PS1 Lab Manual 2

This document describes an experiment to investigate reactive power compensation in a power grid using Power World Simulator software. The objectives are to study reactive power compensation. A power grid is constructed with a 100 KW generator, two buses, a 100 KW load with 75 KVR reactive power, and a switched shunt with 10 KVR steps. Reactive compensation is varied and its effect on reactive power flow, generator kVA output, and power factor is observed.

Uploaded by

nTech World
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views4 pages

PS1 Lab Manual 2

This document describes an experiment to investigate reactive power compensation in a power grid using Power World Simulator software. The objectives are to study reactive power compensation. A power grid is constructed with a 100 KW generator, two buses, a 100 KW load with 75 KVR reactive power, and a switched shunt with 10 KVR steps. Reactive compensation is varied and its effect on reactive power flow, generator kVA output, and power factor is observed.

Uploaded by

nTech World
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Shahjalal University of Science and Technology

(SUST)

Department of Electrical and Electronic Engineering


(EEE)

Experiment name: Investigate the reactive power


compensation in power grid

Experiment No: 02

Course Title: Power System -I


Course Code: EEE -326

Course Teacher: Md. Asaduz Zaman Mamun


Lecturer
Department of Electrical and Electronic Engineering
(EEE)
Shahjalal University of Science and Technology (SUST)
Experiment No: 01 2013
Experiment Name: Introduction to Laboratory Equipment

Objective: To study the reactive power compensation


Equipment: Power World Simulator v17

Procedure: Construct the following power grid system with following values-
 Generator: 100 KW
 Bus 1(one with Generator): Slack bus, Nominal Voltage 16 KV
 Bus 2 (Load bus): Nominal Voltage 16 KV
 Load: 100 KW, 75 KVR
 Switched Shunt: Number of steps 10, KVR per step 10

The speed and size of the green arrows are proportional to the real power supplied to the load
bus, and the blue arrows are proportional to the reactive power. Here reactive compensation can
be supplied in discrete 10-kVar steps and load kvr can be increased by 5 kvr by clicking on the
arrows in the capacitor’s kvar field and the load field, and the load can be varied by clicking on
the arrows in the load field.

Notice that increasing the reactive compensation decreases both the reactive power flow on the
supply line and the kVA power supplied by the generator; the real power flow is unchanged

Prepared by Tuhin Dev, Lecurer,


Department of Electrical and Electronic Engineering
Shahjalal University of Science and Technology (SUST) Page 2
Experiment No: 01 2013
Experiment Name: Introduction to Laboratory Equipment

When Load supply is 100 KW, 75 KVR

Shunt Generator Real Generator Supplied Power Factor


Compensation Power Reactive Apparent
(KW) Power(KVR) Power(KV)

Comment:

Prepared by Tuhin Dev, Lecurer,


Department of Electrical and Electronic Engineering
Shahjalal University of Science and Technology (SUST) Page 3
Experiment No: 01 2013
Experiment Name: Introduction to Laboratory Equipment

When Load supply is 100 KW, 95 KVR

Shunt Generator Real Generator Supplied Power Factor


Compensation Power Reactive Apparent
(KW) Power(KVR) Power(KV)

Comment:

Prepared by Tuhin Dev, Lecurer,


Department of Electrical and Electronic Engineering
Shahjalal University of Science and Technology (SUST) Page 4