0% found this document useful (0 votes)
212 views40 pages

Advanced MxPro4

This user manual provides instructions for operating and programming the Mx-4100, Mx-4200, Mx-4400, and Mx-4800 Fire Alarm Control Panels. The panels include a graphical display, LED status indicators, control buttons, navigation buttons, number/letter buttons, and an audible buzzer. The manual describes the panels' access levels, functions for fire alarms, faults, disablements, and more. It also covers menu navigation, viewing events and logs, testing, printing, and general operation.

Uploaded by

ahmed elkhouly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
212 views40 pages

Advanced MxPro4

This user manual provides instructions for operating and programming the Mx-4100, Mx-4200, Mx-4400, and Mx-4800 Fire Alarm Control Panels. The panels include a graphical display, LED status indicators, control buttons, navigation buttons, number/letter buttons, and an audible buzzer. The manual describes the panels' access levels, functions for fire alarms, faults, disablements, and more. It also covers menu navigation, viewing events and logs, testing, printing, and general operation.

Uploaded by

ahmed elkhouly
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

User Manual

The operation and functions described in this manual are available from Software Version Mx4100-023, Mx4200-023 and
Mx4400-023 onwards.

www.advancedco.com
This page is intentionally left blank.

www.advancedco.com
Contents
1 INTRODUCTION 5
1.1 STANDARDS 5
1.2 CAUTIONS AND W ARNINGS 6
1.3 GENERAL DESCRIPTION 6
2 CONTROLS AND INDICATIONS 7
2.1 GRAPHICAL DISPLAY 7
2.2 LED STATUS INDICATORS 8
2.3 CONTROL BUTTONS 8
2.4 NAVIGATION BUTTONS 9
2.5 NUMBER AND LETTER BUTTONS 9
2.6 BUZZER 9
3 OPERATION 10
3.1 ACCESS LEVELS 10
3.1.1 Changing from Access Level 1 to Level 2 10
3.1.1.1 Menu Access 10
3.1.1.2 Control Buttons at Level 1 11
3.1.2 Changing from Access Level 2 to 1 11
3.2 FIRE ALARM CONDITION 11
3.2.1 Detailed Fire Alarm Information 12
3.2.2 Investigation Delays 13
3.3 FAULT CONDITION 14
3.4 DISABLEMENT CONDITION 15
3.4.1 Disabled Inputs 15
3.4.2 Disabled Outputs 16
3.5 ALARM CONDITION 16
3.6 MENU FUNCTIONS 17
3.6.1 Using the Buttons to Navigate Menus 18
3.6.1.1 Selecting Menu Options 18
3.6.1.2 Selecting Individual Zone Numbers 18
3.7 VIEWING 19
3.7.1 View - Fires 19
3.7.2 View - Faults 19
3.7.3 View - Alarms 19
3.7.4 View - Disabled 19
3.7.5 View - Inputs 19
3.7.6 View - Outputs 20
3.7.7 View - Panel 21
3.7.8 View - Log 22
3.7.8.1 Event Log 22
3.7.8.2 Alarm Counter 22
3.7.9 View - Network 22
3.7.10 View - Logic 23
3.8 DISABLING 23
3.8.1 Disable - Zones and Inputs 23
3.8.2 Disable - Outputs 24
3.8.2.1 All Sounder Outputs 25
3.8.2.2 All Other Outputs 25
3.8.2.3 Selected Outputs 25
3.8.2.4 Fire Routing Output 25
3.8.2.5 Fault Routing Output 25
3.8.2.6 Pager 25
3.8.3 Disable - Controls 25
3.8.4 Disable - Delay-Mode 26
3.8.5 Disable – User ID 27
3.8.6 Disable – Groups 27
3.9 ENABLING 28
3.9.1 Enable - Zones and Inputs 28
3.9.2 Enable - Outputs 28
3.9.3 Enable - Delay-Mode 28
3.9.3.1 Extend Delays 28

www.advancedco.com 3
3.9.3.2 Holiday / Inhibit 28
3.9.4 Enable - Groups 29
3.9.5 Enable - Change-Time 29
3.9.6 Enable - Remote 30
3.10 TESTING 31
3.10.1 Test - Zones 31
3.10.2 Test - Display 32
3.10.3 Test - Buzzer 32
3.10.4 Test - Printer 33
3.10.5 Test - Outputs 33
3.11 PRINTING 34
3.11.1 Printer Communications Settings 34
3.11.2 Set-up Printer 34
3.11.3 Print Inputs 34
3.11.4 Print Outputs 35
3.11.5 Print Faults 35
3.11.6 Print Disabled 35
3.11.7 Print - Log 36
3.11.8 Print - Feed Paper 36

4 www.advancedco.com
1 Introduction
1.1 Standards
Advanced Electronics Ltd declare that the products identified below conform to the essential requirements
specified in the Construction Products Directive 89/106/EEC:

0086-CPD-549125
EN54-2: 1997 +A1:2006
Control and indicating equipment for fire detection and fire
alarm systems for buildings

Provided options:
- Outputs to Fire Alarm Devices
- Output to Fire Routing Equipment
- Output to Fault Routing Equipment
- Investigation Delays to Outputs
- Dependency on more than one alarm signal
- Fault Signals from Points
- Disablement of Points
- Alarm Counter
- Test Condition
- Standardised Input / Output

EN54-4: 1997 +A1:2002 +A2:2006


Power supply equipment for fire detection and fire alarm
systems for buildings

Mx-4100, Mx-4100/L, Mx-4200, Mx-4200/D, Mx-4400, Mx-


4400/D, Mx-4400/LE and Mx-4800

In addition, the products comply with the following:

Low Voltage Directive 2006/95/EC


EN60950-1: 2006 Safety of information technology equipment

Electromagnetic Compatibility Directive 2004/108/EC


EN61000-6-3:2001 Emissions, Class B
EN50130-4: 1995 +A1:1998 +A2: 2003 Immunity, Product Family Standard

www.advancedco.com 5
1.2 Cautions and Warnings
Before commencing with installation or operation of the panel, please read this
STOP manual carefully. If you are unclear on any point DO NOT proceed. Contact the
manufacturer or supplier for clarification and guidance.

Only Trained service personnel should undertake the Installation, Programming and
maintenance of this equipment.

This product has been designed to comply with the requirements of the Low Voltage
Safety and the EMC Directives. Failure to follow the installation instructions may
compromise its adherence to these standards.

This Fire Alarm Control Panel is compliant with the requirements of EN54 parts 2
and 4 (1998).
Where appropriate, reference is made in this manual to the relevant sections of the
EN54 standard for clarification and to ensure that the installation is compliant with
the requirements of EN54.

1.3 General Description


This manual covers the use and operation of the Mx-4100, Mx-4200 Mx-4400 and Mx-4800 Fire Alarm Control
Panels. Refer to the Installation and Commissioning Manual (Document No. 680-014) for details of how to install
and program the panel.
The Mx-4100 is a Single Loop, Analogue Addressable Fire Alarm Control Panel.
The Mx-4200 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to two
loops.
The Mx-4400 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to four
loops.
The Mx-4800 is a Multiple Loop, Analogue Addressable Fire Alarm Control Panel with provision for up to
eight loops.
All four panels are designed for use with the Apollo Discovery, Explorer, XP95, Series 90 and Hochiki ESP
ranges of fire detection equipment.

6 www.advancedco.com
2 Controls and Indications
The Mx-4100, Mx-4200, Mx-4400 and Mx-4800 are provided with indications and control functions as shown in
the diagram below and described in the following text. The Mx-4800 has two such display elements, one for
loops 1-4 and the other for loops 5-8. Normal operator level indications, controls and user programming can all
be achieved using either display.
Graphic Liquid Navigation
Crystal Display Buttons

SOU N D ER
FIRE SIL EN C ED RESET
AB C DEF
SOU N D ER
FA U LT
FA U LT

DI SA B LE
SOU N D ER
! MU TE
GH I JKL MNO
DI SA B LE D
SILENCE/
T EST SYS TEM FA U LT RESOU ND
PQRS TUV WXYZ

POW ER DE L AYED EVAC UATE


ESC MEN U

LED Status Control Number and


Indicators Buttons Letter Buttons

2.1 Graphical Display


The graphical display provides detailed information of the source of fire alarms, faults and warnings. It also
shows menus for use when inspecting or programming the operation of the panel.
Under normal conditions the panel display shows the access level, time, date and status: -

LEVEL 2
16:05
04 MAR 2006

NORMAL PANEL OPERATION


(Press Menu to View)

www.advancedco.com 7
2.2 LED Status Indicators
The LED Status Indications show the basic operational state of the panel and whether the panel is in a fire
alarm, fault, disabled or test condition.

Function Colour Description


FIRE Red Indicates that the system has detected a fire alarm condition (flashes on
a new alarm and turns on steady when mute button is pressed).
Fault Yellow Indicates that the system has detected a fault condition (flashes on a
new fault and turns on steady when mute button is pressed).
Disable Yellow Indicates that part of the system has been disable (i.e. isolated)
Test Yellow Indicates that part of the system is in a test condition
Power Green Indicates the presence of power
Sounder Silenced Yellow Indicates that the sounders have been silenced
Sounder Fault Yellow Indicates the presence of a fault in one or more sounder wiring circuits
Sounder Disabled Yellow Indicates that one or more sounders have been disabled (i.e. isolated)
System Fault Yellow Indicates the presence of a system fault
Delayed Yellow Indicates that one or more output circuits are in a delayed operating
condition
Function 1 Red Fire Brigade Output Activated Or Spare function LED
Function 2 Yellow Fire Brigade Output Disabled Or Spare function LED
Function 3 Yellow Fire Brigade Output Fault Or Spare function LED
Function 4 Yellow Spare function LED
Function 5 Yellow Spare function LED

The function LED Indicators are programmable and will have been configured and labelled accordingly during
installation and commissioning of the system.

2.3 Control Buttons

Reset Only available with


Press to reset the panel from a fire alarm condition. Level 2 Access.

Mute
! Press to mute the internal buzzer.
Available in both
Level 1 and Level 2

Silence / Resound
Only available with
Press to silence the sounders.
Level 2 Access.
Press again to re-activate the sounders.

Evacuate Only available with


Press to initiate a manual evacuation and sound the alarms. Level 2 Access.

8 www.advancedco.com
2.4 Navigation Buttons


Press to scroll through Menu Options.
Press to display more information.
Press to scroll through lists of zones or devices.

Press to confirm entry of numeric or letter information entry.


✔ Press to confirm selection of a menu option.
Press to change some of the configuration options.

2.5 Number and Letter Buttons

ABC D EF

GHI JKL MNO

Used to enter numbers or letters.

PQRS TUV WXYZ

ESC MENU

Press to return to a previous menu.


Esc
Press to exit the menu functions and return to the normal display.

Menu Press to show or return to Menu Functions.

2.6 Buzzer
The buzzer produces two different sounds to differentiate between fire alarm conditions and fault conditions.

Condition Operation
Fire Alarm The buzzer operates with a continuous tone.
Fault The buzzer operates intermittently.

www.advancedco.com 9
3 Operation
3.1 Access Levels
The panel operation is protected from inadvertent and erroneous misuse by means of four access levels. These
levels are as follows:
Level 1 Untrained user
Level 2 Authorised User
Level 3 Service and Maintenance Engineer
Level 4 Service and Maintenance Engineer – Special Tools required

 A Level 1 Untrained User can view the current operational condition of the system and may
MUTE the internal buzzer.
NOTE: Depending on the configuration settings, a Level 1 user may also be permitted to EVACUATE and/or SILENCE
and/or RESET the system by pressing the appropriate button and entering a password.

 A Level 2 Authorised User can view the operational condition of the system and may MUTE the
internal buzzer. In addition, the EVACUATE, SILENCE and RESET buttons are enabled and
access to the Level 2 Menu functions is available.
NOTE: There are up to 10 User ID codes available, each with its own password, which can be configured with varying
permissions to specific menu function options.

 A Level 3 User has access to program and configure the operation of the panel. This is described in
detail in the Installation and Commissioning Manual (Part Number 680-014).

3.1.1 Changing from Access Level 1 to Level 2


If the panel has an access key switch fitted, use the key in preference to the menu options shown
below.
3.1.1.1 Menu Access
Press the ‘MENU’ button. The level 1 menu will be displayed as shown below:
[ CONTROLS DISABLED ]

ENABLE CONTROLS VIEW


LED TEST STATUS

To enable the controls, ensure the “Enable Controls” option is highlighted and then press the ✔ button. The
display then requests entry of the Level 2 or 3 passwords as follows:
[ CONTROLS DISABLED ]
Please Enter Your Password

Enter the password using the number buttons and then press the ✔ button. As each number is entered, an
asterisk (*) is shown on the display. For example:
[ CONTROLS DISABLED ]
Please Enter Your Password
**

If the password is correct, the Level 2 Menu options will be shown.


If the password is incorrect, the display briefly shows the following message.

10 www.advancedco.com
[ CONTROLS DISABLED ]
Please Enter Your Password
Password Not Recognised !

3.1.1.2 Control Buttons at Level 1


If any of the control buttons (Reset, Silence / Resound or Evacuate) are pressed, the display automatically
prompts for the password. Enter the password as above

3.1.2 Changing from Access Level 2 to 1


If the panel has an access key switch fitted, use the key switch.
Alternatively, if passwords are used, select the “Disablement” menu and then select “Disable/Controls” – see
section 3.8.3 for details.

3.2 Fire Alarm Condition


When the system registers a fire alarm condition the Red Fire Indicator illuminates, the internal buzzer sounds
(continuously) and the display shows the zone in which the fire originated. The sounders, relays and other
outputs will be turned on depending on the programming in the panel. An example of the display is shown
below: -

FIRE STARTED IN ZONE 0001 .


BASEMENT WEST < Location Text for First Zone
KITCHEN <CALL POINT > < Location Text and Type of Device

[ 1 Zone in Fire][Last Fire in Z0001] < No. of Zones in Fire & Last Zone
BASEMENT WEST < Zone Description for Last Zone

The upper part of the display shows the origin of the fire. The lower part of the display shows the number of
zones in a fire alarm condition and the last zone to enter the fire alarm condition. This lower fire alarm status
display is always present when the panel has registered a fire alarm condition.
If more than one fire alarm condition occurs, the total number of zones in an alarm condition and the last zone in
an alarm condition will be updated on the display. If the sounders were silenced, they will sound again whenever
the fire spreads to a new zone.

FIRE STARTED IN ZONE 0001. More Alarms>


BASEMENT WEST < Location Text for First Zone
KITCHEN <CALL POINT > < Location Text and Type of Device

[ 2 Zones in Fire][Last Fire in Z0005] < No. of Zones in Fire & Last Zone
BASEMENT EAST < Zone Description for Last Zone

Press the ‘MUTE’ button to silence the internal buzzer (the FIRE LED will change from flashing to steady
illumination).
When the panel is enabled for Level 2 Access or, if configured, by entering a password at Level 1, the following
functions are available.
Press the ‘SILENCE / RESOUND’ button to silence the sounders.
Press the ‘SILENCE / RESOUND’ button again to re-activate the sounders.
Press the ‘RESET’ button to clear the alarm condition and restore the panel to normal operation.
Press the ‘EVACUATE’ button to initiate a manual evacuation and to activate the sounders. The display will
show this fire alarm condition. For example:

www.advancedco.com 11
FIRE STARTED IN ZONE 0100 .
MAIN RECEPTION < Location Text for First Zone
Evacuation Key <SWITCH > < Confirmation of Evacuation

[ 1 Zone in Fire][Last Fire in Z0100] < No. of Zones in Fire & Last Zone
MAIN RECEPTION < Zone Description for Last Zone

3.2.1 Detailed Fire Alarm Information


Press the  buttons to view a list of all zones in a fire alarm condition.

Zone FIRE-LOCATION Scroll  More>


0001 BASEMENT WEST < List of Zones in Alarm including
0005 BASEMENT EAST < Zone No. and location text

If more detail regarding the source of any fires is required, press the  buttons to highlight the required zone
in alarm and press the  button to show further information. For example:

[ FIRES IN ZONE 001 ] More>


LP ADRS DEVICE LOCATION
< List of devices within the Zone
1 001.0 KITCHEN < that are in Alarm

[ 2 Zones in Fire][Last Fire in Z0005] < No. of Zones in Fire & Last Zone
BASEMENT EAST < Zone Description for Last Zone

This shows that the device at address 1 on the loop initiated the fire in Zone 1. If there are more Zone 1 devices
in alarm, these will be shown in the list. Press the  buttons to scroll through the devices.
Press the  button or the ‘Esc’ button to return to the previous display. If no button is pressed within 15-
seconds, the display automatically reverts to the main display.

12 www.advancedco.com
3.2.2 Investigation Delays

The Investigation Delay Function can be disabled or enabled as required by EN54: 2.


Refer to Section 3.8.4.

If the Investigation Delay Function (Stage 1 / Stage 2 Investigation Delay) is enabled, a fire alarm is registered
at the panel but does not immediately activate the sounders. On registering the alarm, the display shows:

FIRE STARTED IN ZONE 0001 .


BASEMENT WEST < Location Text for First Zone
KITCHEN <TEMPERATURE> < Location Text and Type of Device
OUTPUT DELAY 30 s (Press 0 to extend) < Delay Timer (Stage 1)
[ 1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST

The Output Delay Timer shows the amount of time left for investigation.
If the alarm is not acknowledged before the Stage 1 timer elapses, the panel will enter a full alarm condition and
will activate the sounders.
Pressing the ‘0’ button acknowledges the alarm. This extends the time allowed to investigate the source of the
fire.

FIRE STARTED IN ZONE 0001 .


BASEMENT WEST < Location Text for First Zone
KITCHEN <TEMPERATURE> < Location Text and Type of Device
OUTPUT DELAY 120 s < Delay Timer (Stage 2)
[ 1 Zone in Fire][Last Fire in Z0001]
BASEMENT WEST

The cause of the alarm can now be investigated. If the alarm is a false alarm, pressing the ‘RESET’ button will
clear the alarm condition. This must be done before the Stage 2 timer has elapsed or the panel will enter a full
alarm condition and will activate the sounders.
Note: The EVACUATION button will terminate the investigation delays and activate all programmed sounders.

www.advancedco.com 13
3.3 Fault Condition
When the system registers a fault condition the Yellow Fault Indicator is illuminated, the internal buzzer sounds
intermittently and the display shows the cause of the fault in more detail.
An example of the display is shown below:
ZONE 0001 DEVICE MISSING
BASEMENT WEST < Location Text for First Zone
RESTAURANT (MULTI.SENSOR) < Location Text and Type of Device

1 Zone In Fault More> < No. of Zones in FAULT

If more than one fault condition occurs, these will be shown on the display. If the internal buzzer was muted, it
will sound again when a new fault condition is registered.
When the fault condition is corrected, the panel automatically clears the appropriate fault Status Indicators and
Display information.
Press the ‘MUTE’ button to silence the internal buzzer (the general FAULT LED will change from flashing to
steady illumination). The display then shows the current time and date and service centre telephone number
along with the indication of the fault.
FOR SERVICE CALL LEVEL 2 < Panel access level
01234 567890 16:05 < Service Call Number
04 MAR 2006 < and Time / Date

1 Zone In Fault More> < No. of Zones in FAULT

To obtain more detailed information about the faults, press the  button. The display then presents a list of all
of the zones in a fault condition with the first fault highlighted. For example:
[ 2 Zones in Fault] More> < Number of zones in fault
ZONE LOCATION
1 BASEMENT < Zone #, Location Text for each
100 RECEPTION < zone

Press the  buttons to highlight the required fault and then press the  button to show further information.
For example:
[ Faults in Zone 0001 ] More>
LP ADRS STATE
1 004.0 DEVICE MISSING < Address, fault condition

Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return to the previous display.
If no button is pressed within a minute, the display automatically reverts to the main display.

14 www.advancedco.com
3.4 Disablement Condition
If any zones, input devices or output devices have been disabled, the DISABLE Indicator is illuminated. In
addition, the SOUNDER DISABLE Indicator is illuminated if one or more sounder circuits or devices have been
disabled. The display indicates the presence of zone disablement conditions in the lower half of the display as
follows:
LEVEL 2
16:05
04 MAR 2006

1 Zone With Disablements More>

When the disablement conditions are removed, the appropriate indications are cleared from the display and
from the Indicators. When all disablement conditions are removed, the DISABLE Indicator is also turned off.
To obtain more detailed information about the disablement conditions, press the  button. The display will then
present the disablement conditions in the following sequence:
 Zone / Individual Inputs.
 Outputs
3.4.1 Disabled Inputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[ 2 Zones with Inputs Disabled] More>
ZONE MODE LOCATION
0001 PART DISABLED BASEMENT WEST < Zone, disablement condition and
0002 ALL DISABLED BASEMENT EAST < location text

The display shows the status as ALL DISABLED if every input device within the zone has been disabled and
shows the status as PART DISABLED if there is at least one input device within the zone still active.
Press the  buttons to highlight the required zone and then press the  button to view the location text
assigned to the zone in full. For example:
Press the  button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0001 ] <More>
Mode Lp Adrs State
Enabled 1 001.0 Normal
Disabled 1 002.0 Normal
Enabled 1 003.0 Normal
Enabled 1 004.0 Normal

The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (LP), address (ADRS) and type of input are shown. Press the  buttons to scroll
through the inputs.
Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘ESC’ key to return.
If there are Outputs also disabled, these will now be shown.

www.advancedco.com 15
3.4.2 Disabled Outputs
The display presents a list of all of the zones in a disabled condition with the first disablement highlighted. For
example:
[ 2 Zones with Outputs Disabled] More>
Zone Mode Location
0001 DISABLED BASEMENT WEST < Zones with location text where
0100 DISABLED RECEPTION < outputs are disabled

Press the  buttons to highlight the required zone and then press the  button to view the individual outputs
and their disablement condition. For example:
[ Outputs in Zone 0100] More>
Mode Lp Adrs State
Disabled 0 001.0 Off Sounder A
Disabled 0 001.1 Off Sounder B
Enabled 0 011.0 *Off Relay 1
Enabled 0 004.0 Off Relay 2

The above example shows that the panel sounder circuits are disabled.
A * symbol preceding the state (e.g. *Off) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).
Press the  buttons to scroll through the list of individual outputs within the selected zone. Press the ‘Esc’
button to return to previous views and the main display.

3.5 Alarm Condition


When the system registers a pre-alarm or plant alarm condition, the internal buzzer sounds intermittently and
the display shows the cause of the fault in more detail. An example of the display is shown below:
ZONE 0001 PRE-ALARM
BASEMENT WEST < Location Text for First Zone
RESTAURANT (MULTI.SENSOR) < Location Text and Type of Device

1 Zone In Alarm More> < No. of Zones in Alarm

To obtain more detailed information about the alarms, press the  button. The display then presents a list of all
zones in an alarm condition.

16 www.advancedco.com
3.6 Menu Functions
The following Menu Functions are available at Level 2. The display shows the primary Level 2 Menu and the
Level 2 User as follows:
[Level 2 Menu] User 1 Node 1

VIEW DISABLE ENABLE


TEST PRINT COMMISSION
STATUS

The following table gives a list of the Level 2 Menu Functions, the sub-functions available within each main
function and a brief description for each function.

Main Menu Option Sub Menus Comments


VIEW Fires View Zones and Inputs that are reporting a fire alarm condition.
Faults View Zones and Inputs that are reporting a fault condition.
Alarms View Zones and Inputs that are reporting an alarm condition.
Disabled View Zones, Inputs and Outputs that are disabled.
Inputs View the current state of Inputs.
Outputs View the current operational condition of all output circuits / devices.
Log View the Event Log / Alarm Counter
Panel View the operational state, voltage and current loading of the panel input and
output circuits.
Network View Network diagnostics
1
DISABLE Zone / Inputs Disable a complete zone or an individual input.
Outputs 1 Disable sounder outputs or other devices.
2
Controls Cancel Level 2 access.
Delay-Mode Turn off the Stage 1 / Stage 2 Investigation Delay Operation
2
User ID Return Level 2 access to the default User 1
Groups Disable a user-defined disablement group

ENABLE Zone / Inputs Enable a complete zone or an individual input.


Outputs Enable sounder outputs or other devices.
Groups Enable a user-defined disablement group
Delay-Mode Turn on the Stage 1 / Stage 2 Investigation Delay Operation
1
Change-Time Allows authorised level 2 users to change time.
Remote Permits remote access controls
1
TEST Zones Configure one or more zones for walk test.
Display Test the Graphics Display, Status Indicators and Keyboard.
Buzzer Test the Internal Buzzer
Printer Test the connection to the Printer
Outputs Test Output Devices

PRINT Inputs Print the status of inputs


Ouputs Print the status of outputs
Faults Print the fault conditions
Disabled Print the disabled conditions
Log Print the Event Log. (All Events of Fire Only Events Selectable).
Feed Paper Advance the paper in the printer
1
Set-up Configure the printer connection and automatic print options

STATUS -- Returns the display to the normal operating display without wating for the timeout

COMMISSION --- Enter the Level 3 Commissioning and Panel Programming Functions

1
This option can be configured per Level 2 User ID. User 1 does not have permission to change these options.
2
Not required if a key switch is fitted to change access levels.

www.advancedco.com 17
3.6.1 Using the Buttons to Navigate Menus
Press the ‘Menu’ button to bring up the display menu.
3.6.1.1 Selecting Menu Options
The Level 2 Menu is shown below:
[Level 2 Menu] User 1 Node 1

VIEW DISABLE ENABLE


TEST PRINT COMMISSION
STATUS

Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
For example, press the  button followed by the  button to highlight the PRINT option (as shown below) and
then press the ✔ button to select this option.
[Level 2 Menu] User 1 Node 1

VIEW DISABLE ENABLE


TEST PRINT COMMISSION
STATUS

Press the ‘Esc’ button from within a menu option to return to the previous menu.
Press the ‘Esc’ button from the Main Level 2 Menu (shown above) to return to the normal operating display.
If a button is not pressed for one minute (15-seconds if the panel is in a fire alarm condition) the display will
automatically revert to the normal operating display. Press the ‘Menu’ button to return directly to the Level 2
Menu display previously shown.
3.6.1.2 Selecting Individual Zone Numbers
When the display is showing a list of Zone Numbers, it is possible to select a specific zone number by using the
number keys. For example, if the display is showing a list of zones:
[ Inputs] More>
Zone Mode Location
0001 Enabled BASEMENT WEST
0002 Enabled BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA

To select a particular Zone, move to the zone number column. The existing zone number will then be
highlighted.
Enter the required Zone Number using the number buttons, for example 12.
[ Inputs] More>
Zone Mode Location
# 12 Enabled BASEMENT WEST
0002 Enabled BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA

Finally press the ✔ button to confirm. The display will then show a new list of Zones with the selected Zone
highlighted at the top of the list.
If the number is entered incorrectly, press the ‘Esc’ button.

18 www.advancedco.com
3.7 Viewing
[View Menu] User 1 Node 1

FIRES FAULTS ALARMS DISABLED LOG


INPUTS OUTPUTS PANEL NETWORK LOGIC

Note that Fires, Faults, Alarms and Disablements are all normally shown without having to select the view
menu. If, however, you wish to manually View any of these, they can be selected from this menu as required.
3.7.1 View - Fires
This function shows the Zones and Inputs that are currently in a Fire Alarm condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.2 for further information.
If there are no Zones or Inputs in a Fire Alarm condition, the display automatically reverts to the Main View
Menu.
3.7.2 View - Faults
This function shows the Zones, Inputs and Outputs that are currently in a Fault condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.3 for further information.
3.7.3 View - Alarms
This function shows the Zones and Inputs that are currently in an Alarm condition. These may occur if:
 The Zone or Input is currently in a Fire Test condition and / or
 Inputs that are configured to generate an alarm or pre-alarm condition when operated are active.

The operation of the panel and the information that can be shown is identical to the views available from the
main operating display.
3.7.4 View - Disabled
This function shows only Inputs and Outputs that are currently in a Disabled condition.
The operation of the panel and the information that can be shown is identical to the views available from the
main operating display. Refer to Section 3.4 for further information.
If there are both Inputs and Outputs in a Disabled condition, the display presents the inputs first, followed by the
outputs.
If there are no Inputs or Outputs in a Disabled condition, the display does not change and continues to show the
Main View Menu.

3.7.5 View - Inputs


This function shows the current operational condition for all Zones and Individual Inputs. The display presents a
list of all of the zones containing input devices, with the first zone highlighted. For example:

www.advancedco.com 19
[ Inputs] More>
Zone Mode Location
0001 Enabled BASEMENT WEST
0002 ALL DISABLED BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA

Press the  buttons to highlight the required zone and then press the  button to view the full location text
Press the  button again to view the inputs within the zone and their status. For example:
[ Inputs in Zone 0008] <More>
Mode Lp Adrs State
Enabled 1 001.0 Normal
Disabled 1 002.0 Normal
Enabled 1 003.0 Normal
Enabled 1 004.0 Normal

The display shows the current disablement condition (mode) for each input as either enabled or disabled. In
addition, the detection loop (Lp), address (Adrs) and input state are shown.
Press the  buttons to scroll through the inputs.
Press the  button to show further information on device location, type analogue/digital values etc.
Press the ‘Esc’ button to return to previous view.
3.7.6 View - Outputs
This function shows the current operational condition for all Outputs.
[Outputs]
More>
Zone Mode Location
0008 ENABLED GROUND FLOOR
0100 ENABLED MAIN RECEPTION

Press the  buttons to highlight the required zone and then press the  button to view the individual outputs.
For example:
[ Outputs In Zone 0008] More>
Mode Lp Adrs State
Enabled 1 032.0 Off SOUNDER
Enabled 1 056.0 Off SOUNDER
Enabled 2 011.1 *On RELAY
Enabled 3 026.1 Off RELAY

A * symbol preceding the state (e.g. *On) indicates the device has been configured as an inverted output (e.g. a
fault relay that is designed to de-energise when a fault occurs).

20 www.advancedco.com
3.7.7 View - Panel
The View Panel Option provides a diagnostic readout of the operational condition and readings for the internal
panel electronic circuits. When the option is selected, the display shows a list of the circuits. For example:
[Panel Circuits]
ITEM DESCRIPTION VALUE STATE
01.0 Sounder A 5.6V Normal
01.1 Sounder B 5.6V Normal
02.0 Sounder A Load 0mA Normal
02.1 Sounder B Load 0mA Normal

The following table lists the internal panel circuits and indicates the values that can be displayed.

Item Description Value Range Normal Possible States


01.0 Sounder A
3
0V – 14V 5.5V Normal Open Circuit, Short Circuit
01.1 Sounder B
02.0 Sounder A Load 4
3
0mA – 1000mA Normal Too High
02.1 Sounder B Load
5
03.0 Battery 0V – 30V >25.0V Normal Too High, Too Low
04.0 Charger 0V – 30V 27.6V Normal Too High, Too Low
05.0 Earth Monitor 0V – 30V 1.3V Normal Too High, Too Low
4
06.0 Aux Supply 0mA – 500mA Normal Too High
st 6 4
07.0 1 Loop Load 0mA – 500mA Normal Open Circuit, Too High, Short
Circuit
st 6 4
08.0 1 Loop V.Out 24V – 32V Normal
st 6 4
09.0 1 Loop V.In 24V – 32V Normal
10.0 L/H L Normal Programmable inputs
to Panel Switch Inputs Normal
10.7 L/H L Normal
11.0 Relay 1 – – Normal
11.1 Relay 2 – – Normal
11.2 Output 1 – – Normal
11.3 Output 2 – – Normal

Press the  buttons to scroll through the panel internal circuits. Press the ‘Esc’ button to return to the main
view menu.
NOTE: Additional panel circuits may be shown depending on the system configuration and installed options.

3
The MX-4400 also displays Sounders C and D.
4
Depends on the panel configuration, installation and current operating condition (i.e. fire alarm).
5
The voltage shown is the voltage of the battery as measured under full load conditions. If this voltage falls below 23.0V under full load test,
the panel will indicate a Too Low condition.
6
Loop Load, V.Out and V.In displayed for each loop driver (2 on MX-4200, 4 on MX4400).

www.advancedco.com 21
3.7.8 View - Log
After selecting to view the log option the display presents a pop-up window to allow selection between a view of
all of the event history, a view of only the fire alarms that have occurred or a view of the fire alarm counter.

ALL EVENTS .
FIRE EVENTS ONLY
ALARM COUNTER

Press the  buttons to highlight the required menu option and then press the ✔ button to select it. The
display then shows the appropriate list of events.
3.7.8.1 Event Log
The display will always show the most recent event to have occurred, e.g.
[View Fire Events] Entry 0076 < Number of Highlighted Event
Time/Date Node Lp:Addr Zone
10:54:23 1 1:001.0 001 < Time, Origin and Zone
14/03/02 FIRE ALARM 64 < Date, Event and Analogue Value
BASEMENT < Zone Text Description
ROOM 10 < Device Location Description

In the above example, the latest fire occurred (Event No. 76) at 10:54 am on March 14, 2006. This fire alarm
originated at the device at address 001(Addr) on Loop 1 (Lp) on Panel No. 1 (Panel). The device was in Zone
001. The analogue value registered by the device (64) has also been recorded. The lower two lines show the
zone and device location texts descriptions for ease of identification.
Press the  buttons to scroll through the fire alarm events logged in the system. Press the  button to show
more recent events and press the  button to show earlier events.
To view the details for a specific Log Entry Number, it is possible to select the record by typing in the required
number using the number keys.
Press the ✔ button to confirm. The display will then display the required record.
Press the ‘Esc’ button to return to the main view menu.
3.7.8.2 Alarm Counter
Alarm Counter.

The Panel records the number of times that the fire alarm condition has
Section 7.13 occurred at the panel.

[View Alarm Counter]

0000000033

In the above example, the panel has entered the fire alarm condition 33 times since it was installed.
The panel increments the count by one each time it changes from the normal condition to indicate a fire alarm
condition. Whilst in the fire alarm condition, and until it is reset, further fire alarm events do not increment the
counter.
Press the ‘Esc’ button to return to the main view menu.
3.7.9 View - Network
This Option can be used to obtain diagnostic information when a network is used to connect other panels or
remote terminals. The access level of all panels on the network can be checked from this display:

22 www.advancedco.com
[NETWORK – Press 0 to Clear] More>
Node Status
1 LOCAL
2 Level-2
3 Level-1
4 -

Additional network diagnostics are available by selecting the “More>” option.


For further information, refer to the Ad-Net network manual (Document No. 680-027).
Pressing '0' allows the stored network status information to be cleared.

3.7.10 View - Logic


This is a diagnostic aid to assist engineers when first commissioning a complex fire system.

3.8 Disabling
On selecting the Disable Menu, the display shows four possible options. For example:
[Disable] User 1 Node 1

ZONE/INPUTS OUTPUTS CONTROLS


DELAY-MODE USER-ID GROUPS

Press the  buttons to highlight the required menu option and then press the ✔ button to select it.

3.8.1 Disable - Zones and Inputs


This option provides the means to disable a complete zone, disable all input devices except call points or
disable individual input devices.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
On selecting this option, the display shows a list of the current zones and their current disablement status. For
example:
[ 0 Zones with Inputs Disabled] More>
Zone Mode Location
0001 Enabled BASEMENT WEST
0002 Enabled BASEMENT EAST
0008 Enabled GROUND FLOOR
0009 Enabled MAIN RECEPTION AREA

Press the  buttons to scroll through the available zones, or key in a specific zone number.

www.advancedco.com 23
To disable the entire zone, move over to the Mode column and highlight the existing mode. Press the ✔ button
and a pop-up window appears showing the three possible options: -

ALL INPUTS .
ALL EXCEPT CALL POINTS
SELECTED INPUTS

Press the  buttons to scroll through and highlight the required option and then press the ✔ button to select
it.
If ALL INPUTS is chosen, the pop-up window disappears and the State of the Zone is changed to ALL
DISABLED.
If the ALL EXCEPT CALL POINTS is chosen, the pop-up window disappears and the State of the Zone is
changed to PART DISABLED (if there are actually call points in this zone) or is changed to ALL DISABLED if
there are no call points within this zone.
If SELECTED INPUTS is chosen, the pop-up window disappears and a list of the input devices within the
selected zone is presented. For example:
[ Inputs in Zone 001] More>
Mode Lp Adrs State
Enabled 1 001.0 Normal
Disabled 1 002.0 Normal
Enabled 1 003.0 PRE-ALARM
Enabled 1 004.0 Normal

Press the  button to more information on the inputs, including full device text, type, analogue value etc.
Press the  buttons to scroll through and highlight the required input and then press the ✔ button to disable
it. Pressing the ✔ button when the input is already disabled will enable the input.
Press the ‘Esc’ button to return.
3.8.2 Disable - Outputs
The Disable Outputs Option enables the isolation of some or all of the outputs. If disabled, the outputs will not
activate in the event of a fire alarm or other programmed event.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
[Disable]
Please Enter Your Password

Enter the password as normal. Once a valid password has been entered, a pop-up window is shown on the
display to select the type of outputs to disable. Scroll down to view / select the available options.

ALL SOUNDER STYLE OUTPUTS .


ALL OTHER OUTPUTS
SELECTED OUTPUTS
FIRE ROUTING ↓
FAULT ROUTING
PAGER

The selection list only contains Fire Routing, Fault Routing and Pager options if these are configured on the
panel.

24 www.advancedco.com
3.8.2.1 All Sounder Outputs
Press the  buttons to scroll through and highlight the ALL SOUNDER OUTPUTS Option and then press the
✔ button to disable them. The display automatically reverts to the Main Disable Menu.
The ‘Sounder Disabled’ Indicator will be illuminated.
On networked systems, this only disables the outputs connected to this panel.
3.8.2.2 All Other Outputs
Press the  buttons to scroll through and highlight the ALL OTHER OUTPUTS Option and then press the ✔
button to disable them. The display automatically reverts to the Main Disable Menu.
On networked systems, this only disables the outputs connected to this panel. This will disable all
outputs other than sounder type outputs including the fire and fault routing outputs.
3.8.2.3 Selected Outputs
Press the  buttons to scroll through and highlight the ONLY SELECTED OUTPUTS Option and then press
the ✔ button to select it. The display then shows a list of Zones containing outputs. For example:
[ 2 Zones with Outputs Disabled] More>
Zone Mode Location
0008 ENABLED GROUND FLOOR
0100 ENABLED MAIN RECEPTION

Press the  buttons to scroll through and highlight the required Zone and then press the  button to view the
outputs within this zone. For example:
[ Outputs In Zone 0008] More>
Mode Lp Adrs State
Enabled 1 032.0 Off SOUNDER
Enabled 1 056.0 Off SOUNDER
Enabled 2 011.1 *On RELAY
Enabled 3 026.1 Off RELAY

Press the  buttons to scroll through and highlight the required Output and then press the ✔ button to
change the device mode. The device mode will change from Enabled to Disabled and vice-versa.
Press the ‘Esc’ button to return to the Zone list and to the Main Disable Menu.
3.8.2.4 Fire Routing Output
Press the  buttons to scroll through and highlight the FIRE ROUTING OUTPUT Option and then press the
✔ button to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
The ‘Fire Routing Disabled’ Indicator will be illuminated.
3.8.2.5 Fault Routing Output
Press the  buttons to scroll through and highlight the FAULT ROUTING OUTPUT Option and then press the
✔ button to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
3.8.2.6 Pager
Press the  buttons to scroll through and highlight the PAGER OUTPUT Option and then press the ✔ button
to disable it. The display automatically reverts to the Main Disable Menu.
This feature disables the output connected to this panel only.
3.8.3 Disable - Controls
Disabling Controls will cancel Level 2 access and return the panel to Level 1 operation.
If the panel has an access key switch fitted, use the key switch in preference to the menu option shown
below.

www.advancedco.com 25
[Disable] User 1 Node 1

ZONE/INPUTS OUTPUTS CONTROLS


DELAY-MODE USER-ID GROUPS

Press the  buttons to highlight the Controls option and then press the ✔ button to select it.
The display then prompts for password entry. Enter the password as normal.
When a valid password has been entered, the control button functions and menu functions are disabled and the
level 1 menu display will be shown: -
[ CONTROLS DISABLED ]

ENABLE CONTROLS VIEW

The display will automatically revert to the normal operating display after a few seconds.
3.8.4 Disable - Delay-Mode
This operation will cancel the Investigation Delay mode.
[Disable] User 1 Node 1

ZONE/INPUTS OUTPUTS CONTROLS


DELAY-MODE USER- ID GROUPS

Press the  buttons to highlight the Delay-Mode option and then press the ✔ button to select it.
If the delays are configured in the panel, the display shows the following pop-up window when the Disable
Delay-Mode Option is selected. (Note: This delay function can only be configured using the PC Programming
Tool).

NO INVESTIGATION DELAY .
PERMANENT DELAY

Press the ✔ button to select NO INVESTIGATION DELAYS and disable the operation of the Stage 1 / Stage 2
Investigation Function. Otherwise, press the ESC to cancel and keep the investigation delays in operation.
If the investigation delays are in operation then the “Delayed” LED Indicator is illuminated. When the
investigation delays are disabled and turned off, the “Delayed” LED Indicator is turned off.
Press ‘Esc’ to cancel and make no change to the current operational setting.
If the delays are not configured in the panel, the display briefly shows “NOT CONFIGURED” before returning to
the Disable Menu Options.

26 www.advancedco.com
3.8.5 Disable – User ID
This operation will cancel the current User ID and return to the default User 1. User 1 can perform all actions
except those defined as programmable (refer to the menu table).
[Disable] User 5 Node 1

ZONE/INPUTS OUTPUTS CONTROLS


DELAY-MODE USER-ID

Press the  buttons to highlight the User-ID option and then press the ✔ button to select it.
[Disable] User 1 Node 1

ZONE/INPUTS OUTPUTS CONTROLS


DELAY-MODE USER-ID GROUPS

NOTE: If configured to operate with a timeout and if there has been no user activity after the programmable
period of time (default “No Timeout”), the panel will automatically cancel a User ID and return the panel to User
1 ID access. This is to ensure that access to restricted options is automatically cancelled.
3.8.6 Disable – Groups
Disablement Groups are a means of disabling / enabling custom groups of devices. The commands are
command across the network of panels and can be invoked from any panel. The installer will have configured
these groups.
If no groups exist, selection of this option will show a NOT CONFIGURED message.
Some typical examples are:
Stage Smoke Detectors
Floor 2 Sounders
ALL Sounders
The display will show, for example:
[Disable Group] User 5 Node 1
Group Invoke Description
1 . - Stage Smoke Detectors
2 - Floor 2 Sounders
3 - ALL Sounders

Press the  buttons to scroll through and highlight the required option and then press the ✔ button to disable
it. The display will show that the command has been invoked (activated).
[Disable Group] User 5 Node 1
Group Invoke Description
1 . ok Stage Smoke Detectors
2 - Floor 2 Sounders
3 - ALL Sounders

The GENERAL DISABLE and any specific disable indicators will be illuminated on the panel(s).

www.advancedco.com 27
3.9 Enabling
On selection of the Enable Menu Option, the display shows the available Enable Functions.
[Enable] User 1 Node 1

ZONE/INPUTS OUTPUTS GROUPS


DELAY-MODE CHANGE-TIME REMOTE

Press the  buttons to highlight the required menu option and then press the ✔ button to select it.
3.9.1 Enable - Zones and Inputs
Selecting this option will show a list of zones containing disabled input devices. Either the complete zone, or
individual devices within the zone can then be enabled (Display format is virtually identical to the Disable
displays).
3.9.2 Enable - Outputs
When this option is selected, pop-up menu appears asking if you want to enable ALL SOUNDER OUTPUTS,
ALL OTHER OUTPUTS, ONLY SELECTED OUTPUTS, the FIRE ROUTING OUTPUT, the FAULT ROUTING
OUTPUT or the PAGER OUTPUT. If ONLY SELECTED OUTPUTS is selected, the display will list only zones
containing outputs that have been disabled. The individual outputs within the zone can then be enabled.
(The display format is virtually identical to the Disable displays).
3.9.3 Enable - Delay-Mode
This option allows the enablement of Investigation Delays and other related functions.
The Investigation Delays can be invoked as manual operation delays (Permanent and Once Only), Automatic
delays (configured to run with a time clock) and Extend delays. A further option is provided to Inhibit delays for
holiday periods. The options that appear in the menu depend on the installation configuration programmed by
the installer.
On selection of the ENABLE DELAY option, the display will show a pop-up menu list. For example:

NO INVESTIGATION DELAY
PERMANENT DELAY
AUTOMATIC ↓ ↓ Indicates if there are more options configured.

Press the  buttons to scroll through and highlight the required option and then press the ✔ button to enable
it.
The display will confirm the selection and indicate WORKING whilst it performs the operation. On completion, it
reverts to the pop-up menu.
For Extended and Holiday/Inhibit, further menus are presented.
3.9.3.1 Extend Delays
To extend any current automatic delays (for example overtime working).

Extend Delays for : ..0 hour(s)

Use the number keys to enter the required number of hours beyond the current configured end time.
3.9.3.2 Holiday / Inhibit
The panel can be enabled to prevent any pre-programmed daily automatic delays from activating during holiday
periods. On selection, the display shows:

28 www.advancedco.com
[Inhibit Delay End Date]

TIME = 15:49
DATE = 02/07/08 WED 02 JUL 2008

Press the  buttons to select the time / date fields. Enter the required time and date using the number
buttons.
Any pre-configured automatic delays or manual delays will be immediately suspended and the panel will
operate without any investigation delays.
On reaching the time / date programmed, the panel will automatically revert to use any investigation delays as
programmed and configured.

3.9.4 Enable - Groups


This option allows the re-enabling of User-defined Disablement Groups. The display is identical to the disable
option.

3.9.5 Enable - Change-Time


Allows the clock time to be changed.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
For example:
[SET TIME/DATE]

TIME = 15:28
DATE = 15/04/06 SAT 15 APR 2006

To change the settings, use the  buttons to highlight the required option. Directly enter the new time or date
using the number buttons. As soon as a number button is pressed, the display will clear the current setting and
show the new value as it is entered. For example:

[SET TIME/DATE]

TIME = 1-:--
DATE = 15/04/06 SAT 15 APR 2006

If this panel is connected to a network, ALL panels on the network will assume this new value.

www.advancedco.com 29
3.9.6 Enable - Remote
Information on the detectors connected to the panel and on the condition of all zones can be obtained with an
ipGateway interface.
In addition, the user can be assisted with operations such as disabling / enabling a detector from external
commands over a TCP/IP system. In order to ensure this only happens with the consent of the user the
REMOTE option must be enabled by the user.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
After selecting the option, a selection list is presented on the display as follows:

[Remote Access Options]


DISABLE REMOTE ACCESS
ALLOW REMOTE ACCESS .

Use the  buttons to highlight the required option and then press the ✔ button to confirm.

30 www.advancedco.com
3.10 Testing
[Test Menu] User 1 Node 1

ZONES DISPLAY BUZZER PRINTER


OUTPUTS

Press the  buttons to highlight the required menu option and then press the ✔ button to select it.

3.10.1 Test - Zones


The Test Zones function provides the means to implement a one-person walk test in order to test specific call
points or detectors in one or more zones.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
When the Test Zones option is selected, a pop-up window is shown on the display to select whether the
sounders will activate (for about 10-seconds) when an input device is activated. For example:

WITHOUT SOUNDERS .
WITH SOUNDERS

Press the  buttons to scroll through and highlight the required option and then press the ✔ button to select
it.
Note that the panel will have been programmed during commissioning to define which of the sounders are
activated during a test.
The display then shows a list of the available Zones and their current test status. For example:
[ 0 Zones in Test ]
Zone Test State Location
>0001 - BASEMENT WEST
0002 - BASEMENT EAST
0100 - MAIN RECEPTION

Press the  buttons to scroll through and highlight the required zone and then press the ✔ button to change
the Test State. For example:
[ 1 Zone in Test ]
Zone Test State Location
0001 IN TEST BASEMENT WEST
0002 - BASEMENT EAST
0008 - GROUND FLOOR
0009 - MAIN RECEPTION AREA

When one or more Zones are placed in a Test State, the Test Indicator will be illuminated. When an input device
is activated (i.e. break glass test on a call point or introducing test smoke into a smoke detector), the bells will
ring (if selected) and the display will indicate that a zone is registering a test condition by showing an
exclamation mark (!) on the display.
[ 2 Zones in Test ]
Zone Test State Location
0001 IN TEST ! BASEMENT WEST
0002 - BASEMENT EAST
0008 - GROUND FLOOR
0009 IN TEST MAIN RECEPTION AREA
When the activating test key is removed from the call point or the smoke clears from the detector chamber, the
panel will automatically reset and clear the test condition.

www.advancedco.com 31
As an alternative to scrolling, a specific zone number can be entered by using the  button to move to the zone
number column, and then typing in the required number, followed by the ✔ button.
If several consecutive zones are to be tested, an alternative to selecting them all individually is to specify a
range of zones as follows: -
Move to the zone number column and highlighting the first zone to test, then
Press the ✔ button – the display will then ask for the last zone to be tested.
Individual zones can then be toggled in or out of test by pressing the ✔ button.
To leave the Zone Test menu, press the ‘Esc’ button. If there are still any zones in a test condition a pop-up
window with the following options: -

FINISHED TEST .
KEEP ZONES IN TEST

Selecting the FINISHED TEST option will cancel all zone tests. The Test LED will then extinguish.
Alternatively, it is possible to leave the Zone Test Function with one or more Zones still in Test by selecting the
KEEP ZONES IN TEST option. This will enable the inspection or use of other menu functions and return the
display to the normal operating mode. The Test LED will stay illuminated if this option is selected.
3.10.2 Test - Display
The Test Display option checks the operation of all the Indicators and the Graphic Display. All of the Indicators
are turned on and the entire display is shown in reverse.
During this test, it is possible to test the operation of the ,,,,✔ and 0-9 buttons. When a button is
pressed, it is indicated on the display. For example:

LCD & KEY TEST


Press the ‘Esc’ button to return to the Test Menu. If no button is pressed for 1-minute, the display will
automatically revert to the normal operating display.
3.10.3 Test - Buzzer
[Test Menu] User 1 Node 1

ZONES DISPLAY BUZZER PRINTER

When the Test Buzzer option is selected, the internal buzzer will sound for about five seconds.

32 www.advancedco.com
3.10.4 Test - Printer
To invoke the printing of a test print sequence, highlight the Test Print Option and press the ✔ button to confirm.
The panel transmits 16 lines of test characters to the printer. The information sent is echoed on the display.
When the test print is completed, the display automatically reverts to the Test Options Menu.
Press the ‘Esc’ button at any time to cancel the test print.
3.10.5 Test - Outputs
Output devices can be individually tested for operation.
To test an individual output device (sounder or relay), highlight the Test Outputs Option and press the ✔ button
to confirm. The display will present a list of the zones that contain output devices.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent operation.
[Outputs]
Zone Location
0001 BASEMENT WEST
0002 BASEMENT EAST
0037 EAST PLANT ROOM
0100 MAIN RECEPTION

Press the  buttons to scroll and highlight the required zone (or key in the required zone number) and then
press the  button to show the output devices in that zone. For example:
[Loop 1 Devices] <More>
Address State Type Value
005.1 Normal SOUNDER -
006.0 Normal MULTI.SENSOR 16
006.1 Normal RELAY -
007.0 Normal CALL POINT 16

Press the  buttons to scroll and highlight the required zone (or key in the required zone number) and then
press the ✔ button to test the output. The display will prompt to confirm the “Test this device”. Press the ✔
button again to accept. The output device will turn on and this will be confirmed on the display by the status
changing from OFF to ON.
The general “TEST” LED will illuminate whenever an output is in test. The test is cancelled by either pressing
the ESC button or by scrolling to the next / previous device in the list. If the display is left for one minute without
pressing any buttons, the output will revert to its quiescent state.
On networked systems, the Test – Outputs option also supports testing of outputs connected to other panels.

www.advancedco.com 33
3.11 Printing
[Print Menu] User 1 Node 1

INPUTS OUTPUTS FAULTS DISABLED


LOG FEED-PAPER SETUP PRINTER

3.11.1 Printer Communications Settings


The information is sent to the printer in a serial form. If an external printer is used, ensure that the
communications settings in the printer are set as follows:
Interface Type: RS232
Baud Rate: 9600
Parity: None
Data Bits: 8
Stop Bits: 1
3.11.2 Set-up Printer
To enable or set-up the operating characteristics of the printer, highlight the Set-up Printer Option and press the
✔ button to confirm.
If the current User ID does not have the necessary permission, the display prompts for entry of a password to
guard against inadvertent changes.
Enter the password as normal. The display then shows a pop-up window giving programming options as
follows:

[FIRES] [ALARMS] [FAULTS] [TESTS]


✔ ✔ - -
( Printer: Internal External/Wide )
- ✔ -

The upper line of options determines whether the panel shall automatically print specific events as they occur.
The lower line of options determines whether a printer is connected and its type.
Use the ,,, and ✔ buttons to highlight the required option and change its setting. Pressing the ✔ button
turns the option on (✔ is shown) or off (- is shown) accordingly.
In the above option, an external printer is selected, with automatic printing of fires and alarms.
Setting the wide option will change the printing from the default 40 characters per line to 80 characters per line.
Note: Only faults registered on this panel are printed.
3.11.3 Print Inputs
To print information on any input, highlight the Inputs option and press the ✔ button to confirm. The display will
show the following:
[Inputs]

First Zone : 98
Last Zone : 98

(Press → to Start Print)

The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones
used in the system. Use the arrow () buttons to highlight the first and last zone number and use the number
keys to change the zone number required.

34 www.advancedco.com
Press the  key to start printing.
The display will show the following whilst information is sent to the printer and printed.

WORKING ...

(Press Esc to Stop)

After all information has been printed, the display will automatically revert to the Print Menu. Press the “Esc” key
to stop printing if required.
The printout will show all input points for the zones selected. Information printed includes Device Text, Zone
Number, Loop and address, current status and analogue value.
3.11.4 Print Outputs
To print information on any output, highlight the Outputs option and press the ✔ button to confirm. The display
will show the following:
[Outputs]

First Zone : 98
Last Zone : 98

(Press → to Start Print)

The display will prompt the zones in use on this panel. For networked systems, it is possible to select any zones
used in the system. Use the arrow () buttons to highlight the first and last zone number and use the number
keys to change the zone number required.
Press the  key to start printing.
The printout will show all output points for the zones selected. Information printed includes Device Text, Zone
Number, Loop and address, current status and analogue value.
3.11.5 Print Faults
To print information on any faults, highlight the Faults option and press the ✔ button to confirm. The display will
show the following:
[ 2 Zones in Fault]

First Zone : 98
Last Zone : 99

(Press → to Start Print)

The panel analyses the network and the display will prompt the zones in a fault condition.
Use the arrow () buttons to highlight the first and last zone number and use the number keys to change the
zone number as required.
Press the  key to start printing.
The printout will show the location and state of all input and output points in a fault condition for the zones
selected.
Note: If there aren’t any fault conditions present then selecting this menu option will no effect.
3.11.6 Print Disabled
To print information on any disablement, highlight the Disabled option and press the ✔ button to confirm. The
display will show the following depending on the disabled conditions present:
If there are zones with inputs disabled:

www.advancedco.com 35
[ 2 Zone(s) with Inputs Disabled]

First Zone : 98
Last Zone : 99

(Press → to Start Print)

If there are zones with outputs disabled:


[ 1 Zone(s) with Outputs Disabled]

First Zone : 98
Last Zone : 98

(Press → to Start Print)

The panel analyses the network and the display will prompt the zones in a disabled condition.
Use the arrow () buttons to highlight the first and last zone number and use the number keys to change the
zone number as required.
Press the  key to start printing.
The printout will show the location and state of all input and output points in a disabled condition for the zones
selected.
The display always present the zones with inputs disabled first (if any exist). After printing the inputs the display
will present the information on disabled outputs (if any exist).
Note: If there aren’t any disabled conditions present then selecting this menu option will no effect.
3.11.7 Print - Log
To print information from the History Log, highlight the Print Log Option and press the ✔ button to confirm. A
pop-up window will be shown asking if all events, or just fires should be printed.
Highlight the required option using the  buttons and press the ✔ button to confirm.
When the Log Print is completed, the display automatically reverts to the Print Options Menu.
Press the ‘Esc’ button at any time to cancel the log print.
Note: The pop-up window also allows selection of the Fire Alarm Counter. On selection, this is shown on the
display but is not printed.

3.11.8 Print - Feed Paper


Highlight the Feed Paper Option and press the ✔ button to confirm. The display does not change but a
command is sent to the printer to advance the paper.

36 www.advancedco.com
In the event of a fire alarm, call: -
Quick Reference Guide TEL:
For Service & Maintenance,
contact: -

TEL:

Controls & Indications


Graphic Liquid Navigation Navigation Buttons
Crystal Display Buttons

  Press to scroll through Menu Options.


Press to display more information.

  Press to scroll through menu Options.


Press to scroll through lists of zones or
devices.

 Press to confirm entry of numeric or letter


information entry.
SOU N D ER
FI R E SIL EN C ED RESET Press to confirm selection of a menu
SOU N D ER
AB C DEF option.
FA U LT
FA U LT

DI SA B LE
SOU N D ER
! MU TE
GH I JKL MNO
Press to change some of the configuration
options.
DI SA B LE D
SILENCE/
TEST SYS T EM FA U LT RESOU ND
PQRS TUV WXYZ
Number Buttons
POW ER DE LAYED EVAC UATE
0 to 9wxyz Used to enter numbers or letters.

LED Status Control Number and


Indicators Buttons Letter Buttons Esc Press to return to a previous menu.
Press to exit the menu functions and return
to the normal display.
The panels may be fitted with separate zone fire indicators comprising of 20, 50, 100 or 200 red Menu Press to show or return to Level 1 or Level
indicators – these show the zones in a fire alarm condition. 2 Menu Functions.
In addition, the panels may be fitted with separate indications showing the loaction of fire alarms in Main User functions are VIEW, TEST,
a pictorial display (mimic diagram). DISABLE & ENABLE.
For easy reference, cut out and frame / mount on the wall next to the panel.

Graphic Display Control Buttons


The graphical display provides detailed information of the source of fires, faults and warnings. It Reset: Press to reset the panel from a
also shows menus for use when inspecting or programming the operation of the panel. latched condition.
Under normal conditions the panel display shows the time, date and status: -
Mute: Press to mute the internal buzzer.

LEVEL 2 Silence / Re-sound: Press to silence the


bells. Press again to re-sound the bells.
16:05
04 MAR 2006 Evacuate: Press to initiate a manual
evacuation and sound the alarms.

Level 2 Access is required for Reset, Silence / Re-sound &


NORMAL PANEL OPERATION Evacuate buttons and for programming Menu functions.
Level 2 operation can be enabled using a key-switch (if
(Press Menu to View) fitted) or by entry of a pass-code.

LED Status Indicators


The following is a typical menu display.

[Level 2 Menu] RED Separate LED Indicators show the


presence of a fire alarm condition and (if
configured) that the fire brigade has been
VIEW DISABLE ENABLE called.

TEST PRINT COMMISSION YELLOW Indicate other system operating conditions


including Fault, Test and Disablement
STATUS conditions.

GREEN Indicates the presence of power to the


system – if flashing, indicates that the panel
is running on battery standby power.

Refer to the User Manual (Document Number 680-015) for full operating instructions.

www.advancedco.com 37
This page is intentionally left blank.

38 www.advancedco.com
USER NOTES

www.advancedco.com 39
Doc Number: 680-015

Revision: 10
Advanced Electronics Ltd
Moorland Way, Cramlington, Northumberland, NE23 1WE UK
First Issued: 2013-mm-dd
Tel: +44 (0)1670 707 111 Fax: +44 (0)1670 707 222
Email: [email protected] Web: www.advancedco.com

www.advancedco.com

You might also like