of the FR-D700 series and FR-S500 and FR-S500E series are different.
(FR-D700 series: 10mm, FR-S500, FR-S500E series: 6mm)

6/19 BCN-C21002-106
3. Parameter
Although most parameter numbers are the same, some setting values differ. Refer to the following table and set the parameter.

List of FR-D700 series parameters compatible with the FR-S500 and S500E series

The following shows parameter settings when replacing the FR-S500 and S500E series by the FR-D700 series.
When the FR-S500 and FR-S500E series settings are changed from factory settings, set parameters of the FR-D700 series according to the following table.
When the FR-S500 and S500E series settings are factory settings, it is unnecessary to change parameters of the FR-D700 series.

Numbers of parameters differ from that of the Setting ◎: Set the same value as FR-S500 and S500E
FR-S500 and S500E series.
△: Setting needs to be changed from FR-S500
and S500E
X: Adjust and set on the FR-D700
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
0 Torque boost 0 to 15% Except for the 0 Torque boost 0 to 30% 0.75K or less: 6% △ If the setting of the S500 is the factory setting,
following: 6% 1.5K to 3.7K: 4% setting change is not required for D700.
S540-1.5K, 2.2K: 5.5K to 7.5K: 3% If there is a setting change, set an percentage ratio
5% of factory setting.
S540E-1.5K, 2.2K: (Example)
5% When the FR-S540-1.5K setting is 6%,
S540-3.7K: 4% set (6/5) x 4 = 4.8% for the FR-D740-1.5K.
S540E-3.7K: 4%
1 Maximum frequency 0 to 120Hz 60Hz 1 Maximum frequency 0 to 120Hz 120Hz ◎ Factory setting was changed.
7/19

2 Minimum frequency 0 to 120Hz 0Hz 2 Minimum frequency 0 to 120Hz 0Hz ◎


3 Base frequency 0 to 120Hz 60Hz 3 Base frequency 0 to 400Hz 60Hz ◎
4 Multi-speed setting (high 0 to 120Hz 60Hz 4 Multi-speed setting (high 0 to 400Hz 60Hz ◎
speed) speed)
5 Multi-speed setting (middle 0 to 120Hz 30Hz 5 Multi-speed setting (middle 0 to 400Hz 30Hz ◎
speed) speed)
6 Multi-speed setting (low 0 to 120Hz 10Hz 6 Multi-speed setting (low 0 to 400Hz 10Hz ◎
speed) speed)
7 Acceleration time 0 to 999s 5s 7 Acceleration time 0 to 3600s 3.7K or less: 5s ◎
5.5K or more: 10s
8 Deceleration time 0 to 999s 5s 8 Deceleration time 0 to 3600s 3.7K or less: 5s ◎
5.5K or more: 10s
9 Electronic thermal O/L relay 0 to 50A Rated output 9 Electronic thermal O/L relay 0 to 500A Rated output current ◎ Set the rated motor current.
current
10 DC injection brake 0 to 120Hz 3Hz 10 DC injection brake 0 to 120Hz 3Hz ◎
operation frequency operation frequency
11 DC injection brake 0 to 10s 0.5s 11 DC injection brake 0 to 10s 0.5s ◎
operation time operation time
12 DC injection brake voltage 0 to 15% 6% 12 DC injection brake 0 to 30% 0.1K, 0.2K: 6% △ If the setting of the S500 is the factory setting,
operation voltage 0.4K to 7.5K: 4% setting change is not required for D700. If there is
a setting change, set an percentage ratio of factory
setting.
(Example)
When the FR-S540-7.5K setting is 7%,
BCN-C21002-106

set (7/6) x 4 = 4.7% for the FR-D740-7.5K.


Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
13 Starting frequency 0 to 60Hz 0.5Hz 13 Starting frequency 0 to 60Hz 0.5Hz ◎
14 Load pattern selection 0 to 3 0 14 Load pattern selection 0 to 3 0 ◎
15 Jog frequency 0 to 120Hz 5Hz 15 Jog frequency 0 to 400Hz 5Hz ◎
16 Jog acceleration/ 0 to 999s 0.5s 16 Jog acceleration/ 0 to 3600s 0.5s ◎
deceleration time deceleration time
17 RUN key rotation direction 0, 1 0 40 RUN key rotation direction 0, 1 0 ◎
selection selection
19 Base frequency voltage 0 to 1000V, 888, --- --- 19 Base frequency voltage 0 to 1000V, 8888, 9999 9999 ◎
20 Acceleration/deceleration 1 to 120Hz 60Hz 20 Acceleration/deceleration 1 to 400Hz 60Hz ◎
reference frequency reference frequency
21 Stall prevention function 0 to 31, 100 0 156 Stall prevention operation 0 to 31, 100, 101 0 ◎
selection selection
22 Stall prevention operation 0 to 200% 150% 22 Stall prevention operation 0 to 200% 150% ◎
level level
23 Stall prevention operation 0 to 200%, --- --- 23 Stall prevention operation 0 to 200%, 9999 9999 ◎
level compensation factor level compensation factor at
at double speed double speed
24 Multi-speed setting (speed 0 to 120Hz, --- --- 24 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
4) 4)
25 Multi-speed setting (speed 0 to 120Hz, --- --- 25 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
5) 5)
26 Multi-speed setting (speed 0 to 120Hz, --- --- 26 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
6) 6)
27 Multi-speed setting (speed 0 to 120Hz, --- --- 27 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
7) 7)
8/19

28 Stall prevention operation 0 to 120Hz 60Hz 66 Stall prevention operation 0 to 400Hz 60Hz ◎
reduction starting frequency reduction starting frequency
29 Acceleration/deceleration 0, 1, 2 0 29 Acceleration/deceleration 0, 1, 2 0 ◎
pattern pattern selection
30 Extended function display 0, 1 0 160 Extended function display 0, 9999 9999 △ Set 0 to select extended mode.
selection selection
31 Frequency jump 1A 0 to 120Hz, --- --- 31 Frequency jump 1A 0 to 400Hz, 9999 9999 ◎
32 Frequency jump 1B 0 to 120Hz, --- --- 32 Frequency jump 1B 0 to 400Hz, 9999 9999 ◎
33 Frequency jump 2A 0 to 120Hz, --- --- 33 Frequency jump 2A 0 to 400Hz, 9999 9999 ◎
34 Frequency jump 2B 0 to 120Hz, --- --- 34 Frequency jump 2B 0 to 400Hz, 9999 9999 ◎
35 Frequency jump 3A 0 to 120Hz, --- --- 35 Frequency jump 3A 0 to 400Hz, 9999 9999 ◎
36 Frequency jump 3B 0 to 120Hz, --- --- 36 Frequency jump 3B 0 to 400Hz, 9999 9999 ◎
37 Speed display 0, 0.1 to 999 0 37 Speed display 0, 0.01 to 9998 0 ◎
BCN-C21002-106
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
38 Frequency setting voltage 1 to 120Hz 60Hz 125 Terminal 2 frequency setting 0 to 400Hz 60Hz △ Frequency at 5V(10V) input for the FR-S500, and
gain frequency gain frequency frequency to the voltage set with C4 for the
FR-D700. If frequencies do not match, calibrate
again.
39 Frequency setting current 1 to 120Hz 60Hz 126 Terminal 4 frequency setting 0 to 400Hz 60Hz △ Frequency at 20mA input for the FR-S500 and
gain frequency gain frequency frequency to the current set with C7 for the
FR-D700. If frequencies do not match, calibrate
again.

40 Start-time earth(ground) 0, 1 0 249 Earth (ground) fault 0, 1 0 ◎


fault detection selection detection at start
41 Up-to-frequency sensitivity 0 to 100% 10% 41 Up-to-frequency sensitivity 0 to 100% 10% ◎
42 Output frequency detection 0 to 120Hz 6Hz 42 Output frequency detection 0 to 400Hz 6Hz ◎
43 Output frequency detection 0 to 120Hz, --- --- 43 Output frequency detection 0 to 400Hz, 9999 9999 ◎
for reverse rotation for reverse rotation
44 Second acceleration/ 0 to 999s 5s 44 Second 0 to 3600s 3.7K or less: 5s ◎
deceleration time acceleration/deceleration 5.5K, 7.5K: 10s
time
45 Second deceleration time 0 to 999s, --- - 45 Second deceleration time 0 to 3600s, 9999 9999 ◎
46 Second torque boost 0 to 15%, --- --- 46 Second torque boost 0 to 30%, 9999 9999 △ Set same value as S500.
(When PWM frequency selection Pr. 72 = 1 for
E500)
47 Second V/F (base 0 to 120Hz, --- --- 47 Second V/F (base 0 to 400Hz, 9999 9999 ◎
frequency) frequency)
48 Output current detection 0 to 200% 150% 150 Output current detection 0 to 200% 150% ◎
level level
9/19

49 Output current detection 0 to 10s 0s 151 Output current detection 0 to 10s 0s ◎


signal delay time delay time
50 Zero current detection level 0 to 200% 5% 152 Zero current detection level 0 to 200% 5% ◎
51 Zero current detection 0.05 to 1s 0.5s 153 Zero current detection time 0 to 1s 0.5s ◎
period
52 Control panel display data 0, 1, 100 0 52 DU/PU main display data 0, 5, 7 to 12, 14, 20, 0 ◎ When Pr. 52 = 23, unit of actual operation time is
selection selection 23 to 25, 52 to 57, different.
61, 62, 100
53 Frequency setting operation 0, 1 0 161 Frequency setting/key lock 0, 1, 10, 11 0 ◎
selection operation selection
54 FM terminal function 0, 1 0 54 FM terminal function 1 to 3, 5, 7 to 12, 14, 1 △ Set 1 when a setting value of S500 is 0, or set 2
selection selection 21, 24, 52, 53, 61, 62 when a setting value of S500 is 1.
55 Frequency monitoring 0 to 120Hz 60Hz 55 Frequency monitoring 0 to 400Hz 60Hz ◎
reference reference
56 Current monitoring 0 to 50A Rated output 56 Current monitoring 0 to 500A Rated output current ◎
reference current reference
57 Restart coasting time 0 to 5s, --- --- 57 Restart coasting time 0, 0.1 to 5.8s, 9999 9999 △ When Pr.57 = 0, coasting time is different.
Generally, setting is not required. To make the time
same as S500, set 0.5s for 1.5K or less, or set 1.0s
for 2.2K or more.
58 Restart cushion time 0 to 60s 1.0s 58 Restart cushion time 0 to 60s 1.0s ◎
59 Remote setting function 0, 1, 2 0 59 Remote function selection 0, 1, 2, 3 0 ◎
selection
BCN-C21002-106
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
60 RL terminal function 0, 1, 2, 3, 4, 5, 6, 7, 8, 0 180 RL terminal function 0 to 5, 7, 8, 10, 12, 14, 16, 0 ◎
selection 9, 10, 14, 16、--- selection 18, 24, 25, 62, 65 to 67,
61 RM terminal function 1 181 RM terminal function 9999 1 ◎
selection selection
62 RH terminal function 2 182 RH terminal function 2 ◎
selection selection
63 STR terminal function --- 179 STR terminal function 61 ◎
selection selection
64 RUN terminal function 0, 1, 2, 3, 4, 5, 6, 7, 8, 0 190 RUN terminal function 0, 1, 3, 4, 7, 8, 11 to 16, 0 ◎
selection 9, 10, 14, 15, 16, 93, selection 25, 26, 46, 47, 64, 70, 90,
65 A, B, C terminal function 95, 98, 99 99 192 A, B, C terminal function 91, 95, 96, 98, 99, 100, 99 ◎
selection selection 101, 103, 104, 107, 108,
111 to 116, 125, 126, 146,
147, 164, 170, 190, 191,
195, 196, 198, 199, 9999
66 Retry selection 0, 1, 2, 3 0 65 Retry selection 0 to 5 0 ◎
67 Number of retries at alarm 0 to 10, 101 to 110 0 67 Number of retries at fault 0 to 10, 101 t o110 0 ◎
occurrence occurrence
68 Retry waiting time 0.1 to 360s 1s 68 Retry waiting time 0.1 to 360s 1s ◎
69 Retry count display erase 0 0 69 Retry count display erase 0 0 ◎
70 Soft-PWM setting S500:0, 1 1 240 Soft-PWM operation 0, 1 1 △ Set 0 when a setting value of S500E is 10, and set
S500E:0, 1, 10, 11 selection 1 when a setting value of S500E is 11.
71 Applied motor S500:0, 1 0 71 Applied motor 0, 1, 3 to 6, 13 to 16, 23, 0 △ When 100s value is set for S500E, set a value
S500E:0, 1, 100, 101 24, 40, 43, 44, 50, 53, 54 taking 100 from the value, and set Pr. 450 = 1.
450 Second applied motor 0, 1, 9999 9999 ×
10/19

72 PWM frequency selection 0 to 15 1 72 PWM frequency selection 0 to 15 1 ◎


73 0-5V/0-10V selection 0, 1 0 73 Analog input selection 0, 1, 10, 11 1 △ Set 1 when a setting value of S500 and S500E is 0,
or set 0 when a setting value of S500 and S500E is
1.
74 Input filter time constant 0 to 8 1 74 Input filter time constant 0 to 8 1 ◎

75 Reset selection/PU stop 0, 1, 14, 15, 14 75 Reset selection 0 to 3, 14 to 17 14 ◎


selection /disconnected PU detection
/PU stop selection
76 Cooling fan operation 0, 1 1 244 Cooling fan operation 0, 1 1 ◎
selection selection
77 Parameter write disable 0, 1, 2 0 77 Parameter write selection 0, 1, 2 0 ◎
selection
78 Reverse rotation prevention 0, 1, 2 0 78 Reverse rotation prevention 0, 1, 2 0 ◎
selection selection
79 Operation mode selection 0 to 4, 7, 8 0 79 Operation mode selection 0 to 4, 6, 7 0 △ If the setting of the S500 is 8, set Pr. 79 = 7 and Pr.
182 = 16 for D700.
80 Multi-speed setting (speed 0 to 120Hz, --- --- 232 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
8) 8)
81 Multi-speed setting (speed 0 to 120Hz, --- --- 233 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
9) 9)
82 Multi-speed setting (speed 0 to 120Hz, --- --- 234 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
10) 10)
83 Multi-speed setting (speed 0 to 120Hz, --- --- 235 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
BCN-C21002-106

11) 11)
84 Multi-speed setting (speed 0 to 120Hz, --- --- 236 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
12) 12)
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
85 Multi-speed setting (speed 0 to 120Hz, --- --- 237 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
13) 13)
86 Multi-speed setting (speed 0 to 120Hz, --- --- 238 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
14) 14)
87 Multi-speed setting (speed 0 to 120Hz, --- --- 239 Multi-speed setting (speed 0 to 400Hz, 9999 9999 ◎
15) 15)
88 PID action selection 20, 21 20 128 PID action selection 0, 20, 21, 40 to 43 0 △ Set same value as S500.
89 PID proportional band 0.1 to 999%, --- 100% 129 PID proportional band 0.1 to 1000%, 9999 100% ◎
90 PID integral time 0.1 to 999s, --- 1s 130 PID integral time 0.1 to 3600s, 9999 1 ◎
91 PID upper limit 0 to 100%, --- --- 131 PID upper limit 0 to 100%, 9999 9999 ◎
92 PID lower limit 0 to 100%, --- --- 132 PID lower limit 0 to 100%, 9999 9999 ◎
93 PID action set point for PU 0 to 100% 0% 133 PID action set point 0 to 100%, 9999 9999 △ When using terminal 2 of D700 as set point, set
operation 9999. Note that, if a value other than 9999 is set for
D700, the value is used as the set point including
other operation mode.
94 PID differential time 0.01 to 10s, --- --- 134 PID differential time 0.01 to 10s, 9999 9999 ◎
95 Rated motor slip 0 to 50%, --- --- 245 Rated slip 0 to 50%, 9999 9999 ◎
96 Slip compensation time 0.01s to 10s 0.5s 246 Slip compensation time 0.01 to 10s 0 ◎
constant constant
97 Constant power range slip 0, --- --- 247 Constant-power range slip 0, 9999 9999 ◎
compensation selection compensation selection
98 Automatic torque boost 0.1 to 3.7kW --- 80 Motor capacity 0.1 to 7.5kW, 9999 9999 ◎ Use general-purpose magnetic flux vector control
selection for D700 if automatic torque boost is selected for
(Motor capacity) S500.
82 Motor excitation current 0 to 500A, 9999 9999 Set the same value as S500 in Pr. 80, and perform
11/19

×
83 Rated motor voltage 0 to 1000V 200/400V × auto tuning with setting Pr. 71, 83, and 84.
84 Rated motor frequency 10 to 120Hz 60Hz ×
99 Motor primary resistance 0 to 50Ω , --- --- 90 Motor constant (R1) 0 to 50Ω , 9999 9999 ×
96 Auto tuning setting/status 0, 11, 21 0 ×
C1 FM terminal calibration - - 900 FM terminal calibration - - ◎
(900)
C2 Frequency setting voltage 0 to 60Hz 0Hz 902 Terminal 2 frequency 0Hz △
0 to 400Hz Different calibration method
(902) bias frequency setting bias frequency
C3 Frequency setting voltage 0 to 300% 0% 902 Terminal 2 frequency 0% △
0 to 300% Different calibration method
(902) bias setting bias
903 Terminal 2 frequency 60Hz △
0 to 400Hz Different calibration method
setting gain frequency
C4 Frequency setting voltage 0 to 300% 96% 903 Terminal 2 frequency 0 to 300% 100% △ Different calibration method
(903) gain setting gain
C5 Frequency setting current 0 to 60Hz 0Hz 904 Terminal 4 frequency 0Hz △ Different calibration method
0 to 400Hz
(904) bias frequency setting bias frequency
C6 Frequency setting current 0 to 300% 20% 904 Terminal 4 frequency 0 to 300% 20% △ Different calibration method
(904) bias setting bias
905 Terminal 4 frequency 0 to 400Hz 60Hz △ Different calibration method
setting gain frequency
C7 Frequency setting current 0 to 300% 100% 905 Terminal 4 frequency 0 to 300% 100% △ Different calibration method
(905) gain setting gain
BCN-C21002-106
Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
(The following parameters are available for FR-S500E)
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
H1(503) Maintenance timer 0 to 999 0 503 Maintenance timer 0 to 9998 0 - Read only
H2(504) Maintenance timer alarm 0 to 999, --- 36 504 Maintenance timer alarm 0 to 10s 0 △ To make the same setting as S500E, set a value of
output set time output set time 10 times of the S500.
H3(555) Current average time 0.1 to 1s 1s 555 Current average time 0.1 to 1s 1s ◎
H4(556) Data output mask time 0 to 20s 0s 556 Data output mask time 0 to 20s 0s ◎
H5(557) Current average value 0.1 to 999A 1A 557 Current average value 0 to 500A Rated inverter △ Set same value as S500E.
monitor signal output monitor signal output current
reference current reference current
H6(162) Automatic restart after 0, 1, 10 1 162 Automatic restart after 0, 1, 10, 11 1 ◎
instantaneous power failure instantaneous power failure
selection selection
H7(559) Second electronic thermal 0 to 50A, --- --- 51 Second electronic thermal 0 to 500A, 9999 9999 ◎
O/L relay O/L relay
b 1(560) Regenerative function 0, 1 0 30 Regenerative function 0, 1, 2 0 ◎
selection selection
b 2(561) Special regenerative brake 0 to 30% 0% 70 Special regenerative brake 0 to 30% 0% ◎
duty duty

Parameter List of FR-S500 and S500E FR-D700 Compatible Parameters Parameter Setting
(The following parameters are available for FR-S500-□k-R, FR-S500E)
Function Name Setting Range Factory Setting Function Name Setting Range Factory Setting Setting Remarks
Number Number
n1(331) Communication station 0 to 31 0 117 PU communication station 0 to 31 0 ◎
number number
12/19

n2(332) Communication speed 48, 96, 192 192 118 PU communication speed 48, 96, 192, 384 192 ◎
n3(333) Stop bit length 0, 1, 10, 11 1 119 PU communication stop bit 0, 1, 10, 11 1 ◎
length
n4(334) Parity check 0, 1, 2 2 120 PU communication parity 0, 1, 2 2 ◎
presence/absence check
n5(335) Number of communication 0 to 10, --- 1 121 Number of PU 0 to 10, 9999 1 ◎
retries communication retries
n6(336) Communication check time 0 to 999s --- 122 PU communication check 0 to 999.8s, 9999 0 ◎
interval time interval
n7(337) Waiting time setting 0 to 150ms, --- --- 123 PU communication waiting 0 to 150ms, 9999 9999 △
time setting
n8(338) Operation command source 0, 1 0 338 Communication operation 0, 1 0 ◎
command source
n9(339) Speed command source 0, 1 0 339 Communication speed 0, 1, 2 0 ◎
command source
n10 Link startup mode selection 0, 1 0 340 Communication startup 0, 1, 10 0 ◎
(340) mode selection
n11 CR/LF selection 0, 1, 2 1 124 PU communication CR/LF 0, 1, 2 1 ◎
(341) selection
n12 EEPROM write selection 0, 1 0 342 Communication E2PROM 0, 1 0 ◎
(342) write selection
n13 PU display language 0 to 7 0 145 PU display language 0 to 7 0 ◎
(145) selection selection
n14 PU buzzer control 0, 1 1 990 PU buzzer control 0, 1 1 ◎
BCN-C21002-106

(990)
n15 PU contrast adjustment 0 to 63 58 991 PU contrast adjustment 0 to 63 58 ◎
(991)
n16 PU main display screen 0, 100 0 Set by Pr. 52
(992) data selection
n17 Disconnected PU 0, 1, 10 0 75 Reset selection 0 to 3, 14 to 17 14 △ Set 14 when a setting value of S500 and S500E is
(993) detection/PU setting lock /disconnected PU detection 0, 10, or set 16 when a setting value of S500 and
/PU stop selection S500E is 1.
4. Option
The following shows the compatibility of options used with the FR-S500 (S500E) series on the
FR-D700 series.
Option Type
Name
FR-S500, S500E FR-D700
There are some restrictions, such as parameter
Parameter unit FR-PU04
copy is invalid, etc.
Parameter unit
FR-CB201, 203, 205 Compatible
connection cable
MRS□□, MYS□□ Compatible
Brake resistor
FR-ABR-(H)□□K Compatible
BU-1500 to 15K, H7.5K,
Brake unit Compatible
H15K
Discharging
GZG□□, GRZG□□ Compatible
resistor
Power factor improving
FR-BAL-(H)□□K Compatible
Stand-alone

AC reactor
Power factor improving
FR-BEL-(H)□□K Compatible
DC reactor
Capacitor type filter FR-BIF-(H) Compatible
Common mode filter FR-BSF01、FR-BLF Compatible
FR-CV type power
regeneration common FR-CV-(H)7.5K(-AT) Compatible
converter
Dedicated,
standalone FR-CVL-(H)7.5K Compatible
reactor
FR-HC type high power
FR-HC-(H)7.5K Compatible
factor converter
Surge voltage
FR-ASF-H□□K Compatible
suppression filter
Manual controller FR-AX Compatible
Manual controller/speed

DC tach. follower FR-AL Compatible


Three speed selector FR-AT Compatible
Remote speed setter FR-FK Compatible
controller

Ratio setter FR-FH Compatible


Speed detector FR-FP Compatible
Master controller FR-FG Compatible
Soft starter FR-FC Compatible
Deviation detector FR-FD Compatible
Preamplifier FR-FA Compatible
Pilot generator QVAH-10 Compatible
Deviation sensor YVGC-500W-NS Compatible
Frequency setting
WA2W 1kΩ Compatible
Others

potentiometer
Frequency meter YM206NRI 1mA Compatible
Calibration resistor RV24YN 10kΩ Compatible
Not compatible.
Inverter setup software FR-SW1-SETUP-WJ
(compatible with the FR-SW3-SETUP-WJ)

13/19 BCN-C21002-106
5. Main differences with the FR-S500, S500E series
1) Main specification comparison and differences
Item FR-S500, S500E FR-D700
Three-phase FR-S520(E)-0.1K to 3.7K
(To be released)
200V class (seven models)
Three-phase FR-S540(E)-0.4K to 3.7K FR-D740-0.4K to 15K (nine models)
400V class (five models) (11K and 15K will be released)
Model
Single phase FR-S520S(E)-0.1K to 1.5K
(To be released)
200V class (five models)
Single phase FR-S510W (E)-0.1K to 0.75K
(To be released)
100V class (four models)
Soft-PWM control/high carrier frequency PWM
Soft-PWM control/high carrier
control
frequency PWM control
(V/F control, general-purpose magnetic flux vector
Control method (V/F control, or automatic torque
control, optimum excitation control can be selected)
boost control can be selected)
Long wiring mode became unnecessary and was
Long wiring mode
deleted.
150% 60s, 200% 0.5s
Overload capacity 150% 60s, 200% 0.5s (inverse-time characteristics)
(inverse-time characteristics)
Terminal 2: 0 to 10V, 0 to 5V can Terminal 2: 0 to 10V, 0 to 5V can be selected
Frequency Analog input be selected Terminal 4: 0 to 10V, 0 to 5V, 4 to 20mA can be
setting Terminal 4: 4 to 20mA selected
signal Input using the setting dial of the Input using the setting dial of the operation panel or
Digital input
operation panel or parameter unit parameter unit
<Additional function>
Inverter operation enable (X10),
PU operation external interlock (X12),
Terminal
Magnetic flux vector/V/F switchover (X18),
function
PU-NET operation switchover (X65),
Input signal External-NET operation switchover (X66),
Command source switchover (X67)
Terminal
Pr.60 to Pr.63 (input terminal
function Addition of Pr.178 (STF)
function selection)
selection
<Additional function>
Regeneration brake pre-alarm (RBP), electronic
thermal pre-alarm (THP), brake opening request
(BOF), fan failure (FAN), heatsink overheat
Terminal With current average value pre-alarm (FIN), deceleration at an instantaneous
function monitor (Y93) power failure (Y46), PID control activated (PID),
during retry (Y46), PID output interruption (SLEEP),
life alarm (Y90), current average value monitor
(Y93)
*Negative logic is added to all terminal functions
Output
signal
<Additional function>
Output voltage, frequency setting value, converter
output voltage, regenerative brake duty, electronic
thermal relay function load factor, output current
Output signal Output frequency and output
peak value, converter output voltage peak value,
for indicator voltage only
output power, reference voltage output, motor load
factor, cumulative power, PID set point, PID
measured value, PID deviation, motor thermal load
factor, inverter thermal load factor

<Additional function>
Input phase loss, brake transistor alarm, output
phase loss, output current detection value excess,
inrush resistor overheat, communication alarm,
Protective/warning function With brake transistor alarm
analog input alarm, PTC thermistor operation, safety
circuit alarm, regeneration brake pre-alarm,
electronic thermal pre-alarm, maintenance output,
operation panel lock, password locked, safety input

14/19 BCN-C21002-106
Item FR-S500, S500E FR-D700
Outline dimension Compatible
Installation size Compatible
Main circuit terminal block Compatible (screw type terminal block)
Fixed insertion terminal block Refer to
Control circuit terminal block Flathead screw M3: ABC terminal Spring clamp terminal
and screw size Flathead screw M2: except for ABC 1. Size
terminal
Control terminal cable size 2 2
0.3 to 0.75mm 0.3 to 1.5mm
when bar terminal is used
For all capacities, fans are
placed on top of the inverter.
Cooling fan position Placed below the inverter Clearance is necessary in
the above for replacement of
the cooling fan.
Operation panel Integrated to the body, not removable. Integrated to the body, not removable.
Compatible with the conventional models (some functions were partially changed or
Parameter (function)
deleted)
FR-PU07 Compatible Compatible
FR-PU04 Compatible Compatible (partially restricted)
Parameter FR-PU03
unit /FR-ARW03
Not compatible Not compatible
FR-DU01
FR-PU02/FR-ARW
PU FR-CB2□□ Compatible Compatible
connection Not compatible Not compatible
cable FR-CBL□□
Plug-in option Not compatible Not compatible
Provided with all capacity
Inrush current limit circuit Provided with all capacity
Cooling fan 2 to 3 years 10 years
Design life Electrolytic
5 years 10 years
capacitor
Stand-alone option Compatible
Refer to 4. Option
(noise filter, reactor, etc.)

15/19 BCN-C21002-106
2) Parameter comparison description and main difference
Main differences with the
FR-S500 and S500E
Parameter
Item

Parameter
Comparison Remarks

Function
function

number
change

change

change
Added

Name
Description

Change: Initial value change


FR-S500、S500E FR-D700
Torque boost Other than below: 6% 0.75K or less: 6%
1 ○
(Pr.0) S540, S540E-1.5K, 2.2K: 5% 1.5K to 3.7K: 4%
S540, S540E-3.7K: 4% 5.5K, 7.5K: 3%

Change: Initial value change


DC injection brake FR-D700
2 operation voltage ○ S540, S540E-0.4K to 3.7K: 6% 0.1K, 0.2K: 6%
(Pr.12) 0.4K to 7.5K: 4%

3 MRS input selection ○ Selection of a, b contact input of the MRS signal


RUN key rotation direction selection (Pr.40), frequency
4 Operation panel ○ setting/key lock operation selection (Pr.161), and monitor
digits selection (Pr.268) have added
1) Addition: Setting of second stall prevention operation
level (Pr.48)
Stall prevention
5 ○ ○ 2) Addition: Selection of fast-response current limit
function
operation at driving (Pr.156)
3) Addition: Setting of OL signal output timer (Pr.157)
Second electronic Changed from H7 (559) to Pr.51
6 ○
thermal O/L relay
1) Addition/change: Monitor item of operation panel and
Monitor function terminal FM (Pr.52 and Pr.54)
(DU/PU monitor
7 ○ ○ 2) Addition: Setting of watt-hour meter clear (Pr.170)
display, terminal FM
output) 3) Addition: Energization time and operating time
carrying-over times (Pr.563, Pr.564)
Remote setting Addition: Clear of remotely set frequency by turning OFF
8 ○
function STF and STR (Pr.59)
Energy saving Optimum excitation control can be selected under V/F
9 ○
control selection control (Pr.60)
10 Retry selection ○ Addition: Description of fault which perform retry
1) Addition: Selection of SF-HR, SF-HRCA (Pr.71)
2) Addition: Selection for reading and changing of offline
auto tuning data
Applied motor 3) Addition: Setting of second stall prevention operation
11 (second applied ○ ○
level (Pr.450)
motor)
4) Change: Change applied motor (Pr.71) to the second
applied motor (Pr.450) by turning ON/OFF of
RT signal

16/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item

Parameter
Comparison Remarks

Function
function

number
change

change

change
Added

Name
Description

1) Name: Change of 0 to 5, 0 to 10V selection to analog


input selection
2) Change: Change of the Pr.73 setting value and initial
value
Selection of analog
12 ○ ○ ○
input specifications FR-S500、S500E FR-D700
0: 0 to 5V (initial value) 0: 0 to 10V
1: 0 to 10V 1: 0 to 5V (initial value)

2) Addition: Terminal 4 input selection (Pr.267)


1) Addition/change: Operation command source, speed
command source selection (Pr.338,
Pr.339)
Selection of
operation mode, 2) Addition/change: Link startup mode selection (Pr.340)
13 ○ ○
command source, 3) Addition: PU mode operation command selection
and control source (Pr.551)
4) Change: Operation mode setting 8 was deleted, but
compatible with using X16 signal
1) Addition: Setting of motor constants (R1) (Pr.90)
2) Addition: Selection of auto tuning setting of motor
Offline auto tuning
14 ○ ○ constants of motor constants (R1) (Pr.96)
function
3) Change: Setting range of the rated motor frequency
(Pr.84)
1) Addition: Setting of communication speed 38400bps
(Pr.118)
2) Addition: Modbus RTU communication setting (Pr.549)
Communication
15 ○ ○ 3) Addition: Stop mode at fault selection (Pr.502)
setting
4) Addition: Addition of "multi command mode"
5) Change: Setting range of communication station
number (Pr.117)

17/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item

Parameter
Comparison Remarks

Function
function

number
change

change

change
Added

Name
Description

1) Name: Frequency setting voltage (current) bias and


gain changed to Terminal 2 (terminal 4)
Terminal 2 (terminal frequency setting bias and gain
4) frequency setting 2) Addition: Setting of analog input display unit switchover
bias (frequency), (Pr.241)
16 Terminal 2 (terminal ○ ○ ○ 3) Change: Setting range of bias and gain of terminal 2
4) frequency setting and terminal 4
gain (frequency) 4) Change: Frequency setting of the maximum voltage
(Pr.902 to 905) (current) input
・Change from Pr.38 to Pr.125
・Change from Pr.39 to Pr.126
1) Addition: PID control automatic switchover function
(Pr.127)
17 PID control function ○ ○ 2) Addition: PID action selection item (Pr.128)
3) Addition: Input signal (PID control valid terminal: X14),
Output signal (during PID control: Y47)
Output current Change: Setting range of zero current detection time
18 ○
detection function (Pr.153)
Extended function Change: Parameter number is changed from Pr.30 to
19 display selection ○ Pr.160
(Pr.160)
Setting of automatic restart after instantaneous power
Automatic restart failure selection (Pr.162), stall prevention operation level
after instantaneous
20 ○ for restart (Pr.165), rotation direction detection selection
power failure
function at restarting (Pr.299), acceleration time at a restart
(Pr.611)
Function selection of 1) Addition: STF terminal function selection
21 input terminal ○ 2) Addition: Item of input terminal assigned function
(Pr. 178 to Pr.182)
Function selection of Addition: Item of output terminal assigned function
22 output terminal ○
(Pr.190, 192)
Change: The initial value is for cooling fan on/off control
23 Cooling fan ○
valid (Pr.244)
Soft-PWM, long Long wiring mode became unnecessary and was deleted.
24 ○
wiring mode
Display function of Inrush current limit circuit, control circuit capacitor, main
25 the life of the inverter ○ circuit capacitor, estimation and display of the cooling fan
parts life (Pr.255 to Pr.259)
Power failure stop Selection of power failure stop function (Pr.261)
26 ○
selection

18/19 BCN-C21002-106
Main differences with the
FR-S500 and S500E
Parameter
Item

Parameter
Comparison Remarks

Function
function

number
change

change

change
Added

Name
Description

Selection of operation when the start signal is turned OFF


27 Stop selection ○
(Pr.250)
Name: Capacitor life timer and Capacitor life alarm output
Maintenance timer
28 ○ set time changed to Maintenance timer and
alarm
Maintenance timer alarm output set time

Current average Setting of average value of the output current at a


29 value monitor ○ constant speed operation and pulse output function of the
function maintenance timer value (Pr.555 to Pr.557)
Start-time hold Setting of time to hold the starting frequency
30 ○
function
General-purpose For selecting general-purpose magnetic flux vector
31 magnetic flux vector ○ control
control (Pr.80, 82 to 84)
Speed smoothing Function to suppress vibration generated between the
32 ○
control mechanical system and electrical system (Pr.653)
Input phase loss Setting of Input/output phase loss protection function
33 ○
protection function operation selection (Pr.251, Pr.872)
Regeneration Setting of regeneration avoidance function operation
34 ○
avoidance function selection, operation level (Pr.882 to Pr.886)
35 Free parameter ○ Available for any purposes by users (Pr.888, Pr.889)

19/19 BCN-C21002-106