0% found this document useful (0 votes)
116 views3 pages

Exercises Problem 4 Ref and Air Con

The document is a student's solution to a refrigeration and air conditioning problem set. It involves calculating: 1) The specific humidity, enthalpy, and relative humidity of air with a dry bulb temperature of 30°C and wet bulb temperature of 25°C. 2) The values are calculated and compared to those obtained from a psychrometric chart. 3) The specific humidity is calculated to be 0.0178 kg water vapor/kg dry air, the enthalpy is 75.7 kJ/kg dry air, and the relative humidity is 66.31%. These values match closely those obtained from the psychrometric chart.

Uploaded by

Ariel Gamboa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
116 views3 pages

Exercises Problem 4 Ref and Air Con

The document is a student's solution to a refrigeration and air conditioning problem set. It involves calculating: 1) The specific humidity, enthalpy, and relative humidity of air with a dry bulb temperature of 30°C and wet bulb temperature of 25°C. 2) The values are calculated and compared to those obtained from a psychrometric chart. 3) The specific humidity is calculated to be 0.0178 kg water vapor/kg dry air, the enthalpy is 75.7 kJ/kg dry air, and the relative humidity is 66.31%. These values match closely those obtained from the psychrometric chart.

Uploaded by

Ariel Gamboa
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Module 7: Activity No.

4
Refrigeration and Air Conditioning Exercises Problems

Name: Gamboa, Ariel C.


Student No. 20151157958

Problem:

A sample of air has a dry bulb of 30 deg C and a wet bulb of 25 deg C. Considering
standard condition, calculate:
a. specific humidity
b. enthalpy
c. relative humidity

Compare the values solved using psychrometric chart.

Solution:
DBT =30 ℃
WBT =25 ℃
dpT =23 ℃ (¿ Chart )

¿ table by Stoecker :
t v =Psat @ dpT=23℃

Solving by interpolation of DBT ∧WBT :


Pv =2.812kPa

Pv Pv
a) SH=0.622 =0.622
Pa Patm −Pv
2.812kPa
SH=0.622
(101.325−2.812) kPa
kg W .V .
SH=0.0178
kg d . a.

b) h=ha + ( hv ) ( SH )
kJ kJ
(
h a=( Cpa ) ( DBT )= 1.0062
kg . C)( 30 ℃ )=30.186
kg d . a .
kJ
h v ≈ h g at 30 ℃=2556.4
kg W . V .
kJ kJ kg W . V .
h=30.186
kg d . a . (
+ 2556.4
kg W . V . )(
0.0178
kg d . a . )
kJ
h=75.7
kg d . a .
Pv
c) RH =
P sat @ DBT
2.812 kPa
RH = × 100 %
4.241 kPa
RH =66.31 %

Comparing the values solved using psychrometric chart:

Values ¿ the psychrometric chart :

kg W . V .
SH=0.018
kg d . a.

kJ
h=77
kg d . a .

RH =67 %