SR-2 SPECTRUM Multi-Temp Microprocessor Control System (TK 53080-2-OD) PDF
SR-2 SPECTRUM Multi-Temp Microprocessor Control System (TK 53080-2-OD) PDF
SR-2 SPECTRUM Multi-Temp Microprocessor Control System (TK 53080-2-OD) PDF
TK 53080-2-OD (01/07)
DIAGNOSTIC MANUAL
PART 1 – (Sections 1-5)
PART 2 – (Sections 6-9)
This manual is published for informational purposes only and the information so provided should not be
considered as all-inclusive or covering all contingencies. If further information is required Thermo King
Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo King's terms and conditions including, but
not limited to, the THERMO KING LIMITED EXPRESS WARRANTY. Such terms and conditions are
available upon request. Thermo King's warranty will not apply to any equipment which has been "so
repaired or altered outside the manufacturer’s plants as, in the manufacturer’s judgment, to affect its
stability".
This manual contains information, data, procedures, and processes covered by the
following SR-2 software revisions:
Earlier versions of software are similar but may not include or support all features as
shown in this manual.
HOW TO USE THIS MANUAL
Because not everyone is familiar with microprocessor based control systems, please take a few
minutes to read this page. It explains the content and structure of this manual. This will make it
easier for you to find the information you need.
x Section 4 - Operation
This section explains how to operate the SR-2 SPECTRUM control system. This information is referenced by
material in Section 5 Diagnostics.
x Section 5 - Diagnostics
This section explains how to diagnose units equipped with the SR-2 SPECTRUM control system. It includes
both Alarm Code Diagnostics and Other Symptom Diagnostics. This section will reference material in Section
4 Operation and Section 6 Service Procedures.
The following procedures must be followed when working on units equipped with
microprocessor based control systems.
x Never use testers consisting of a battery and a light bulb to test circuits on any
microprocessor based equipment.
x The unit must be turned off before connecting or disconnecting the battery.
x Any time the Base Controller is replaced, these Service Procedures must be used:
A02A Recording Existing Programmable Feature Settings
A03A Replacement of the Base Controller or Interface Board
A04A Programmable Feature Setup
x Any time the Interface Board is replaced, Service Procedure A03A Replacement of the
Base Controller or Interface Board must be followed.
x Any time welding is to be done on the unit or vehicle Service Procedure A26A Welding
on Units Equipped with Microprocessors must be followed.
Section 1 – SR-2 SPECTRUM Safety Information
1-1
09 January 2007
Section 1 – SR-2 SPECTRUM Safety Information
1-2
09 January 2007
Section 1 – SR-2 SPECTRUM Safety Information
6. Refrigerants in the presence of an open flame SR-2 units have options that allow for
produce toxic gases. These gases are severe remote starting from a fully off state. Be
respiratory irritants capable of causing death. sure to turn the unit Microprocessor On/Off
switch "off" before opening doors,
7. Be sure all mounting bolts are the correct length
inspecting or working on any part of the
for the application and are securely tightened.
unit.
1-3
09 January 2007
Section 1 – SR-2 SPECTRUM Safety Information
REFRIGERANT
At Thermo King we recognize the need to preserve Refrigerant First Aid
the environment and limit the potential harm to the
1. Warm the frozen area by immersing it in luke-
ozone layer that can result from allowing refrigerant
warm (not hot) water or by covering the area
to escape into the atmosphere.
with warm blankets.
1-4
09 January 2007
Section 1 – SR-2 SPECTRUM Safety Information
ELECTRICAL
2. Use tools with insulated handles that are in good
CONSIDERATIONS condition. Never hold metal tools in your hand if
exposed high voltage conductors are within
Controller Service reach.
1-5
09 January 2007
Section 1 – SR-2 SPECTRUM Safety Information
Low Voltage
Control circuits are typically 12 volts dc. This
voltage potential is not considered dangerous, but
the large amount of current available can cause
severe burns if shorted to ground.
1-6
09 January 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-1
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-2
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-3
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-4
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-5
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
ZONE 1
CONTROL DEVICES Not all devices
Hot Gas Solenoid shown here are
Suction Line Solenoid used on all
applications
ZONE 2 ZONE 3
REMOTE REMOTE
EVAPORATOR(S) EVAPORATOR(S)
SR2
MULTI-TEMP
EXPANSION MODULE
ZONE 2 LED Indicators
ZONE 3
SENSORS Smart FETs SENSORS
Return Air Temp Sensor Return Air Temp Sensor
Discharge Air Temp Sensor Discharge Air Temp Sensor
Evap Coil Temp Sensor Evap Coil Temp Sensor
ZONE 2 ZONE 3
SWITCHES SWITCHES
Door Switch Door Switch
ZONE 2 ZONE 3
CONTROL DEVICES CONTROL DEVICES
Fan Motor(s) 1 Fan Motor(s) 1
Fan Motor(s) 2 Fan Motor(s) 2
Fan Motor(s) 3 Fan Motor(s) 3
Fan Motor Speed Control Fan Motor Speed Control
Hot Gas Solenoid(s) Hot Gas Solenoid(s)
Liquid Line Solenoid(s) Liquid Line Solenoid(s)
Suction Line Solenoid(s) Suction Line Solenoid(s)
Drain Tube Heater(s) Drain Tube Heater(s)
Damper Solenoid (DE Only)
2-6
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
CAUTION
GENERAL DESCRIPTION
Dangerous three phase AC power is present
The SR-2 SPECTRUM Multi-Temp controller is a
whenever the unit is operating in Electric mode
self-contained temperature control unit designed for
and whenever the unit is connected to external
trailer applications. Model 30 units are powered by
standby power. Voltages of this magnitude can
a diesel engine and Model 50 units are powered by
be lethal. Exercise extreme caution when
either the diesel engine or an external electric
working on the unit.
standby power source powering an electric motor.
The host unit mounts on the nose of the trailer. Heat
and defrost is by means of hot gas. Optional Zone 1 CONTROL SYSTEM
electric heat is available on Model 50 units (does not The SR-2 SPECTRUM Control System consists of
include DE units). the following main components:
x Base Controller On/Off Switch
The host unit is the main refrigeration unit. It also x HMI (Human Machine Interface) Control Panel
provides the evaporator coil, control solenoids, and x Base Controller
evaporator blower to serve Zone 1. The host unit x Interface Board
includes the engine, compressor, condenser coil,
x Unit Sensors and Transducers
control box, condenser blower and host unit sensors
x Refrigeration Control Components
and solenoid valves. It also includes the Zone 1
x Engine Control Components
evaporator coil, Zone 1 evaporator blower, Zone 1
x Communication Ports
temperature sensors and Zone 1 defrost damper.
x Multi-Temp Expansion Module
x Optional Electric Standby
If the unit is a DE unit, the host unit also includes the
Zone 2 evaporator coil, Zone 2 evaporator blower,
Zone 2 temperature sensors and Zone 2 defrost
damper.
2-7
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
J1
REV. B000
C
J2
2-8
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2
35.8
TEMP F
controller/interface board via a controller area ON
-8. SET
-10 35 POINT
2-9
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
SET
power to the controller and most controller
-10 35 POINT
3 OFF
ZONE 1 ZONE 2 MENU outputs. It does not disconnect HMI supply
power. The HMI is directly connected to the unit
starting battery.
SmartReefer2
IMPORTANT
Always turn the unit Base Controller On/Off
1 CargoWatch Download Port switch "off" before inspecting or working on any
2 Base Controller On/Off Switch part of the unit.
3 CargoWatch Printer Port
4 HMI Control Panel SB Series Units
The Base Controller On/Off switch is located on the
side of the control box. It can be reached by
opening the engine compartment doors.
MICRO-
PROCESSOR
ON
OFF
2-10
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
OVERCURRENT PROTECTION
Overcurrent protection is provided by a fusible link
located in the positive battery cable. A 15 amp main
power fuse F2 is located in the “2A/2AB” circuit.
2-11
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
-8.2 35.8
ON
TEMP F
SET
OFF
-10 35 POINT
Real Time Clock
ZONE 1 ZONE 2 MENU
2-12
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-13
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-14
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
12 1
23 13
35 24
2-15
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-16
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-17
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
12 1
23 13
35 24
2-18
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
REMOTE LIGHT
15A
K5 J8
2A
ON/OFF
interface board and expansion module. The relays K4
SWITCH
F10
F9 F12 F8 2A
3A 5A 5A
control power to the high amperage loads. The
10A
LED4 F7 LED23 K9
J27 J6
ELECTRIC
LED26
K3
RS232-1 RS232-2
Smart FETs control power to the lower amperage J9 J10
15A
F6
LED5
LED6
J102 J103 F11
loads. Each relay is individually fuse protected. The J15
J101 K1 F4
10A
29 7D F15
Smart FETs are self-protecting A LED next to each
GM1
8
DF
F12
relay or Smart FET is illuminated when the relay or GM2 8S
LED21
K8
LED25 LED17
FET is energized by the base controller. With relays 8D 8DP
LED24 1 LED18
LED22
LED19
the LED lights only when the relay coil is energized K6 K7
LED20
F20 2A F25
60A
onto the base controller and is secured with
7.5A
LED30
F5
LED27
J25 2A H
mounting hardware. The controller to interface K2
3 LED29
LED28
J26
J3
board electrical connections are made through the
1
2-19
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Service Part # 45-2148 Interface Board. See It is designed for use with the Yanmar engine air
Section 7 of this manual for details and preheater. Always replace the fuse with the TK
2-20
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
K2 Preheat Relay
K3 High Speed Relay Output Function
2-21
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
output is energized. To identify LEDs see page 2- when the base controller is powered and operating
2-22
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Output Function
EVA, EVB, EVC, EVD ETV Outputs
HG / LV2 Hot Gas Sol or
Loader Valve 2
ALPC Alarm Light
ALM Alarm Light
LV1 Loader Valve 1
EXC Alternator Excite
WV Water Valve
LQI Liquid Injection Valve
LLS Liquid Line Solenoid
GM1, GM2 Damper Gear Motor
(NOTE 1)
2-23
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
J102
J101 Cold Start jumper Not Used
Shown in the normal position
J103
Not Used
2-24
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-25
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
3 2 1 8
J4 F2
4
LED7 CAN 3 CAN 2 CAN 1
J14 J13 J12
F13
REMOTE LIGHT
15A
K5 J8
5
2A
ON/OFF
SWITCH
F10
K4 F9 F12 F8 2A
3A 5A 5A
10A
LED4 F7 LED23 K9
J27 J6
ELECTRIC
LED26
K3
RS232-1 RS232-2
J9 J10
15A
F6
LED5
LED6
J102 J103 F11
J101 K1 F4
J15
10A
29 7D F15
GM2 GM1
8
DF
F12
LED21
8S
LED25
6 7 K8
LED17
9 8D 8DP
LED24 LED18
LED22 13
LED19
LED20
K6 K7
J23
40A LED8 CH
J24 F3 LED9
2 LED10
LED11
11 LED3
F20 2A F25
60A
7.5A
LED30
F5
LED27
J25 2A H
K2
10 LED29
LED28
J26
J3
12 1
14
J7
2-26
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-27
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
12 1
13
24
36 25
2-28
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
J12 – Expansion Module CAN Bus Communication and Power Connector – arranged by pin number
Pin Wire Description
Number Number
1 CANL-BLU To expansion module J2 pin 1
2 CANH-GRE To expansion module J2 pin 2
3 SHLD To expansion module J2 pin 3
4 ON - RED To expansion module J2 pin 4
5 2A - BLK To expansion module J2 pin 5
6 8XP-YEL To expansion module J2 pin 6
7 Not Used
8 CH - ORA Chassis ground to expansion module J2 pin 8
Mini Mate-N-Lok Harness Connectors – shown from pin side of harness connector
1 2 1 2 3 1 2 3 4
3 4 4 5 6 5 6 7 8
2-29
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
J14 - HMI CAN Bus Communication and Power Connector– arranged by pin number
Pin Wire Description
Number Number
Mini Mate-N-Lok Harness Connectors – shown from pin side of harness connector
1 2 1 2 3 1 2 3 4
3 4 4 5 6 5 6 7 8
2-30
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Mini Mate-N-Lok Harness Connectors – shown from pin side of harness connector
1 2 1 2 3 1 2 3 4
3 4 4 5 6 5 6 7 8
2-31
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-32
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
REMOTE LIGHT
15A
K5 J8
2A
ON/OFF
SWITCH
F10
K4 F9 F12 F8 2A
3A 5A 5A
10A
LED4 F7 LED23 K9
J27 J6
ELECTRIC
LED26
K3
RS232-1 RS232-2
J9 J10
15A
F6
LED5
LED6
J102 J103 F11
J101 K1 F4
J15
10A
29 7D F15
J1
GM2 GM1
8
DF
F12
LED21
8S
K8
LED25 LED17
8D 8DP
LED24 LED18
LED22
LED19
LED20
K6 K7
ASS'Y P/N: 1E19308G01 REV. B000
S.P. P/N: 45-2013
C
S/N:XXXXXXXXXXX
J23
40A LED8 CH
J24 F3 LED9
2 LED10
LED11
LED3
J2
F20 2A F25
60A
7.5A
LED30
F5
LED27
J25 2A H LED29
K2
LED28
J26
J3
1
ASS'Y P/N: 1E19311G01
S.P. P/N: 45-2015
S/N:XXXXXXXXXXX
REV. B000 A ND
J3
J7
2-33
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
MULTI-TEMP EXPANSION
1
MODULE
The expansion module is a hardware module that
allows for operation of up to three temperature
controlled zones. The module provides the interface
5
between the base controller and the zone 1, zone 2
and zone 3 multi-temperature components such as
4
sensors, solenoids, valves, and fan motors. It also
provides overcurrent and short circuit protection for
the associated circuits. The EM features 100% solid
2
state outputs All outputs are SmartFet outputs.
13 23 4 3 2 1
Zone 1 return air temperature sensor, Zone 1 8 7 6 5
24 35
2-34
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-35
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-36
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-37
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
12 1
23 13
35 24
2-38
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Mini Mate-N-Lok Harness Connectors – shown from pin side of harness connector
1 2 3 4
5 6 7 8
Expansion Module Fan Harness Connectors – shown from pin side of harness connector
6 5 4 3 2 1
1 12
13 23 J1 4 3 2 1
8 7 6 5
J2
24 35
1 2 3 4 5 6
J13
2-39
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-40
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Graded Sensor
Un-graded Sensor
with Yellow Shrink Tube Marker
2-41
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
CARGOWATCH SENSORS
The CargoWatch Data Logger is internal to the HMI
Control Panel. This Data Logger conforms to
European standard EN12830. The Data Logger
supports up to 6 temperature sensors and 3 digital
inputs.
IMPORTANT
The CargoWatch sensors ARE NOT inter-
changeable with the unit temperature sensors.
CargoWatch Sensor
No Shrink Tubing
2-42
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-43
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Discharge Pressure Transducer (DPT) The Zone 1 damper solenoid is energized and
This transducer supplies the discharge pressure at interface board LED 4 is lit when the base controller
the compressor to the base controller. This energizes the K4 Damper Relay. The K4 Damper
information is used by the base controller and Relay normally open contacts supply power via the
software to determine the unit operating conditions. 29 wire to the damper solenoid. The circuit is
protected by the 15 amp fuse F6.
pressure. This pressure may be higher than the open and close the host unit defrost damper door.
compressor suction pressure. The interface board for units with damper solenoids
is different than the one used with defrost damper
motors. See the information in Section 7 - Hardware
Damper Solenoid (DS)
Features and Interchange for Service Parts
Two methods are used to open and close the host
numbers.
unit defrost damper doors. Damper solenoids are
used on SB model units. Damper gear motor
actuators are used on SLX units. The DE model
units have damper solenoids in both Zone 1 and
Zone 2.
2-44
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-45
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
ENGINE CONTROL
Oil Level Switch (OLS)
COMPONENTS The normally open oil level switch monitors the oil
These components are used by the base controller level in the diesel engine. It is located above the oil
to sense conditions and control operation of the pan on the door side of the engine. It supplies
diesel engine (or electric motor, if present). information on the oil level to the base controller via
the J3 connector OLS wire. The switch is closed
Coolant Temperature Sensor when the oil level is low.
2-46
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Starter Motor (SM) Fuel Solenoid Pull-in Relay normally open contacts
The starter motor is located on the access door side supply power via the 8DP wire to the fuel solenoid
of the engine. The starter motor is energized and pull-in coil to positively open the fuel solenoid. The
interface board LED 25 is lit when the base circuit is protected by the 40 amp fuse F3.
contacts supply power via the 8S wire to the starter connected directly to the unit starting battery via the
The fuel solenoid is located at the rear of the injector High Speed Relay. The interface board K3 High
pump and is used to start and stop the flow of fuel to Speed Relay contacts supply power to the 7D wire
the diesel engine during diesel mode operation. The to the high speed solenoid to enable high speed
fuel solenoid features two coils, a pull-in coil and a operation. The circuit is protected by the 15 amp
hold coil. The pull-in coil transfers the fuel solenoid fuse F6.
2-47
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
COMMUNICATION PORTS
The SR-2 features three externally accessible
communication ports.
CargoWatch Port
The CargoWatch port is used to download the
CargoWatch data logger and to flash load software
to the HMI Control Panel. It is located on the control
panel next to the ServiceWatch port. This is a serial
RS-232 communication port.
ServiceWatch Port
The ServiceWatch port is used to download the
ServiceWatch data logger and to flash load software
to the base controller. It is located on the control
panel next to the CargoWatch port on SB units. The
connector is located inside the control box on SLX
units. This is a serial RS-232 communication port.
Printer Port
This port is used to print trip records from the
CargoWatch data logger. It is located inside the
control box on SB units. The connector is located
on control box door on SLX units. This is a serial
RS-232 communication port.
2-48
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-49
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
Heater Contactor HC
The heater contactor is used to supply standby
power to the electric heaters during heat and defrost
mode electric operation. The heater contactor is
energized and interface board LED 5 is lit when the
base controller energizes the interface board K3
High Speed Relay during electric mode operation.
The K3 High Speed Relay supplies chassis ground
via the 26E wire to the heater contactor.
2-50
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
T3 T2 T1 T3 T2 T1
L3
L1
L2
THERMO KING
9131C98G06 OVL PSM
0202
98 NO 97
2T1
1L1
L3
0202
L2
4T2
3L2
L1
9131C98G06
THERMO KING
96 NC 95
6T3
5L3
T3 T2 T1 T3 T2 T1 SLX Unit Electric Standby Components
L2 L3 L1 L2 L3 L1
2-51
02 February 2007
Section 2 – SR-2 SPECTRUM Hardware Description
2-52
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
This manual considers Base Controller Software Revision C000, HMI Control Panel
Software Revision 6510/6610 or 6710 and Supervisor Software Revision 120.
Earlier versions of software are similar but may not include or support all features as
shown in this manual.
3-1
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-2
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-3
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-4
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
SOFTWARE OPERATION
The Expansion Module software is used for control
of the zone evaporator’s operational functions. The
Software is a very complex set of instructions used
Expansion Module software is part of the Base
by the Base Controller, HMI Control Panel and
Controller software and is not shown as a separate
Expansion Module to control the refrigeration system
software revision.
and interface with the operator. The Base
Controller, HMI Control Panel and Expansion
The Supervisor software (12x) is also part of the
Module microprocessors examine the conditions of
Base Controller software. The Supervisor software
all the inputs and compare them to the instructions
revision is shown when checking software revisions.
contained in the software. The outputs are then
See Section 4 for details.
energized as specified by the software instructions.
3-5
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-6
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-7
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-8
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Standard Display
TemperatureWatch®
The Standard Display is the default display that
The TemperatureWatch Display shows the zone
appears if no other display function is selected. The
return air temperature and setpoint for each installed
Standard Display shows the zone return air
zone using large numbers that allow unit conditions
temperature and setpoint for up to 3 zones. The
to be checked from a distance. If there are no
Standard Display soft keys provide direct operator
alarms other than Log Alarms present then the
access to turn Zone 2 and Zone 3 on and off, to
TemperatureWatch display appears 2½ minutes
change the setpoint for each zone and to select the
after the last key is pressed and will remain until any
Main Menu.
soft key is pressed. To return to the Standard
Display press any soft key.
Turning Zones On and Off Zone 2 and Zone 3
can be turned on and off from the Standard Display
The TemperatureWatch display will not appear if any
using the soft key under each zone display. Zone 1
Check, Prevent or Shutdown alarms are present or if
is always turned on when the HMI ON hard key is
the CargoWatch -15°C Alarm is active. If the
pressed. All zones are turned off when the HMI
TemperatureWatch display is active and any of
OFF hard key is pressed.
these alarm conditions occur the display will return
to the Standard Display. If a shutdown alarm is
The On/Off state of Zone 2 and Zone 3 (if present) is
present the display will flash. This provides a quick
saved when the unit is turned off. If Zone 2 or Zone
method to check for units that may have an alarm
3 were turned on when the unit the unit was turned
set.
off, then they will still be on when the unit is turned
back on.
3-9
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-10
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
MAIN MENU
Gauges
The Gauges menu allows the operator to display
Main Menu Features operating information such as coolant level and
The Main menu allows the operator to check other temperature, engine RPM, battery amps, battery
unit conditions, change operating modes and volts, and suction and discharge pressure. The I/O
perform other operator functions. The Main menu is selection under Gauges indicates the named
accessed from the Standard Display by means of outputs as either On or Off.
the Menu soft key. The following menus are NOTE: This menu contains the same
available. information as the Maintenance Menu - Gauge
menu.
Language
If more than one language is enabled, this menu Sensors
item allows the operator to select a language from a The Sensors menu allows the operator to display the
list of up to 11 languages at one time. All reading of all unit temperature sensors as well as
subsequent displays are shown in the selected the calculated temperature differential.
language. Three different language packages with a NOTE: This menu contains the same
total of 24 languages are available. English is the information as the Maintenance Menu - Sensors
default language and is provided in each of the menu.
packages.
Datalogger
Alarms
This menu allows the operator to set a Start of Trip
The Alarms display allows the operator to display
marker or print the contents of the CargoWatch data
any existing alarms. The operator can also clear
logger.
most alarms from this menu
Hourmeters
NOTE: Some alarms are clearable in Guarded
The Hourmeters menu allows the operator to view
Access only. Alarms with this feature will not the unit hourmeters that have the view feature
provide a soft key “Clear” function. See Section enabled in the Guarded Access menu. If the view
4 for additional details feature for a particular hourmeter is not enabled then
that hourmeter cannot be viewed.
A simplified list of Alarm Codes is presented in
Section 4 of this manual. A list of Alarm Codes NOTE: All active hourmeters are available for
including diagnostic procedures for each code is viewing in the Maintenance Menu.
presented in Section 5 of this manual.
3-11
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Pretrip
A Pretrip Test is used to confirm unit operation. This Time
menu allows a Pretrip Test to be initiated by the This menu allows the operator to view the unit time
operator. If the test is started with the engine or and date. The time and date cannot be changed
motor off a full test including the non-running amp from this menu.
3-12
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-13
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-14
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Gauges
MAINTENANCE MENU
The Gauges menu allows the technician to display
FEATURES operating information such as coolant level and
The Thermo King SR2 control system features many temperature, engine RPM, battery amps, battery
special technician functions. These functions are volts, and suction and discharge pressure. The I/O
available from the Maintenance Menus. A brief selection under Gauges indicates the named
explanation of each menu is included here. outputs as either On or Off. Some Gauges can also
be viewed from the Service Test Mode and Interface
For complete details see Section 4 of this Board Test Mode displays.
3-15
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-16
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-17
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-18
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
The Guarded Access Menu allows unit operation to Bypassing the Security Code
be configured to user requirements. OptiSet If a Security Code is set and the Guarded Access
features can also be programmed. Menu must be accessed, the Security Code can be
bypassed by entering “4444”.
3-19
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-20
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-21
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
IMPORTANT
If a feature has been programmed in OptiSet, the
HMI will display “programmed in OptiSet”, and
the feature cannot be updated from this menu.
Temperature Units
Control Rev C000
HMI Rev 6510
Choices FAHRENHEIT or CELSIUS
Factory Set FAHRENHEIT
Exceptions If OptiSet is active this feature is set
from the OptiSet Menu. The setting selected is used
for all ranges.
Description The controller can be set to display
temperatures in either degrees FAHRENHEIT or
degrees CELSIUS.
3-22
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Restart Unit After Shutdown Setpoint High Limit (for the indicated Zone)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices ENABLED, DISABLED, or Choices Maximum is 90°F (32°C)
CONTINUOUS Minimum is Setpoint Low Limit
Factory Set ENABLED Factory Set 80°F (27°C)
Exceptions Use the CONTINUOUS option for Exceptions If OptiSet is active this feature is set
rail applications only. from the OptiSet Menu. The Setpoint High Limit
Description Standard restart alarms become setting selected is used for all ranges in the
permanent shutdown alarms after several attempts indicated zone.
to start and run. The CONTINUOUS feature is Description Setpoint High Limit allows the
designed for rail applications where the unit runs upper setpoint limit to be set to a maximum of 90°F
unattended or is inaccessible for service. It allows (32°C) in one degree increments. The minimum
unlimited restart attempts to be made if the following setting is determined by the setting of Setpoint Low
restart alarms occur: Limit. If the driver attempts to select a setpoint
x Alarm Code 10 High Discharge Pressure higher than the Setpoint High Limit, the display will
x Alarm Code 18 High Engine Coolant Temp show Setpoint Limit, indicating that the selected
x Alarm Code 63 Engine Stopped Setpoint High Limit has been reached. Setting
x Alarm Code 82 High Compressor Temp Setpoint High Limit and the Setpoint Low Limit to the
If restarts are disabled, the unit will shut down on the same temperature results in a single setpoint
The following differences exist between a Standard If the Limited Setpoint feature is enabled this setting
3-23
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Setpoint Low Limit (for the indicated zone) Fresh Frozen Range
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices Minimum is –25°F (-32°C) Choices 24°F (-4°C) or 15°F (-9°C)
Maximum is Setpoint High Limit Factory Set 15°F (-9°C)
Factory Set -20°F (-29°C) Exceptions If OptiSet is active this feature is set
Exceptions If OptiSet is active this feature is set from the OptiSet Menu. The setting selected is used
from the OptiSet Menu. The Setpoint Low Limit for all ranges.
setting selected is used for all ranges. Description One set of general control
Description The Setpoint Low Limit allows the specifications is used when operating in the Fresh
lower setpoint limit to be set to a minimum of -25°F range, and another set of general operating
(-32°C) in one degree increments. The maximum specifications is used when operating in the Frozen
setting available is determined by the setting of range. This feature allows the line between Fresh
Setpoint High Limit. If the driver attempts to select a and Frozen ranges to be selected as either 15°F (-
setpoint lower than the Setpoint Low Limit, the 9°C) or 24°F (-4°C). All setpoints less than or equal
display will show Setpoint Limit, indicating that the to this value will be treated as frozen ranges. All
selected Setpoint Low Limit has been reached. setpoints greater than this value will be treated as
Setting the Setpoint High Limit and the Setpoint Low Fresh ranges.
Limit to the same temperature results in a single
setpoint temperature available. The Frozen setpoint range is from the limit of the
Setpoint Limit Low setting to the Fresh Frozen range
If the Limited Setpoint feature is enabled this setting setting. The Fresh setpoint range is from the limit of
is not used. the Fresh Frozen range + 1 degree to the setpoint
high limit setting.
This setting is zone specific.
When programming OptiSet, no range may include
both Frozen and Fresh range setpoints. This value
is the high value of the last frozen range
programmed. The next range programmed will start
at this value + 1-degree depending on the selection
made above. Changing this feature will reset all
OptiSet range values to default.
3-24
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-25
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-26
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-27
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
HMI Control Panel COM 3 Default Baud Rate Number of Limited Setpoints
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices 1200, 2400, 4800, 9600, 19200, Choices 0, 1, 2, 3 or 4
38400, 57600, and 115200 BPS Factory Set 0
Factory Set 9600 Exceptions
Exceptions Description This feature allows programming of
Description This feature allows the default baud a limited number of predetermined setpoints to be
rate to be selected for the HMI Control Panel COM made available to the driver. From 1 to 4 setpoints
port 3. can be programmed. Setting this feature to [0]
results in normal operation with all setpoints
COM port 3 is used by R:COM or other Telematics available from the setting of Setpoint Low Limit to
devices. The setting of this feature should not be Setpoint High Limit.
changed.
As an example, if this feature is set to [3] then only
three setpoints can be programmed. If the Limited
Setpoints are set to -10°F, 35°F and 50°F then
pressing the Up or Down keys when selecting a
setpoint will scroll between these three setpoints
only. No other setpoints are available.
3-28
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-29
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-30
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
the Keypad Lockout, Sleep Mode and Single Zone Control Rev C000
Control menus are visible in the Main Menu | Mode HMI Rev 6510
Menu. These features are set to factory defaults Choices Enabled or Disabled
when shipped, but can easily be changed to suit the Factory Set Disabled
end user’s needs. Exceptions
Description Sleep Mode allows the operator to
place the unit in Sleep Mode from the Mode Menu.
Add Keypad Lockout to Mode Menu
Control Rev C000 Setting this feature Enabled adds the Sleep Mode
HMI Rev 6510 feature to the Mode Menu.
Choices Enabled or Disabled
Factory Set Disabled Setting this feature Disabled removes the Sleep
3-31
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-32
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-33
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
requirements. There are two sub-menus under the HMI Rev 6510
Hourmeter Setup Menu. Choices OFF, 1 to 99,999
Factory Set OFF
Programmable Hourmeter Sub-menu Exceptions If a time limit is set and exceeded
The hourmeters listed below allow a time limit to be then Alarm Code 132 will be set as a stored alarm.
established for each programmable Hourmeter. Description Total Run Time Reminder #1 Hours
These time limits are defined by the customer and is one of two hourmeters that track the total amount
are typically used as maintenance reminders. With of time the unit has run in both diesel and electric
the exception of Controller Power On Hours and mode. If a time limit is set and exceeded then Alarm
Pretrip Reminder Hours there are two hourmeters Code 132 will be set as a stored alarm.
for each feature to allow two different maintenance
intervals to be set. This feature sets the meter limits for this
programmable hourmeter. The default setting is
The Program Hourmeter Sub-menu is used to set OFF. Time limits start at 100 hours and can be
and clear the adjustable time limits for each decreased to 1 and then OFF or increased to a
Hourmeter, as required by a customer’s maximum of 99,999 hours.
maintenance program. The default time limit for all
hourmeters is 100 hours. The hourmeters appear in
the order shown here.
3-34
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-35
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-36
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Engine Run Time Reminder # 2 Hours Electric Run Time Reminder # 1 Hours
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices OFF, 1 to 99,999 Choices OFF, 1 to 99,999
Factory Set OFF Factory Set OFF
Exceptions If a time limit is set and exceeded Exceptions If a time limit is set and exceeded
then Alarm Code 129 will be set as a stored alarm. then Alarm Code 130 will be set as a stored alarm.
Description Engine Run Time Reminder #2 Only appears if the unit is configured as being
Hours is one of two hourmeters that track the total equipped with optional electric standby.
amount of time the unit has run in diesel mode. If a Description Electric Run Time Reminder #1
time limit is set and exceeded then Alarm Code 129 Hours is one of two hourmeters that track the total
will be set as a stored alarm. amount of time the unit has run in electric mode. If a
time limit is set and exceeded then Alarm Code 130
This feature sets the meter limits for this will be set as a stored alarm.
programmable hourmeter. The default setting is
OFF. Time limits start at 100 hours and can be This feature sets the meter limits for this
decreased to 1 and then OFF or increased to a programmable hourmeter. The default setting is
maximum of 99,999 hours. OFF. Time limits start at 100 hours and can be
decreased to 1 and then OFF or increased to a
maximum of 99,999 hours.
3-37
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-38
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-39
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-40
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-41
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Engine Run Time Reminder # 1 Hours Electric Run Time Reminder # 1 Hours
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices Disabled Choices Disabled
Factory Set Disabled Factory Set Disabled
Exceptions Exceptions Only appears if the unit is
Description The setting of this feature configured as being equipped with optional electric
determines if the Engine Run Time Reminder # 1 standby.
Hours hourmeter can be viewed from the Main Description The setting of this feature
Menu. If the hourmeter is Enabled it can be viewed determines if the Electric Run Time Reminder # 1
from the Main Menu. If it is Disabled it cannot be Hours hourmeter can be viewed from the Main
viewed from the Main Menu but is visible from the Menu. If the hourmeter is Enabled it can be viewed
Maintenance Menu. from the Main Menu. If it is Disabled it cannot be
viewed from the Main Menu but is visible from the
Maintenance Menu.
3-42
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-43
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
correctly for the unit to operate properly. Sensor Control Rev C000
grades were defined such that a sensor grade 5H HMI Rev 6510
does not exist. The default setting for a new Choices 1L thru 9H
controller or after a cold start is 5H. This serves as Factory Set 5H
a warning that the sensor grade is not set. The Exceptions
default grade of 5H is not a valid grade and will not Description This feature is used to set the
be stamped on any sensor. sensor grade for the Zone 1 Return Air Sensor.
If a sensor grade for a return air or discharge air The default setting for a new base controller or after
sensor is set to grade 5H, the alarm code for that a ServiceWatch base controller cold start is 5H.
sensor and Alarm Code 92 Sensor Grade Not Set This serves as a warning that the sensor grade is
will occur. not set. The default grade of 5H is not a valid grade
and will not be stamped on any sensor. If a sensor
Spare Sensors 1 thru 3 are graded sensors but an grade for a return air or discharge air sensor is set to
alarm code is not set if this sensor grade is set to grade 5H, the alarm code for that sensor and Alarm
5H. Code 92 Sensor Grade Not Set will occur. Alarm
Code 92 is not set if a Spare Sensor is set to 5H.
NOTE: To insure proper operation the grades must
be properly set to match the actual sensor grades to To insure proper operation the grades must be
prevent false alarm codes. Exercise care to properly properly set to match the actual sensor grades to
identify the sensor grades. The best way to prevent nuisance alarm codes. Exercise care to
positively identify the sensor grade is to physically properly identify the sensor grades. The best way to
check the sensor grade stamped on each graded positively identify the sensor grade is by physically
sensor. checking the sensor grade stamped on each graded
sensor.
The Sensor Calibration Menu allows the operator to
select the correct grade for all graded sensors.
Sensor grades range from 1L through 9H.
3-44
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Zone 1 Discharge Air Sensor Grade Zone 2 Return Air Sensor Grade
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices 1L thru 9H Choices 1L thru 9H
Factory Set 5H Factory Set 5H
Exceptions Exceptions
Description This feature is used to set the Description This feature is used to set the
sensor grade for the Zone 1 Discharge Air Sensor. sensor grade for the Zone 2 Return Air Sensor.
The default setting for a new base controller or after The default setting for a new base controller or after
a ServiceWatch base controller cold start is 5H. a ServiceWatch base controller cold start is 5H.
This serves as a warning that the sensor grade is This serves as a warning that the sensor grade is
not set. The default grade of 5H is not a valid grade not set. The default grade of 5H is not a valid grade
and will not be stamped on any sensor. If a sensor and will not be stamped on any sensor. If a sensor
grade for a return air or discharge air sensor is set to grade for a return air or discharge air sensor is set to
grade 5H, the alarm code for that sensor and Alarm grade 5H, the alarm code for that sensor and Alarm
Code 92 Sensor Grade Not Set will occur. Alarm Code 92 Sensor Grade Not Set will occur. Alarm
Code 92 is not set if a Spare Sensor is set to 5H. Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation the grades must be To insure proper operation the grades must be
properly set to match the actual sensor grades to properly set to match the actual sensor grades to
prevent nuisance alarm codes. Exercise care to prevent nuisance alarm codes. Exercise care to
properly identify the sensor grades. The best way to properly identify the sensor grades. The best way to
positively identify the sensor grade is by physically positively identify the sensor grade is by physically
checking the sensor grade stamped on each graded checking the sensor grade stamped on each graded
sensor. sensor.
3-45
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Zone 2 Discharge Air Sensor Grade Zone 3 Discharge Air Sensor Grade
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices 1L thru 9H Choices 1L thru 9H
Factory Set 5H Factory Set 5H
Exceptions Exceptions Only appears if the unit is
Description This feature is used to set the configured as being equipped with 3 zones.
sensor grade for the Zone 2 Discharge Air Sensor. Description This feature is used to set the
sensor grade for the Zone 3 Return Air Sensor.
The default setting for a new base controller or after
a ServiceWatch base controller cold start is 5H. The default setting for a new base controller or after
This serves as a warning that the sensor grade is a ServiceWatch base controller cold start is 5H.
not set. The default grade of 5H is not a valid grade This serves as a warning that the sensor grade is
and will not be stamped on any sensor. If a sensor not set. The default grade of 5H is not a valid grade
grade for a return air or discharge air sensor is set to and will not be stamped on any sensor. If a sensor
grade 5H, the alarm code for that sensor and Alarm grade for a return air or discharge air sensor is set to
Code 92 Sensor Grade Not Set will occur. Alarm grade 5H, the alarm code for that sensor and Alarm
Code 92 is not set if a Spare Sensor is set to 5H. Code 92 Sensor Grade Not Set will occur. Alarm
Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation the grades must be
properly set to match the actual sensor grades to To insure proper operation the grades must be
prevent nuisance alarm codes. Exercise care to properly set to match the actual sensor grades to
properly identify the sensor grades. The best way to prevent nuisance alarm codes. Exercise care to
positively identify the sensor grade is by physically properly identify the sensor grades. The best way to
checking the sensor grade stamped on each graded positively identify the sensor grade is by physically
sensor. checking the sensor grade stamped on each graded
sensor.
3-46
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
The default setting for a new base controller or after The default setting for a new base controller or after
a ServiceWatch base controller cold start is 5H. a ServiceWatch base controller cold start is 5H.
This serves as a warning that the sensor grade is This serves as a warning that the sensor grade is
not set. The default grade of 5H is not a valid grade not set. The default grade of 5H is not a valid grade
and will not be stamped on any sensor. If a sensor and will not be stamped on any sensor. If a sensor
grade for a return air or discharge air sensor is set to grade for a return air or discharge air sensor is set to
grade 5H, the alarm code for that sensor and Alarm grade 5H, the alarm code for that sensor and Alarm
Code 92 Sensor Grade Not Set will occur. Alarm Code 92 Sensor Grade Not Set will occur. Alarm
Code 92 is not set if a Spare Sensor is set to 5H. Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation the grades must be To insure proper operation the grades must be
properly set to match the actual sensor grades to properly set to match the actual sensor grades to
prevent nuisance alarm codes. Exercise care to prevent nuisance alarm codes. Exercise care to
properly identify the sensor grades. The best way to properly identify the sensor grades. The best way to
positively identify the sensor grade is by physically positively identify the sensor grade is by physically
checking the sensor grade stamped on each graded checking the sensor grade stamped on each graded
sensor. sensor.
3-47
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
The default setting for a new base controller or after The default setting for a new base controller or after
a ServiceWatch base controller cold start is 5H. a ServiceWatch base controller cold start is 5H.
This serves as a warning that the sensor grade is This serves as a warning that the sensor grade is
not set. The default grade of 5H is not a valid grade not set. The default grade of 5H is not a valid grade
and will not be stamped on any sensor. If a sensor and will not be stamped on any sensor. If a sensor
grade for a return air or discharge air sensor is set to grade for a return air or discharge air sensor is set to
grade 5H, the alarm code for that sensor and Alarm grade 5H, the alarm code for that sensor and Alarm
Code 92 Sensor Grade Not Set will occur. Alarm Code 92 Sensor Grade Not Set will occur. Alarm
Code 92 is not set if a Spare Sensor is set to 5H. Code 92 is not set if a Spare Sensor is set to 5H.
To insure proper operation the grades must be To insure proper operation the grades must be
properly set to match the actual sensor grades to properly set to match the actual sensor grades to
prevent nuisance alarm codes. Exercise care to prevent nuisance alarm codes. Exercise care to
properly identify the sensor grades. The best way to properly identify the sensor grades. The best way to
positively identify the sensor grade is by physically positively identify the sensor grade is by physically
checking the sensor grade stamped on each graded checking the sensor grade stamped on each graded
sensor. sensor.
3-48
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-49
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Description This feature selects the timed setting applies to all zones.
Defrost Interval Not In Range with Fresh Setpoint HMI Rev 6510
Description This feature selects the timed setpoints when the temperature is not in range. This
interval between defrost cycles with Fresh range setting applies to all zones.
3-50
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-51
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
selected, as required. When a language is selected language included in the installed HMI software
all subsequent displays are in that language. version. English is included in all language sets and
is factory set as Enabled. Only enabled languages
The languages available are dependent on the will appear in the Main Menu Language selections.
software revision in the HMI control panel. Only one All languages other than English are factory set as
of the three software revisions can be installed, and Disabled. If only one language is enabled the
only the languages in that revision are available. Language selection screen does not appear in the
HMI control panel software revisions support the HMI Rev 6510
languages shown in the table below. Choices See Language Support Table
Factory Set English only
Software Revision Language Support Exceptions
Revision 65xx Revision 66xx Revision 67xx Description This feature allows any or all of the
English English English included languages to be enabled. Only enabled
Spanish Russian Japanese languages will appear in the Operators Language
French Polish Menu. All languages other than English are factory
German Hungarian set as Disabled. If only one language is enabled the
Italian Romanian Language Menu screen will not appear in the Main
Portuguese Czech
Greek Danish
Turkish Swedish
Hebrew Norwegian
Arabic Finnish
3-52
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-53
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
OptiSet Menu
The OptiSet™ Temperature Management System x Ranges are programmed from the coldest
allows up to ten different temperature ranges to be range to the warmest range. If ranges have
defined and tailored for maximum operating been programmed and any range is
efficiency, as determined by customer load subsequently changed, the range that was
requirements. The term “OptiSet” refers to both the changed and all warmer ranges are reset to
OptiSet is programmed using the HMI Control Panel Programming OptiSet Features
keypad. The OptiSet features are programmed from the HMI
Control Panel OptiSet Menu. The flowchart on the
next page illustrates the features and menu flow.
OptiSet Reset Each feature is discussed fully in the following
ranges are set as desired. required. Only valid programmable features will be
displayed as determined by the setting of Economy
x If any OptiSet features have been previously Mode, Cycle Sentry Mode and Continuous Mode. If
set, an OptiSet Reset is provided at the a feature is not allowed, it will not be displayed.
3-54
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
OptiSet
(in GA Menu)
Select
Reset
(only if OptiSet
is active)
19 July 2006
3-55
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
The global features listed below affect all other Control Rev C000
OptiSet ranges and settings. If any of these are HMI Rev 6510
changed, all existing OptiSet programmable settings Choices Maximum is 90°F (32°C)
are returned to the default settings. Minimum is Setpoint Low Limit
Factory Set 80°F (27°C)
Note: Some of these settings are available in the Exceptions If OptiSet is active this feature is set
HMI Programmable Features Menu. If OptiSet has from the OptiSet Menu. The Setpoint High Limit
been programmed, then the Programmable setting selected is used for all ranges in the
Features screen will display “Programmed in indicated zone.
OptiSet”. Programming of the feature will not be Setpoint High Limit allows the upper setpoint limit to
allowed in the Programmable Features menu. be set to a maximum of 90°F (32°C) in one degree
increments. The minimum setting is determined by
x Temperature Units for all zones the setting of Setpoint Low Limit. If the driver
x Zone Setpoint High Limit for each zone attempts to select a setpoint higher than the Setpoint
x Zone Setpoint Low Limit for each zone High Limit, the display will show Setpoint Limit,
x Limited Setpoints for all Zones indicating that the selected Setpoint High Limit has
x Fresh Frozen Range for all zones been reached. Setting Setpoint High Limit and the
x Running Fans in Null Setpoint Low Limit to the same temperature results
in a single setpoint temperature available.
Temperature Units (for all zones) If the Limited Setpoint feature is enabled this setting
3-56
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Setpoint Low Limit (for the indicated zone) Number of Limited Setpoints (for all zones)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices Minimum is –25°F (-32°C) Choices 0, 1, 2, 3 or 4
Maximum is Setpoint High Limit Factory Set 0
Factory Set -25°F (-32°C) Exceptions
Exceptions If OptiSet is active this feature is set Description This feature allows a limited number
from the OptiSet Menu. The Setpoint Low Limit of predetermined setpoints to be made available to
setting selected is used for all ranges in the the driver. From 1 to 4 setpoints can be
indicated zone. programmed. Setting this feature to [0] results in
Description The Setpoint Low Limit allows the normal operation with all setpoints available from the
lower setpoint limit to be set to a minimum of -25°F setting of Setpoint Low Limit to Setpoint High Limit.
(-32°C) in one degree increments. The maximum
setting available is determined by the setting of As an example, if this feature is set to [3] then only
Setpoint High Limit. If the driver attempts to select a three setpoints can be programmed. If the Limited
setpoint lower than the Setpoint Low Limit, the Setpoint features below are set to -10°F, 35°F and
display will show Setpoint Limit, indicating that the 50°F then pressing the Up or Down keys when
selected Setpoint Low Limit has been reached. selecting a setpoint will scroll between these three
Setting the Setpoint High Limit and the Setpoint Low setpoints only. No other setpoints are available.
Limit to the same temperature results in a single
setpoint temperature available. This feature is not zone specific. The Limited
Setpoints selected are available in all zones.
If the Limited Setpoint feature is enabled this setting
is not used.
3-57
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Limited Setpoint # 1 (for all zones) Limited Setpoint # 3 (for all zones)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices From Setpoint Low limit to Setpoint Choices From Setpoint Low limit to Setpoint
High Limit High Limit
Factory Set -13°F (-25°C) Factory Set 37°F (3°C)
Exceptions Only available if Number of Limited Exceptions Only available if Number of Limited
Setpoints is set greater that 0. Setpoints is set greater that 2.
Description The Number of Limited Setpoints Description The Number of Limited Setpoints
feature above determines the number of limited feature above determines the number of limited
setpoints allowed (from 1 to 4). This feature allows setpoints allowed (from 1 to 4). This feature allows
the first limited setpoint to be programmed. It can be the third limited setpoint to be programmed. It can
set to any temperature from Setpoint Low Limit to be set to any temperature from Setpoint Low Limit to
Setpoint High Limit. Setpoint High Limit.
Limited Setpoint # 2 (for all zones) Limited Setpoint # 4 (for all zones)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices From Setpoint Low limit to Setpoint Choices From Setpoint Low limit to Setpoint
High Limit High Limit
Factory Set 32°F (0°C) Factory Set 55°F (13°C)
Exceptions Only available if Number of Limited Exceptions Only available if Number of Limited
Setpoints is set greater that 1. Setpoints is set greater that 3.
Description The Number of Limited Setpoints Description The Number of Limited Setpoints
feature above determines the number of limited feature above determines the number of limited
setpoints allowed (from 1 to 4). This feature allows setpoints allowed (from 1 to 4). This feature allows
the second limited setpoint to be programmed. It the fourth limited setpoint to be programmed. It can
can be set to any temperature from Setpoint Low be set to any temperature from Setpoint Low Limit to
Limit to Setpoint High Limit. Setpoint High Limit.
3-58
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-59
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-60
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Range Limits (for all zones) OptiSet Range (for all zones)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices Up to 10 ranges, from 0 through 9 Choices Up to 10 ranges, from 0 through 9
Factory Set Range 0 is from -25qF (-32°C) to Factory Set
24°F (-4°C) Exceptions
Range 1 is from 25°F (-3°C) to 90°F Description This feature selects one of the
(32°C) ranges established by Range Limits (above) to be
Exceptions programmed. The ranges available are as
Description Up to 10 ranges (numbered from 0 determined by the setting of the Range Limits
to 9) can be programmed. Each range is defined by feature above. There can be up to 10 ranges. The
a minimum and maximum setpoint temperature. first range to be programmed is Range 0.
The first range programmed automatically starts at
the setting of Setpoint Limit Low. The last range
programmed automatically ends at the setting of
Setpoint Limit High. All ranges programmed must
be completely above or below the setting of
Fresh/Frozen range. No range can contain both
Fresh and Frozen setpoints. When programming
ranges, the next range automatically begins one full
degree (F or C) higher than the last range
programmed. Changing any range temperature limit
will void all existing range settings above that range
and will reset that range and all ranges above it to
the default configuration. The default setting is
Range 0 (Frozen) and Range 1 (Fresh).
3-61
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
These features allow the desired operating modes to Control Rev C000
be established for each range. The available modes HMI Rev 6510
are selected for the range being programmed. Choices Off or On
Cycle Sentry Mode and Continuous Mode are Factory Set On
available. Either of these modes can be turned on Exceptions
or off for each range, but either Cycle Sentry or Description Cycle Sentry Mode automatically
Continuous must be turned on. If more than one starts the unit when cooling, heating or defrosting is
mode is available in a range, it can be selected required and stops the unit when all requirements
using the Mode Menu or the Mode key. are satisfied. In Diesel Mode operation the unit also
starts and stops as necessary to keep the engine
The custom features for each range are determined warm and the unit battery charged. In Electric Mode
by the modes selected for that range. operation the unit starts and stops as necessary to
keep the unit battery charged.
x Cycle Sentry Mode A number of Cycle
Sentry features can be customized if Cycle This feature allows Cycle Sentry Mode to be turned
Sentry mode is allowed. These features are On or Off for the selected range. If both Cycle
the same for both Frozen and Fresh ranges. Sentry and Continuous are turned On, then they are
selectable using the Mode key or the Main Menu on
x Continuous Mode A number of the HMI Control Panel.
Continuous Mode features can be
customized. These features are different If Cycle Sentry is set On the Cycle Sentry OptiSet
with Frozen and Fresh ranges. custom features are available. The Cycle Sentry
OptiSet custom features are the same for Fresh and
Frozen ranges. These features are shown on the
following pages.
3-62
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-63
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Factory Set 5.0°F (2.8°C) action to be set. The setting applies to all zones
Description This feature determines the number NULL the base controller shuts the unit down and
of degrees above setpoint that the temperature must logs the door opening 4 seconds after the door is
rise before the unit restarts in Cycle Sentry Mode. opened. If the any zone is in defrost when the door
is opened, the defrost cycle will be completed before
With frozen range setpoints, the maximum restart the unit shuts down.
The Null Restart Temperature below setpoint is a opening 4 seconds after the door is opened. The
fixed value and cannot be changed. unit will remain running if any other zone requires
cooling or heating. If the zone is in defrost when the
door is opened, the defrost cycle will be completed
before the zone shuts down. If all zone door switch
inputs are open, the unit will be forced to NULL.
3-64
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Cycle Sentry Door Open Timeout (for selected Cycle Sentry Run Fans in Null (for selected
range) range)
Control Rev C000 Control Rev C000
HMI Rev 6510 HMI Rev 6510
Choices 1:00 to 4:00 (Hours) in 10 Min Choices On or Off
Increments or OFF Factory Set Off
Factory Set OFF Exceptions
Exceptions Only appears if the DOOR OPEN Description This feature allows the fans in a zone
FORCES feature is set to ZONE NULL or UNIT to run when the zone is in running null. This
NULL. maintains airflow in the zone and is normally used
Description This feature allows the unit to restart if with fresh loads.
the door open time exceeds the set limit.
If this feature is set ON the zone fans will run for 3
Door Open Timeout for the selected range can be minutes, shut down for three minutes and then
set to OFF or for a time limit from 1 to 4 hours, in 10- restart for 3 minutes as long as the zone is in
minute increments. If set to OFF the unit will remain running null.
off or in zone null until the door is closed. If a time
period is selected the unit will restart and run after If this feature is Set OFF the zone fans will not run
the time period elapses. It will continue to run even when the zone is in running null.
if the door is still open.
3-65
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-66
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Continuous Door Open Timeout (for selected Continuous Run Fans in Null (for selected range)
range) Control Rev C000
Control Rev C000 HMI Rev 6510
HMI Rev 6510 Choices On or Off
Choices 1:00 to 4:00 (Hours) in 10 Min Factory Set Off
Increments or OFF Exceptions
Factory Set OFF Description This feature allows the fans in a zone
Exceptions Only appears if the DOOR OPEN to run when the zone is in running null. This
FORCES feature is set to ZONE NULL or UNIT maintains airflow in the zone and is normally used
NULL. with fresh loads.
Description This feature allows the unit to restart if
the door open time exceeds the set limit. If this feature is set ON the zone fans will run for 3
minutes, shut down for three minutes and then
Door Open Timeout for the selected range can be restart for 3 minutes as long as the zone is in
set to OFF or for a time limit from 1 to 4 hours, in 10- running null.
minute increments. If set to OFF the unit will remain
off or in zone null until the door is closed. If a time If this feature is Set OFF the zone fans will not run
period is selected the unit will restart and run after when the zone is in running null.
the time period elapses. It will continue to run even
if the door is still open.
3-67
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
not the same as the temperature sensors used to Description This feature allows the desired
control the unit. The CargoWatch data logger sensors to be logged.
features the ability to customize logging parameters
and enable product temperature checking. Note that
the CargoWatch data logger does not record unit
sensors. Unit sensors and other unit operating data
are recorded by the ServiceWatch data logger. The
CargoWatch logger records the unit setpoint,
operating mode, and shutdown alarms.
Sensor Programming
Logging Interval
Control Rev C000
HMI Rev 6510
Choices 1 minute, 2 minutes and 5 to 60
minutes in 5-minute intervals
Factory Set 15 Minutes
Exceptions Wintrac is capable of setting
additional intervals as short as 1 minute.
Description This feature allows the desired
logging interval to be set.
3-68
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
x Side
Independent Sensor Name (for CargoWatch x Right Side
sensor 1, 2, 3, 4, 5 or 6) x Left Side
Control Rev C000 x Spare Front
HMI Rev 6510 x Spare Rear
Choices See table below x Spare Side
Factory Set Log Sensor 1 through 6 x Spare Right Side
Exceptions x Spare Left Side
Description This feature allows the desired x Fresh
sensor name to be specified. These names appear x Frozen
only on handheld printer reports. This aids in x Chilled
reading and understanding data logger printer x Dry
reports.
x Spare Fresh
Choices
x Spare Frozen
x Independent Sensor 1, 2, 3, 4, 5 or 6
x Spare Chilled
x Return Air
x Spare Dry
x Return Air Zone 1, 2 or 3
x Ambient
x Other Return Air
x Spare Ambient
x Discharge Air
x Log Sensor 1, 2, 3, 4, 5 or 6
x Discharge Air Zone 1, 2 or 3
x Other Discharge Air
x Spare Return Air
x Spare Return Air Zone 1, 2 or 3
x Other Spare Return Air
x Spare Discharge Air
x Spare Discharge Air Zone 1, 2 or 3
x Other Spare Discharge Air
x USDA 1, 2 or 3
x Spare USDA 1, 2 or 3
x Spare
x Other
x Other Spare
x Front
x Rear
3-69
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
for Out of Range Checking to be set.
3-70
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
SET
POINT
35 GAUGES
.8
SENSORS
35
MENU
logged instead of the actual instantaneous value. If
the Logging Interval is set for 10 minutes, the
previous 10 sensor readings are averaged and
logged.
3-71
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-72
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-73
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
The Unit Setup Menu is used to specify the actual Control Rev C000
unit configuration. These features are set at the HMI Rev 6510
factory as required for each unit. The factory Choices YES or NO
settings shown below are for a replacement base Factory Set NO
controller. Exceptions If this feature is set YES then Unit
Model is forced to [SB] and Number of Zones is
Alarm Code 111 Unit Not Configured Correctly forced to [2].
If the base controller detects a mismatch between Description This feature enables the dual host
the detected unit components and the Unit (DE) evaporator configuration.
Configuration selections, Alarm Code 111 Unit Not
Configured Correctly will be set.
How Many Zones in This Unit
Control Rev C000
Engine Type Is HMI Rev 6510
Control Rev C000 Choices 2 or 3
HMI Rev 6510 Factory Set 2
Choices Exceptions
Factory Set Yanmar 2.1 Description This feature specifies if the unit is
Exceptions equipped with 2 or 3 zones. If the unit is equipped
Description This feature allows the engine type with 2 zones, this feature should be set to 2. If the
to be selected. Only Yanmar 2.1 is available on unit is equipped with 3 zones, this feature should be
trailer multi-temp units. set to 3.
Compressor Type Is
Control Rev C000
HMI Rev 6510
Choices
Factory Set Recip
Exceptions
Description This feature allows the compressor
type to be selected. Only Recip is available on
trailer multi-temp units.
3-74
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Exceptions This screen only appears if the unit Control Rev C000
3-75
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-76
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
Factory Set NONE automatically start and run all configured zones
3-77
02 February 2007
Section 3 – SR-2 SPECTRUM Software Description
3-78
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-1
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-2
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
CONTINUOUS
TEMP F
-8.2 35.1 48.8
ON
SET
OFF
-10 35 50 POINT
SmartReefer2
The keys on the left and right sides of the display are dedicated or single function keys. These are termed “hard”
keys.
The four keys under the display are termed “soft” keys. The functions of these keys change depending on the
operation being performed. If a soft key is active the current key function is shown in the display directly above
the key.
4-3
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Display
CONTINUOUS
TEMP F
-8.2 35.1 48.8
ON
SET
OFF
-10 35 50 POINT
SmartReefer2
The display presents information to the operator. This information can include setpoint and temperature for each
zone, unit or zone operating information, gauge readings, temperatures and other information as selected by the
operator.
The Standard Display of box temperature and setpoint for 3 zones is shown here. The unit is running in
Continuous Mode. Zone 1 has a setpoint of -10°F, and a return air temperature of -8.2°F. The downward
pointing arrow shows this zone is cooling. Zone 2 has a setpoint of 35°F, and a return air temperature of 35.1°F.
The absence of an arrow indicates that this zone is in null. Zone 3 has a setpoint of 50°F, and a return air
temperature of 48.8°F. The upward pointing arrow shows this zone is heating.
Pressing the soft key under each zone allows the setpoint for that zone to be changed. In addition, the soft keys
under Zone 2 and Zone 3 are used to turn those zones on and off. Pressing the soft key under MENU accesses
the MAIN MENU.
4-4
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Keys
Hard Keys
CONTINUOUS
ON
SET
SmartReefer2
The keys on either side of the display are dedicated or “hard” keys. Their function always remains the same.
They are described below.
This key is used to turn the host unit and Zone 1 on. First the display will briefly show the
ON Thermo King Logo and then the statement “Configuring System – Please Wait”. When the
power-up sequence is complete the display shows the Standard Display of box temperature and
setpoint. For more information see “Turning the Unit On and Off” later in this section.
This key is used to turn the host unit and Zone 1 off. First the display will briefly show “System
OFF is Powering Down – Please Wait. Press On to Resume” and then “Off” will appear momentarily.
When the power-down sequence is complete the display will be blank. For more information
see “Turning the Unit On and Off” later in this section.
This key is used to initiate a manual defrost cycle. For more information see “Initiating a Manual
Defrost Cycle” later in this section.
This key is used to select Cycle Sentry Mode or Continuous Mode operation if allowed by
OptiSet. For more information see “Selecting Cycle Sentry or Continuous Mode” later in this
section.
4-5
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Soft Keys
CONTINUOUS
ON
TEMP F
-8.2 35.8 48.8 SET
SmartReefer2
The four “soft” keys under the display are multi-purpose keys. Their function changes
depending on the operation being performed. If a soft key is active the key function is shown in
the display directly above the key. The keys are numbered from left to right, with Key 1 on the
far left and Key 4 on the far right.
4-6
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Display Heater
The HMI control panel is equipped with a display heater. This heater is needed to make the display visible in cold
ambient temperatures.
The HMI has its own internal temperature sensor for the display heater. The heater is energized when the unit is
turned on and the ambient temperature is below 29.4°F (-2°C). The heater turns off when the temperature
sensed by the internal sensor rises above 37.4°F (+3°C). The heater draws from 1.4 to 1.7 amps when
energized.
The colder the ambient temperature the longer it will take for the heater to make the display visible on a cold
startup. It may take 10-15 seconds for the display to appear with very cold temperatures.
4-7
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The unit is turned on by pressing the ON hard key and off by pressing the OFF hard key. When the On key is
pressed the display briefly shows the THERMO KING Logo as the display initializes.
NOTE: With SPECTRUM Multi-Temp applications, Zone 1 is turned on any time the host unit is turned on. Zone
1 is turned off when the host unit is turned off.
NOTE: With extremely cold ambient temperatures it may take up to 15 seconds for the display to appear on initial
startup.
ON
OFF
Then the startup screen shown below appears while communications are established and the unit prepares for
operation.
ON CONFIGURING SYSTEM
4-8
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
When the unit is ready to run the Standard Display appears. The 2 Zone display is shown here.
CONTINUOUS
ON
-8.2 35.8
TEMP F
SET
Pressing the OFF hard key stops unit operation. The controller shuts down immediately and the display briefly
shows the power down message.
OFF
PRESS ON TO RESUME
The display briefly shows OFF and then goes blank. To start the unit again, press the ON hard key.
ON
OFF
OFF
4-9
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ON
TEMP F
2
-8. 35.8 SET
The Standard Display is the default display that appears if no other display function is selected. A 2 Zone
Standard display is shown here. The 2 Zone Standard Display above shows the return air temperature and
setpoint for two zones. The top of the display shows that the unit is operating in Continuous mode. The return air
temperature for Zone 1 is -8.2°F with a -10°F setpoint. The down-pointing arrow indicates that Zone 1 is cooling.
The return air temperature for Zone 2 is 35.8°F with a 35°F setpoint. The down-pointing arrow indicates that Zone
2 is also cooling. The soft key under each zone allows the Setpoint for that zone to be changed. In addition, the
soft key under Zone 2 is used to turn that zone on and off. The soft key labeled MENU allows the Main Menu to
be selected.
TEMP F
-8.2 35.8 48.8
ON
SET
OFF
-10 35 50 POINT
The 3 Zone Standard Display adds the third zone for units equipped with three zones. The 3 Zone Standard
Display functions the same way as the 2 Zone Standard Display, but with a third zone. The top of the display
shows that the unit is operating in Continuous mode. The return air temperature for Zone 1 is -8.2°F with a -10°F
setpoint. The down-pointing arrow indicates that Zone 1 is cooling. The return air temperature for Zone 2 is
35.8°F with a 35°F setpoint. The down-pointing arrow indicates that Zone 2 is also cooling. The return air
temperature for Zone 3 is 48.8°F with a 50°F setpoint. The up-pointing arrow indicates that Zone 3 is heating.
The soft key under each zone allows the Setpoint for that zone to be changed. In addition, the soft keys under
Zone 2 and Zone 3 are used to turn those zones on and off. The soft key labeled MENU allows the Main Menu to
be selected.
4-10
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
SETPOINT
°F
35.8
SETPOINT
35
MENU
This feature, if enabled in Guarded Access, allows Single Zone Control operation to be selected by choosing the
Main Menu and then selecting Single Zone Control from the Mode submenu. When this feature is selected, all
zones will be forced on and will control to the same selected setpoint. The Single Zone Control Standard Display
functions the same way as the other Standard Displays. The top of the display shows that the unit is operating in
Continuous mode. The box temperature for all zones is 35.8°F and all zones are controlling to a 35°F setpoint.
The down-pointing arrow indicates that all zones are cooling. The soft key labeled Setpoint allows the setpoint for
all zones to be changed. The soft key labeled Menu allows the Main Menu to be selected.
x If Single Zone Control operation is selected then all zones will be forced on and will control to the same
setpoint. The Zone 1 sensors are used to determine box temperature. All bulkheads should be taken
down to create one large compartment. With the exception of defrost the operating mode of each zone
evaporator(s) will be same when in this mode. Unit control is based on the temperature sensors of one
zone, (usually Zone 1).
x If Single Zone Control operation is selected the Single Zone Standard Display provides one soft key
labeled Set Point as shown above. This allows the setpoint for all zones to be changed simultaneously.
x If Single Zone Control operation is selected the individual zones cannot be turned off. The unit and all
zones are turned On and Off simultaneously using the On and Off hard keys at the left side of the display.
4-11
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ON
-8 36
OFF
-10 35
ZONE 1 °F ZONE 2 MENU
If an alarm condition (other than a log alarm) is present the TemperatureWatch Display will not appear. If an
alarm condition occurs while the TemperatureWatch Display is present the display will return to the Standard
Display. If the Defrost or Cycle Sentry keys are pressed the display will return to the TemperatureWatch Display
after defrost is initiated or the operating mode is changed.
In the Three Zone TemperatureWatch display the Menu soft key label covers the Zone 3 label as shown below
ON
-8 36 48
OFF
-10 35 50
ZONE 1 °F ZONE 2 MENU
If the unit is operating in Cycle Sentry mode the Cycle Sentry icon will appear near Zone 2 as shown above. If the
unit is operating in Continuous Mode the Cycle Sentry icon will not be present.
4-12
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
-10 35 POINT
-10 F
OFF
+/- TO CHANGE
- + EXIT
The “-“ and “+” soft keys are used to increase or decrease the setpoint until the desired setpoint is shown. Here
the setpoint has been changed to 0°F using the “+” key.
0F
OFF
+/- TO CHANGE OK?
- + YES NO
4-13
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The YES and NO soft keys confirm the setpoint change. When the desired setpoint has been selected using the
“+” and/or “-“ keys, press the YES soft key to confirm and load the new setpoint. If the setpoint is changed using
the “+” or “-“ keys, the change must be confirmed or rejected by pressing the YES or NO soft key within 10
seconds of changing the setpoint. A warning beep will sound after 5 seconds as a reminder. Failure to confirm
the new setpoint by pressing Yes or No within 10 seconds of changing the setpoint will result in no setpoint
change. If the setpoint is not confirmed, then Alarm Code 127 Setpoint Not Entered is set, to indicate that the
setpoint change was not completed.
0F
OFF
+/- TO CHANGE OK?
- + YES NO
After the YES soft key has been pressed, the display will briefly show PROGRAMMING NEW SETPOINT –
PLEASE WAIT. The display then confirms the new setpoint for two seconds.
NEW SETPOINT IS
ON
0F
OFF
If the NO soft key is pressed the display will briefly show SETPOINT NOT CHANGED and return to the Standard
Display. The Standard Display will show the old setpoint.
4-14
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The display then returns to the Standard Display showing the new setpoint. Notice that the Zone 1 arrow now
points up, to indicate that Zone 1 is heating.
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
0 35 POINT
IMPORTANT: If the setpoint is changed using the “+” or “-“ keys, the change must be confirmed or
rejected by pressing the YES or NO soft key within 10 seconds of changing the setpoint.
x If the YES key is pressed, the setpoint change made with the “+” or “-“ key is accepted, the setpoint
changes, and the display returns to the Standard Display.
x If the NO key is pressed the setpoint change made with the “+” or “-“ key is not accepted, the setpoint is
not changed, and the display returns to the Setpoint Display.
x If the YES or NO key is not pressed within 10 seconds of making a change with the “+” or “-“ key, the
setpoint is not changed and the display returns to the Setpoint Display. The display briefly shows
[SETPOINT NOT CHANGED] and Alarm Code 127 Setpoint Not Entered is set, to indicate that the
setpoint change was started but not completed.
4-15
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The state of each zone is retained when the unit is turned off and on. For example, on a three zone unit if zone 2
is turned off and Zone 3 is turned on and the unit is turned off, the zone states remain as they were. When the
unit is turned back on Zone 2 will still be off and Zone 3 will still be on.
NOTE: Units equipped with a remote control may operate in a slightly different manner. See Optional Flush
Mount Remote Control Panel in this section for additional details.
To turn Zone 2 or Zone 3 on or off, press the soft key under the desired zone. Zone 2 is selected here.
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
0 35 POINT
The Zone 2 setpoint display appears as shown below. If the zone is turned on, the third soft key will be labeled
TURN ZONE OFF. If the zone is turned off, the third soft key will be labeled TURN ZONE ON. In this case
TURN ZONE OFF is shown.
35 F
OFF
+/- TO CHANGE
- + TURN
ZONE OFF
EXIT
4-16
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Press the TURN ZONE OFF soft key to turn the zone off
35 F
OFF
+/- TO CHANGE
- + TURN
ZONE OFF
EXIT
The display briefly shows PROGRAMMING ZONE ON/OFF – PLEASE WAIT. The display then confirms the new
Zone 2 setting for several seconds.
ZONE 2 IS
ON
OFF
OFF
The display then returns to the Standard Display showing Zone 2 is off. The setpoint for Zone 2 has been
replaced with OFF as shown below to indicate that the zone is now off.
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
4-17
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Diesel engine preheating and starting is automatic in both Continuous Mode and Cycle Sentry Mode. The engine
will preheat and start as required when the unit is turned on. If any keys are being pressed on the HMI control
panel prior to the engine start, the engine preheat and start will be delayed until 10 seconds after the last key is
pressed.
NOTE: If the unit is equipped with optional Electric Standby there may be some additional prompts
before the engine will start. See STARTING THE ELECTRIC MOTOR on the following pages for details.
CAUTION: The engine may start automatically any time the unit is turned on.
When the engine is preparing to start the HMI control panel will display the engine start screen, as shown below.
The preheat buzzer sounds during the engine preheat and crank sequence.
ON
DIESEL ENGINE STARTING
OFF
After the engine is started the display returns to the Standard Display of temperature and setpoint.
4-18
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Electric motor starting is automatic in both Continuous Mode and Cycle Sentry Mode. The motor will start as
required when the unit is turned on. If any keys are being pressed on the HMI control panel prior to the motor
start, the motor start will be delayed until 10 seconds after the last key is pressed.
CAUTION: The motor may start automatically any time the unit is turned on.
When the motor is preparing to start the HMI control panel will display the motor start screen, as shown below.
The preheat buzzer sounds for 20 seconds before the electric motor starts.
ON
ELECTRIC MOTOR STARTING
OFF
4-19
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If the Electric to Diesel Autoswitch Enabled feature in Guarded Access is set YES then the unit will automatically
switch to Electric Mode operation when standby power is connected and available.
If the Electric to Diesel Autoswitch Enabled feature in Guarded Access is set NO then the prompt screen shown
below will appear when standby power is connected and available.
YES NO
If YES is selected then the display will briefly show the screen below.
ON PROGRAMMING ELECTRIC
STANDBY
Electric Mode operation will briefly be confirmed. If unit operation is required the electric motor will start as shown
above in STARTING THE ELECTRIC MOTOR.
4-20
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If the Diesel to Electric Autoswitch Enabled feature in Guarded Access is set YES then the unit will automatically
switch to Diesel Mode operation when standby power is turned off or is no longer available.
If the Diesel to Electric Autoswitch Enabled feature in Guarded Access is set NO then the prompt screen shown
below will appear when standby power is turned off or is no longer available.
YES NO
If YES is selected then the display will briefly show the screen below.
ON
PROGRAMMING DIESEL MODE
Diesel Mode operation will briefly be confirmed. If unit operation is required the diesel engine will start as shown
above in STARTING THE DIESEL ENGINE.
4-21
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Defrost cycles are usually initiated automatically based on time or demand. Manual defrost is also available
Manual defrost is only available if the zone is running and the zone evaporator coil temperature is less than or
equal to 45°F (7°C). Other features such as door switch settings may not allow manual defrost under some
conditions.
NOTE: If the Rail Alternate feature is set ENABLED then a manual defrost cycle is available with
temperatures less than or equal to 55qF (13qC).
To initiate a manual defrost cycle, press the Defrost Key as shown below.
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
0 35 POINT
The display will briefly show [DEFROST]. Then the Zone Select display will appear. Zone 1 has been selected
here.
ON
SELECT ZONE TO DEFROST
OFF
4-22
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The display briefly shows [DEFROST], [PROGRAMMING DEFROST - PLEASE WAIT] and then [DEFROST
STARTED].
ON
DEFROST STARTED
OFF
The display then shows the Defrost display. The bar indicator shows approximately the percentage of time
remaining to complete the defrost cycle. The bar indicator below shows that the Zone 1 defrost cycle is
approximately 25% complete.
CONTINUOUS
ON
TEMP F
35.8 SET
OFF 35 POINT
NOTE: If the Rail Alternate feature is set ENABLED then a defrost cycle will terminate with temperatures
greater than or equal to 70qF (21qC).
4-23
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
When Cycle Sentry mode is selected the unit will start and stop automatically to maintain setpoint, keep the
engine warm and the battery charged. When Continuous Mode is selected, the unit starts automatically and runs
continuously to maintain setpoint and provide constant airflow. Cycle Sentry or Continuous may not be available
from the Mode menu if OptiSet is in use. The Cycle Sentry/Continuous selection affects all zones.
If allowed by OptiSet, Cycle Sentry or Continuous Mode is selected by pressing the Cycle Sentry/Continuous key.
Note that Continuous is shown at the top of the display.
CONTINUOUS
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
If the unit is in Continuous Mode, pressing the Cycle Sentry/Continuous key changes the mode from Continuous
Mode to Cycle Sentry Mode. The display confirms the change, as shown below.
OFF
PLEASE WAIT
4-24
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
OFF
CYCLE SENTRY
The display then returns to the Standard Display. In the example here the unit is running in Cycle Sentry Mode as
shown at the top of the display.
CYCLE SENTRY
ON
-8.2 35.8
TEMP F
SET
OFF
0 OFF POINT
Pressing the Cycle Sentry/Continuous key again allows the operator to change back to Continuous Mode
operation.
IMPORTANT: If the unit is in Cycle Sentry null and the mode is switched to Continuous Mode, the unit
will start automatically.
4-25
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The optional flush mount remote control panel is connected to the control system and is used to operate the unit
from a remote location, typically the rear of the trailer. All remote control panels feature 3 zones. The third zone
is not used on two zone applications.
When turned on either the Standard Display for each installed zone or [STAnd by] will appear on the display. The
zone currently being shown is identified by the Zone icon.
ZONE ZONE
2 2
ON OFF
ZONE
1234
ZONE ZONE
3 3
ON OFF
IMPORTANT: The SR-2 SPECTRUM remote control panel is capable of turning the control system on from a
powered down condition. It is not necessary to turn the control system on using the unit HMI Control Panel before
the remote control panel will operate.
IMPORTANT: There are two versions of the flush mount rear remote control panel available. They can be
identified by the color of the wide border around the actual control panel. SR-2 SPECTRUM flush mount rear
remote control panels have a blue border. uP-IV MultiTemp flush mount rear remote control panels have a black
border. These versions are not interchangeable.
4-26
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
STAND BY
If the Rear Remote Control Action feature is set for STAND BY the following functions are available from the
remote control panel.
x When powered up the unit will not start and run. The unit must be started from the HMI Control Panel
on the unit. The control system can only be powered up to change the setpoint(s).
x The control system can be powered up to change setpoints by pressing the ZONE 1 ON key. If the
control system is powered up from the rear control panel, both the rear control panel and the unit HMI
control panel will display a stand by message as shown below.
x The setpoints can be changed in all installed zones.
x The installed zones can not be turned on or off.
x The control system can be powered down by pressing the ZONE 1 OFF key.
x The unit can be started and run by pressing the unit HMI control panel ON key.
If the control system is powered up from the remote control panel a stand by message will appear in both the
remote control panel display and the unit HMI control panel display as shown below.
STAND BY
4-27
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-28
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ZONE ZONE
2 2
ON OFF
ZONE
1234
ZONE ZONE
3 3
ON OFF
Keypad
The nine touch sensitive keys are used to turn the unit and all installed zones on and off. They also allow the
setpoint to be changed in all installed zones.
ZONE ZONE 1 ON KEY Turns the unit on. Also turns Zone 1 on unless Rear Remote Control Action
1
ON
is set for STAND BY. Unlike previous versions, the SR-2 SPECTRUM
remote control panel can turn the control system on from a fully powered
down state. It is not necessary to turn the host unit on for the remote control
panel to operate.
ZONE ZONE 1 OFF KEY Turns the unit off. Also turns Zone 1 off.
1
OFF
ZONE ZONE 2 ON KEY Turns Zone 2 on unless Rear Remote Control Action is set for STAND BY.
2
ON
ZONE ZONE 3 ON KEY Turns Zone 3 on (if installed) unless Rear Remote Control Action is set for
3
ON
STAND BY.
ZONE ZONE 3 OFF KEY Turns Zone 3 off (if installed).
3
OFF
ENTER KEY Loads the new setpoint for the selected zone.
4-29
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ZONE ZONE
2 2
ON OFF
ZONE
1234
ZONE ZONE
3 3
ON OFF
Display
The display normally shows the Standard Display of return air temperature, setpoint and zone. If a zone is turned
on the operating mode is also shown. If a zone is turned off the display will show the return air temperature and
OFF. The display shown here has all possible segments lighted. The display icons are defined below.
Cool Icon This icon appears when the indicated zone is cooling.
Heat Icon This icon appears when the indicated zone is heating.
Not Used This icon appears during a remote control panel test but is not currently
used.
Defrost Icon This icon appears when the indicated zone is defrosting.
Cycle Sentry Icon This icon appears when the unit is operating in Cycle Sentry mode.
Alarm Icon This icon appears when an alarm condition has been detected by the
controller.
Electric Standby Icon This icon appears when the unit is operating in the optional electric standby
mode.
Setpoint Icon This icon appears when the setpoint is being shown in the display.
Not Used This icon appears during a remote control panel test but is not currently
used.
4-30
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ZONE Zone Icon This icon indicates which zone is currently being shown on the display.
1234
The Remote Standard Display for each installed zone will appear on the display for 10 seconds. Then the next
installed zone will appear. Only installed zones will appear.
ZONE
2
4-31
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Turning the Unit and Zone 1 On or Off (Configured for STAND BY operation)
The control system is turned on by pressing the ON key and off by pressing the OFF key. When the On key is
pressed the remote display briefly shows all segments and then STAnd by as shown below. A stand by message
will also appear on the unit HMI control panel display. All setpoints can be changed but the unit will not start and
run. The unit can be started and run by pressing the unit HMI control panel ON key.
ZONE ZONE
2 2
ON OFF
ZONE ZONE
3 3
ON OFF
Turning the Unit and Zone 1 On and Off (Configured for RUN ALL ZONES or RUN LAST
CONFIG operation)
The unit and Zone 1 are turned on by pressing the ON key and off by pressing the OFF key. When the On key is
pressed the remote display briefly shows all segments and then COn FIg as the control system initializes. Then
the Remote Standard Display will appear as shown below. The unit will start and run if necessary.
ZONE ZONE
2 2
ON OFF
ZONE
2
ZONE ZONE
3 3
ON OFF
4-32
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Turning Remote Zones On and Off (Configured for STAND BY operation only)
The remote zones can not be turned on and off – only the setpoints can be changed.
Turning Remote Zones On and Off (Configured for RUN ALL ZONES or RUN LAST
CONFIG operation only)
Zone 2 and Zone 3 (if installed) are turned on by pressing the ON key and off by pressing the OFF key for the
appropriate zone. When a zone is turned on the return air temperature and setpoint is shown on the remote
standard display for that zone. In the illustration below Zone 2 is shown below turned on.
ZONE ZONE
2 2
ON OFF
ZONE
2
ZONE ZONE
3 3
ON OFF
When a zone is turned off the return air temperature and OFF is shown on the remote standard display for that
zone. In the illustration below Zone 2 is shown turned off.
ZONE ZONE
2 2
ON OFF
ZONE
2
ZONE ZONE
3 3
ON OFF
4-33
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
A zone must be currently shown on the display in order to change the zone setpoint.
ZONE ZONE
2 2
ON OFF
ZONE
2
ZONE ZONE
3 3
ON OFF
1. Press the On Key for the desired zone or wait until the desired zone is shown on the display. Pressing
the On key will immediately display that zone. If the Rear Remote Control Action feature is set for RUN
ALL ZONES or RUN LAST CONFIG pressing the On key will also turn the zone on if it was not already
on.
2. Immediately press the Up or Down Arrow Keys to select the desired setpoint for the selected zone.
3. When the desired setpoint for the selected zone is shown on the display, immediately press the Enter Key
to load the new setpoint into the microprocessor. The display will briefly show [Lod] and then the new
setpoint will reappear in the display.
IMPORTANT: The Enter key must be pressed or the setpoint will not be changed. The display will return to the
Standard Display and the setpoint will return to the old setpoint in about 10 seconds if the Enter Key is not
pressed.
IMPORTANT: Confirm that the correct setpoint is set for the each zone.
4-34
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ZONE ZONE
2 2
ON OFF
ZONE ZONE
3 3
ON OFF
4-35
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
MENU OVERVIEW
Not all menu features Temp Watch
may appear Display
Press Any
2.5 Minute Soft Key
Time-out
Zone 1 Soft Key
Zone 1 Setpoint Change
4-36
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-37
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-38
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The Main Menu contains submenus that allow the operator to view information and modify unit operation. To
access the Main Menu press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The first Main Menu choice will appear. Press the NEXT and BACK keys to scroll thru the menu choices. When
the desired selection is shown on the display, press the SELECT key to access it. The Pretrip selection is shown
here.
MAIN MENU
ON
PRETRIP
OFF
The Main Menu choices are shown on the next page. For detailed information see the individual explanations of
each submenu item on the following pages.
4-39
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
LANGUAGE – If more than one language is enabled, this menu item allows the operator to select a language
from a list of up to 11 languages at one time. All subsequent displays are shown in the selected language. Three
different language packages with a total of 24 languages are available. English is the default language and is
provided in each of the packages.
ALARMS – Allows the operator to view any active alarms, and allows most alarms to be cleared. If only one
language is enabled this will be the first menu item to appear.
GAUGES – Allows the operator to view the unit gauges and the state of the Inputs and Outputs on both the
Interface Board and Expansion Module.
SENSORS– Allows the operator to view the unit temperature sensors. If CargoWatch sensors are installed they
can be viewed as well.
DATA LOGGER – Allows the operator to set a Start of Trip marker to the CargoWatch and ServiceWatch data
loggers and print the contents of the CargoWatch data logger.
HOURMETERS – Allows the operator to view the unit hourmeters that have the view feature enabled in the
Guarded Access menu. If the view feature for a particular hourmeter is not enabled then that hourmeter cannot
be viewed.
MODE – Allows the operator to change the unit operating modes if allowed. Not all modes may appear
depending on the settings selected from the Guarded Access menu.
x Turn Off Cycle Sentry Mode/Turn On Cycle Sentry Mode (If Cycle Sentry is Off unit runs
in Continuous)
x Allow Single Zone Control or Multi Zone Control to be selected.
x Allow Keypad Lockout to be selected.
x Start Sleep Mode.
PRETRIP – Allows the operator to start a Pretrip Test. If an alarm is active, the Pretrip Test is not allowed and
the operator is prompted to clear the alarm(s).
4-40
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
ELECTRIC STANDBY – If the Electric Standby option is present and the Diesel to Electric Auto-switch feature is
set NO, this feature allows the operator to manually select electric mode operation. This feature does not appear
if the unit does not feature optional Electric Standby or if the Diesel to Electric Auto-switch feature is set YES.
DIESEL MODE – If a unit equipped with electric standby is running in electric mode and the Electric to Diesel
Auto-switch feature is set NO, this feature allows the operator to manually select diesel mode operation. This
feature does not appear if the unit does not feature optional Electric Standby or if the Electric to Diesel Auto-
switch feature is set YES.
ADJUST BRIGHTNESS – Allows the operator to adjust the HMI control panel display backlight intensity as
required by local conditions.
TIME – Allows the operator to view the unit time and date. The time and date cannot be changed from this menu.
4-41
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Languages
If the Language feature is enabled, an alternate language can be selected from the Language Menu. After a new
language is chosen all displays will appear in that language. If the language feature is not enabled this menu
does not appear. The default language is English. Only languages that have been enabled in Guarded Access
will appear.
The languages available are dependant on the HMI control panel software revision. Languages currently
supported by software revision 65xx are English, Spanish, French, German, Italian, Dutch, Portuguese, Greek,
Turkish, Hebrew and Arabic. Languages currently supported by software revision 66xx are English, Russian,
Polish, Hungarian, Romanian, Bulgarian, Czech, Danish, Swedish, Norwegian and Finnish. Languages currently
supported by software revision 67xx are English and Japanese. Other than the languages supported, software
revisions 65xx, 66xx and 67xx are identical.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
If enabled, the Language Menu is the first menu item to appear as shown below. Press the SELECT key to
choose the Language menu.
MAIN MENU
ON
LANGUAGE
OFF
4-42
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The Language menu will appear as shown below. Press the + or – keys to select the desired language. When
the desired language is shown press the YES key to confirm the choice.
DEUTSCH
OFF
USE +/- TO CHANGE OK?
- + YES NO
The display will briefly show PROGRAMMING LANGUAGE – PLEASE WAIT in the new language. The display
will then return to the Language Menu, but will show the new language. German is shown below.
HAUPTMENU
ON
SPRACHE
OFF
x Exercise care when changing languages, as once changed all HMI Control panel displays will be in the
new language. If the user is not familiar with the new language, problems may be experienced returning
to the default language.
Repeat the process to select a different language. To select a different Main Menu item press the NEXT key. To
return to the Standard Display press the EXIT key.
NOTE: English and all other enabled languages may be accessed from the Standard Display. When the
Standard Display is shown press and hold the first and last soft key for 5 seconds as shown below.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
4-43
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Alarms
Alarm Display
If a unit alarm condition occurs the large Alarm Icon will appear on the Standard Display as shown below.
CONTINUOUS
ON
-8.2 35.8
OFF
0 35
ZONE 1 ZONE 2 MENU
If an alarm specific to a zone occurs then a small zone alarm icon will appear next to the affected zone as well.
Both Alarm Icons will be present. Here the small zone Alarm Icon indicates that an alarm exists specific to Zone
2.
CONTINUOUS
ON
-8.2 35.8
OFF
0 35
ZONE 1 ZONE 2 MENU
NOTE: Zone specific alarm codes use the standard Thermo King alarm code numbers. If an alarm is
specific to a zone then both the alarm code number and affected zone number are displayed.
NOTE: If the large alarm icon only appears, then the active alarm(s) are unit level alarm(s). If a zone
alarm icon and the large alarm icon are displayed there is a zone level alarm or a combination of zone
level and unit level alarms present.
4-44
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Log Alarms
Log Alarms are indicated for 60 seconds each time the unit is turned on. This level of alarm serves as a notice to
take corrective action before a problem becomes severe. Maintenance items such as maintenance hourmeter
time-outs are log alarms. The Temperature Watch screen is not disabled if only log alarm(s) are active.
When the unit is turned on the display will show the Thermo King Logo and then the “Configuring System”
message. If log alarm(s) are present the Log Alarm notice will appear on the display for 60 seconds as shown
below. The remote indicator alarm light (if installed) will also be on during this period. The Standard Display will
appear and the remote indicator alarm light will go off after 60 seconds.
NOTE: The Alarm Icon does not appear on startup with log alarms present.
EXIT
NOTE: If required, an engine start may occur while the display above is still shown. This is normal
operation.
Check Alarms
Check Alarms are indicated by a steady alarm icon at the side of the display. If the alarm is specific to a zone
then a smaller alarm icon will appear next to the affected zone. This level of alarm serves as a notice to take
corrective action before a problem becomes severe. The unit will run with check alarms but some features and
functions may be inhibited. The Temperature Watch screen is disabled if a check alarm is active.
4-45
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
NOTE: If the Restart After Shutdown feature in the Guarded Access Menu is set for CONTINUOUS, then
an unlimited number of restart attempts are allowed.
Unit level shutdown alarms will force the unit into shutdown. The unit will remain in shutdown until the shutdown
alarm is manually cleared. Exceptions are some engine and electric shutdown alarms that become log alarms
when switched to the alternate operating mode (diesel to electric or electric to diesel). The Temperature Watch
screen is disabled if a unit level shutdown alarm is active.
4-46
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
In the same manner, if a shutdown alarm occurs that affects only electric mode operation and the unit is switched
to diesel, the electric mode shutdown alarm becomes a diesel mode log alarm to allow diesel mode operation. If
the unit is switched back to electric mode, the alarm reverts to an electric mode shutdown alarm and prevents unit
operation.
4-47
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The following sensor alarm codes can only be cleared from the Guarded Access Menu. The CLEAR soft key will
not appear if the alarms are displayed from the Main Menu or the Maintenance Menu.
x Alarm Code 03 Check (Control) Return Air Sensor for all zones.
x Alarm Code 04 Check (Control) Discharge Air Sensor for all zones.
If the Limited Alarm Restarts feature is enabled the following additional alarm codes may only be cleared from the
Guarded Access Menu. If this is the case, the CLEAR soft key will not appear if the alarms are displayed from the
Main Menu or the Maintenance Menu. See the Limited Alarm Restarts feature in Section 3 for details.
x Alarm Code 10 High Discharge Pressure
x Alarm Code 23 Cooling Cycle Fault
x Alarm Code 24 Heating Cycle Fault
x Alarm Code 32 Refrigeration Capacity Low
4-48
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
02 Check Evaporator Coil Sensor (for Manually monitor load temperature. Report alarm at end of the
specified zone) day.
03 Check Return Air Sensor (for Manually monitor load temperature. Report alarm at end of the
specified zone) day.
04 Check Discharge Air Sensor (for Manually monitor load temperature. Report alarm at end of the
specified zone) day.
05 Check Ambient Air Sensor Report alarm at end of the day.
09 High Evaporator Temperature Manually monitor load temperature. Report alarm at end of the
day.
10 High Discharge Pressure If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
11 Unit Controlling on Alternate Sensor Manually monitor load temperature. Report alarm at end of the
day.
12 Sensor or Digital Input Shutdown The indicated zone is not longer able to operate and has been
shut down. Repair immediately.
13 Sensor Check Manually monitor load temperature. Report alarm at end of the
day.
15 Check Glow Plugs or Intake Air If unit is shut down repair immediately. Otherwise, report alarm
Heater at end of the day.
17 Engine Failed to Crank If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
18 High Engine Coolant Temperature If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
4-49
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
29 Check Defrost Damper Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
30 Defrost Damper Stuck If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
31 Check Oil Pressure Switch If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
32 Refrigeration Capacity Low The unit is no longer able to operate and has been shut down.
Repair immediately.
33 Check Engine RPM Report alarm at end of the day.
35 Check Run Relay Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
4-50
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
38 Electric Phase Reversed If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
39 Check Water Valve Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
40 Check High Speed Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
41 Check Engine Coolant Temperature If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
42 Unit Forced to Low Speed Report alarm at end of the day.
44 Check Fuel System If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
45 Check Hot Gas or Hot Gas Bypass If unit is shut down repair immediately. Otherwise, report alarm
Circuit at end of the day.
46 Check Air Flow If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
48 Check Belts or Clutch If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
52 Check Heat Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
54 Test Mode Timeout Service Test or Interface Board Test timed out after 15 minutes.
Report alarm at end of the day.
61 Low Battery Voltage If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
62 Ammeter Out of Calibration If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
4-51
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
65 Abnormal Temperature Differential If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
66 Low Engine Oil Level Check engine oil level. If unit is shut down repair immediately.
Otherwise, report alarm at end of the day.
67 Check Liquid Line Solenoid Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
68 Internal Controller Fault Code Report alarm at end of the day.
77 Controller EEPROM Checksum If unit is shut down repair immediately. Otherwise, report alarm
Failure at end of the day.
79 Internal Data Log Overflow Report alarm at end of the day.
90 Electric Overload If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
4-52
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
93 Low Compressor Suction Pressure If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
96 Low Fuel Level Check engine fuel level. If unit is shut down repair immediately.
Otherwise, report alarm at end of the day.
98 Check Fuel Level Sensor Report alarm at end of the day.
105 Check Receiver Tank Press Sol If unit is shut down repair immediately. Otherwise, report alarm
Circuit at end of the day.
106 Check Purge Valve Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
107 Check Condenser Inlet Sol Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
108 Door Open Timeout Close Doors. Report alarm at end of the day.
110 Check Suction Line Solenoid Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
111 Unit Not Configured Correctly Report alarm at end of the day.
112 Check Remote Fans If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
113 Check Electric Heat Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
114 Multiple Alarms – Can Not Run If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
117 Auto Switch from Diesel to Electric Report alarm at end of the day.
4-53
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
120 Check Alternator Excite Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
121 Check Liquid Injection Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
122 Check Diesel/Electric Circuit If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
127 Setpoint Not Entered Be sure the setpoint is set to the required temperature.
128 Engine Run Time Maintenance Report alarm at end of the day.
Reminder #1
129 Engine Run Time Maintenance Report alarm at end of the day.
Reminder #2
130 Electric Run Time Maintenance Report alarm at end of the day.
Reminder #1
131 Electric Run Time Maintenance Report alarm at end of the day.
Reminder #2
132 Total Unit Run Time Reminder #1 Report alarm at end of the day.
133 Total Unit Run Time Reminder #2 Report alarm at end of the day.
136 Check Spare Digital Outputs Report alarm at end of the day.
137 Check Damper Motor Heater Output Report alarm at end of the day.
4-54
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
144 Loss of CAN Communication If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
145 Loss of 8X Input If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
146 Software Version Mismatch If unit is shut down repair immediately. Otherwise, report alarm
at end of the day.
147 Check Multi-Temp Fan Speed If unit is shut down repair immediately. Otherwise, report alarm
Control Output at end of the day.
148 Autoswitch Electric to Diesel Report alarm at end of the day.
Disabled
153 Expansion Module Flash Load If unit is shut down repair immediately. Otherwise, report alarm
Failure at end of the day.
4-55
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If an alarm condition occurs that is not zone specific, the Alarm Icon will appear in place of the textual information
in the display as shown below.
CONTINUOUS
-8.2 35.8
ON
OFF
0 35
ZONE 1 ZONE 2 MENU
If the alarm condition is zone specific, the Alarm Icon will also appear in the appropriate zone. An alarm specific
to Zone 2 is shown below.
CONTINUOUS
-8.2 35.8
ON
OFF
0 35
ZONE 1 ZONE 2 MENU
Alarms are displayed and cleared using the Alarm Menu. From the Standard Display, press the MENU key.
CONTINUOUS
2
35.8
ON
-8.
OFF
0 35
ZONE 1 ZONE 2 MENU
4-56
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The Language Menu or Alarm Menu will appear. If the Language Menu appears press the NEXT key to display
the Alarm Menu. When the Alarm Menu is shown press the SELECT key.
MAIN MENU
ON
ALARMS
OFF
The Alarm Display will appear. If no alarms are present NO ALARMS will be shown on the display.
NO ALARMS
ON
0 OF 0 ALARMS
NO ALARMS
OFF
EXIT
If alarms are present, the quantity of alarms (if more than one), the alarm code number and alarm description will
be shown on the display. In the example below, there are two alarms present. The most recent is Alarm Code 6.
This alarm code indicates a problem with the coolant temperature sensor.
ALARM 6
ON
1 OF 2 ALARMS
COOLANT TEMP SENSOR
OFF
4-57
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
After the alarm situation is resolved press the CLEAR key to clear the alarm. For additional information regarding
the alarm shown on the display, press the HELP key. To display the next alarm, press the NEXT key.
ALARM 5
ON
2 OF 2 ALARMS
AMBIENT TEMP SENSOR
OFF
For additional information regarding the alarm shown on the display, press the HELP key. A help message will
appear. For the alarm shown below, the message “Check engine oil level. If unit is shut down repair
immediately. Otherwise, report alarm at end of the day.” will be shown on the display.
ALARM 66
ON
1 OF 1 ALARMS
LOW ENGINE OIL LEVEL
OFF
After the alarm situation is resolved press the CLEAR key to clear the alarm. To display the next alarm code
press the NEXT key. To return to the Standard Display press the EXIT key.
x If an alarm cannot be cleared from the Main menu, the Clear key will not appear. These alarms must be
cleared from the Guarded Access Menus.
x All alarms must be viewed before any of the alarms can be cleared.
4-58
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Gauges
Unit Gauges and I/O (Input/Output) State are viewed using the Gauges menu. From the Standard Display, press
the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Gauges menu.
When the Gauges menu is shown press the SELECT key.
MAIN MENU
ON
GAUGES
OFF
The first Gauge menu display will appear. Press the NEXT and BACK keys to scroll thru the gauges. Pressing
the LOCK key will lock the gauges on the display for fifteen minutes.
COOLANT TEMPERATURE
ON
183 °F
OFF
The gauges available are shown on the next page. To return to the Standard Display press the EXIT key.
4-59
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Gauges Available
Amps – Displays the current flow in amps flowing to or from the unit battery
Fuel Level Sensor – Displays the fuel level in the unit fuel tank.
I/O (Input/Output State) – Displays the current state of the input/output devices listed on the next page.
4-60
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
I/O (Input/Output State) – Displays the current state of the input/output devices listed below.
4-61
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Sensors
Unit temperature sensors are viewed using the Sensors menu. From the Standard Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Sensors menu.
When the Sensors menu is shown press the SELECT key.
MAIN MENU
ON
SENSORS
OFF
The first Sensors menu display will appear. Press the NEXT and BACK keys to scroll thru the sensors. Pressing
the LOCK key will lock the sensor on the display.
35. 7 °F
OFF
The sensors available are shown on the next page. Only configured and enabled sensors are shown. For
example, if the unit is configured as a two zone unit, then zone 3 sensors are not shown. If the CargoWatch
sensors are not enabled, they will not be shown. To return to the Standard Display press the EXIT key.
4-62
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Sensors Available
Zone 1 Return Air Temperature – Displays the temperature of the Zone 1 Return Air Sensor.
Zone 1 Discharge Air Temperature – Displays the temperature of the Zone 1 Discharge Air Sensor.
Zone 1 Evaporator Coil Temperature – Displays the temperature of the Zone 1 Evaporator Coil sensor.
Zone 2 Return Air Temperature – Displays the temperature of the Zone 2 Return Air Sensor.
Zone 2 Discharge Air Temperature – Displays the temperature of the Zone 2 Discharge Air Sensor.
Zone 2 Evaporator Coil Temperature – Displays the temperature of the Zone 2 Evaporator Coil sensor.
Zone 3 Return Air Temperature – Displays the temperature of the Zone 3 Return Air Sensor.
Zone 3 Discharge Air Temperature – Displays the temperature of the Zone 3 Discharge Air Sensor.
Zone 3 Evaporator Coil Temperature – Displays the temperature of the Zone 3 Evaporator Coil sensor.
Ambient Air Temperature – Displays the temperature of the ambient air temperature sensor.
4-63
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
CargoWatch Data Logger Sensor 1 Temperature – Displays the temperature of the CargoWatch Data Logger 1
temperature sensor.
CargoWatch Data Logger Sensor 2 Temperature – Displays the temperature of the CargoWatch Data Logger 2
temperature sensor.
CargoWatch Data Logger Sensor 3 Temperature – Displays the temperature of the CargoWatch Data Logger 3
temperature sensor.
CargoWatch Data Logger Sensor 4 Temperature – Displays the temperature of the CargoWatch Data Logger 4
temperature sensor.
CargoWatch Data Logger Sensor 5 Temperature – Displays the temperature of the CargoWatch Data Logger 5
temperature sensor.
CargoWatch Data Logger Sensor 6 Temperature – Displays the temperature of the CargoWatch Data Logger 6
temperature sensor.
Board Temperature Sensor – Displays the temperature of the HMI control panel pc board.
4-64
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The CargoWatch Data Logger is physically located in the HMI Control Panel. It can support up to 6 optional
temperature sensors.
A Start of Trip can be sent to the unit ServiceWatch and CargoWatch Data Loggers and the CargoWatch Data
Logger contents can be printed with a hand-held printer.
The ServiceWatch and CargoWatch Data Logger are accessed using the Data Logger Menu. From the Standard
Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Data Logger
menu. When the Data Logger menu is shown press the SELECT key.
MAIN MENU
ON
DATA LOGGER
OFF
4-65
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The first feature that appears is the Start of Trip. To send a Start of Trip press the SELECT key to select the
feature, and then press it again to send the Start of Trip. The display will briefly show START OF TRIP
COMPLETE to confirm that a Start of Trip marker was set in the data logger.
START OF TRIP
ON
START OF TRIP
OFF
NOTE: The start of trip marker is sent to both the CargoWatch and ServiceWatch data loggers.
Press the NEXT key to select the PRINT / VIEW feature. The PRINT / VIEW screen will appear.
DATALOGGER
ON
PRINT / VIEW
OFF
Press the SELECT key. The first PRINT / VIEW screen allows the operator to print a Delivery Ticket. Pressing
the SELECT key will print a delivery ticket. The Delivery Ticket is a short ticket that shows delivery specific details
including the current temperature.
PRINT DATA
ON
DELIVERY TICKET
OFF
4-66
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Pressing the NEXT key allows the operator to print a Trip Ticket using a hand held printer. Pressing the SELECT
key will print a Trip Ticket. The Trip Ticket is a long ticket that shows details for the current trip including a
temperature history. The Trip Ticket is also called a Journey Ticket.
PRINT DATA
ON
TRIP TICKET
OFF
Pressing the EXIT key returns the display to the Main Menu.
For additional information concerning the CargoWatch Data Logger see Service Procedure A49A in Section 6 of
this manual.
4-67
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Hourmeters
Unit Hourmeters are viewed using the Hourmeters menu. From the Standard Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Hourmeters
menu. When the Hourmeters menu is shown press the SELECT key.
MAIN MENU
ON
HOURMETERS
OFF
The first Hourmeters menu display will appear. Press the NEXT and BACK keys to scroll thru the hourmeters.
Pressing the LOCK key will lock the hourmeter on the display.
TOTAL HOURS
ON
7
138
OFF
Hourmeter names and definitions are shown in the table on the next page in the order they appear. Only
configured hourmeters that have been enabled for viewing in Guarded Access will be shown.
4-68
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Total Run Time Hours Total number of hours the unit has run in both diesel and electric mode.
Engine Hours Total number of hours the unit has run in diesel mode.
Electric Run Hours Total number of hours the unit has run in electric mode.
Zone 1 Run Time Hours Total number of hours Zone 1 has run in both diesel and electric mode.
Zone 2 Run Time Hours Total number of hours Zone 2 has run in both diesel and electric mode.
Zone 3 Run Time Hours Total number of hours Zone 3 has run in both diesel and electric mode.
Total Run Reminder 1 Hours User Programmable – The number of hours before a Total Unit Run Time
Maintenance Reminder 1 occurs.
Total Run Reminder 2 Hours User Programmable – The number of hours before a Total Unit Run Time
Maintenance Reminder 2 occurs.
Controller Power On Hours Total hours the controller and HMI control panel have been turned on.
Pretrip Reminder Hours User Programmable – number of hours before a Pretrip Reminder occurs.
Engine Reminder 1 Hours User Programmable – The number of hours before an Engine Run Time
Maintenance Reminder 1 occurs.
Engine Reminder 2 Hours User Programmable – The number of hours before an Engine Run Time
Maintenance Reminder 2 occurs.
Electric Reminder 1 Hours User Programmable – The number of hours before an Electric Run Time
Maintenance Reminder 1 occurs.
Electric Reminder 2 Hours User Programmable – The number of hours before an Electric Run Time
Maintenance Reminder 2 occurs.
4-69
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Mode
Various operating modes can be selected using the Mode menu. Not all modes may be available, depending on
OptiSet usage and settings of other programmable features. The following modes may be available.
Keypad Lockout
If enabled in Guarded Access, the keypad can be locked to prevent unauthorized use. If the keypad is locked
only the On and Off keys function. The keypad will remain locked even if the unit is turned off and back on. If
Keypad Lockout is active, press and hold any soft key for 5 seconds to deactivate the feature.
4-70
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Mode changes are made using the Mode Menu. From the Standard Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Mode menu.
When the Mode menu is shown press the SELECT key.
MAIN MENU
ON
MODE
OFF
The first Mode menu screen will appear. To chose that function press the SELECT key. To Scroll through the
Mode Menu press the NEXT key.
CHANGE MODE
ON
OFF
Possible Mode selections are shown on the previous page. Not all modes may be available, depending on
OptiSet usage and the settings of other programmable features.
4-71
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Pretrip
A Pretrip Test verifies unit operation. This display allows a Pretrip Test to be selected and initiated by the
operator. If the Pretrip Test is entered with the engine not running a Full Pretrip Test with device amp checks will
be performed. If the Pretrip Test is entered with the unit running in either diesel or electric mode a Running
Pretrip Test is performed. Test results are reported as PASS, CHECK or FAIL when the Pretrip Test is
completed.
4-72
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-73
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Pretrip Tests are initiated using the Pretrip Menu. From the Standard Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Pretrip menu.
When the Pretrip menu is shown press the SELECT key to start a Pretrip Test.
MAIN MENU
ON
PRETRIP
OFF
If the unit is not running a Full Pretrip Test will be initiated. If the unit is running in either diesel or electric mode a
Running Pretrip will be performed.
OFF
PLEASE WAIT
4-74
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If all alarms were not cleared a prompt appears as shown below. Exit the Pretrip Test, clear all alarms and repeat
the Pretrip Test.
ON
NO PRETRIP -- ALARM ACTIVE
OFF
EXIT
NON-RUNNING PRETRIP
TEST 1 OF 55
ON
SENSOR CHECK
OFF
x The top line of the display indicates the unit is performing the non-running portion of the Pretrip Test.
x The second line shows Test 1 of 55 is being performed. Note that the tests may not be performed in
numerical order.
x The soft keys may be used during the Pretrip Test to select the Hourmeter, Gauge or Sensor menus.
x To stop a Pretrip Test at any time, turn the unit off. This will generate Alarm Code 28 Pretrip Abort. Other
alarm codes may also be generated. This is normal when the Pretrip Test is halted before completion.
4-75
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
When the non-running tests are complete the unit will start automatically and continue with the Running Pretrip
Test. In the example shown below the unit is in the Running Pretrip and is performing Test 3 of 15 Zone 1 Cool
Test.
RUNNING PRETRIP
TEST 3 OF 15
ON
When all tests are complete, the results are reported as PASS, CHECK or FAIL. If the results are CHECK or
FAIL, the accompanying alarm codes will direct the technician to the cause of the problem.
PRETRIP
ON
PASS
OFF
EXIT
If the Pretrip Test results are CHECK or FAIL the problem should be diagnosed and corrected and the Pretrip
Test repeated and passed before the unit is released for service. The Pretrip Test result screen will exit to the
Main Menu Alarm Submenu for convenient access to any alarms generated during the Pretrip Test.
4-76
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The Diesel Mode/Electric Standby menu allows the operator to manually select diesel or electric mode operation.
The unit can also be programmed to automatically select electric mode operation when standby power is
available and diesel mode operation if standby power fails or is removed. If the unit is programmed to switch
automatically from diesel to electric and electric to diesel these screens do not appear.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to display the Electric Standby
menu. When the Electric Standby menu is shown press the SELECT key to switch to electric mode operation.
MAIN MENU
ON
ELECTRIC STANDBY
OFF
NOTE: This screen will not appear if diesel to electric switchover is enabled.
4-77
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If the unit has standby power available and is turned on, the electric standby run screen will appear. The new
mode is then confirmed for 10 seconds. The unit will start and run in electric mode and the display will return to
the Standard Display. If electric standby power is not available the display will prompt for a return to diesel mode
as shown below.
If the electric standby power source fails or is disconnected and manual switching to diesel mode is selected, the
unit will prompt for a switch to diesel. Selecting YES will switch unit operation back to diesel mode. Pressing the
NO key will force the unit to remain in Electric Standby mode even though standby power is not available. The
unit will not run and Alarm Code 91 Check Electric Ready Input will be set as a prevent alarm.
YES NO
4-78
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to show the Diesel Mode
Menu. When the Diesel Mode Menu is shown press the SELECT key.
MAIN MENU
ON
DIESEL MODE
OFF
NOTE: This screen will not appear if electric to diesel switchover is enabled.
The unit can be programmed to automatically switch to electric mode operation when standby power is available.
It can also be programmed to automatically switch to diesel mode operation if the standby power fails or is
disconnected.
4-79
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Adjust Brightness
The brightness of the HMI Control Panel display backlight can be adjusted to allow for changing ambient light
conditions. The choices available to the operator are HIGH, MEDIUM, LOW and OFF. OFF actually results in a
very dim backlight suitable for low light conditions.
IMPORTANT: Before replacing an HMI with no backlight check the Adjust Backlight feature to be sure the
backlight is turned on.
Backlight brightness is adjusted using the Adjust Brightness Menu. From the Standard Display, press the MENU
key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to show the Adjust Brightness
Menu. When the Adjust Brightness Menu is shown press the SELECT key.
MAIN MENU
ON
ADJUST BRIGHTNESS
OFF
4-80
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The Display Brightness menu will appear as shown below. Press the + or – keys to select the desired display
backlight brightness. When the desired backlight brightness is shown press the YES key to confirm the choice.
MEDIUM
OFF
USE +/- TO CHANGE OK?
- + YES NO
ON ADJUSTING BRIGHTNESS
OFF
PLEASE WAIT
4-81
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Time
The Time and Date held by the HMI Control Panel real time clock can be checked. Time and Date cannot be
changed from the Main Menu.
The time and date is accessed using the Main Menu. From the Standard Display, press the MENU key.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Language Menu or Alarm Menu will appear. Press the NEXT key as required to show the Time. When Time
is shown press the SELECT key. The current time and date will appear.
TIME MENU
ON
01:01 SUNDAY DECEMBER 10 2006
OFF
EXIT
4-82
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-83
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-84
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Maintenance Menu is accessed from the first Main Menu screen that appears; either the Language Display or
the Alarms Display. The Alarms Display is shown here. Press and hold both the unlabelled soft key and the Exit
key for 5 seconds as shown below.
MAIN MENU
ON
ALARMS
OFF
4-85
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The first Maintenance Menu feature will appear. Press the NEXT and BACK keys to scroll thru the Maintenance
Menu choices. When the desired choice is shown on the display, press the SELECT key to access it.
MAINTENANCE MENU
ON
HOURMETERS
OFF
The Maintenance Menu choices are shown on the next page. For detailed information see the individual
explanations of each item later in this section of the manual.
The HMI control panel will also return to the Standard Display 30 seconds after the last key is pressed.
4-86
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Hourmeters
This menu allows the technician to view all the active unit hourmeters, even if the Main Menu hourmeter view has
been turned off. The Maintenance Menu Hourmeter Display also allows the technician to reset the time on
hourmeters with a programmed time limit.
Choose Hourmeters by pressing the SELECT key when HOURMETERS is shown by the Maintenance Menu.
The hourmeter screen appears as shown below.
The NEXT and BACK keys are used to scroll through the hourmeters.
4-87
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Hourmeter Displays
Hourmeter Name Definition
Total Hours Total number of hours the unit has been turned on (protection hours).
Total Run Time Hours Total number of hours the unit has run in both diesel and electric mode.
Engine Hours Total number of hours the unit has run in diesel mode.
Electric Run Hours Total number of hours the unit has run in electric mode.
Zone 1 Run Time Hours Total number of hours that Zone 1 has run, including Null hours.
Zone 2 Run Time Hours Total number of hours that Zone 1 has run, including Null hours.
Zone 3 Run Time Hours Total number of hours that Zone 1 has run, including Null hours.
Total Run Reminder 1 Hours User Programmable – The number of hours before a Total Unit Run Time
Maintenance Reminder 1 occurs.
Total Run Reminder 2 Hours User Programmable – The number of hours before a Total Unit Run Time
Maintenance Reminder 2 occurs.
Controller Power On Hours Total hours the controller and HMI control panel have been turned on.
Pretrip Reminder Hours User Programmable – number of hours before a Pretrip Reminder occurs.
Engine Reminder 1 Hours User Programmable – The number of hours before an Engine Run Time
Maintenance Reminder 1 occurs.
Engine Reminder 2 Hours User Programmable – The number of hours before an Engine Run Time
Maintenance Reminder 2 occurs.
Electric Reminder 1 Hours User Programmable – The number of hours before an Electric Run Time
Maintenance Reminder 1 occurs.
Electric Reminder 2 Hours User Programmable – The number of hours before an Electric Run Time
Maintenance Reminder 2 occurs.
4-88
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Gauges
This menu allows the technician to view the unit gauges.
Choose Gauges by pressing the SELECT key when GAUGES is shown by the Maintenance Menu. The first
Gauges screen appears as shown below.
COOLANT TEMPERATURE
ON
183 °F
OFF
The NEXT and BACK keys are used to scroll through the gauges.
The LOCK key allows a gauge display to be “locked” on the display for 15 minutes at the operator’s discretion.
Not all gauges are available on all units. Only gauges used by the specific unit will appear.
The I/O submenu shows the state of each named device – either On or Off.
The Gauges Menu can also be accessed from the Main Menu.
4-89
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Gauge Displays
4-90
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Sensors
This menu allows the technician to view the unit temperature sensors.
Choose Gauges by pressing the SELECT key when SENSORS is shown by the Maintenance Menu. The
SENSORS screen appears as shown below.
83 °F
OFF
The NEXT and BACK keys are used to scroll through the sensors.
The LOCK key allows a sensor display to be “locked” on the display to prevent the display from timing out.
The Sensors Menu can also be accessed from the Main Menu.
4-91
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Sensor Displays
4-92
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Alarms
Allows the technician to view all alarms and clear most alarms. The Alarms Menu is also available from the Main
Menu.
Choose Alarms by pressing the SELECT key when ALARMS is shown by the Maintenance Menu. The Alarms
screen appears as shown below.
ALARM 10
ON
1 OF 2 ALARMS
HIGH DISCHARGE PRESSURE
OFF
For as list of possible alarm codes and alarm code diagnostics see Section 5 of this manual.
4-93
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The following control and display sensor alarm codes can only be cleared from the Guarded Access Menu. The
CLEAR soft key will not appear if the alarms are displayed from the Main Menu or the Maintenance Menu.
x Alarm Code 03 Check (Control) Return Air Sensor for all zones.
x Alarm Code 04 Check (Control) Discharge Air Sensor for all zones.
If the Limited Alarm Restarts feature is enabled the following additional alarm codes may only be cleared from the
Guarded Access Menu. If this is the case, the CLEAR soft key will not appear if the alarms are displayed from the
Main Menu or the Maintenance Menu. See the Limited Alarm Restarts feature in Section 3 for details.
x Alarm Code 10 High Discharge Pressure
x Alarm Code 23 Cooling Cycle Fault
x Alarm Code 24 Heating Cycle Fault
x Alarm Code 32 Refrigeration Capacity Low
4-94
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
IMPORTANT: Service Test Mode is not allowed if any shutdown alarms exist or if the unit is in a Prevent Mode
shutdown null (Alarm Code 84). Clear all alarms before using Service Test Mode.
Choose Service Test Mode by pressing the SELECT key when SERVICE TEST is shown by the Maintenance
Menu. Select either Running or Non Running tests.
A typical Service Test Mode screen is shown below. The test shown is the Zone 1 Low Speed Cool test.
The Return, Discharge and Evaporator Coil temperatures as well as the Temperature Differential are shown. The
soft key functions are as follows.
x Pressing the EXIT key terminates Service Test Mode and returns to the Maintenance Menu.
x Pressing the TEST key scrolls thru the various tests available for the current zone.
x Pressing the GAUGES key scrolls through the unit gauges.
x Pressing the NEXT key switches between zones to allow a different test mode to be selected for each
zone.
A test will remain active for 15 minutes. A countdown timer shows the time remaining for the test. If the test
times out the test will terminate, the unit will be shut down (if running) and Alarm Code 54 Test Mode Timeout is
set.
Not all tests are available on all units. Only tests that apply to the specific unit will appear.
4-95
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-96
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
x Service Test Mode operation is forced operation to allow servicing to proceed under known conditions.
All protection controls are active during Service Test Mode operation to prevent unit damage. All other
controls (such as programmable features) are disabled when Service Test Mode is active.
x When a zone is cooling the Liquid Line Solenoid (LLS) is energized (open).
x When a zone is heating or defrosting then the Liquid Line Solenoid (LLS) is energized (open) and the Hot
Gas Solenoid (HGS) is energized (open). If a defrost test is being performed in a host zone, then the
defrost damper will be energized (closed). If a defrost test is being performed in a remote zone, then the
evaporator fan motors will be de-energized.
x When a zone is in reverse cycle heat then the Liquid Line Solenoid (LLS) for that zone is energized
(open), the Hot Gas Solenoid (HGS) is energized (open) and the Suction Line Solenoid (SLS) is
energized (closed).
x When a zone is in Null then the Liquid Line Solenoid (LLS) is de-energized (closed) and the Hot Gas
Solenoid (HGS) is de-energized (closed). If the test is being performed in a host zone, then the defrost
damper will be closed. If the test is being performed in a remote zone, then the evaporator fan motors will
be de-energized.
x When a zone is in minimal heat then the Liquid Line Solenoid (LLS) is energized (open) and the Hot Gas
Solenoid (HGS) is energized (open).
4-97
02 February 2007
02 February 2007
Service Test Mode Output States
Low Speed High Speed Low Speed High Speed Minimal
Null Defrost
Cool Cool Heat Heat Heat
UNIT DEVICES
Condenser Inlet Solenoid (CIS) On or Off On or Off On or Off
Note 1 Note 1 Note 1 Note 1
Receiver Tank Press Sol (RTPS) On or Off On or Off On or Off
Note 1 Note 1 Note 1 Note 1
Purge Valve (PV) On or Off On or Off On or Off
Note 1 Note 1 Note 1 Note 1
4-98
On
Liquid Line Solenoid (LLS) On On On On On
Operation of SR-2 SPECTRUM Unit Solenoids and Valves
Note 4
On
Hot Gas Solenoid (HGS) On On On
Note 4
Suction Line Solenoid (SLS) On if other On if other On if other
Note 5 zone in cool zone in cool zone in cool
Fan Motors On
Note 3 On On On On
Note 3 Note 4
Note 1 - These devices operate as required depending on system pressures and ambient temperature.
Note 2 - Damper solenoid on host unit and Zone 2 if unit is a DE.
Note 3 - Fan motors operate in Running Null.
Note 4 - Minimal Heat is allowed only if all other zones are in Null or Off.
Note 5 - Suction Line Solenoid is On only if another zone is cooling (Reverse Cycle operation).
Section 4 – SR-2 SPECTRUM Operation
Section 4 – SR-2 SPECTRUM Operation
IMPORTANT: Interface Board Test Mode is not allowed if any shutdown alarms exist or if the unit is in a Prevent
Mode shutdown null (Alarm Code 84). Clear all alarms before using Interface Board Test Mode.
Choose Interface Board Test by pressing the SELECT key when INTERFACE BOARD TEST is shown by the
Maintenance Menu. The first Interface Board Test screen appears. Press the NEXT soft key as required to
select the desired test. The Run Relay test is shown below.
RUN RELAY
ON
HED-P 169 AMPS 0.0
SCT-P 169 VOLTS 13.2
OFF
EXIT TEMP ON LOCK ON NEXT
Discharge Pressure, Suction Pressure, Amps and Volts are displayed. The soft key functions are as follows.
x Pressing the EXIT key returns to the Maintenance Menu.
x Pressing the TEMP ON key momentarily energizes the indicated control device.
x Pressing the LOCK ON key locks the indicated control device on for 15 minutes. If the test times out
Alarm Code 54 Test Mode Timeout is set. Not all tests can be locked on. See the next page.
x Pressing the NEXT key allows a test mode to be selected. There is no BACK key – the Next key scrolls
through the entire test list and then starts over at the beginning of the list.
The LOCK ON key energizes the device for 15 minutes. Not all tests can be locked on. Here the Run Relay has
been locked on. Comparing the AMPS display with the display above where the Run Relay was not energized, it
can be seen that the Run Relay is drawing about 1.7 amps.
RUN RELAY
ON
HED-P 169 AMPS -1.7
SCT-P 169 VOLTS 13.2
OFF
EXIT UNLOCK
4-99
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-100
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Choose Display Self Test by pressing the SELECT key when DISPLAY SELF TEST is shown by the Maintenance
Menu. The Display Self Test screen appears. Select a test from the list below.
x LCD Test – This test allows the technician to select a normal or inverted display. If inverted is chosen the
display is reversed – segments that were turned on are now turned off and segments that were turned off
are now turned on. The technician visually verifies that all display segments are functioning properly.
x Keypad Test – This test prompts the technician to press the four soft keys, the Defrost key and the Cycle
Sentry key. Each time the requested key is pressed the next prompt is displayed, allowing the technician
to verify proper operation on these keys.
x Backlight Test – This test allows the technician to turn the backlight on and off to confirm operation.
x Brightness Test – This test allows the technician to select Low, Medium or High backlight intensity.
x Buzzer Test – This test allows the technician to turn the HMI buzzer on and off to verify operation.
x Heater Output – This test allows the technician to turn the HMI display heater on and off.
x Serial E2 – This test allows the technician to perform an internal HMI memory test. The test takes less
than 1 second and the results are reported as PASS or FAIL.
x Datalog Flash – This test allows the technician to perform an internal HMI CargoWatch data logger
memory test. The test takes less than 1 second and the results are reported as PASS or FAIL.
x RTC Update – This test allows the technician to perform an internal HMI real time clock test. The test
takes less than 3 seconds and the results are reported as PASS or FAIL.
4-101
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Evacuation Test
This menu allows the technician to open all normally closed refrigeration system valves to evacuate and charge
the unit with refrigerant. If the battery voltage falls below 13.0 Vdc the technician is prompted to connect a battery
charger to maintain sufficient voltage to hold all valves open.
IMPORTANT: Evacuation mode has no time-out. The unit will remain in Evacuation Mode indefinitely
unless the battery voltage becomes excessive.
All selectable unit features will be disabled when in evacuation mode. Auto switch from diesel to electric or from
electric to diesel is allowed, but unit will not start.
Choose Evacuation Test by pressing the SELECT key when EVACUATION TEST is shown by the Maintenance
Menu. The Evacuation Test display shown below will appear and remain on the display so long as the battery
voltage does not fall below 13.0 Vdc. All normally closed refrigerant valves are energized to the open position to
allow system evacuation to effectively remove air and moisture from the refrigeration system.
OFF
13.1 V
EXIT
4-102
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
If the battery voltage falls below 13.0 Vdc the technician is prompted to install a battery charger to guarantee
sufficient voltage to keep all valves open during the evacuation process.
OFF
12.9 V
EXIT
To exit Evacuation Mode press the EXIT soft key or turn the unit off.
Software Revision
This menu allows the technician to view the software revision for the HMI control panel, the controller and the
supervisor.
Choose Software Revision by pressing the SELECT key when SOFTWARE REVISION is shown by the
Maintenance Menu. The Software Revision display appears as shown below.
6510
OFF
EXIT NEXT
The NEXT and BACK soft keys allow the technician to scroll through the software revisions. Software revisions
appear in the order shown below:
x Display Software Rev
x Controller Software Rev
x Supervisor Software Rev
NOTE: Supervisor software revision will not appear on HMI-1 Control Panels.
4-103
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Choose Set Time and Date by pressing the SELECT key when SET TIME AND DATE is shown by the
Maintenance Menu. The Set Time and Date display appears as shown below.
ENTER HOUR
ON
16:00
OFF
+/- TO CHANGE OK?
- + YES NO
The – and + soft keys are used to change the hour as required. Pressing YES changes the hour to the selected
time and then shows the next Time/Date screen. The screens appear in the order shown below.
x Hour
x Minute
x Date (Day)
x Month
x Year
After the YEAR is set the new time and date are displayed to allow the technician to verify they are correct.
4-104
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-105
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
See Section 3 of this manual for a complete description of each Guarded Access Menu features.
Guarded Access Menu Guarded Access Menu
3 of 4 4 of 4
Language Setup Sensor Configuration (CargoWatch)
Default Language (See Cargo Watch description in Diagnostic Manual)
Enable Lanuages Logging Interval (15 Minutes)
HMI Rev 65xx HMI Rev 66xx HMI Rev 67xx Log Sensor 1
English English English Sensor Logging (On)
Spanish Russian Japanese Independant Sensor #1 Name (Log Sensor 1)
French Polish Out of Range Checking (Off)
German Hungarian Italian Option (Available with sensor 1 only) (Off)
Italian Romanian Sensor Averaging (Off)
Dutch Bulgarian Log Sensor 2
Portuguese Czech Sensor Logging (On)
Greek Danish Independant Sensor #1 Name (Log Sensor 2)
Turkish Swedish Out of Range Checking (Off)
Hebrew Norwegian Sensor Averaging (Off)
Arabic Finnish Log Sensor 3
Access Code Setup Same as Sensor 2
Enter Access Code Log Sensor 4
OptiSet Same as Sensor 2
Temperature Units (F) Log Sensor 5
Setpoint High Limit Zone 1 (80°F) Same as Sensor 2
Setpoint Low Limit Zone 1 (-20°F) Log Sensor 6
Setpoint High Limit Zone 2 (80°F) Same as Sensor 2
Setpoint Low Limit Zone 2 (-20°F) Log Digital In 1
Setpoint High Limit Zone 3 (80°F) Door Open Logging (On)
Setpoint Low Limit Zone 3 (-20°F) Digital Input #1 Name (Digital Input #1)
Number of Limited Setpoints Log Digital In 2
Limited Setpoint # 1 Degrees Same as Digital Input 1
Limited Setpoint # 2 Degrees Log Digital In 3
Limited Setpoint # 3 Degrees Same as Digital Input 1
Limited Setpoint # 4 Degrees Unit Configuration
Fresh | Frozen Range Engine Type (Yanmar 2.1)
Range Limits Compressor Type (Recip)
OptiSet Range Dual Evaporator Configuration (No)
Cycle Sentry (On) How Many Zones in This Unit? (2 or 3)
Continuous (On) Zone 2 Evap Fans Configuration (2 Fans)
Cycle Sentry Null Restart Temperature (5.0°F) Zone 3 Evap Fans Configuration (2 Fans)
Cycle Sentry Door Open Forces (Log Only) Electric Standby Equipped? (No)
Cycle Sentry Run Fans in Null (Off) Electric Heat Option (No)
Continuous Door Open Forces (Log Only) Diesel to Electric Autoswitch Enabled? (No)
Continuous Run Fans in Null (Off) Electric to Diesel Autoswitch Enabled? (No)
Unit Model (SB)
Defrost Motor Equipped? (No)
Fuel Sensor Type (None)
Rear Remote Control (None)
Rear Remote Control Action (Stand By)
Pretrip/Sleep Switch Options (Disable)
4-106
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
NOTE: A warm restart is performed when the Guarded Access menu is exited. The unit is reconfigured so that
any changes that were made from the Guarded Access menu take affect.
The Guarded Access Menu is entered from the last feature of the Maintenance Menu. The unit must not be
running in order to enter the Guarded Access Menu. If the unit is running, enter Interface Board Test from the
Maintenance menu to shut the unit down. Press the EXIT key to return to the Maintenance Menu and continue
scrolling to the end of the Maintenance Menu.
CYCLE SENTRY
ON TEMP F
-8.2 35.8 SET
OFF
0 OFF POINT
The Maintenance Menu is accessed from the first Main Menu screen that appears; either the Language Display or
the Alarms Display. The Alarms Display is shown here. Press and hold both the unlabelled soft key and the Exit
key for 5 seconds.
MAIN MENU
ON
ALARMS
OFF
4-107
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
The first Maintenance Menu feature will appear. Press the NEXT key to scroll to the Maintenance Menu/Set Time
and Date selection. The NEXT key will disappear. Press and hold both the unlabelled soft key and the Exit key
for 5 seconds as shown below.
NOTE - If the unit is running, enter Interface Board Test from the Maintenance menu to shut the unit down. Press
the EXIT key to return to the Maintenance Menu and continue scrolling to the end of the Maintenance Menu.
MAINTENANCE MENU
ON
OFF
If an Access Code is required the operator will be prompted to enter the code. If an Access Code is not enabled
or when the correct security code is entered (4444 always works) the first Guarded Access menu feature will
appear. Press the NEXT and BACK keys to scroll thru the Guarded Access Menu choices. When the desired
feature is shown on the display, press the SELECT key to access it.
PROGRAMMABLE FEATURES
OFF
4-108
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
Service Procedure A02A explains how to read and record the Guarded Access feature settings. Service
Procedure A04A explains how to set the Guarded Access features.
To return to the Standard Display press the EXIT key. NOTE: A warm restart is performed when the Guarded
Access menu is exited.
4-109
02 February 2007
Section 4 – SR-2 SPECTRUM Operation
4-110
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
5-1
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
5-2
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
70 Hourmeter Failure............................................................................................................................................. 79
74 Controller Reset to Defaults ............................................................................................................................ 80
77 Controller EPROM Checksum Failure ............................................................................................................ 80
79 Internal Data Logger Overflow ........................................................................................................................ 81
84 Restart Null........................................................................................................................................................ 82
85 Forced Unit Operation...................................................................................................................................... 83
86 Check Discharge Pressure Sensor................................................................................................................. 84
86 Check Discharge Pressure Sensor................................................................................................................. 85
87 Check Suction Pressure Sensor ..................................................................................................................... 86
90 Electric Overload .............................................................................................................................................. 88
91 Check Electric Ready Input ............................................................................................................................. 89
92 Sensor Grades Not Set .................................................................................................................................... 90
93 Low Compressor Suction Pressure ............................................................................................................... 91
96 Low Fuel Level .................................................................................................................................................. 92
98 Check Fuel Level Sensor ................................................................................................................................. 93
105 Check Receiver Tank Pressure Sol Circuit.................................................................................................. 94
106 Check Purge Valve Circuit............................................................................................................................. 96
107 Check Condenser Inlet Solenoid Circuit...................................................................................................... 98
108 Door Open Timeout ...................................................................................................................................... 100
110 Check Suction Line Solenoid Circuit.......................................................................................................... 101
111 Unit Not Configured Correctly..................................................................................................................... 104
112 Check Remote Fans ..................................................................................................................................... 105
113 Check Electric Heat Circuit.......................................................................................................................... 108
114 Multiple ALarms – Can Not Run.................................................................................................................. 109
117 Auto Switch From Diesel to Electric........................................................................................................... 109
118 Auto Switch From Electric to Diesel........................................................................................................... 110
120 Check Alternator Excite Circuit................................................................................................................... 111
121 Check PWM/Liquid Injection Circuit ........................................................................................................... 113
122 Check Diesel/Electric Circuit....................................................................................................................... 114
127 Setpoint Not Entered.................................................................................................................................... 115
128 Engine Run Time Maintenance Reminder #1............................................................................................. 116
129 Engine Maintenance Run Time Reminder #2............................................................................................. 116
130 Electric Run Time Maintenance Reminder #1............................................................................................ 116
131 Electric Run Time Maintenance Reminder #2............................................................................................ 116
132 Total Unit Run Time Maintenance Reminder #1 ........................................................................................ 116
133 Total Unit Run time maintenance Reminder #2......................................................................................... 116
5-3
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
5-4
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
SR-2 DIAGNOSTICS
Section 5 is devoted to diagnostic routines designed to help the technician quickly identify the cause of a problem
and repair it using the correct tools, information and procedures. It is important that the required procedures be
followed exactly. Failure to do so may result in an incomplete repair.
The remaining material is divided into two sections. The first section suggests corrective actions as a result of
alarm codes. The second section suggests corrective actions as a result of symptoms other than alarm codes.
x Every effort should be made to perform a Pretrip Test on a suspect unit. In almost all cases, the Pretrip Test
will result in one or more alarm codes that will lead you directly to the problem.
x Operators should record all alarm codes in sequence for reference. Alarm codes are displayed in order of
occurrence, with the most recent alarm code displayed last.
x Use Interface Board Test and Service Test Mode as appropriate to verify unit operation
x Be certain all connectors on the interface board, HMI Control Panel and Expansion Module are properly
seated.
x Be certain all harness connectors are properly seated. Be sure to check harness connectors located in the
evaporator section.
x Make sure all programmable features are set to the customer’s specifications before releasing the unit for
service.
5-5
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
The following procedures must be followed when working on units equipped with SR-2 base controllers.
x Never use testers consisting of a battery and a light bulb to test circuits on any solid state control
systems.
x Any time a Return Air or Discharge Air sensor is changed, it must be calibrated using the Sensor
Calibration feature in the Guarded Access Menu.
x Any time the base controller is replaced these Service Procedures must be used:
ELECTROSTATIC DISCHARGE
The following electrostatic precautions must be taken.
x Keep all SR-2 base controllers/interface boards, expansion modules, and HMI control panels in anti-static
bags at all times.
PHYSICAL PROTECTION
x Protect any defective SR-2 base controllers and HMI control panels from physical damage by placing them in
the shipping carton supplied with the replacement. They will be returned for failure analysis and possible re-
manufacture.
5-6
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Every effort should be made to perform a Pretrip Test on a unit suspected of having a defect. In almost
all cases, the Pretrip Test will result in one or more alarm codes that will lead you directly to the problem.
ALARM TYPES
Alarms may be one of four types as shown below.
Log Alarms
Log Alarms are indicated for 60 seconds each time the unit is turned on. This level of alarm serves as a notice to
take corrective action before a problem becomes severe. Maintenance items such as maintenance hourmeter
time-outs are log alarms. The Temperature Watch screen is not disabled if only log alarm(s) are active.
When the unit is turned on the display will show the Thermo King Logo and then the “Configuring System”
message. If log alarm(s) are present the Log Alarm notice will appear on the display for 60 seconds as shown
below. The remote indicator alarm light (if installed) will also be on during this period. The Standard Display will
appear and the remote indicator alarm light will go off after 60 seconds.
Check Alarms
Check Alarms are indicated by a steady alarm icon at the side of the display. If the alarm is specific to a zone
then a smaller alarm icon will appear next to the affected zone. This level of alarm serves as a notice to take
corrective action before a problem becomes severe. The unit will run with check alarms but some features and
functions may be inhibited. The Temperature Watch screen is disabled if a check alarm is active.
5-7
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
NOTE: If the Restart After Shutdown feature in the Guarded Access Menu is set for CONTINUOUS, then
an unlimited number of restart attempts are allowed.
Unit level shutdown alarms will force the unit into shutdown. The unit will remain in shutdown until the shutdown
alarm is manually cleared. Exceptions are some engine and electric shutdown alarms that become log alarms
when switched to the alternate operating mode (diesel to electric or electric to diesel). The Temperature Watch
screen is disabled if a unit level shutdown alarm is active.
5-8
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
In the same manner, if a shutdown alarm occurs that affects only electric mode operation and the unit is switched
to diesel, the electric mode shutdown alarm becomes a diesel mode log alarm to allow diesel mode operation. If
the unit is switched back to electric mode, the alarm reverts to an electric mode shutdown alarm and prevents unit
operation.
5-9
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
SPECIAL CONSIDERATIONS
The following sensor alarm codes can only be cleared from the Guarded Access Menu. The CLEAR soft key will
not appear if the alarms are displayed from the Main Menu or the Maintenance Menu.
x Alarm Code 03 Check (Control) Return Air Sensor for all zones.
x Alarm Code 04 Check (Control) Discharge Air Sensor for all zones.
If the Limited Alarm Restarts feature is enabled the following additional alarm codes may only be cleared from the
Guarded Access Menu. If this is the case, the CLEAR soft key will not appear if the alarms are displayed from the
Main Menu or the Maintenance Menu. See the Limited Alarm Restarts feature in Section 3 for details.
x Alarm Code 10 High Discharge Pressure
x Alarm Code 23 Cooling Cycle Fault
x Alarm Code 24 Heating Cycle Fault
x Alarm Code 32 Refrigeration Capacity Low
5-10
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
This sensor circuit is a two wire circuit and is polarity sensitive. The Zone 1 sensor is connected to the base
controller. Zone 2 and Zone 3 sensors are connected to the expansion module. The CTP (+) wire connects to
the blue sensor wire. The CTN (-) wire connects to the brown sensor wire. The Zone 1 sensor wires are routed
in the Sensor Harness. The Zone 2 and Zone 3 sensor wires are located in the Expansion Module Harness. The
Zone 1 sensor is hard-wired to the harness. See the Schematic Diagram and Wiring Diagram for connectors and
pin numbers for each zone sensor.
Considerations
1. Sensors should be positioned to minimize the potential for moisture entry where the wires enter the
sensor shell. Mount sensors with the barrel up and the wires down wherever possible.
2. The sensors located in remote evaporators have two harness connections. One connection point is
located in the host evaporator section. The second connection is located in the remote evaporator. If
remote zone alarm code is present, inspect both connectors for contamination and proper connection,
(e.g. pushed or damaged pins).
5-11
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the sensor reading is under -50°F (-46°C) for 10 seconds then Alarm Code 02 is set as a check alarm.
The sensor reading will display dashes [ - - - ] and may return to normal. The -50°F (-46°C) check is
ignored when the zone is in a Low Evaporator Coil Temperature Demand Defrost. This condition is
termed a “hard” sensor failure.
3. If the differential between the coil and other sensors is too large when Alarm Code 02 is cleared then
Alarm Code 02 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This condition is
termed a “soft” sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F (-46°C) then
Alarm Code 02 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This condition is
termed a “soft” sensor failure.
5. If a valid sensor reading is detected in a zone that has not been configured then Alarm Code 02 is set as
a check alarm and Alarm Code 111 Unit Not Configured Correctly is set as a log alarm.
If the alarm is set by Condition #5 above, Alarm Codes 02 and 111 will clear automatically if the unit configuration
is changed to allow the sensor in that zone or if the sensor is no longer exhibiting a valid reading.
Programmable Settings
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
5-12
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the problem reoccurs, check the sensor connector as shown in Service Procedure D01A.
If all or many of the Sensor Codes (02, 03, 04, 05, 06, 11, 12 and 13) are set
1. Be sure the 35 pin base controller sensor connector J3 is securely attached.
3. Be sure the CAN connector on the expansion module is connected securely (Zone 2 and Zone 3 specific
alarms).
5-13
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
This sensor circuit is a two wire circuit and is polarity sensitive. The RTP (+) wire connects to the blue sensor
wire. The RTN (-) wire connects to the brown sensor wire. The Zone 1 sensor is connected to the base
controller. Zone 2 and Zone 3 sensors are connected to the expansion module. The Zone 1 sensor wires are
routed in the Sensor Harness. The Zone 2 and Zone 3 sensor wires are located in the Expansion Module
Harness. The Zone 1 sensor is hard-wired to the harness. See the Schematic Diagram and Wiring Diagram for
connectors and pin numbers for each zone sensor.
Considerations
1. The unit normally controls on return air temperature. If a problem occurs with the return air sensor, the
unit will switch to Discharge Air Control. Alarm Code 03 Check Return Air Sensor and Alarm Code 11
Unit Controlling on Alternate Sensor will be set.
2. Sensor grades must be correctly set to the actual grade of the sensor installed. Failure to do so may
result in nuisance sensor alarm codes.
3. Sensors should be positioned to minimize the potential for moisture entry where the wires enter the
sensor shell. Mount sensors with the barrel up and the wires down wherever possible.
4. The sensors located in remote evaporators have two harness connections. One connection point is
located in the host evaporator section. The second connection is located in the remote evaporator. If
remote zone alarm code is present, inspect both connectors for contamination and proper connection,
(e.g. pushed or damaged pins).
5-14
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the sensor reading is under -50°F (-46°C) for 10 seconds then Alarm Code 03 is set as a check alarm.
The sensor reading will display dashes [ - - - ] may return to normal. This condition is termed a “hard”
sensor failure.
3. If the differential between the return air temperature and other temperature sensors is too large when
Alarm Code 03 is cleared then Alarm Code 03 and Alarm Code 13 Sensor Calibration Check are set as
check alarms. This condition is termed a “soft” sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F (-46°C) then
Alarm Code 03 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This condition is
termed a “soft” sensor failure.
5. If the sensor grade is set to 5H then Alarm Code 03 and Alarm Code 92 Sensor Grades Not Set are set
as check alarms.
6. If a valid sensor reading is detected in a zone that has not been configured then Alarm Code 03 is set as
check alarm and Alarm Code 111 Unit Not Configured Correctly is set as a log alarm.
If the alarm is set by Condition #5 above, Alarm Code 92 will clear automatically if the sensor grade is changed
from 5H. If the sensor grade remains 5H, Alarm Code 92 can not be cleared.
If the alarm is set by Condition #6 above, Alarm Codes 03 and 111 will clear automatically if the unit configuration
is changed to allow the sensor in that zone or if the sensor is no longer exhibiting a valid reading.
Programmable Settings
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
5-15
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Alarm Code 03 and Alarm Code 13 (Sensor drifted or was reading erratically)
1. Review the ServiceWatch data logger and check the senor reading at the time the alarm was set. Also,
review the history to see if previous alarm codes exist that would indicate an intermittent problem. If the
sensor appears to have read incorrectly, it should be replaced.
2. Be sure the sensor grades are set to the actual sensor grade.
4. If the problem reoccurs, check the sensor connector as shown in Service Procedure D01A.
If all or many of the Sensor Codes (02, 03, 04, 05, 06, 11 and 12) are set
1. Be sure the 35 pin base controller sensor connector J3 is connected securely.
3. Be sure the CAN connector on the expansion module is connected securely (Zone 2 and Zone 3 specific
alarms).
5-16
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
This sensor circuit is a two wire circuit and is polarity sensitive. The DTP (+) wire connects to the blue sensor
wire. The DTN (-) wire connects to the brown sensor wire. The Zone 1 sensor is connected to the base
controller. Zone 2 and Zone 3 sensors are connected to the expansion module. The Zone 1 sensor wires are
routed in the Sensor Harness. The Zone 2 and Zone 3 sensor wires are located in the Expansion Module
Harness. The Zone 1 sensor is hard-wired to the harness. See the Schematic Diagram and Wiring Diagram for
connectors and pin numbers for each zone sensor.
Considerations
1. Sensor grades must be correctly set to the actual grade of the sensor installed. Failure to do so may
result in nuisance sensor alarm codes.
2. Sensors should be positioned to minimize the potential for moisture entry where the wires enter the
sensor shell. Mount sensors with the barrel up and the wires down wherever possible.
3. The sensors located in remote evaporators have two harness connections. One connection point is
located in the host evaporator section. The second connection is located in the remote evaporator. If
remote zone alarm code is present, inspect both connectors for contamination and proper connection,
(e.g. pushed or damaged pins).
5-17
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the sensor reading is under -50°F (-46°C) for 10 seconds then Aalrm Code 04 is set as a check alarm.
The sensor reading will display dashes [ - - - ] may return to normal. This condition is termed a “hard”
sensor failure.
3. If the differential between the discharge and other sensors is too large when Alarm Code 04 is cleared
then Alarm Code 04 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This
condition is termed a “soft” sensor failure.
4. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F (-46°C) then
Alarm Code 04 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This condition is
termed a “soft” sensor failure.
5. If the sensor grade is set to 5H then both Alarm Code 04 and Alarm Code 92 Sensor Grades Not Set are
set as check alarms.
6. If a valid sensor reading is detected in a zone that has not been configured then Alarm Code 04 is set as
a check alarm and Alarm Code 111 Unit Not Configured Correctly is set as a log alarm.
If the alarm is set by Condition #5 above, Alarm Code 92 will clear automatically if the sensor grade is changed
from 5H. If the sensor grade remains 5H, Alarm Code 92 can not be cleared.
If the alarm is set by Condition #6 above, Alarm Codes 04 and 111 will clear automatically if the unit configuration
is changed to allow the sensor in that zone or if the sensor is no longer exhibiting a valid reading.
Programmable Settings
This is a graded sensor. The sensor grade must be correctly set in the Guarded Access Menu.
5-18
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Alarm Code 04 and Alarm Code 13 (Sensor drifted or was reading erratically)
1. Review the ServiceWatch data logger and check the sensor reading at the time the alarm was set. Also,
review the history to see if previous alarm codes exist that would indicate an intermittent problem. If the
sensor appears to have read incorrectly, it should be replaced.
2. Be sure the sensor grades are set to the actual sensor grade.
4. If the problem reoccurs, check the sensor connector as shown in Service Procedure D01A.
If all or many of the Sensor Codes (02, 03, 04, 05, 06, 11 and 12) are set
1. Be sure the 35 pin base controller sensor connector J3 is connected securely.
3. Be sure the CAN connector on the expansion module is connected securely (Zone 2 and Zone 3 specific
alarms).
5-19
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
This sensor circuit is a two wire circuit and is polarity sensitive. The ATP (+) wire connects to the blue sensor
wire. The ATN (-) wire connects to the brown sensor wire. The wires are routed in the Sensor Harness and the
sensor is hardwired to the harness. See the Schematic Diagram and Wiring Diagram for connectors and pin
numbers for the ambient sensor.
Considerations
1. Sensors should be positioned to minimize the potential for moisture entry where the wires enter the
sensor shell. Mount sensors with the barrel up and the wires down wherever possible.
2. If the sensor reading is under -50°F (-46°C) for 10 seconds then set alarm code 05 as a check alarm.
The sensor reading will display dashes [ - - - ] may return to normal. This condition is termed a “hard”
sensor failure.
3. If the sensor reading is erratic over time but does not go above 200°F (93°C) or below -50°F (-46°C) then
Alarm Code 05 and Alarm Code 13 Sensor Calibration Check are set as check alarms. This condition is
termed a “soft” sensor failure.
5-20
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Alarm Code 05 and Alarm Code 13 (Sensor drifted or was reading erratically)
1. Review the ServiceWatch data logger and check the sensor reading at the time the alarm was set. Also,
review the history to see if previous alarm codes exist that would indicate an intermittent problem. If the
sensor appears to have read incorrectly, it should be replaced.
3. If the problem reoccurs, check the sensor connector as shown in Service Procedure D01A.
If all or many of the Sensor Codes (02, 03, 04, 05, 06, 11 and 12) are set
1. Be sure the 35 pin base controller sensor connector J3 is connected securely.
5-21
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
This sensor circuit is a two wire circuit and is polarity sensitive. The WTP (+) wire connects to the blue sensor
wire. The WTN (-) wire connects to the brown sensor wire. The wires are routed in the Sensor Harness. The
sensor is connected to the harness with a Deutsch connector. See the Schematic Diagram and Wiring Diagram
for connectors and pin numbers for the coolant temperature sensor.
Considerations
1. Connectors should be positioned to minimize the potential for moisture entry where the wires enter the
connector shell.
2. If the sensor reading is under -50°F (-46°C) for 10 seconds then alarm code 06 is set as a check alarm.
The sensor reading will display dashes [ - - - ] may return to normal.
5-22
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If all or many of the Sensor Codes (02, 03, 04, 05, 06, 11 and 12) are set
1. Be sure the 35 pin base controller sensor connector J3 is connected securely.
5-23
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Component Description and Location
The flywheel sensor is a proximity sensor that generates a pulse as each flywheel tooth passes the sensor. The
base controller counts these pulses and performs the math necessary to convert the pulses into engine rpm. The
flywheel sensor is located on the flywheel housing above the starter.
Circuit Description
The flywheel sensor circuit is a two wire circuit and is not polarity sensitive. The FS1 wire connects the interface
board 36 pin connector J7 pin 35 to one side of the flywheel sensor. The FS2 wire connects the interface board
36 pin connector J7 pin 36 to the other side of the flywheel sensor. The sensor wires are routed in the Main
Harness.
2. If the alternator frequency is greater than 100 Hz and oil pressure input is high but the RPM sensor
indicates less than 300 RPM for 4 seconds then Alarm Code 07 is set as a check alarm.
3. If the RPM is less than 40 during an engine start attempt then Alarm Code 07 is set as a check alarm.
5-24
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Disconnect the sensor wires at the flywheel sensor. Check the ac voltage at the sensor with the engine
running. If a small ac voltage (greater than 1.0 VAC) is not present check the sensor adjustment. Turn
the unit off, loosen the lock nut and turn the sensor in until it contacts the flywheel. Back the sensor out ½
turn and tighten the lock nut. Start the unit and recheck the sensor voltage. If more than 1.0 VAC is still
not present the sensor is defective and must be replaced.
2. If ac voltage is present, disconnect the flywheel harness at the base controller and disconnect the
flywheel sensor. Using a Fluke meter set for ohms, check for shorts to chassis ground on the FS1 and
FS2 wires. If a short exists, examine the wiring harness for chaffed areas and repair, as required.
3. If no shorts to chassis ground exist, connect the FS1 wire to the FS2 wire at the sensor. Check continuity
from FS1 to FS2 at the 36 pin interface board connector. The circuit should measure less than 1 ohm. If
the circuit is open, check the harness using the wiring diagram for the unit.
4. Disconnect the FS1 and FS2 connections and check the flywheel sensor continuity. The resistance
between the flywheel sensor terminals should be approximately 250 to 300 ohms. Also check from each
flywheel sensor terminal to ground. If either terminal is shorted to ground the flywheel sensor is defective.
5-25
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Check evaporator coil sensor operation, as shown in Alarm Code 02 Check Evaporator Coil Sensor. If
the evaporator coil sensor reads high due to a defective sensor Alarm Code 09 High Evaporator
Temperature may be set.
3. The sensors located in remote evaporators have two harness connections. One connection point is
located in the host evaporator section. The second connection is located in the remote evaporator. If a
remote zone alarm code is present, inspect both connectors for contamination and proper connection,
(e.g. pushed or damaged pins).
5-26
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
The high pressure cutout circuit is a two wire circuit. The HPCO wire connects the interface board 36 pin
connector J7 pin 17 to one side of the high pressure cutout switch. The PHPC wire connects the interface board
36 pin connector J7 pin 18 to the other side of the high pressure cutout switch. The switch is not polarity
sensitive. The switch wires are routed in the Main Harness. The switch is connected to the sensor harness with
a Deutsch connector.
If continuous restarts are enabled, a shutdown alarm is not set after 2 attempts. The temporary shutdown
period is 60 minutes if continuous restarts are enabled. Code 84 restart null is set along with the code 10
alarm to indicate the unit is in a temporary shutdown mode.
If restarts are disabled, the alarm will be set as a shutdown on the first occurrence.
2. If the discharge pressure transducer exceeds a pre-set value and the discharge pressure transducer is
not failed then alarm code 10 is set as a prevent alarm. Two restart attempts will be made to allow
continued operation at temporarily reduced performance. If, at the end of the two attempts full
performance is not possible, the alarm is set as a Shutdown alarm. The temporary shutdown period is 15
minutes Code 84 restart null is set along with the code 10 alarm to indicate the unit is in a temporary
shutdown mode.
If continuous restarts are enabled, a shutdown alarm is not set after 2 attempts. The temporary shutdown
period is 60 minutes if continuous restarts are enabled. Code 84 restart null is set along with the code 10
alarm to indicate the unit is in a temporary shutdown mode.
If restarts are disabled, the alarm will be set as a shutdown on the first occurrence.
2. The alarm will clear automatically at the conclusion of a successful prevent routine.
5-27
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the refrigeration system for high discharge pressure and correct as required.
2. Check the High Pressure Cutout Switch for proper operation (closed under normal conditions). Check the
switch for excessive resistance. The nominal switch resistance is less than 1 ohm.
4. Check the discharge pressure transducer for correct and accurate readings.
5. Check the refrigeration system valves for correct operation. A fault that prevents refrigerant flow from the
system high side to the system low side may create high discharge pressure.
6. Review the ServiceWatch download in technician level view. The associated alarm data will show the
status of the HPCO switch.
5-28
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
See Alarm Codes indicated above.
If Alarm Code 12 Sensor Shutdown is set then Alarm Code 11 will be auto cleared.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Determine the cause for Alarm Codes 03. Proceed as shown for that alarm code.
5-29
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
See Alarm Codes indicated above.
2. If more than one zone is running, a zone shutdown alarm will be set for the affected zone but the unit can
continue to run as required by unit or other zone demands. The affected zone will be forced to zone null.
3. If the affected zone setpoint is changed to a frozen range setpoint, the zone will remain in zone shutdown.
2. If the affected zone setpoint is changed to a fresh range setpoint, the zone check alarm will become a
zone shutdown alarm and the affected zone will be forced to zone null.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Determine the cause for sensor Alarm Codes 03 and 04. Proceed as shown for those alarm codes.
5-30
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
See Alarm Codes indicated above.
2. Return and Discharge Sensor Check If sensors drift apart then set Alarm Code 65 Abnormal
Temperature Differential. If the return and discharge sensors are reading erratically over a specified time
then Alarm Code 13 will be set as a check alarm along with the alarm code for the erratic sensor (Alarm
Code 03 or Alarm Code 04). If the erratic sensor cannot be determined and the temperature differential is
greater than 35°F then Alarm Code 13 and Alarm Code 65 Abnormal Temperature Differential will be set.
3. Return, Discharge, Evaporator Coil and Ambient Sensor Check If one or more of the return, discharge,
evaporator coil or ambient sensors are reading erratically over a specified time then Alarm Code13 will be
set along with the alarm code for the erratic sensor (Alarm Code 02, Alarm Code 03, Alarm Code 04 or
Alarm Code 05).
5-31
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Determine which sensor Alarm Codes (02, 03, 04, or 05) are present. Proceed as shown for that Alarm Code.
A “Hard Failure” is defined by an out of range sensor reading, typically caused by an open or shorted sensor,
connector, or harness conductor. The sensor display will show dashes if a hard failure occurs. If this occurs, only
the alarm code for that sensor will be set (such as Alarm Code 03 if the return air sensor failed). Note: The
controller may not be showing dashes for the sensor reading, but the alarm will be active when the unit is
inspected. If a sensor alarm code is set, a failure did occur at some point. Checking a ServiceWatch data logger
download (if available) may indicate when the hard failure occurred.
A “Soft Failure” is defined by erratic operation or sensor drift that exceeds acceptable tolerances (sensor is out of
calibration). If this occurs, the alarm code for the suspect sensor will be set along with Alarm Code 13. This
indicates a potential problem that may not be immediately apparent, and that a hard failure as defined above did
not occur. Note: Alarm Code 13 alarm is driver clearable, while sensor Alarm Codes 03 and 04 are Guarded
Access clearable only. If the unit has only Alarm Code 03 or 04 set when inspected, then Alarm Code 03 or 04
may have been originally set with Alarm Code 13. Checking a ServiceWatch data logger download (if available)
may indicate when the failure occurred.
If Alarm Code 13 occurs with Alarm Code 65, it indicates that a potential problem may exist, but the suspect
sensor or problem cannot be determined. This condition can be caused by a sensor “Soft Failure” or may be an
indication of an airflow problem. See Alarm Code 65 Abnormal Temperature Differential for additional details.
5-32
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
Power to the intake air heater is supplied by the H circuit. The associated interface board fuse is F5. Intake air
heater current is monitored by the Interface Board shunt.
2. If the current draw is out of specification during a Pretrip Test then Alarm Code 15 is set as a check
alarm. Minimum preheat current on the Yanmar engine is 63 amps. Maximum preheat current on
Yanmar engine is 80 amps.
3. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 15 is set as a shutdown alarm.
Diagnostic Procedure
1. Check the operation of the preheat circuit using Interface Board Test Mode. LED 3 should light. Current
draw should be approximately 70 amps.
2. If the current draw is zero, check for an open heater, blown fuse F5 or defective K2 Preheat Relay.
3. If the current draw is low check for low battery voltage or high circuit resistance. The intake air heater
nominal resistance is 0.0433 ohms.
4. If the current draw is in excess of 80 amps, check for a shorted intake air heater. The intake air heater
nominal resistance is 0.0433 ohms.
5. Check for battery voltage at the intake air heater when the preheat circuit is energized. The voltage
should be above 11.2 volts. If the voltage is low, check the entire preheat circuit for excessive resistance
due to burned preheat relay contacts or loose or corroded connections. Be sure all connections are
secure.
5-33
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
An Alarm Code 17 that follows an Alarm Code 20/84 Failed to Start will be set as a shutdown alarm.
If Alarm Code 17 follows an Alarm Code 63 alarm clear, only one crank attempt will be made.
How Alarm is Cleared
The alarm is cleared manually.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
3. Check the operation of the starter circuit by forcing an engine start in Continuous mode. LED 25 should
light indicating the starter motor is energized and the engine should start.
4. Check the 8S circuit for a pushed pin, loose pin crimp or broken wire.
5. Check the High Current Harness 8S wire with an ohmmeter for continuity, per Service Procedure H04A.
7. If a Model 50 electric standby unit, check for a failed clutch or seized electric motor.
5-34
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If continuous restarts are enabled, a shutdown alarm is not set after 2 attempts. .The temporary
shutdown period is 60 minutes if continuous restarts are enabled. Code 84 restart null is set along with
the code 18 alarm to indicate the unit is in a temporary shutdown mode. If restarts are disabled, the
alarm will be set as a shutdown on the first occurrence.
2. If the coolant temperature is high as determined by the coolant temperature sensor and the coolant level
sensor is indicating low coolant level then alarm Code 18 is set as a shutdown alarm.
2. The alarm will clear automatically at the conclusion of a successful prevent routine.
Considerations
This alarm becomes a log alarm if the unit is switched to electric mode. Alarm Code 18 alarm conditions will be
monitored while the unit is operating in electric mode, and will auto-clear when the engine coolant temperature is
reduced to a safe value.
Diagnostic Procedure
1. Check the engine water temperature using the Gauge Menu. If the temperature is above 220°F (104°C),
check the engine cooling system to determine the cause of overheating.
2. Check the engine coolant level. Bleed air from the cooling system if necessary. CAUTION: Do not
open the cap on the expansion tank when the coolant is hot!
5-35
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
The low oil pressure switch circuit is a single wire circuit. The 20B wire connects the interface board 36 pin
connector J7 pin 28 to the low oil pressure switch. The switch is not polarity sensitive and is closed on low oil
pressure. This applies chassis ground to the base controller. The switch wire is routed in the Main Harness.
Circuit Description
See Alarm Code 31 Check Oil Pressure Switch
Considerations
This alarm becomes a log alarm if the unit is switched to electric mode. It will again become a shutdown alarm if
the unit is switched to diesel mode.
5-36
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
3. Display the oil pressure when the unit is running, using the Gauge menu. The oil pressure should be
[OK]. If not, the switch may be stuck closed or the switch circuit may be shorted.
4. Verify the oil pressure switch is open with good oil pressure and closed with low oil pressure. The oil
pressure switch should be closed when the engine is not running and open when the engine is running.
Confirm using an ohmmeter.
5. Check the voltage of the 20B-01 wire at the 36 pin interface board connector J7 pin 28. Battery volts
should be present when the engine is running.
6. Check the 20B wire in the Main Harness with an ohmmeter for continuity per Service Procedure H04A
7. Connect an external oil pressure gauge and confirm that adequate oil pressure (20 psig or above) is
present when the unit is running.
5-37
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If the engine coolant sensor temperature is greater than 10qF, (-12qC), the crank timer on the first start
attempt is 15 seconds. The crank timer on the second start is 15 seconds.
If the engine coolant temperature is less than 10qF (-12qC), the crank timer on the first start attempt is 6
seconds. The crank timer on the second start is 30 seconds.
Notes:
If Alarm Code 20 follows an Alarm Code 17/84 Failed to Crank then alarm code 20 will be set as a shutdown
alarm.
If Alarm Code 20 follows an Alarm Code 63 alarm clear, only one crank attempt will be made.
Considerations
This alarm becomes a log alarm if the unit is switched to Electric mode.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Check fuel solenoid, fuel pump, and fuel system electrically, mechanically and for fuel flow restrictions or
blockages.
6. Verify the intake air heater is operating properly, using Interface Board Test Mode.
7. If a Model 50 electric standby unit, check for a failed clutch or seized electric motor.
5-38
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
1. This is a Prevent alarm. A second occurrence of this alarm will be set as Alarm Code 23 Cooling Cycle
Fault shutdown alarm.
2. If restarts are disabled, Alarm Code 23 will be set as a shutdown alarm on the first occurrence of the
alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling, caused by a blocked air flow path, may generate this code.
6. Check the zone hot gas valve. A defective valve that does not return to the cooling position may cause
this alarm.
5-39
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
1. This is a Prevent alarm. A second occurrence of this alarm will be set as Alarm Code 24 Heating Cycle
Fault shutdown alarm if the zone is operating in the Fresh setpoint range.
2. The alarm is set as a check level alarm if the zone is operating in the frozen setpoint range. Heat
operation is locked out if an Alarm Code 24 is set in a zone that is operating in the frozen setpoint range.
3. If restarts are disabled, Alarm Code 24 will be set as a shutdown alarm on the first occurrence of the
alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling, caused by a blocked air flow path, may generate this code.
6. Check the zone hot gas valve. A defective valve that does not shift to the heating position may cause this
alarm.
5-40
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If restarts are disabled Alarm Code 24 will be set as a shutdown alarm on the first occurrence of the alarm.
Considerations
1. This is a Shutdown alarm. It is typically preceded by Alarm Code 21 Cooling Cycle Check alarm.
2. If restarts are disabled, Alarm Code 23 will be set as a shutdown alarm on the first occurrence of the
alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling, caused by a blocked air flow path, may generate this code.
6. Check the zone hot gas valve. A defective valve that does not return to the cooling position may cause
this alarm.
5-41
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If restarts are disabled Alarm Code 24 will be set as a shutdown alarm on the first occurrence of the alarm.
Considerations
1. This is a Shutdown alarm. It is typically preceded by Alarm Code 22 Heating Cycle Check alarm.
2. If restarts are disabled Alarm Code 24 will be set as a shutdown alarm on the first occurrence of the
alarm.
3. This alarm cannot be set in a zone operating in the frozen setpoint range. See the Alarm Code 22
description.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling, caused by a blocked air flow path, may generate this code.
6. Check the zone hot gas valve. A defective valve that does not shift to the heating position may cause this
alarm.
5-42
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the engine or electric motor is running, and the battery voltage is greater than 16.0 volts for 3 minutes
then Alarm Code 25 is set as a Shutdown alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Start the engine or electric motor and check the battery voltage and amperage, using the Gauge Display
in the Maintenance Menu. The voltage should be greater than 13.2 volts but less than 16 volts. Current
flow should be greater than –1.0 amps. Test and repair charging system as required.
4. Check the excitation voltage at the alternator. Excitation voltage should be equal to the battery voltage.
5. Check the operation of the Alternator Excite Relay using Interface Board Test Mode. Be sure the
Alternator Excite LED 18 lights.
6. Check the sense voltage at the alternator. Sense voltage should be equal to the battery voltage
8. If the unit is equipped with a Prestolite alternator, verify that fuse F4 is in place on the interface board and
is not open. Units equipped with a Bosch or a Thermo King alternator should not have fuse F4 installed
on the interface board.
5-43
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
If all configured zones have an Alarm Code 26 set, then a unit level Alarm Code 32 Refrigeration Capacity Low
will be set. See the description for Alarm Code 32 Refrigeration Capacity Low for details.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling, caused by a blocked air flow path, may generate this code.
5-44
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. This is a normal alarm any time the Pretrip Test is terminated before the completion of all tests.
2. Proceed with the corrective actions for any alarm codes that occurred.
3. After repairs, repeat the Pretrip Test. See Section 4 for details.
4. If only Alarm Code 28 is set, the unit may have been turned off during a Pretrip Test, or the test may have
been interrupted by a communications request. Clear the alarm and repeat the Pretrip Test.
5-45
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
1. Power for the Zone 1 damper circuit requires the run relay to be energized.
2. The damper gear motor requires the use of the appropriate interface board with the damper gear motor
circuitry.
DE Unit Only: DE units feature a split evaporator coil and two defrost dampers to serve two separate zones.
Zone 1 is on the street side and Zone 2 is on the curb side. They are both located in the discharge air streams at
the top of the unit and each is operated by a separate damper solenoid and linkage.
Circuit Description
The Damper Solenoid circuit is a two wire circuit. The Damper Solenoid is energized by Relay K4 and Fuse F6
on the Interface Board. The 29 wire applies 12 VDC to one side of the Damper Solenoid to energize the solenoid.
The CHD wire connects the other side of the solenoid to chassis ground at the ground plate near the unit battery.
The solenoid is not polarity sensitive, but the suppression diode must be installed with the bar end of the diode
toward the 29 wire. The wires are routed in the Main Harness.
DE Unit Only: DE units feature a split evaporator coil and two defrost dampers to serve two separate zones.
Zone 1 is on the street side and Zone 2 is on the curb side. The Zone 1 damper circuit is as described above.
The Zone 2 damper circuit is the same but is energized by the expansion module fan motor output that would
otherwise be used by Zone 2 fans.
5-46
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. Zone 2 DE only If the zone is configured with a damper solenoid and current does not return to less than
0.5 amps 3 seconds after the solenoid is de-energized then Alarm Code 29 is set as a check alarm.
3. If during a Pretrip Test the zone is configured with a damper solenoid and current is not between 2 to 10
amps when the solenoid is energized then Alarm Code 29 is set as a check alarm.
4. If during a Pretrip Test the zone is configured with a damper solenoid and current does not return to less
than or equal to 0.5 amps when de-energized then Alarm Code 29 is set as a shutdown alarm.
5. If during a Pretrip Test the unit is equipped with a damper gear motor and the motor travel timer exceeds
its limit and the motor stall current has not been exceeded then Alarm Code 29 is set as a check alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the damper door circuit using Interface Board Test Mode. Be sure the damper
relay LED 4 lights (for Zone 1). Fan output 1 is used for the Zone 2 damper on DE units. (Damper
Solenoid Only)
2. Use the HMI Control Panel amps gauge to check the current drawn by the damper solenoid while
operating the damper door with Interface Board Test Mode. The current draw should be approximately 6
amps. (Damper Solenoid Only)
3. Energize the damper solenoid using Interface Board Test Mode and check for battery voltage on the 29
circuit. If voltage is present and no current was measured in the step above replace the damper solenoid.
(Damper Solenoid Only)
5-47
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Component Description and Location
The defrost damper door is located in the discharge air stream at the top of the unit. It is closed during defrost to
prevent warm air from being circulated over the load. The Damper Gear Motor is mounted just outside the
discharge plenum and is connected to the damper door by means of mechanical linkage.
Circuit Description
The damper motor circuit is a two wire circuit. The GM- (black) wire is connected to one side of the damper gear
motor and the GM+ (red) wire is connected to the other side of the gear motor. The motor wires are routed in the
Main Harness. The Damper Heater wires 8F-01 and CH-19 are also routed in the Main Harness.
Considerations
1. The damper gear motor requires an interface board equipped with damper motor provisions. See Section
7 Information for Service Part Numbers.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the damper door gear motor circuit, using Interface Board Test Mode. Be sure
LED31 Damper Door Open and LED32 Damper Door Close light as appropriate.
2. The initial (breakaway) current draw occurs over a very short period of time and cannot be accurately
measured. Once the motor is running the current draw should not exceed 0.8 amps.
3. Check for ice buildup between the damper blade and damper housing. Breaking the ice may cause
excessive current draw.
4. Check the door and linkage for binding, ice or other restrictions to proper door operation.
5-48
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
See alarm code 19 circuit description.
2. If the unit is in diesel mode but is not running, the oil level is not good, and the oil pressure switch is
indicating oil pressure for more than 30 seconds then Alarm Code 31 Check Oil Pressure Switch is set as
a Shutdown alarm. The shutdown alarm becomes a log alarm if the unit is switched to electric mode.
3. If the unit is running in electric mode and the oil pressure switch is indicating oil pressure then Alarm
Code 31 Check Oil Pressure Switch is set as a Log alarm.
Considerations
If this alarm is set as a Shutdown alarm in diesel mode operation, it becomes a log alarm if unit is switched to
electric mode operation.
If the alarm exists in electric mode and the unit is switched to diesel, either condition #1 or #2 in the “How Alarm is
Set” section apply.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Display the oil pressure when the unit is not running, using the Gauge menu. The oil pressure should
show [LOW]. If not, the switch may be stuck open or the switch circuit may be open.
2. Check the 20B wires in the Main Harness for continuity with an ohmmeter as shown by Service
Procedure H04A
5-49
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
NOTE: Alarm Code 26 Check Refrigeration Capacity must be set in all zones prior to the unit level Alarm Code
32 being set.
If restarts are disabled Alarm Code 32 will be set as a shutdown alarm on the first occurrence of the alarm.
Considerations
Alarm Code 32 requires that Alarm Code 26 Check Refrigeration Capacity has been set in all active zones.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check temperature differential by displaying the temperature differential, or by checking the difference
between the zone return and discharge air temperature sensors.
5. Check for proper air flow. Short cycling caused by a blocked air flow path may generate this code.
5-50
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If during a Pretrip Test the engine low speed RPM is not within the correct range for the unit configuration
then Alarm Code 33 is set as a check alarm.
NOTE: For engine RPM speeds see the Maintenance Manual for the unit.
Considerations
Only checked during a Pretrip Test.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check and adjust high speed, as shown in the Maintenance Manual for the unit.
2. Check and adjust low speed, as shown in the Maintenance Manual for the unit.
4. Verify the selected High and Low speeds match the programmed unit configuration.
NOTE: Use Service Test Mode to run the unit in high speed cool and low speed cool. See Section 4 for
details.
5-51
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
The K1 Run Relay, LED 6, and fuse F25 are located on the Interface Board. The 7K circuit is only on the SR-2
interface board and base controller.
When the Run Relay is energized, 8 power is supplied to the 7K circuit. This alarm code indicates that 7K circuit
digital input is not present when the Run Relay output is energized or that 7K power is present when the Run
Relay is de-energized.
How Alarm is Set
1. If the Run Relay is energized and the 7K input is low at the base controller then Alarm Code 35 is set as a
Shutdown Alarm.
2. If the Run Relay is not energized and the 7K input is high at the base controller for 4 seconds then Alarm
Code 35 is set as a Shutdown Alarm.
3. If current draw is not between 0.4 to 5 amps when the Run Relay is energized during a Pretrip Test Amps
Check then Alarm Code 35 is set as a shutdown alarm.
4. If current draw is not less than 0.5 amps when the Run Relay is de-energized during a Pretrip Test Amps
Check then Alarm Code 35 is set as a shutdown alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
3. Check the operation of the K1 Run Relay circuit using Interface Board Test Mode.
4. Check to be sure the High Pressure Cutout Switch is closed (HPCO and PHPCO circuits).
5. Check the voltage of the HPCO wire at the HPCO switch. Battery volts should be present when the unit
is turned on.
6. Review the ServiceWatch download in technician level view. The associated alarm data will show the
status of the 7K circuit when the alarm was set.
5-52
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
This alarm becomes a log alarm if the unit is switched to diesel.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the motor, motor contactor, overload relay and other associated electric standby motor circuitry. The
internal pull coil/hold coil circuits in the contactor may be defective, requiring replacement of contactor.
2. Check the voltages at the phase detect module. Battery voltage should be present on the ER wire and the 8
wire.
3. Check the standby power voltage at the phase detect module. Standby power should be available at L1, L2
and L3.
4. Check the voltage at the motor contactor coils. Battery voltage should be present on either the 7EC or 7EB
wire when the motor should be running.
5. Check for reason that the motor fails to turn the alternator, such as slipping belts, clutch, etc.
7. Download and inspect the ServiceWatch data logger to determine the operating conditions present when the
alarm code was set. Use the running Service Test Mode Feature to duplicate the operating conditions. The
alternator frequency and engine RPM are logged in ServiceWatch and this information is viewable in
technician mode. This information can be used to confirm the RPM sensor reading and alternator frequency
when the alarm was set.
5-53
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
The Discharge Pressure Transducer, Suction Pressure Transducer and Coolant Level switch each have a
separate 5 Vdc power supply. A short circuit condition in one transducer or switch circuit should not affect the
others.
2. If Alarm Code 06 Check Coolant Temp Sensor is set and the engine coolant level input indicates low
coolant level for 3 minutes and the unit is in electric mode then Alarm Code 37 will be set as a check
alarm. If Alarm Code 06 Check Coolant Temp Sensor is set and the engine coolant level input indicates
low coolant level for 3 minutes and the unit is in diesel mode then Alarm Code 37 will be set as a
shutdown alarm.
5-54
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Check the engine coolant level and mixture. Be sure coolant is above the sensor when the coolant is
cold.
2. Check the sensor connector for a pushed pin or missing orange pin lock, loose pin crimp or broken wire.
3. Check that +5 Vdc is present between the (CLP-01) wire from the base controller and chassis ground.
4. Check the voltage between the (CLS-01) wire and chassis ground. Voltage should be +5 Vdc when the
coolant level is adequate and less than +0.5 Vdc when the coolant level is low.
See Service Bulletin T&T 379 for additional information on testing the coolant level switch.
5-55
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. If the unit is running in electric mode and the temperature differential between Zone 1 return air
temperature and discharge air temperature is greater than 50°F (10°C) and is still greater than 45°F (7°C)
after 5 minutes then Alarm Code 38 is set as a shutdown alarm. The large temperature differential
indicates the motor is rotating in the wrong direction.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Confirm that the 7EC-01 wire is connected to the MCB motor contactor and the 7EB-01 wire is connected
to the MCA motor contactor.
3. Check the voltages at the phase detect module. Battery voltage should be present on the 7EA wire and
the 8 wire.
4. Check the standby power voltage at the phase detect module. Standby power should be available at L1,
L2 and L3.
5. Confirm that the phase wiring between contactor MCA and MCB is correct.
5-56
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. If current flow is detected during the output energized phase of the Non-running Pretrip Test then Alarm
Code 39 will be set as a check alarm. The Non-running Pretrip Test will be allowed to complete.
2. If current draw is detected during the output de-energized phase of the Non-running Pretrip Test then
Alarm Code 39 is set as a check alarm and Alarm Code 28 Pretrip Abort will be set as a shutdown alarm.
The Pretrip Test will be aborted.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Check the interface board wiring to insure that there is no connection to connector J7, pin 9.
5-57
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
The High Speed Solenoid circuit is a two wire circuit. The High Speed Solenoid is energized by Relay K3 and
Fuse F6 on the Interface Board. The 7D wire applies 12 VDC to one side of the High Speed Solenoid to energize
the solenoid. The CHHS wire connects the other side of the solenoid to chassis ground at the ground plate near
the unit battery. The solenoid is not polarity sensitive, but the suppression diode must be installed with the bar
end of the diode toward the 7D wire. The wires are routed in the Main Harness.
2. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 40 is set as a shutdown alarm. If current draw is detected during the output de-energized phase of
the Non-running Pretrip Test then Alarm Code 40 is set as a check alarm and Alarm Code 28 Pretrip
Abort will be set as a shutdown alarm. The Pretrip Test will be aborted.
5-58
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Check the operation of the high speed circuit, using Interface Board Test Mode. Be sure the High Speed
Relay LED 5 lights. If LED 5 does not light the base controller or interface board may be defective.
Check the base controller and Interface Board as shown by Service Procedure A01A.
2. Use the HMI control panel amps gauge to check the current drawn by the high speed solenoid, while
operating the high speed solenoid with Interface Board Test Mode. The current draw should be
approximately 4.6 amps. If the current is greater than 8 amps check the circuit for a shorted conductor or
speed solenoid. If the current draw is zero check interface board fuse F6. See the unit wiring diagrams
for wire numbers, locations and additional details.
3. Energize the high speed solenoid using Interface Board Test Mode, and check for battery voltage on the
7D-01 circuit. If voltage is present at the solenoid terminals and no current was measured in the step
above replace the high speed solenoid. If voltage is not present at the solenoid terminals check the high
speed circuit conductors for continuity. See the unit wiring diagrams for wire numbers, locations and
additional details.
5-59
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
5. Download and inspect the ServiceWatch data logger information to determine the operating conditions
that were present when the alarm code was set. Use running Service Test Mode to duplicate the
operating conditions.
5-60
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Download and inspect the ServiceWatch data logger information to determine the operating conditions
that were present when the alarm code was set. Use running Service Test Mode to duplicate the
operating conditions.
5-61
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Circuit Description
2. If after a successful engine start the fuel pressure switch indicates low fuel pressure for 15 seconds, the
following occurs:
x Engine goes to high speed for 2 minutes.
x If the 2 minutes is exceeded and fuel pressure is low, set Alarm Code 44 as a shutdown alarm.
x If fuel pressure is good after 2 minutes return to normal operation.
Considerations
This alarm becomes a log alarm if the unit is switched to electric operation.
This alarm is only active if the unit is equipped with a low fuel pressure switch.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. Check for loose fuel lines and/or air in the fuel lines.
3. Check for gelled diesel fuel when operating in extremely cold conditions.
5-62
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During a non-running Pretrip the current draw is determined by the shunt reading feedback to the base controller.
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
Circuit Description
The hot gas solenoid circuit is a two wire circuit. Smart FETs in the Expansion Module energize the Hot Gas
Solenoids for all zones on multi-temp units. The HGSx wire applies 12 VDC to one side of the Hot Gas Solenoid
to energize the solenoid. The CHHG wire connects the other side of the solenoid to chassis ground. All ground
wires are run back to the unit ground plate. Solenoid valves in remote zones have supply circuits with connectors
in the remote evaporator and at the host unit. The solenoid is not polarity sensitive. The wires are routed in the
Main Harness or Expansion Module Harness. The circuits have connectors in the remote evaporator and at the
host unit. See the unit Wiring Diagram for wire numbers, locations and additional details.
5-63
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the solenoid
is de-energized then Alarm Code 45 is set as a check alarm. Hot gas valve operation is not allowed until
Alarm Code 45 is cleared. The zone will continue to run but with reduced performance until the condition
is corrected and the alarm is cleared.
3. If during a Pretrip Test the current is not between 0.5 to 3 amps (1.0 to 6 amps if parallel evaporators)
when the solenoid is energized then Alarm Code 45 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 45 is set as a shutdown alarm.
5-64
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Verify that the Expansion Module status LED (heartbeat LED) is flashing. If it is not then check the
Expansion Module for proper operation as shown by Service Procedure A01D in Section 6.
2. If the Expansion Module Status LED is flashing then check the operation of the hot gas circuit using
Interface Board Test Mode. Be sure the appropriate Expansion Module hot gas circuit LED lights. For
Expansion Module LED identification see the LED decal on the control box door. If the Expansion
Module hot gas circuit LED lights go to Step 3. If the Expansion Module hot gas circuit LED does not light
go to Step 4.
3. If the Expansion Module hot gas circuit LED does light then use the HMI Control Panel amps gauge to
check the current drawn by the hot gas solenoid, while operating the solenoid with Interface Board Test
Mode. The current draw should be approximately 1.5 amps (3.0 amps if parallel evaporators). If the
current is not within limits then check for a short circuit, open circuit or loose ground connection as shown
in Step 4. Verify that all circuit connectors are secure.
4. If the Expansion Module hot gas circuit LED does not light then disconnect the Expansion Module 35 pin
connector J1 and check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose
connection. The solenoid coil resistance should be approximately 8.3 ohms (4.1 ohms with parallel
evaporators).
5. If no problems are found in steps 1-4 and the output LED does not turn on then replace the Expansion
Module.
7. To verify the multi-temp refrigeration system operation of the Hot Gas Solenoid see Service Procedure
R03A Hot Gas Solenoid Test in Section 8.
5-65
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
Applies to units equipped with electric standby only. This alarm is set in diesel mode only.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
4. Check "W" circuit including resistor for continuity. Monitor with Wintrac or a frequency meter.
5. Check unit configuration if this alarm occurs on a Model 30 (diesel only) unit.
6. Verify the unit model is correctly configured. This alarm is dependant on the alternator drive pulley sizes
used in the unit. The pulley sizes can vary between unit models.
7. Verify that the correct pulley is installed on the alternator. This code can occur if the alternator is replaced
with an alternator with the wrong size pulley installed.
8. Download and inspect the ServiceWatch data logger to determine the operating conditions present when
the alarm code was set. Use the running Service Test Mode Feature to duplicate the operating
conditions. The alternator frequency and engine RPM are logged in ServiceWatch and this information is
viewable in technician mode. This information can be used to confirm the RPM sensor reading and
alternator frequency when the alarm was set.
5-66
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the unit has been in the same Interface Board Test Mode function for 15 minutes then Alarm Code 54 is
set as a shutdown alarm.
Diagnostic Procedure
1. If the unit is in Service Test Mode or Interface Board Test Mode and the function is not changed for 15
minutes then Alarm Code 54 is set as a shutdown alarm. Clear the alarm and re-enter the test mode as
necessary to complete the diagnosis or repair.
5-67
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
No other alarm codes are set after this alarm code is set as a shutdown alarm and is not cleared.
This alarm code can be set by either low voltage or excessive voltage conditions.
2. If during the preheat cycle prior to an engine start the battery voltage is below 10 volts during an engine
start, Alarm Code 61 is set as a Log alarm. NOTE: The preheat output will be have been de-energized
prior to the alarm being set.
3. If during a Pretrip Test the preheat amps check is not within limits, and battery voltage is less than 11.3
volts, Alarm Code 61 is set as a Shutdown alarm.
4. If during a Pretrip Test all outputs are de-energized, and battery voltage is not within limits, Alarm Code
61 is set as a Shutdown alarm.
5. If the unit is in Evacuation mode, and battery voltage is greater than 16.0 volts for 3 minutes, Alarm Code
61 is set as a Shutdown alarm
6. If three power-up and start attempt are made, Alarm Code 61 is set as a Shutdown Alarm. This indicates
that the battery voltage dropped low enough during the start sequence that the base controller powered
down.
5-68
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
3. Check the unit ground plate connections for tightness and corrosion.
4. With the engine running, check the battery voltage and charge rate using the Gauge Menu.
5. Check the operation of the alternator. Be sure the belt is properly adjusted.
7. Download and inspect the ServiceWatch data logger to determine the operating conditions present when
the alarm code was set. The battery voltage, charge current, and alternator frequency are logged in
ServiceWatch and this information is viewable in technician mode. This information can be used to
determine which condition caused the alarm to be set.
5-69
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
The current shunt on SR-2 interface boards is a surface mount device and is conformal coated for protection.
Field resistance measurement of this circuit cannot be made.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the base controller/interface board assembly, using Service Procedure A01A. The Diagnostic Tool
may indicate a defective Interface Board, but this Alarm Code usually indicates a defective Base
Controller.
2. Check the current draw with the unit off and compare it to the reading of a clamp-on ammeter.
5-70
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If the Restart Unit After Shutdown feature is set for Continuous, then the shutdown alarm condition is disabled
and the interval between restart attempts is increased from 15 minutes to 1 hour. Note: This feature is
recommended only for rail application where the equipment is operated unattended for long periods of time. See
the Restart Unit After Shutdown feature in Section 3 for additional information.
2. If Alarm Code 17 Engine Failed to Crank, or Alarm code 20 Engine Failed to Start alarm occurs after
Alarm Code 63 is cleared then Alarm Code 63 will be set as a Shutdown alarm.
5-71
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Download the ServiceWatch data logger and check the conditions when the alarm code was set.
2. Check for other alarm codes and proceed as indicated for each code.
4. Verify the fuel level and check the fuel pump for proper operation.
10. Be sure all ground connections on the master ground plate are secure.
12. Download and inspect the ServiceWatch datalogger information to determine the operating conditions
that were present when the alarm code was set. Use the running service test mode feature to duplicate
the operating conditions as required. Unit operating data is logged in ServiceWatch and the data is
viewable in technician mode.
5-72
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
The alarm is cleared when Pretrip Test is entered. If the Pretrip Test is not successful, the alarm will not be reset.
If the Pretrip Test is not successful then diagnose and correct the fault.
Programmable Features
This feature must be programmed. See Section 3 Hourmeters for details.
Diagnostic Procedure
1. Perform a Pretrip Test to confirm unit operation.
5-73
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
The temperature differential is monitored in both cool and heat mode. If the temperature differential becomes
unrealistic, Alarm Code 65 Abnormal Temperature Differential is set. This alarm may result from incorrect sensor
readings, if defrost damper is stuck closed, if a remote evaporator fan motor(s) has failed, or as a result of
severely restricted air flow.
If Alarm Code 65 Abnormal Temperature Differential occurs with a frozen range setpoint, the alarm is set as a
check alarm and the unit will be forced to low speed cool. If Alarm Code 65 Abnormal Temperature Differential
occurs with a fresh range setpoint, the alarm is set as a zone shutdown alarm.
Alarm Code 65 checks are not active during defrost mode and for 20 minutes after defrost.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the sensor connector at the affected remote evaporator for pushed or damaged pins
2. Check the zone to host evaporator sensor connectors for pushed or damaged pins.
5-74
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
A shutdown level Alarm Code 66 becomes a log alarm if the unit is switched from diesel mode to electric mode. A
log level Alarm Code 66 becomes a shutdown alarm if the unit is switched from electric to diesel mode.
Circuit Description
The wiring is located in the Main Harness via the OLS and CHOL circuits.
2. If Alarm Code 66 is manually cleared and the engine oil level is still low then Alarm Code 66 is reset as a
Shutdown Alarm.
Diagnostic Procedure
1. Check and adjust the engine oil level.
2. Check the switch with an ohmmeter. It should be open when the oil level is satisfactory.
3. Check the harness wires OLS-01 and CHOL with an ohmmeter for continuity, per Service Procedure H04A.
5-75
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During a non-running Pretrip the current draw is determined by the shunt reading feedback to the base controller.
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
NOTE: If the unit is a DE unit the Zone 2 liquid line solenoid is located in the host unit Zone 2 evaporator section.
Circuit Description
The Liquid Line Solenoid circuit is a two wire circuit. See the unit wiring diagram for connector and pin number
identification. The Zone 1 Liquid Line Solenoid is controlled from the interface board. The remote zone Liquid
Line Solenoids are controlled from the Expansion Module (including Zone 2 on DE units).
Zone 1
The Liquid Line Solenoid is energized by Relay K8 and Fuse F11 on the Interface Board. The LLS wire applies
12 VDC to one side of the Liquid Line Solenoid to energize the solenoid. The CHLL wire connects the other side
of the solenoid to chassis ground at the ground plate near the unit battery. The solenoid is not polarity sensitive.
The wires are routed in the Main Harness. See the unit wiring diagrams for wire numbers, locations and
additional details.
Remote Zones
The Liquid Line Solenoid is energized by a Smart FET on the Expansion Module. The LLS wire applies 12 VDC
to one side of the Liquid Line Solenoid to energize the solenoid. The CH wire connects the other side of the
solenoid to chassis ground. All ground wires are run back to the unit ground plate. Solenoid valves in remote
zones have supply circuits with connectors in the remote evaporator and at the host unit. The solenoid is not
polarity sensitive. The wires are routed in the Expansion Module Harness. The circuits have connectors in the
remote evaporator and at the host unit. See the unit wiring diagrams for wire numbers, locations and additional
details.
5-76
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the current does not return to less than 0.5 amps 3 seconds after the solenoid is de-energized then
Alarm Code 67 is set as a shutdown alarm. If the setpoint is in the frozen range and Alarm Codes 67 and
12 are set then Alarm Code 114 Multiple Alarms – Can Not Run will be set. In single zone frozen range
operation the unit will shut down. In multiple zone frozen range operation the offending zone will shut
down. The unit or zone will remain shut down until the alarms are cleared.
3. If during a Pretrip Test the current is not between 0.5 to 5 amps (1.0 to 6 amps if parallel evaporators)
when the solenoid is energized then Alarm Code 67 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 67 is set as a shutdown alarm.
5. If during a Pretrip Test the unit is not configured for the zone being tested and amp draw is greater than
the allowable limit then Alarm Code 67 is set as a check alarm and Alarm Code 111 Unit Not Configured
Correctly is set as a log alarm.
5-77
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Verify that the Expansion Module status LED (heartbeat LED) is flashing. If it is not then check the
Expansion Module for proper operation as shown by Service Procedure A01D in Section 6.
2. If the Expansion Module Status LED is flashing then check the operation of the liquid line circuit using
Interface Board Test Mode. Be sure the appropriate Expansion Module liquid line circuit LED lights. For
Expansion Module LED identification see the LED decal on the control box door. If the Expansion
Module liquid line circuit LED lights go to Step 3. If the Expansion Module liquid line circuit LED does not
light go to Step 4.
3. If the Expansion Module liquid line circuit LED does light then use the HMI Control Panel amps gauge to
check the current drawn by the liquid line solenoid, while operating the solenoid with Interface Board Test
Mode. The current draw should be approximately 1.5 amps (3.0 amps if parallel evaporators). If the
current is not within limits then check for a short circuit, open circuit or loose ground connection as shown
in Step 4. Verify that all circuit connectors are secure.
4. If the Expansion Module liquid line circuit LED does not light then disconnect the Expansion Module 35
pin connector J1 and check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose
connection. The solenoid coil resistance should be approximately 8.3 ohms (4.1 ohms with parallel
evaporators).
5. If no problems are found in steps 1-4 and the output LED does not turn on then replace the Expansion
Module.
7. To verify the refrigeration system operation of the Liquid Line Solenoid see Service Procedure R04A
Liquid Line Solenoid and Liquid Return Check Valve Solenoid Test.
5-78
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If a check level internal fault occurs in the base controller then Alarm Code 68 is set as a check alarm.
3. If a log level internal fault occurs in the base controller the Alarm Code 68 is set as a log alarm.
Diagnostic Procedure
1. Replace the base controller.
Associated Alarm
Codes
How Alarm is Set
1. If one or more hourmeters exceeds 499,999 hours the Alarm Code 70 is set as a log alarm.
Diagnostic Procedure
1. If the hourmeter readings are normal, perform a Cold Start per Service Procedure A07A.
2. If the code can now be cleared, proceed with base controller setup, using Service Procedure A04A.
IMPORTANT: Any time a Cold Start is performed the base controller must be set up using Service
Procedure A04A. Failure to do so may result in the unit not operating to customer specifications.
5-79
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
1. Be sure the interface board cold start jumper J101 is in the correct (up) position. It should match the
white mark on the interface board, at the side of the jumper. If the jumper is in the wrong position a cold
start will occur every time the unit is turned on.
IMPORTANT: Any time Alarm Code 74 occurs the base controller must be set up using Service Procedure
A04A. Failure to do so may result in the unit not operating to customer specifications.
Diagnostic Procedure
1. Replace the base controller.
5-80
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
No corrective action is possible. This serves only as an indication that an event occurred that was not recorded
by the data logger.
5-81
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm Alarm Codes 10, 17, 18. 20, 21, 22, 36, 42, 63, 90, 91 and 93
Codes
Considerations
x This alarm is a secondary alarm that is set along with the associated primary alarm.
x The alarm indicates that the unit is in a temporary (“prevent” or “restart null”) shutdown. The alarm clears
automatically if the condition does not re-occur.
x Many of these actions include a “waiting period” (to allow the engine to cool down, a high pressure
condition to subside or the like). The alarm code that caused the condition and Alarm Code 84 might be
present to indicate that the base controller is taking a corrective action and that a restart will be attempted
when conditions permit.
x If the corrective action is successful, the original alarm code and Alarm Code 84 are cleared
automatically. If the original alarm condition continues to occur, and the corrective actions taken by the
base controller are not successful, the original alarm code remains. Alarm Code 84 is automatically
cleared and the unit shuts down.
x This alarm occurs if unit operation is not allowed as a result of the associated prevent alarm. For
example, if a high discharge pressure condition shuts the unit down, a waiting period occurs to allow
system pressures to equalize. A restart occurs when conditions permit.
x Most prevent alarms become shutdown alarm if three occurrences of the alarm occur within a set time
period.
x Alarm Codes 10, 18 and 63 are not promoted to shutdown level if the Continuous Restarts feature is
enabled.
x Alarm Codes 32 and 63 are promoted to guarded access clearable shutdown alarms if the Limited
Restarts Feature is enabled and the shutdown alarm occurs 3 times with a 12 hour time period.
x Some prevent alarms will result in modified unit operation after the alarm is self cleared. For example,
Alarm Code 10 High Discharge Pressure will result in Alarm Code 42 Unit Forced to Low Speed being set
and the unit being forced to low speed for a 1 hour period.
x If the unit is turned off while Alarm Code 84 is present the primary alarm becomes a shutdown alarm
when the unit is turned back on.
5-82
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Check for associated alarms and repair as required.
5-83
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
The 3-wire discharge pressure sensor is supplied with +5 Vdc and ground from the base controller. The wiring is
located in the Sensor Harness via the DPP, DPN and DPI circuits.
Considerations
The Discharge Pressure Transducer, Suction Pressure Transducer and Coolant Level switch each have a
separate 5 Vdc power supply. A short circuit condition in one transducer or switch circuit should not affect the
other devices.
The maximum discharge pressure that can be displayed is 500 psig. If the sensed pressure is greater than 500
psig, the HMI Control Panel will display [ - - - - ] instead of the discharge pressure.
The minimum discharge pressure that can be sensed is –10 psig. The control system cannot determine if the
minimum sensed pressure is the result of an electrical short or very low system pressure.
If Alarm Code 86 Check Discharge Pressure Sensor is set then the control system will revert to the High Pressure
Control Switch (HPCS) switch to control the Condenser Inlet Solenoid (CIS) and the engine high speed output for
refrigeration system control.
The Discharge Pressure Transducer will have a “500” on the body of the part. The Suction Pressure Transducer
will have a “200” on the body of the part. They are not interchangeable.
2. If the unit is running, the ambient temperature is greater than 10°F (-12°C) and the discharge pressure
transducer reading is less than +15 psig for 10 seconds then Alarm Code 86 is set as a check alarm. If
the unit is in a Pretrip Test this alarm is set as a shutdown alarm.
3. If Alarm Code 10 is cleared and the discharge pressure transducer reading is greater than or equal to 425
psig but less than 500 psig then Alarm Code 86 is set as a check alarm.
5-84
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If the discharge pressure is not displayed by the base controller, unplug the transducer and check for +5
Vdc between DPP and DPN. If +5 Vdc is not present check the base controller using Service Procedure
A01A.
3. Check the harness wires DPP, DPN and DPI for continuity using an ohmmeter.
4. Connect refrigeration gauges to verify that the sensor is displaying the correct pressure. Replace the
sensor if required.
5-85
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
The 3-wire suction pressure sensor is supplied with +5 VDC and ground from the base controller. The sensor is
located in the suction line and downstream of the ETV if present. The wiring is located in the Sensor Harness via
the SPP, SPN and SPI circuits.
Considerations
The Discharge Pressure Transducer, Suction Pressure Transducer and Coolant Level switch each have a
separate 5 Vdc power supply. A short circuit condition in one transducer or switch circuit should not affect the
others.
The maximum suction pressure that can be displayed is 200 psig. If the sensed pressure is greater than 200
psig, the HMI Control Panel will display [ - - - - ] instead of the suction pressure. When the unit is off and the
refrigerant pressures have equalized, the system pressure can exceed 200 psig when ambient temperatures are
above 90°F (35°C). If this occurs the HMI Control Panel will display [ - - - - ]. This is normal operation and no
cause for concern.
If the sensor opens the display will read -10 PSIG. An alarm may not be generated immediately but the unit will
be forced to low speed due to low suction pressure.
The Suction Pressure Transducer will have a “200” on the body of the part. The Discharge Pressure Transducer
will have a “500” on the body of the part. They are not interchangeable.
2. If the unit is running and the suction pressure sensor reading is less than -9 PSIG for 20 minutes then the
unit will be forced into a prevent alarm condition. During the prevent shutdown period Alarm Code 93
Low Suction Pressure and Alarm Code 84 Restart Null will be set. If during the prevent shutdown period
the suction pressure does not rise then Alarm Code 87 is set as a check alarm. If the unit is in a Pretrip
Test this alarm is set as a shutdown alarm.
5-86
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Check the suction pressure display using the Gauge Menu. If the suction pressure is -10 psig then turn
the unit off and allow the system refrigerant pressures to equalize. If the displayed suction pressure
remains at –10 psig then the suction pressure transducer is defective and must be replaced. NOTE:
System refrigerant pressures can equalized quickly by energizing the zone hot gas valves using Interface
Board Test.
2. Check the suction pressure display using the Gauge Menu. If the sensor reads [ - - - - ] psig then turn
the unit off and allow the system pressures to equalize.
x If the suction pressure is less than 180 psig, but the displayed suction pressure remains at
[ - - - - ] then the transducer is defective and must be replaced.
x If the suction pressure is greater than 180 psig, the suction pressure transducer may be operating
normally. Place Zone 1 in full cool and allow the return air temperature to drop below 50qF
(10qC). If the suction pressure display remains at [ - - - - ] then the transducer, controller power
supply, or conductors are faulty. NOTE: System refrigerant pressures can equalized quickly by
energizing the zone hot gas valves using Interface Board Test.
3. If the suction pressure is not displayed by the base controller, unplug the transducer and check for +5 Vdc
between SPP-01 and SPN-01. If 5 volts is not present check the base controller, using Service
Procedure A01A.
4. Connect refrigeration gauges to verify that the sensor is not displaying the correct pressure. Replace the
sensor.
5. Check the harness wires SPP-01, SPN-01 and SP-01 for continuity using an ohmmeter.
5-87
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If during a Pretrip Test the unit is not configured electric standby and the EOL input is low then Alarm
Code 90 Electric Overload is set as a check alarm and Alarm Code 111 Unit Not Configured Correctly is
set as a log alarm.
Considerations
This alarm becomes a Log alarm if the unit is switched from electric mode to diesel mode.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
CAUTION: High voltage is present any time the unit is connected to standby power. Exercise extreme
care.
1. Check the electric motor for current draw. Refer to the motor nameplate for the Full Load Amperage
rating (FLA) of the motor.
2. Check the setting of the motor overload relay. It should be 10% greater than full load rating of the motor.
3. Check the EOL circuit for continuity from J6 pin 2 on the interface board to the overload relay.
4. Check for continuity between the overload relay terminals 95 and 96. The contacts should be normally
closed.
5-88
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
This alarm automatically clears if the unit is switched from electric mode to diesel mode.
The electric standby phase detection module contains protection for missing phase, low voltage, and over
voltage. If any of these 3 standby power conditions are present the module with not energize it ER output.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
CAUTION: High voltage is present any time the unit is connected to standby power. Exercise extreme
care.
1. Check the ER-01 Circuit from the phase detect module for 12 volts to chassis ground when standby
power is connected to the unit.
3. Check to be sure standby power of the correct voltage is present at L1, L2 and L3 on the phase detect
module.
4. Check the ER-01 Circuit for continuity from J6 pin 5 on the interface board to the phase detect module.
5. If steps 1-5 above are correct, check the base controller using Service Procedure A01A.
6. If steps 1, 2, 4 or 5 above do not correct the fault, replace the phase detect module.
5-89
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
The sensor grade must be set using the Sensor Calibration feature in the Guarded Access Menu. If the sensor
grade is not properly set the sensor reading will not be accurate. Grade 5H is set as the default grade on factory
base controllers and is used as an indication that the sensor grade has not been set.
Diagnostic Procedure
1. Verify actual sensor grades for all graded sensors.
2. Using this information, calibrate the sensors using the Sensor Calibration feature in the Guarded Access
Menu. See Service Procedure A15A in Section 6 of this manual for details.
5-90
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. The alarm will clear automatically at the conclusion of a successful prevent routine.
Considerations
If Alarm Code 87 Check Suction Pressure Sensor is set then Alarm Code 93 is disabled.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
3. Attach gauges and evaluate unit refrigeration system performance for causes of low suction pressure.
5-91
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
1. Check fuel tank level and fill as required.
5-92
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
1. Check fuel level sensor harness to be sure it is connected and secure.
5-93
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
Circuit Description
The Receiver Tank Pressure Solenoid circuit is a two wire circuit. The Receiver Tank Pressure Solenoid is
energized by a Smart FET on the Interface Board. The RTPS wire applies 12 VDC to one side of the Receiver
Tank Pressure Solenoid to energize the solenoid. The CHRT wire connects the other side of the solenoid to
chassis ground at the ground plate near the unit battery. The solenoid is not polarity sensitive. The wires are
routed in the Main Harness.
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the solenoid
is de-energized then Alarm Code 105 is set as a check alarm. Receiver Tank Pressure Solenoid
operation is not allowed until Alarm Code 105 is cleared. The unit will continue to run but with reduced
performance until the condition is corrected and the alarm is cleared.
3. If during a Pretrip Test the current is not between 0.5 to 3 amps when the solenoid is energized then
Alarm Code 105 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 105 is set as a shutdown alarm.
5-94
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the receiver tank pressure solenoid circuit using Interface Board Test Mode. Be
sure the interface board receiver tank pressure solenoid circuit LED lights. For interface board LED
identification see the LED decal on the control box door. If the interface board receiver tank pressure
solenoid circuit LED lights go to Step 2. If the interface board receiver tank pressure solenoid circuit LED
does not light go to Step 3.
2. If the interface board receiver tank pressure solenoid circuit LED does light then use the HMI Control
Panel amps gauge to check the current drawn by the receiver tank pressure solenoid, while operating the
solenoid with Interface Board Test Mode. The current draw should be approximately 0.7 amps. If the
current is not within limits then check for a short circuit, open circuit or loose ground connection as shown
in Step 3. Verify that all circuit connectors are secure.
3. If the interface board receiver tank pressure solenoid circuit LED does not light then disconnect the 36 pin
connector J7 and check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose
connection. The solenoid coil resistance should be approximately 17.0 ohms.
4. If no problems are found in steps 1-3 and the output LED does not turn on then test the base
controller/interface board assembly as shown in Service Procedure A01A.
5. To verify the refrigeration system operation of the Receiver Tank Pressure Solenoid see Service
Procedure R08A Condenser Inlet Solenoid, Receiver Tank Pressure Solenoid and Purge Check Valve
Solenoid Test.
5-95
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
Circuit Description
The Purge Valve circuit is a two wire circuit. The Purge Valve is energized by a Smart FET on the Interface
Board. The PV wire applies 12 VDC to one side of the Purge Valve to energize the solenoid. The CHPV wire
connects the other side of the solenoid to chassis ground at the ground plate near the unit battery. The solenoid
is not polarity sensitive. The wires are routed in the Main Harness.
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the solenoid
is de-energized then Alarm Code 106 is set as a check alarm. Purge valve operation is not allowed until
Alarm Code 106 is cleared. The unit will continue to run but with reduced performance until the condition
is corrected and the alarm is cleared.
3. If during a Pretrip Test the current is not between 0.5 to 3 amps when the solenoid is energized then
Alarm Code 106 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 106 is set as a shutdown alarm.
5-96
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the purge valve circuit using Interface Board Test Mode. Be sure the interface
board purge valve circuit LED lights. For interface board LED identification see the LED decal on the
control box door. If the interface board purge valve circuit LED lights go to Step 2. If the interface board
purge valve circuit LED does not light go to Step 3.
2. If the interface board purge valve circuit LED does light then use the HMI Control Panel amps gauge to
check the current drawn by the purge valve, while operating the valve with Interface Board Test Mode.
The current draw should be approximately 0.7 amps. If the current is not within limits then check for a
short circuit, open circuit or loose ground connection as shown in Step 3. Verify that all circuit connectors
are secure.
3. If the interface board purge valve circuit LED does not light then disconnect the 36 pin connector J7 and
check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose connection. The
valve coil resistance should be approximately 17.0 ohms.
4. If no problems are found in steps 1-3 and the output LED does not turn on then test the base
controller/interface board assembly as shown in Service Procedure A01A.
5. To verify the refrigeration system operation of the Purge Valve see Service Procedure R07A Purge Valve
Test and Service Procedure R08A Condenser Inlet Solenoid, Receiver Tank Pressure Solenoid and
Purge Check Valve Solenoid Test.
5-97
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
Circuit Description
The Condenser Inlet Solenoid circuit is a two wire circuit. The Condenser Inlet Solenoid is energized by a Smart
FET on the Interface Board. The CIS wire applies 12 VDC to one side of the Condenser Inlet Solenoid to
energize the solenoid. The CHCI wire connects the other side of the solenoid to chassis ground at the ground
plate near the unit battery. The solenoid is not polarity sensitive. The wires are routed in the Main Harness.
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the solenoid
is de-energized then Alarm Code 107 is set as a check alarm. Condenser Inlet Solenoid operation is not
allowed until Alarm Code 107 is cleared. The unit will continue to run but with reduced performance until
the condition is corrected and the alarm is cleared.
3. If during a Pretrip Test the current is not between 0.5 to 3 amps when the solenoid is energized then
Alarm Code 107 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 107 is set as a shutdown alarm.
5-98
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the condenser inlet solenoid circuit using Interface Board Test Mode. Be sure the
interface board condenser inlet solenoid circuit LED lights. For interface board LED identification see the
LED decal on the control box door. If the interface board condenser inlet solenoid circuit LED lights go to
Step 2. If the interface board condenser inlet solenoid circuit LED does not light go to Step 3.
2. If the interface board condenser inlet solenoid circuit LED does light then use the HMI Control Panel
amps gauge to check the current drawn by the condenser inlet solenoid, while operating the solenoid with
Interface Board Test Mode. The current draw should be approximately 1.3 amps. If the current is not
within limits then check for a short circuit, open circuit or loose ground connection as shown in Step 3.
Verify that all circuit connectors are secure.
3. If the interface board condenser inlet solenoid circuit LED does not light then disconnect the 36 pin
connector J7 and check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose
connection. The solenoid coil resistance should be approximately 9.6 ohms.
4. If no problems are found in steps 1-3 and the output LED does not turn on then test the base
controller/interface board assembly as shown in Service Procedure A01A.
5. To verify the refrigeration system operation of the Condenser Inlet Solenoid see Service Procedure R08A
Condenser Inlet Solenoid, Receiver Tank Pressure Solenoid and Purge Check Valve Solenoid Test.
5-99
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
If the unit is programmed to force the unit or zone to null when the door switch is open, the unit or zone will not re-
enter null until after the door switch is closed and then re-opened.
Changes in the door switch state are not recognized for 4 seconds. This is to prevent rapid unit or zone operation
changes if the door is ajar or the door switch is defective.
The unit or zone will be restarted after the off timer expires.
Diagnostic Procedure
1. Download the ServiceWatch data logger and inspect the information to determine if the door switch is
defective or if the door was left open for an extended period of time during loading or unloading of the
trailer.
5-100
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
During a non-running Pretrip the current draw is determined by the shunt reading feedback to the base controller.
During normal operation the current draw is determined by the Smart FET feedback to the base controller.
If a code is set during normal operation then the ServiceWatch Datalogger will list the Code, FLTCT (Fault
Current), Battery Volts, and the Shunt Current. The FLTCT will be the high or low current draw as determined by
the Smart FET feedback that caused the code to set.
NOTE: If the unit is a DE unit the Zone 2 suction line solenoid is located in the host unit Zone 2 evaporator
section.
Circuit Description
The Suction Line Solenoid circuit is a two wire circuit. The Suction Line Solenoids are energized by Smart FETs
in the Expansion Module. The SLS wire applies 12 VDC to one side of the Suction Line Solenoid to energize the
solenoid. The CHSL wire connects the other side of the solenoid to chassis ground. The solenoid is not polarity
sensitive. The wires are routed in the Expansion Module Harness. The circuits have connectors in the remote
evaporator and at the host unit.
5-101
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
If in multi-zone operation and all the zones are running in cool, heat, or heat and defrost then the unit
runs normally.
If the offending zone requires heat and one or more zones are in cool, force the offending zone into
null.
If the offending zone requires defrost and one or more zones are in cool, force all zones in cool into
running null. Zones will resume cooling after defrost in the offending zone is completed.
If in multi-zone operation and all the zones are running in cool, heat, or heat and defrost then the unit
runs normally.
If the offending zone requires heat or defrost and one or more zones are in cool then force all zones
in cool into running null. Zones will resume cooling after heating and or defrost in the offending zone
is completed.
2. If the current does not return to less than 0.5 amps 3 seconds after the solenoid is de-energized and
the unit is in multi-zone operation then Alarm Code 110 is set as a check alarm. If the current does
not return to less than 0.5 amps 3 seconds after the solenoid is de-energized and the unit is in single
zone operation then Alarm Code 110 is set as a shutdown alarm.
3. If during a Pretrip Test the current is not between 0.5 to 3 amps (1.0 to 6 amps if parallel evaporators)
when the solenoid is energized then Alarm Code 110 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then
Alarm Code 110 is set as a shutdown alarm.
5-102
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Verify that the Expansion Module status LED (heartbeat LED) is flashing. If it is not then check the
Expansion Module for proper operation as shown by Service Procedure A01D in Section 6.
2. If the Expansion Module Status LED is flashing then check the operation of the suction line solenoid
circuit using Interface Board Test Mode. Be sure the appropriate Expansion Module suction line solenoid
LED lights. For Expansion Module LED identification see the LED decal on the control box door. If the
Expansion Module suction line solenoid circuit LED lights go to Step 3. If the Expansion Module suction
line solenoid circuit LED does not light go to Step 4.
3. If the Expansion Module suction line solenoid circuit LED does light then use the HMI Control Panel amps
gauge to check the current drawn by the suction line solenoid, while operating the solenoid with Interface
Board Test Mode. The current draw should be approximately 1.3 amps (2.6 amps if parallel evaporators).
If the current is not within limits then check for a short circuit, open circuit or loose ground connection as
shown in Step 4. Verify that all circuit connectors are secure.
4. If the Expansion Module suction line solenoid circuit LED does not light then disconnect the Expansion
Module 35 pin connector J1 and check the circuit with an accurate ohmmeter for a short circuit, open
circuit or loose connection. The solenoid coil resistance should be approximately 9.6 ohms (4.8 ohms
with parallel evaporators).
5. If no problems are found in steps 1-4 and the output LED does not turn on then replace the Expansion
Module.
7. To verify the refrigeration system operation of the Suction Line Solenoid see Service Procedure R05A
Suction Line Solenoid Test and Service Procedure R06A Suction Line Check Valves and Condenser Inlet
Check Valve Test.
5-103
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm 02, 03, 04, 29, 30, 45, 67, 90, 110, 113, 122, 137 and 143
Codes
How Alarm is Set
1. If a mismatch exists between the unit hardware configuration and the unit hardware as detected by the
base controller then Alarm Code 111 is set as a log alarm.
Diagnostic Procedure
1. Verify actual unit configuration.
2. Set the unit configuration using the Unit Configuration sub-menu of the Programming Menu, as shown in
Service Procedure A04A.
5-104
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
Fan power is supplied from the Expansion Module. 2A power is connected to the Expansion Module at the large
power studs on the module.
Remote evaporators will have 2 or 3 fan motors. Any zone can have a minimum of 2 fan motors and a maximum
of 6 fan motors. An individual unit can support up to 12 fan motors.
On systems with parallel remote zone evaporators the respective Expansion Module fan motor output will supply
power to two fan motors. See the respective unit wiring diagram for details.
On systems with single remote zone evaporators the respective Expansion Module fan motor output will supply
power to one fan motor. See the respective unit wiring diagram for details.
On DE units the Zone 2 fan motor output is used to operate the Zone 2 damper. See Alarm Code 29 Defrost
Damper Circuit Check for additional details.
The Pretrip and SmartFet current limits will be adjusted for current draw based on the zone configuration
settings.
The circuits have connectors in the remote evaporator and at the host unit.
Circuit Description
The evaporator fans are energized by Smart FETs in the Expansion Module. The blue wires connect the fan
motor to chassis ground. All ground wires are run back to the unit ground plate. The wires are routed in the
Expansion Module Harness. The circuits have connectors in the remote evaporator and at the host unit.
5-105
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
x If the unit is in single temperature operation and all fan motors have Alarm Code 112 set then
Alarm Code 114 will be set as a shutdown alarm. If one or more fans are allowed to run then the
unit will continue to run.
x If in multi-temperature operation and all fan motors in a remote evaporator have Alarm Code 112
set then the remote evaporator will be forced into shutdown and all remote evaporator outputs for
that evaporator will be forced off. Alarm Code 12 will be set as a zone shutdown alarm.
2. If during normal operation the current is greater than 20.0 amps 30 seconds after the fan(s) are energized
then Alarm Code 112 is set as a check alarm and the output is turned off.
x If the unit is in single temperature operation and all fan motors have Alarm Code 112 set then
Alarm Code 114 will be set as a shutdown alarm. If one or more fans are allowed to run then the
unit will continue to run.
x If in multi-temperature operation and all fan motors in a remote evaporator have Alarm Code 112
set then the remote evaporator will be forced into shutdown and all remote evaporator outputs for
that evaporator will be forced off. Alarm Code 12 will be set as a zone shutdown alarm.
3. If during normal operation the current is greater than 0.5 amps 3 seconds after the fan(s) are de-
energized then Alarm Code 112 is set as a check alarm and the output is turned off.
4. If during normal operation the current is greater than the Smart FET current limit 1 second after the fan(s)
are energized then Alarm Code 112 is set as a check alarm and the output is turned off.
x If the unit is in single temperature operation and all fan motors have Alarm Code 112 set then
Alarm Code 114 will be set as a shutdown alarm. If one or more fans are allowed to run then the
unit will continue to run.
x If in multi-temperature operation and all fan motors in a remote evaporator have Alarm Code 112
set then the remote evaporator will be forced into shutdown and all remote evaporator outputs for
that evaporator will be forced off. Alarm Code 12 will be set as a zone shutdown alarm.
5. If during a Pretrip Test the current is not in specification when the fans are energized then Alarm Code
112 is set as a check alarm.
6. If during a Pretrip Test the current does not return to less than 0.5 amps when the fans are de-energized
then Alarm Code 112 is set as a shutdown alarm.
5-106
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Verify that the Expansion Module status LED (heartbeat LED) is flashing. If it is not then check the
Expansion Module for proper operation as shown by Service Procedure A01D in Section 6.
2. If the Expansion Module Status LED is flashing then check the operation of the fan circuit using Interface
Board Test Mode. Be sure the appropriate Expansion Module fan circuit LED lights. For Expansion
Module LED identification see the LED decal on the control box door. If the Expansion Module fan circuit
LED lights go to Step 3. If the Expansion Module fan circuit LED does not light go to Step 4.
3. If the Expansion Module fan circuit LED does light then use the HMI Control Panel amps gauge to check
the current drawn by the fan circuit, while operating the fans with Interface Board Test Mode. If the
current is not within limits then check for a short circuit, open circuit or loose ground connection as shown
in Step 4. Verify that all circuit connectors are secure.
4. If the Expansion Module fan circuit LED does not light then disconnect the Expansion Module 6 pin
connector J13 and check the circuit with an accurate ohmmeter for a short circuit, open circuit or loose
connection.
5. If no problems are found in steps 1-4 and the output LED does not turn on then replace the Expansion
Module.
5-107
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If during a Pretrip Test the current does not return to within 0.25 amps of reference amps when de-
energized then Alarm Code 113 is set as a shutdown alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
5-108
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
Associated Alarm Alarm Code 118 Auto Switch from Electric to Diesel
Codes
How Alarm is Set
1. If the unit is switched from diesel operation to electric operation during a Pretrip Test then set Alarm code
117 as a log alarm. The Pretrip Test will be restarted from the beginning in Electric Mode.
2. If the unit is switched from diesel operation to electric operation during a non-running Service Test Mode
operation then set Alarm code 117 as a shutdown alarm.
3. If the unit is switched from electric operation to diesel operation during normal operation this alarm is set
as a log alarm for information only.
Diagnostic Procedure
Information only. No action is required.
5-109
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm Alarm Code 117 Auto Switch from Diesel to Electric
Codes
How Alarm is Set
1. If the unit is switched from electric operation to diesel operation during a Pretrip Test then set Alarm code
117 as a log alarm. The Pretrip Test will be restarted from the beginning in Diesel Mode.
2. If the unit is switched from electric operation to diesel operation during a non-running Service Test Mode
operation then set Alarm code 117 as a shutdown alarm.
3. If the unit is switched from diesel operation to electric operation during normal operation this alarm is set
as a log alarm for information only.
Diagnostic Procedure
Information only. No action is required.
5-110
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
The alternator excite output is featured on revision SR-2/C base controller and revision IB/B interface boards.
This hardware can be identified by the “T3” suffix on the respective hardware serial number. Unit’s manufactured
with “T3” hardware must use “T3” replacement hardware.
Circuit Description
The Alternator Excite circuit is a single wire circuit. The Alternator Excite circuit is energized by a Smart FET on
the Interface Board. The EXC wire applies 12 VDC to energize the alternator excite circuit. The wire is routed in
the Main Harness.
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the alternator
excite output is de-energized then Alarm Code 120 is set as a check alarm. Alternator excite operation is
not allowed until Alarm Code 120 is cleared. The unit will continue to run but with reduced performance
until the condition is corrected and the alarm is cleared.
3. If during a Pretrip Test the current is not within specifications when the alternator excite output is
energized then Alarm Code 120 is set as a check alarm.
4. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 120 is set as a shutdown alarm.
5-111
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Check the operation of the alternator excite circuit using Interface Board Test Mode. Be sure the
alternator excite circuit LED lights. If the alternator excite circuit LED lights then go to Step 2. If the
alternator excite circuit LED does not light then go to Step 3.
2. If the alternator excite circuit LED does light then check for 12 Vdc at the alternator excite terminal. If 12
Vdc is not present check for a short circuit, open circuit or loose connection.
3. If the alternator excite circuit LED does not light then check the circuit with an accurate ohmmeter for a
short circuit, open circuit or loose connection.
4. Disconnect the EXC wire at the alternator and check for 12 Vdc when the engine is running.If 12 VDC is
not present check the EXC circuit for continuity.
5-112
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. If current flow is detected during the output energized phase of the Non-running Pretrip Test then Alarm
Code 121 will be set as a check alarm. The Non-running Pretrip Test will be allowed to complete.
2. If current draw is detected during the output de-energized phase of the Non-running Pretrip Test then
Alarm Code 121 is set as a check alarm and Alarm Code 28 Pretrip Abort will be set as a shutdown
alarm. The Pretrip Test will be aborted.
Diagnostic Procedure
1. Check unit configuration to confirm proper setting.
2. Check the interface board wiring to insure that there is no connection to connector J7, pin 10.
5-113
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
The Diesel/Electric circuit is energized by the Diesel/Electric Relay K5 on the Interface Board. The 7E wire
supplies 12 VDC the Phase Select Module to energize the appropriate Standby Motor contactor.
2. If during a Pretrip Test the zone is configured with Diesel/Electric Relay and current does not return to
less than 0.5 amps of run relay reference when de-energized then Alarm Code 122 is set as a shutdown
alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
1. Check the operation of the Diesel/Electric relay using Interface Board Test Mode in the Maintenance
Menu. Be sure the Diesel/Electric LED 7 lights.
2. Use the HMI control panel amps gauge to check the current drawn by the Diesel/Electric relay while
operating the Diesel/Electric relay with Interface Board Test Mode. The current draw should be between
0.1 to 2 amps.
5-114
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
How Alarm is Set
1. If the setpoint was changed but the change was not confirmed by pressing the YES key then Alarm Code
127 is set as a check alarm. The setpoint has not been changed and has returned to the original setting.
Diagnostic Procedure
Information only. Be sure setpoint is adjusted properly.
5-115
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Considerations
The programmable hourmeter alarms can be cleared from the Guarded Access Menu only.
How Alarm is Set
1. If one of the hourmeters above has exceeded the programmed time limit then the appropriate alarm code
is set as a log alarm.
Diagnostic Procedure
1. Perform required maintenance, as dictated by owner requirements.
2. Reset the hourmeter limit after completion using the Hourmeter menu. See Section 4 for details.
5-116
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
How Alarm is Set
1. If the Pretrip test indicates that a connection has been made to a spare digital output and should not have
been then Alarm Code 136 is set as a check alarm.
Diagnostic Procedure
Correct the wiring error.
5-117
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Considerations
When this alarm is set the unit will remain in diesel mode operation even when connected to a fully functional
electric standby power system.
How Alarm is Set
1. If autoswitch diesel to electric is set yes and the unit switches to electric mode operation and an Electric
Mode shutdown alarm is already set, then set Alarm Code 141 as a check alarm.
Diagnostic Procedure
1. Check for associated alarms and repair as required.
5-118
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Component Description and Location
The drain hose heater is used on remote evaporators to keep the evaporator drain hose free of ice. They are
located in the remote evaporator drain hoses.
Circuit Description
The drain hose heater circuit is a two wire circuit. Smart FETs in the Expansion Module energize the drain hose
heaters for all remote zones on multi-temp units. The DHx wire applies 12 VDC to one side of the drain hose
heater. The CHHG wire connects the other side of the drain hose heater to chassis ground. All ground wires are
run back to the unit ground plate. Drain hose heaters in remote zones have supply circuits with connectors in the
remote evaporator and at the host unit. The heater is not polarity sensitive. The wires are routed in the
Expansion Module Harness. See the unit wiring diagrams for wire numbers, locations and additional details.
Considerations
Drain hose heaters are used in remote zones only. On systems with remote zone parallel evaporators the
respective drain hose heater output will supply power to all of the zone heaters. On zones with a single
evaporator there are two heaters. On zones with parallel evaporators there are four heaters.
On systems with remote zone parallel evaporators the respective Expansion Module drain hose heater output will
supply power to all of the drain tube heaters. The Pretrip and SmartFet current limits will automatically adjust for
the increased current drawn by parallel evaporators based on the zone configuration settings.
5-119
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
2. If during normal operation the current does not return to less than 0.5 amps 3 seconds after the drain
hose heater is de-energized then Alarm Code 143 is set as a check alarm. Zone drain hose heater
operation is not allowed until Alarm Code 143 is cleared.
3. If during normal operation the current is limited by the SmartFET due to excessive current draw 1 second
after the drain hose heater is energized then Alarm Code 143 is set as a check alarm. Zone drain hose
heater operation is not allowed until Alarm Code 143 is cleared.
4. If during a Pretrip Test the current is not between 3 to 10 amps when the drain hose heater is energized
then Alarm Code 143 is set as a check alarm.
5. If during a Pretrip Test the current does not return to less than 0.5 amps when de-energized then Alarm
Code 143 is set as a shutdown alarm.
6. If during a Pretrip Test the unit is a trailer unit and is not configured for the zone being tested and amp
draw is greater than the allowable limit then Alarm Code 143 and Alarm Code 111 Unit Not Configured
Correctly are set as log alarms.
5-120
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
1. Verify that the Expansion Module status LED (heartbeat LED) is flashing. If it is not then check the
Expansion Module for proper operation as shown by Service Procedure A01D in Section 6.
2. If the Expansion Module Status LED is flashing then check the operation of the drain hose heater circuit
using Interface Board Test Mode. Be sure the appropriate Expansion Module drain hose heater LED
lights. For Expansion Module LED identification see the LED decal on the control box door. If the
Expansion Module drain hose heater circuit LED lights go to Step 3. If the Expansion Module drain hose
heater circuit LED does not light go to Step 4.
3. If the Expansion Module drain hose heater circuit LED does light then use the HMI Control Panel amps
gauge to check the current drawn by the hot gas solenoid, while operating the drain hose heater with
Interface Board Test Mode. The current draw should be approximately 0.5 to 6 amps (1 to 12 amps if
parallel evaporators). If the current is not within limits then check for a short circuit, open circuit or loose
ground connection as shown in Step 4. Verify that all circuit connectors are secure.
4. If the Expansion Module drain hose heater circuit LED does not light then disconnect the Expansion
Module 35 pin connector J1 and check the circuit with an accurate ohmmeter for a short circuit, open
circuit or loose connection.
5. If no problems are found in steps 1-4 and the output LED does not turn on then replace the Expansion
Module.
5-121
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
The SR-2 Control Platform utilizes CAN communications to pass information back and forth between the base
controller, HMI control panel and the expansion module. These cables are connected to the Interface Board as
shown here.
J12 – Connects the base controller to the expansion module.
J14 – Connects the base controller to the HMI control panel.
Diagnostic Procedure
1. Check all CAN cables to be sure they are connected securely.
5-122
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Circuit Description
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
4. Check for a defective HMI Control Panel if there is voltage on pin 6 of the HMI Control Panel connector.
5-123
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
How Alarm is Set
1. If single temp software is detected in a unit with an expansion module connected then set Alarm Code
146 as a shutdown alarm.
Diagnostic Procedure
Flash load the correct software. See Section 7 of this manual for the compatible software.
5-124
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
How Alarm is Set
1. If the fan speed feedback control is not within 10% of the requested value then set Alarm Code 147 as a
check alarm.
Diagnostic Procedure
Download the ServiceWatch data logger using Wintrac. Review the data using Technician Level to determine the
conditions at the time the alarm was set. Conditions relevant to the alarm are recorded when the alarm is set and
cleared. This data can be very helpful in determining the cause of the alarm.
2. On remote zones with single evaporators, the fan speed output will be approximately 0 volts during fresh
setpoint operation and 4-5 volt during frozen operation.
3. On remote zones with dual evaporators, the fan speed output will be approximately 4-5 volts during fresh
setpoint operation and 3-4 volts during frozen operation.
5-125
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Diagnostic Procedure
1. Check for associated alarms and repair as required.
5-126
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
Associated Alarm
Codes
Component Description and Location
The Expansion Module is located inside the control box.
Circuit Description
The expansion module allows the addition of up to two additional temperature controlled zones. The module
provides the interface between the base controller and the zone 1, zone 2 and zone 3 multi-temperature
components such as sensors, solenoids, valves, and fan motors. It also provides overcurrent and short circuit
protection for the associated circuits.
Diagnostic Procedure
The Expansion Module software is automatically flash loaded any time software is flash loaded to the SR-2
Controller. Software cannot be flash loaded directly to the Expansion module – it is always part of an SR-2
Controller flash load. See Service Procedure A46A Flash Loading SR-2 Controller Software for flash load details.
1. Check the CAN cable from J12 on the Interface Board to the 8 pin CAN connector on the Expansion
Module. Be sure connections are secure and all pins are fully seated in the connector.
5-127
02 February 2007
Section 5 – SR-2 SPECTRUM Diagnostics
5-128
02 February 2007
THERMO KING
TK 53080-2-OD (01/07)
DIAGNOSTIC MANUAL
PART 1 – (Sections 1-5)
PART 2 – (Sections 6-9)
Earlier versions of software are similar but may not include or support all
features as shown in this manual.
This section contains the safety information for the SR-2 SPECTRUM control system. Read this
material carefully before working on the unit.
This section describes the SR-2 SPECTRUM control system hardware. It identifies and locates
controllers, relays, LED’s, fuses and other components and provides connector maps for all
connectors.
This section discusses the operation of the SR-2 SPECTRUM control system software and
programmable features. Each menu and feature is discussed individually to illustrate how they
are used.
• Section 4 - Operation
This section explains how to operate the SR-2 SPECTRUM control system. This information is
referenced by material in Section 5 Diagnostics.
• Section 5 - Diagnostics
This section explains how to diagnose units equipped with the SR-2 SPECTRUM control system.
It includes both Alarm Code Diagnostics and Other Symptom Diagnostics. This section will
reference material in Section 4 Operation and Section 6 Service Procedures.
This section includes Service Procedures to assist the technician when servicing units equipped
with the SR-2 SPECTRUM control system. These procedures are referenced by the diagnostic
routines in Section 5 Diagnostics.
This section offers Service Information on the basic component parts of the SR-2 SPECTRUM
control system. It includes a software revision history and a list of applicable bulletins.
This section includes Refrigeration Service Procedures to assist the technician when servicing
SR-2 SPECTRUM Multi-Temperature units.
This section includes the SR-2 SPECTRUM control system electrical schematics and unit wiring
diagrams.
The following procedures must be followed when working on units equipped with
microprocessor based control systems.
• Never use testers consisting of a battery and a light bulb to test circuits on any
microprocessor based equipment.
• The unit must be turned off before connecting or disconnecting the battery.
•Any time the Base Controller is replaced, these Service Procedures must be
used:
A02A Recording Existing Programmable Feature Settings
A03A Replacement of the Base Controller or Interface Board
A04A Programmable Feature Setup
• Any time welding is to be done on the unit or vehicle Service Procedure A26A
Welding on Units Equipped with Microprocessors must be followed.
This manual is published for informational purposes only and the information so provided should
not be considered as all-inclusive or covering all contingencies. If further information is required
Thermo King Corporation should be consulted.
Sale of product shown in this manual is subject to Thermo King's terms and conditions
including, but not limited to, the THERMO KING LIMITED EXPRESS WARRANTY. Such
terms and conditions are available upon request. Thermo King's warranty will not apply to
any equipment which has been "so repaired or altered outside the manufacturer’s plants
as, in the manufacturer’s judgment, to affect its stability".
Page 1
05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure Index
Page 2
05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To confirm proper operation of the microprocessor and interface board
Table of Contents
Microprocessor/Interface Board Functional Test....................................................................................................... 1
Materials Required ................................................................................................................................................. 1
Operation ............................................................................................................................................................... 2
Important Notes...................................................................................................................................................... 2
Important PC Notes ............................................................................................................................................... 2
Diagnostic Procedure............................................................................................................................................. 3
Materials Req
uired
IMPORTANT A new Diagnostic Tool (Service Part 3 204-1196) and Diagnostic Tester Software 3.0.0 or greater
is required to test the SR-2/C Base Controller/Interface Board. This tester will also work on previous SR-2 Single
Temp base controllers and interface boards. The new tester can be identified by the blue plastic housing. An
upgrade kit (Service Part # 204-1197) is available to upgrade the original Service Part 204-1102 Diagnostic Tool
to the current standards. The new tester is required for the SR-2/C Base Controller/Interface Board, but not the
HMI Control Panel.
Revision 3.0.0 software will prompt the user that the blue Diagnostic Tool is required.
Page 1
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Operation
The following procedure allows the technician to determine if the microprocessor or interface board is operating
properly using the Thermo King SR-2 Diagnostic Tool.
Important Notes
x Supply power from know good battery, a suitable power supply or by connecting a battery charger to the
unit battery. Low voltage caused by low unit battery will affect results. The threshold for battery power
influencing test results appears to be about 11.5 VDC.
x When testing a microprocessor, supply power to the interface board, not the tester. Supplying power to
the tester may result in a communication failure.
x Be certain to make secure connections both when attaching the tester and when reconnecting the unit
wiring harnesses.
x Never accept an initial failure. Always retest to confirm. If component fails the test, be sure wiring is
connected correctly.
Important PC Notes
The following notes apply to the pc computer used in conjunction with the Thermo King SR-2 Diagnostic Tool.
x The SR-2 Diagnostic Tool may not function properly on pc computers running Windows ME.
x The pc computer must be set for English. Select Control Panel – Regional and Language Options. Then
use the Regional Dropdown menu to select English.
x The pc computer must be set to use the decimal point (.) for the decimal symbol, not the comma (,). If a
comma is used it will be ignored – 12,3 will be read as 123. Select Control Panel – Regional and
Language Options – Customize – Decimal Symbol – select (.) instead of (,).
Page 2
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Diagnostic Procedure
The TKSR-2 Diagnostic Tool will be referred to as the “T ester”in this proc edure.
Step Action Result Comments
Microprocessor/Interface
Board Assembly Test
1 Turn the Microprocessor On/Off Failure to do so may damage the
switch off. microprocessor or interface
board.
4 Connect a serial cable from the The serial cable must be The TK Diagnostic Tool will be
left side tester serial port to a pc connected to the left side Tester referred to as the “Tester” in
computer. serial connector for the base this procedure.
controller/interface board test.
5 Start the TK Diagnostic Tool The TK Diagnostic Tool Software The TK Diagnostic Tool will be
software on the computer. will also provide step by step referred to as the “Tester” in
connection and test instructions. this procedure.
Page 3
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
7 From the Tester software menu Use SR2 SB Series for all SB
select “SR2 SB Series” or “SR2 units with damper solenoids.
SL Series”.
Use SR2 SL Series for all SL
units with damper motors.
Page 4
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Page 5
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
20 If the assembly failed the test, The test results will indicate if a
check the test results for possible problem exists with the
causes and correct as directed. microprocessor or interface
board.
Page 6
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Page 7
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01A
Page 8
P41SA01A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To confirm proper operation of the HMI Control Panel
Materials Required
IMPORTANT A new Diagnostic Tool (Service Part 3 204-1196) and Diagnostic Tester Software 3.0.0 or greater
is required to test the SR-2/C Base Controller/Interface Board. This tester will also work on previous SR-2 Single
Temp base controllers and interface boards. The new tester can be identified by the blue plastic housing. An
upgrade kit (Service Part # 204-1197) is available to upgrade the original Service Part 204-1102 Diagnostic Tool
to the current standards. The new tester is required for the SR-2/C Base Controller/Interface Board, but not the
HMI Control Panel.
Operation
The following procedure allows the technician to determine if the HMI Control Panel is operating properly using
the Thermo King SR-2 Diagnostic Tool.
Page 1
P41SA01B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
Important Notes
x Supply power from know good battery, a suitable power supply or by connecting a battery charger to the
unit battery. Low voltage caused by low unit battery will affect results. The threshold for battery power
influencing test results appears to be about 11.5 VDC.
x When testing an HMI Control Panel, supply power from the interface board, not the tester. Supplying
power from the tester may result in a communication failure.
x Be certain to make secure connections both when attaching the tester and when reconnecting the unit
wiring harnesses.
x Never accept an initial failure. Always retest to confirm. If component fails the test, be sure wiring is
connected correctly.
x There is a Display Self Test included in the Maintenance Menu. See Section 4 and Service Procedure
A01C for details.
Important PC Notes
The following notes apply to the pc computer used in conjunction with the Thermo King SR-2 Diagnostic Tool.
x The SR-2 Diagnostic Tool may not function properly on pc computers running Windows ME.
x The pc computer must be set for English. Select Control Panel – Regional and Language Options. Then
use the Regional Dropdown menu to select English.
x The pc computer must be set to use the decimal point (.) for the decimal symbol, not the comma (,). If a
comma is used it will be ignored – 12,3 will be read as 123. Select Control Panel – Regional and
Language Options – Customize – Decimal Symbol – select (.) instead of (,).
Page 2
P41SA01B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
Diagnostic Procedure
The TK Diagnostic Tool will be referred to as the “Tester” in this procedure.
Step Action Result Comments
HMI Control Panel Test
1 Turn the Microprocessor On/Off Failure to do so may damage the
switch off. microprocessor or interface
board.
3 Connect a serial cable from the The serial cable must be The TK Diagnostic Tool will be
right side tester serial port to a pc connected to the right side referred to as the “Tester” in
computer. Tester serial connector for the this procedure.
HMI Control Panel test.
Page 3
P41SA01B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
Page 4
P41SA01B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
9 Follow the prompts as shown Press any key to step thru the
below to connect the tester to the connection prompts shown on
HMI Control Panel under test. the pc.
Page 5
P41SA01B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A01B
18 If the assembly failed the test, The test results will indicate if a
check the test results for possible problem exists with the HMI
causes and correct as directed. Control Panel.
Page 6
P41SA01B 06 February 2007
Section 6 – SR-2 Service Procedure A01C
Where Used
All SR-2 units
Purpose
To confirm proper operation of the HMI Control Panel using the built in Display Self Test
Materials Required
x None
Operation
The following procedure allows the technician to determine if the HMI Control Panel is operating properly using
the built in HMI Self Tests.
Important Notes
x Replace only one component at a time to be certain the problem component is correctly identified.
Page 1
P41SA01C 06 February 2007
Section 6 – SR-2 Service Procedure A01C
Diagnostic Procedure
Step Action Result Comments
HMI Control Panel Self Test
1 To access the Maintenance
Menu press the MENU key.
Page 2
P41SA01C 06 February 2007
Section 6 – SR-2 Service Procedure A01C
Page 3
P41SA01C 06 February 2007
Section 6 – SR-2 Service Procedure A01C
x LCD Test – This test allows the technician to select a normal or inverted display. If inverted is chosen the
display is reversed – segments that were turned on are now turned off and segments that were turned off
are now turned on. The technician visually verifies that all display segments are functioning properly.
x Keypad Test – This test prompts the technician to press the four soft keys, the Defrost key and the Cycle
Sentry key. Each time the requested key is pressed the next prompt is displayed, allowing the technician
to verify proper operation of these keys.
x Backlight Test – This test allows the technician to turn the backlight on and off to confirm operation.
x Brightness Test – This test allows the technician to select Low, Medium or High backlight intensity.
x Buzzer Test – This test allows the technician to turn the HMI buzzer on and off to verify operation.
x Heater Output – This test allows the technician to turn the HMI display heater on and off.
x Unit On/Off Output Test – This test allows the technician to turn the Unit On/Off output off. This turns
the unit off to confirm that the output can be turned off. To restart the unit, press the On key.
x SPR Digital Output Test – This test allows the technician to turn digital output 2 on and off. This allows
the operation of a device attached to the this output to be checked.
x Serial E2 – This test allows the technician to perform an internal HMI memory test. The test takes less
than 1 second and the results are reported as PASS or FAIL.
x Datalog Flash – This test allows the technician to perform an internal HMI CargoWatch data logger
memory test. The test takes less than 1 second and the results are reported as PASS or FAIL.
x RTC Update – This test allows the technician to perform an internal HMI real time clock test. The test
takes less than 3 seconds and the results are reported as PASS or FAIL.
Page 4
P41SA01C 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To confirm proper operation of the SR-2 SPECTRUM Expansion Module using Interface Board Test Mode
Materials Required
x Accurate digital multimeter.
Operation
The following procedure allows the technician to determine if the SR-2 SPECTRUM Expansion Module is
operating properly.
Important Notes
x Replace only one component at a time to be certain the problem component is correctly identified.
x Under normal unit operation the SmartFET and associated LED for that output will be turned off if an
overcurrent or undercurrent condition exists.
x When using Interface Board Test Mode the SmartFET and associated LED will be on if an undercurrent
condition exists (such as an open solenoid coil). The SmartFET and associated LED will be off if an
overcurrent condition exists (such as a short to ground).
x The expansion module communicates with the base controller via a CAN bus connection.
Page 1
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
Diagnostic Procedure
Step Action Result Comments
Expansion Module Test
This test assumes that a
particular output is to be tested to
verify proper operation.
1 Turn the unit on and check the See the LED location at the back Green Status LED– Flashes
Expansion Module green Status of this procedure or the once per second when the base
LED. The green Status LED Expansion Module LED Location controller is powered and
should be flashing once per decal on the control panel door operating normally.
second when the base controller for LED locations.
is powered and operating Flashes several time per second
normally. when flash loading.
If the Status LED is flashing once Flashes twice within one second
per second go to Step 9. followed by one second off if a
CAN communication error is
present.
Page 2
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
Page 3
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
9 If the Status LED is flashing once The LED for the desired output See Section 4 for information on
per second then use Interface should turn on. operating Interface Board Test
Board Test Mode to energize the Mode.
desired output and lock it on.
11 If the desired output LED will not If a short circuit condition exists
turn on using Interface Board the output SmartFET will turn the
Test Mode there may be a short output off even though the
in the associated circuit. Expansion Module has turned it
on. If this occurs it will happen
so fast the LED will not turn on or
even blink.
Page 4
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
Page 5
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A01D
LED Functions
Expansion Module LED Functions
LED # Function
Output LEDs are provided to indicate outputs that
LED 1 Fan Output # 1 / Zone-2 Damper
are energized. These LED indicators are located in
Solenoid.
the corner of the expansion module body. They are
LED 2 Fan Output # 3
defined by the table below. The LED is illuminated
LED 3 Fan Output # 5
when the associated circuit output is energized.
LED 4 Fan Output # 2
LED 5 Fan Output # 4
LED 6 Fan Output # 6
LED 7 Zone 1 Drain Tube Heater Output Note1
Page 6
P41SA01D 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To retrieve and record the current settings of a microprocessor
Materials Required
x Prepare a copy of the Setup Sheet at the back of this Service Procedure.
Operation
x The settings of all programmable features must be retrieved before replacing a microprocessor or
performing a Cold Start. These settings will then be duplicated in the replacement microprocessor or
after the Cold Start.
x The Guarded Access Menu Overview on the next page will prove helpful.
x See Section 3 of this manual for a complete description of programmable features.
x The default settings are shown on the Setup Sheet at the back of this Service Procedure.
x If a sensor grade is not shown on the setup sheet physically check the sensor to determine the grade. It
is important that sensor grades be set properly.
Page 1
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 2
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 3
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Procedure
Consult the Guarded Access Menu Overview on the previous page for specific menu information.
Step Action Result Comments
1 Turn the unit on.
2 Press the MENU key. The Operator Menu appears. Do not let the unit start. The
Guarded Access Menu can not
be entered in the unit is running.
3 Press and hold both the EXIT The Maintenance Menu appears.
and unlabelled key for 5
seconds.
Page 4
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
8 Check the Time to determine the Record the time zone on the Compare local time to unit time
time zone used by the customer. Setup Sheet. to determine time zone.
9 Be sure the unit is not running. If the unit is running, scroll back
and enter Interface Board Test
Mode. This will cause the unit to
shut down. Scroll back to the
Set Time and Date Menu and
proceed with the next step.
10 Press and hold both the EXIT The Guarded Access Menu If a Security Code is requested
and unlabelled key for 5 appears. then enter the Security Code or
seconds. [4444] to enter the Guarded
Access Menu.
Page 5
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 6
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 7
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
27 Use the NEXT and/or BACK Record the grade of each sensor
keys to scroll through all on the Setup Sheet.
sensors.
Page 8
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
30 Use the NEXT and/or BACK Record the setting of each Cycle
keys to scroll through the Cycle Sentry feature on the Setup
Sentry settings. Sheet.
32 When the Guarded Access Menu The Defrost Setup Menu will
is shown press the NEXT key to appear.
access the Defrost Setup Menu.
Then press the Select key to
enter the Defrost Setup Menu.
Page 9
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 10
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
43 Use the NEXT and/or BACK Record the setting of each Unit
keys to scroll through the Unit Configuration feature on the
Configuration settings. Setup Sheet.
Page 11
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 12
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Setup Sheet
SOFTWARE REVISION
Compare local time to unit time to determine time zone. The real time clock is located in the HMI Control Panel.
The time is supplied to the microprocessor each time the unit is turned on. If the microprocessor is changed the
clock setting will be supplied to the microprocessor when the unit is turned on. If the HMI Control Panel is
changed the time and date must be checked and set if necessary.
Function Default Setting Recorded Setting
Time Zone As specified by
customer
SECURITY CODE
Page 13
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
PROGRAMMABLE FEATURES
Page 14
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 15
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
SENSOR CALIBRATION
Page 16
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
DEFROST SETUP
LANGUAGE SETUP (First language = 65xx, second language 66xx, third language = 67xx)
Page 17
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
OPTISET
Page 18
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
UNIT CONFIGURATION
Page 19
P41SA02A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A02A
Page 20
P41SA02A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A03A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To replace the base controller or interface board
Materials Required
x Cable ties
Operation
The base controller and interface board are removed from the control box as an assembly. They are separated
on the bench and the defective component is replaced.
Important Notes
x Be sure the harnesses are reconnected properly and do not place excessive strain on the connectors.
Secure the harnesses with cable ties as required.
Page 1
P41SA03A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A03A
Diagnostic Procedure
Step Action Result Comments
1 If possible,log existing ba se This information will be used
controller setting using Service to set up the replacement
Procedure A02A. This step is base controller.
not necessary if replacing the
interface board.
Page 2
P41SA03A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A03A
Page 3
P41SA03A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A03A
Page 4
P41SA03A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A03B
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To replace the HMI Control Panel
Materials Required
x Cable ties
Operation
The HMI Control Panel is removed from the control box as an assembly.
Important Notes
x Be sure the harnesses are reconnected properly and do not place excessive strain on the connectors.
Secure the harnesses with cable ties as required.
Page 1
Diagnostic Procedure
Step Action Result Comments
1 Turn the unit off.
Page 2
12 Check the setting of the real time The clock may also be set by
clock as shown in Section 4 and connecting to the
correct if necessary. CargoWatch Datalogger with
Wintrac 4.6
13 Run a Full Pretrip Test as shown
in Section 4 to verify proper unit
operation.
Page 3
Page 4
Where Used
All SR-2 Spectrum Multi-Temp units
Purpose
To replace the SPECTRUM Multi-Temp Expansion Module
Materials Required
x Cable ties
Operation
The expansion module is removed from the control box as an assembly. It has no user repairable parts.
Important Notes
x Be sure the harnesses are reconnected properly and do not place excessive strain on the connectors.
Secure the harnesses with cable ties as required.
Page 1
Diagnostic Procedure
Step Action Result Comments
1 Turn the unit off.
Page 2
Page 3
Page 4
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To program sensor grades and programmable features to customer specifications
Materials Req
uired
x A completed copy of the Setup Sheet at the back of Service Procedure A02A Recording Existing
Programmable Feature Settings.
Operation
x The settings of the programmable features must be programmed after replacing a base controller or
performing a Cold Start.
x The Programming Menu Overview on the next page may prove helpful.
x See Section 3 for a complete description of programmable features.
x The default settings are shown on the Setup Sheet at the back of Service Procedure A02A Recording
Existing Base controller Settings.
x If a sensor grade is not shown on the setup sheet visually check the sensor to determine the grade. It is
very important that sensor grades be set properly.
Page 1
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
~C ontinued Nex
t Page ~
Page 2
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Page 3
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Procedure
Consult the Programming Menu Overview on the previous page for specific menu information.
Step Action Result Comments
1 Turn the unit on.
3 Press and hold both the EXIT The Maintenance Menu appears.
and unlabelled key for 5
seconds.
5 Use the NEXT and/or BACK Verify the Software revisions are
keys to scroll through the HMI as desired.
Control Panel and Base
Controller software revisions.
Page 4
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
9 Press and hold both the EXIT The Guarded Access Menu If a Security Code is requested
and unlabelled key for 5 appears. enter the Security Code or
seconds. [4444] to enter the Guarded
Access Menu.
Page 5
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Page 6
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Page 7
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
30 When the Cycle Sentry Menu is The Cycle Sentry Setup Menu
shown press the Select key to will appear.
access the Cycle Sentry Setup
Menu.
31 Use the NEXT and/or BACK Set each Cycle Sentry setting to
keys to scroll through the Cycle that shown on the Setup Sheet.
Sentry settings.
Page 8
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
35 Use the NEXT and/or BACK Set each Defrost setting to that
keys to scroll through the Defrost shown on the Setup Sheet.
features.
38 When the Language Setup Menu The Language Setup Menu will
is shown press the Select key to appear.
access the Language Setup
Menu.
Page 9
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
43 When the Sensor Configuration The Sensor Configuration Menu The Sensor Configuration menu
Menu is shown press the Select will appear. is used to set up the Cargo
key to access the Sensor Watch data logger.
Configuration Menu.
Page 10
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Page 11
P41SA04A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A04A
Page 12
P41SA04A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To perform a Cold Start
Materials Req
uired
x None
Operation
This procedure will perform a Cold Start on the base controller. All programmable features are reset except
hourmeters and Service Watch data logger. The Cold Start can be performed by means of an Interface Board
jumper or by using Wintrac. Both methods are shown here.
IMPORTANT: All programmable features such as sensor calibration, defrost settings and feature settings will be
returned to the standard (default) settings. They must be set up using Service Procedures A04A after performing
a Cold Start or the unit may not operate to the customer’s requirements.
Page 1
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
3 Locate the J101 jumper on the It is located in the upper center See the illustration on the
relay board. of the interface board. next page.
6 Turn the unit on and check for This confirms the Cold Start
Alarm Code 74 Controller Reset was successful.
to Defaults.
Page 2
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
J4 F2
LED7 CAN 3 CAN 2 CAN 1
J14 J13 J12
F13
REMOTE LIGHT
15A
K5 J8
2A
ON/OFF
SWITCH
F10
K4 F9 F12 F8 2A
3A 5A 5A
10A
LED4 F7 LED23 K9
J27 J6
ELECTRIC
LED26
K3
RS232-1 RS232-2
J9 J10
15A
F6
LED5
LED6
J102 J103 F11
J101 K1 F4
J15
10A
29 7D F15
GM1
8
DF
F12
LED21
GM2
8S
K8
LED25 LED17
8D 8DP
LED24 LED18
LED22
LED19
LED20
K6 K7
J23
40A LED8 CH
J24 F3 LED9
2 LED10
LED11
LED3
F20 2A F25
60A
7.5A
LED30
F5
LED27
J25 2A H LED29
K2
LED28
J26
J3
1
J7
Page 3
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
9 Turn the unit on. The following Alarm Code 74 indicates the The sensor codes will not
Alarm Codes will be present: Cold Start was successful. The clear until the sensor grades
Alarm Code 74 other alarm codes exist because have been set properly set.
Alarm Code 92 the sensor grades have been set The sensor codes and code
All Graded Sensor Alarm to 5H. Alarm Code 92 will clear 74 may be cleared in the
Codes when the sensor grades are Alarms Menu.
properly set.
Page 4
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
5 From the Wintrac display press The Tool Menu appears in the
CTRL-SHIFT-T to enable the Wintrac menu bar.
Wintrac Tool Menu
Page 5
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A07
A
9 Turn the unit on. The following Alarm Code 74 indicates the The sensor codes will not
Alarm Codes will be present: Cold Start was successful. The clear until the sensor grades
Alarm Code 74 other alarm codes exist because have been properly set. The
Alarm Code 92 the sensor grades have been set sensor codes and code 74
All Graded Sensor Alarm to 5H. Alarm Code 92 will clear may be cleared in the Alarms
Codes when the sensor grades are Menu.
properly set.
Page 6
P41SA07A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A15A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To calibrate the sensor grades of replacement Return Air Sensors and Discharge Air Sensors
Materials Req
uired
x None
Operation
The control and display return air temperature sensors and the control and display discharge air temperature
sensors are graded sensors. Any time these sensors are replaced the grade of the new sensor must be correctly
entered to insure optimum performance of the unit. The sensor grade is stamped on the barrel of each
replacement sensor. Failure to properly calibrate sensors may result in nuisance alarm codes.
Important Notes
x Always record the sensor grades of any replacement return or discharge temperature sensors. The
grade is required to complete the sensor calibration procedure.
x If a sensor grade is set 5H then Alarm Code 92 Sensor Grades Not Set will occur.
Page 1
P41SA15A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A15A
Diagnostic Procedure
Step Action Result Comments
1 Verify the sensor grades by
physically checking the sensor.
Record the grades of the Control
and Display Return Air and/or
Discharge Air sensors.
4 Press and hold both the EXIT The Maintenance Menu appears.
and unlabelled key for 5
seconds.
5 Press the NEXT key as required The Set Time and Date Menu
to display the Set Time and Date appears.
Menu.
6 Press and hold both the EXIT The Guarded Access Menu
and unlabelled key for 5 appears.
seconds.
8 When the Sensor Calibration The first graded sensor and the
Menu is shown press the current grade appear.
SELECT key to access the
Sensor Calibration Menu.
Page 2
P41SA15A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A15A
Page 3
P41SA15A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A15A
Page 4
P41SA15A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A26A
Welding on Units Eq
uipped with SR-2 Microprocessor s
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To prevent damage to the microprocessor during welding operations
Materials Req
uired
x None
Operation
Electric welding generates extremely high amperage currents that can damage electrical and electronic
components. In order to minimize the possibility of damage the following procedures must be followed.
Page 1
P41SA26A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A26A
Before Welding
Step Action Result Comments
1. Turn the unit off.
After Welding
Step Action Result Comments
1. Reconnect the battery cable.
Page 2
P41SA26A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A28
A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
This procedure should be followed to set the fixed running time hourmeters Total Hours, Total Run Time Hours,
Engine Hours, Electric Run Time Hours and Zone Run Hours after replacing a microprocessor with a new
replacement microprocessor. If all hourmeters have less than 100 hours accumulated, time can be added to
them as shown in this procedure. If hourmeter time exceeds 100 hours, the hourmeter time can no longer be
changed.
Materials Req
uired
x None
IMPORTANT: Time can only be added if all hourmeters have less than 100 hours accumulated. If hourmeter
time exceeds 100 hours, the hourmeter time can no longer be changed.
IMPORTANT: If time in excess of 100 hours has been entered the hourmeters can no longer be changed.
Exercise care when changing these hourmeter settings. Be sure the correct number of hours are selected for
each hourmeter.
IMPORTANT: Do not allow the 3 minute Guarded Access keypad timeout to occur during this procedure. If the
keypad times out before all desired changes are made and an hourmeter exceeds 100 hours, the hourmeters can
no longer be changed.
IMPORTANT: Do not exit hourmeter setup until all hourmeters have been set as required. Once the hourmeter
setup has been exited this menu is locked out and the hourmeters can no longer be changed.
Page 1
P41SA28A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A28
A
Procedure
Step Action Result Comments
1 Determine the number of hours
to be set on each hourmeter. If
the unit is a Model 50 unit, be
sure the total of Engine Hours
and Electric Run Time Hours is
equal to the number of hours to
be set as Total Run Time Hours.
3 Press the MENU key. The Main Menu appears. Press the MENU key.
4 Press and hold both the EXIT The Maintenance Menu appears.
and unlabelled key for 5
seconds.
6 Press and hold both the EXIT The Guarded Access Menu
and unlabelled key for 5 appears.
seconds. If a Security Code is
requested enter the Security
Code or [4444] to enter the
Guarded Access Menu.
Page 2
P41SA28A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A28
A
11 Press and hold both the EXIT This will add the non- IMPORTANT: Do not exit the
and unlabelled key for 5 programmable hourmeters to the hourmeter setup or allow the
seconds. menu only if these hourmeters Guarded Access keypad
are less than 100 hours. timeout to occur during this
procedure. If the keypad
times out and an hourmeter
exceeds 100 hours, the
hourmeters will be locked and
can no longer be changed.
Page 3
P41SA28A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A28
A
Page 4
P41SA28A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To update software for the Thermo King SR-2 base controller using a computer and Wintrac 4.6 or later software
Materials Req
uired
The following materials are required to perform a flash load.
x Interconnect Cable, Thermo King Service Part Number TK 44-9417 (20 foot, 6 meter) or TK 44-9418 (50 foot,
15 meter).
x Adapter Cable, Thermo King Service Part Number TK 204-918, 15 Pin “D” connector to 5 pin Deutsch.
SR-2/C Multi-Temp (SR-2 SPECTRUM Multi-Temp applications must use revision C0x
xsoft ware)
Microcode Update C0xx for SR2 Microprocessor.exe (where xx = the software revision)
IMPORTANT: There are also flash load files for the SR2 HMI Control Panel. Be sure to select the file for SR2
Microprocessor.
Page 1
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Create a sub-directory and detach or download the necessary file or files. The files must then be prepared for
use.
1. Using Windows Explorer locate the sub-directory containing the files. The files will be in the format:
SR-2/C Multi-Temp (SR-2 SPECTRUM Multi-Temp applications must use revision C0x
xsoft ware)
Microcode Update C0xx for SR2 Microprocessor.exe (where xx = the software revision)
2. Double click the desired file. The file will be uncompressed and installed in the sub-directory
Wintrac\Flashload\SR2. If this directory does not exist it will be created automatically. There will be two files
in this sub-directory. However, only one file will appear when the directory is displayed by Wintrac.
The software files are now ready for flash loading using Wintrac.
Page 2
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Data Cable The data cable has a 9 pin “D” connector installed on one end to attach to the computer and a 15 pin
“D” connector on the other end. The cable is available as either a 20 foot or 50 foot cable as shown below.
Adapter Cable An adapter cable is required to complete the connection to the base controller or data logger.
This cable has a 15 pin “D” connector on one end and a 5 pin Deutsch connector on the other end. The 15 pin
“D” connector is attached to the 15 pin “D” connector on the data cable and the 5 pin Deutsch connector is
attached to the Service Watch connector above the HMI Control Panel. Do not attach the cable to the Cargo
Watch connector.
The unit must remain on and connections must not be disturbed during the flash load process.
If communications are lost, Wintrac will not be able to find the device.
If the Status LED is flashing rapidly (several times per second), the base controller is stuck in a flash load.
If the Status LED is flashing once per second the base controller is operating normally.
Page 3
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
5 Turn the unit on. The unit can be The unit must remain on
running. It will shut down and connections must not
automatically during the flash be disturbed during the
load process. flash load process.
Page 4
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Page 5
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Page 6
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
16 Left click “OK” to SR-2 Base Controllers retain all the programmed
complete the flash features when being flash loaded. It is not
load. The unit will necessary to reprogram the SR-2 Base Controller
automatically restart after a flash load.
and run.
Page 7
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
The Retry flash load differs from the Full flash load as follows. Since the base controller is already in flash load
mode it does not respond to the full set of Datapac commands. Therefore, during a flash load Retry, Wintrac skips
most of the initial communications with the device and goes directly to the actual flash load routine.
Wintrac simply sends the flash load write commands. If these fail then Wintrac will generate an error. If the flash
load write succeeds then Wintrac will finish the flash load in the same way as a normal flash load.
Page 8
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Make the usual connections and start a flash load as described above. The first flash load attempt will be a Full
flash load. Since the base controller is already in flash load mode, it will not respond to the first flash load
command “Searching for Device on COM 1”. If the search continues for more than 5 seconds, click Cancel.
With a Retry flash load, Wintrac skips most of the initial communications checking with the device and goes
directly to the actual flash load routine. Wintrac simply sends the flash load write commands. If these fail then
Wintrac will generate an error. If the flash load write succeeds then Wintrac will finish the flash load in the same
way as a normal flash load. The Retry flash load will usually correct the problem.
Page 9
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46A
Page 10
P41SA46A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To change or update software for the Thermo King SR2 HMI Control Panel using a computer and Wintrac 4.6 or
later software. IMPORTANT: This flash load takes at least 10 minutes. Plan accordingly.
Materials Req
uired
The following materials are required to perform a flash load.
x Interconnect Cable, Thermo King Service Part Number TK 44-9417 (20 foot, 6 meter) or TK 44-9418 (50 foot,
15 meter).
x Adapter Cable, Thermo King Service Part Number TK 204-918, 15 Pin “D” connector to 5 pin Deutsch.
Page 1
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
Microcode Update 65xx for SR2 HMI Control Panel.exe (where xx = the software revision)
or
Microcode Update 66xx for SR2 HMI Control Panel.exe (where xx = the software revision)
The only difference between 65xx and 66xx HMI Control Panel software is language support as shown below.
IMPORTANT: There are also flash load files for the SR2 Base controller. Be sure to select the file for SR2 HMI
Control Panel.
Create a sub-directory and detach or download the necessary file or files. The files must then be prepared for
use.
Page 2
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
1. Using Windows Explorer locate the sub-directory containing the files. The files will be in the format
“Microcode Update 65xx for SR2 HMI Control Panel.exe” (where xx = the software revision)
or
“Microcode Update 66xx for SR2 HMI Control Panel.exe” (where xx = the software revision)
or
“Microcode Update 67xx for SR2 HMI Control Panel.exe” (where xx = the software revision)
2. Double click the desired file. The file will be uncompressed and installed in the sub-directory
Wintrac\Flashload\SR2. If this directory does not exist it will be created automatically. There will be two files
in this sub-directory.
The software files are now ready for flash loading using Wintrac.
Data Cable The data cable has a 9 pin “D” connector installed on one end to attach to the computer and a 15 pin
“D” connector on the other end. The cable is available as either a 20 foot or 50 foot cable as shown below.
Adapter Cable An adapter cable is required to complete the connection to the base controller or data logger.
This cable has a 15 pin “D” connector on one end and a 5 pin Deutsch connector on the other end. The 15 pin
“D” connector is attached to the 15 pin “D” connector on the data cable and the 5 pin Deutsch connector is
attached to the Cargo Watch connector above the HMI Control Panel. Do not attach the cable to the Service
Watch connector.
Page 3
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
If the HMI is turned off during a flash load it will lock up. Power will need be to removed from the HMI before the
flash load can be completed. This can be accomplished by removing the connector at the back of the HMI or by
disconnecting the unit battery).
If the power was turned off during flash load, the next flash load attempt will generate an error, but the second
attempt will flash successfully. The failure on the first attempt is 'as designed'. On the second attempt, some of
the error checking between the HMI and Wintrac is bypassed.
Page 4
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
5 Turn the unit on. The unit can be The unit must remain on
running. It will shut down and connections must not
automatically during the flash be disturbed during the
load process. flash load process.
Page 5
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
9 From the Tools menu left click A download data warning menu
“Flash Load”. appears.
10 Left click “Yes” to continue. A directory containing the flash If the file is not present,
load files appears. navigate to the file using
conventional Windows
navigation methods.
11 Double click the flash load
directory and locate the correct
flash load file.
13 If the information shown is If the unit is running it will shut The unit must remain on
correct left click “Yes” to down. This is normal. The flash and connections must not
continue. The flash load will load will take at least 10 be disturbed during the
proceed automatically. minutes. flash load process.
Page 6
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
Page 7
P41SA46B 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A46B
Page 8
P41SA46B 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To program OptiSet features
Table of Contents
Programming OptiSet Features................................................................................................................................. 1
Table of Contents................................................................................................................................................... 1
OptiSet Menu ......................................................................................................................................................... 2
OptiSet Reset......................................................................................................................................................... 2
Programming OptiSet Features ............................................................................................................................. 2
OptiSet Global Features ........................................................................................................................................ 3
OptiSet Range Limits and Range .......................................................................................................................... 3
Range Mode Settings ............................................................................................................................................ 4
OptiSet Menu Overview ......................................................................................................................................... 5
OptiSet Procedure.................................................................................................................................................. 6
Setup Sheet ............................................................................................................................................................. 11
Materials Req
uired
x Prepare a copy of the Setup Sheet at the back of this Service Procedure.
General Information
x The settings of all OptiSet programmable features must be retrieved before replacing a microprocessor or
performing a Cold Start. These settings will then need to be duplicated in the replacement
microprocessor or after the Cold Start.
x The OptiSet Menu Overview on page 5 may prove helpful.
x See Section 3 of this manual for a complete description of OptiSet programmable features.
x The default settings are shown on the Setup Sheet at the back of this Service Procedure.
Page 1
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
OptiSet Menu
The OptiSet™ Temperature Management System allows up to ten different temperature ranges to be defined and
tailored for maximum operating efficiency, as determined by customer load requirements. The term “OptiSet”
refers to both the programmable ranges and the features that can be tailored as shown below. OptiSet is
programmed using the HMI Control Panel keypad.
OptiSet Reset
OptiSet features may be reset to default settings several different ways. These should be considered when
changing OptiSet settings, to be certain that all ranges are set as desired.
x If any OptiSet features have been previously set, an OptiSet Reset is provided at the beginning of the
OptiSet menu to return all settings to the default values. If this OptiSet Reset feature is used, all OptiSet
settings are returned to factory defaults.
x If any of the four OptiSet global features (Temperature Units, Setpoint High Limit, Setpoint Low Limit, and
Fresh Frozen Range) are changed, all OptiSet settings are also returned to default settings.
x Ranges are programmed from the coldest range to the warmest range. If ranges have been programmed
and any range is subsequently changed, the range that was changed and all warmer ranges are reset to
defaults.
Feature range values are programmable when required. Only valid programmable features will be displayed as
determined by the setting of Economy Mode, Cycle Sentry Mode and Continuous Mode. If a feature is not
allowed, it will not be displayed.
Page 2
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
The global features listed below affect all other OptiSet ranges and settings. If any of these are changed, all
existing OptiSet programmable settings are returned to the default settings.
Note: Some of these settings are available in the HMI Programmable Features Menu. If OptiSet has been
programmed, then the Programmable Features screen will display “Programmed in OptiSet”. Programming of the
feature will not be allowed in the Programmable Features menu.
x Temperature Units for all zones
x Zone Setpoint High Limit for each zone
x Zone Setpoint Low Limit for each zone
x Limited Setpoints for all Zones
x Fresh Frozen Range for all zones
x Running Fans in Null
x Door Open Operation
The operation of each of these ranges can be individually customized for optimum performance as determined by
user requirements. Changing any range temperature limit will void all existing range settings above that range
and will reset that range and all ranges above it to the default configuration.
Page 3
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
These features allow the desired operating modes to be established for each range. The available modes are
selected for the range being programmed. Cycle Sentry Mode and Continuous Mode are available. Either of
these modes can be turned on or off for each range, but either Cycle Sentry or Continuous must be turned on. If
more than one mode is available in a range, it can be selected using the Mode Menu or the Mode key.
The custom features for each range are determined by the modes selected for that range.
x Cycle Sentry Mode The Cycle Sentry Null Restart Temperature, Cycle Sentry Door Open Forces and
Cycle Sentry Run Fans in Null features can be customized if Cycle Sentry mode is allowed.
x Continuous Mode The Continuous Door Open Forces and Continuous Run Fans in Null features can
be customized if Continuous mode is allowed.
Page 4
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
OptiSet
(in GA Menu)
Select
Reset
(only if OptiSet
is active)
Z
one 1 Limited Continuous
OptiSet Range
Setpoint High Setpoint #1 Door Open
0 thru 9
Limit XX Degrees Forces
Z
one 1 Limited Continuous
Cycle Sentry
Setpoint Low Setpoint #2 Door Open
On / Off
Limit XX Degrees Timeout
Z
one 2 Limited Continuous
Continuous
Setpoint High Setpoint #3 Run Fans in
On / Off
Limit XX Degrees Null
Z
one 2 Limited Cycle Sentry
Setpoint Low Setpoint #4 Null Restart
Limit XX Degrees Temperature
Z
one 3 Cycle Sentry
Fresh Frozen
Setpoint High Door Open
Range
Limit Forces
Z
one 3 Cycle Sentry
Setpoint Low Door Open
Limit Timeout
19 July 2006
Page 5
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
OptiSet Procedure
Consult the OptiSet Menu Overview on the previous page for specific menu information.
Step Action Result Comments
1 Turn the unit on.
2 Press the MENU key. The Alarm or Language selection Do not let the unit start. The
of the Main Menu appears. Guarded Access Menu can not
be entered in the unit is running.
3 Press and hold both the EXIT The Maintenance Menu appears.
and unlabelled key for 5
seconds.
4 Press the NEXT key as required If the unit is running, scroll back
to display the Set Time and Date and enter Interface Board Test
Menu. Mode. This will cause the unit to
shut down.
5 Press and hold both the EXIT The Guarded Access Menu If a Security Code is requested
and unlabelled key for 5 appears. then enter the Security Code or
seconds. [4444] to enter the Guarded
Access Menu.
Page 6
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
8 Use the NEXT and/or BACK Set or record all OptiSet Global The OptiSet Setup Sheet is
keys to scroll through all settings Features settings using page 1 located at the back of this
in the OptiSet Global Features of the OptiSet Setup Sheet. See Service Procedure. It is used to
Menu. Use the SELECT key to the OptiSet Menu Overview on specify feature settings when
choose the feature to change or page 5 or the OptiSet Setup setting up OptiSet or to record
read. Use the - and + keys to Sheet for a list of global settings. the existing settings when
change the feature to the desired For information on setting up retrieving OptiSet feature
setting. Press the YES key to OptiSet Global Features see settings. The OptiSet default
save the feature setting or the page 3 of this Service settings are shown on this sheet.
NO key to go back to change the Procedure. Additional
setting. information is available in
Section 3 of this manual.
Page 7
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Page 8
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
18 Use the NEXT and/or BACK Set or record all OptiSet Range 0
keys to scroll through all feature settings using page 2 of the
settings in the OptiSet Range 0 OptiSet Setup Sheet. For
Menu. Use the SELECT key to information on setting up OptiSet
choose the feature to change or Ranges see page 3 of this
read. Use the - and + keys to Service Procedure. Additional
change the feature to the desired information is available in
setting. Press the YES key to Section 3 of this manual.
save the feature setting or the
NO key to go back to change the
setting.
Page 9
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Page 10
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Page 11
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Page 12
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Setup Notes:
Page 13
P41SA47A 06 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure A47
A
Page 14
P41SA47A 06 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units equipped with electric standby
Purpose
To understand phase detect module operation and diagnostic procedures
Description
The phase detect module is designed to monitor 3 phase voltages from 160 volts AC thru 510 volts AC.
Brown
THERMO IK NG
9131C98G06
Blue L1
L2 0202
L3
Black
Page 1
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Operation
The brown, blue and black wires are used to sample the power at L1, L2 and L3 respectively. Operating power
from 12 to 24 VDC is supplied to the module via the #8 wire and CH wire.
When the voltage sensed rises above 180 volts AC and all three phases are present the module ER wire will
output 12-24 VDC after the conditions exist for 2 to 4 seconds. This signal informs the microprocessor that
electric standby operation is possible. If the voltage drops below 160 volts AC or a phase is lost, the output is
turned off after the condition exists for 8 to 10 seconds. The module continues to monitor the power and will
again output 12-24 VDC within 2 to 4 seconds after the voltage rises above 180 volts AC and all three phases are
present.
If phase rotation is L1, L2, L3 the 7EB wire will supply 12 to 24 VDC to energize the appropriate phase rotation
contactor. If phase rotation is L1, L3, L2 the 7EC wire will supply a chassis ground to energize the appropriate
phase rotation contactor. The 7EB and 7EC wires are interlocked to prevent both phase contactors from being
energized at once.
Connections
Connections to the module are shown in the tables below.
Power Connections
Input Description
# 8F Supplies nominal 12-24 volt DC power to the phase detect module.
CH Chassis ground
Inputs
Input Description
L1 This brown wire supplies standby power L1 to the phase detect module.
L2 This blue wire supplies standby power L2 to the phase detect module.
L3 This black wire supplies standby power L3 to the phase detect module.
Page 2
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Outputs
Output Description
7EH With 12-24 VDC is supplied, then outputs 7EB and 7EC will be at 12-24 VDC.
7EB If phase rotation is L1, L2, L3 then this wire will provide 12-24 VDC to energize the appropriate phase
rotation contactor. The 7EC wire is interlocked to prevent both phase contactors from being
energized at once.
7EC If phase rotation is L1, L3, L2 then this wire will provide 12-24 VDC to energize the appropriate phase
rotation contactor. The 7EB wire is interlocked to prevent both phase contactors from being
energized at once.
ER This wire will output 12-24 VDC 2 to 4 seconds after the voltage rises above 180 volts AC and all
three phases are present. If the voltage drops below 160 volts AC or a phase is lost and the
condition remains for 8 to 10 seconds, the output is turned off. The module continues to monitor and
will again output 12-24 VDC 2 to 4 seconds after the power returns to normal (voltage rises above
180 volts AC and all three phases are present).
Connector Pinout
Pin Wire Description
1 #8F Power to Module
2 CH Chassis ground
3 ER Power OK
4 7EH Switches the 7EC and 7EB from grounding to power logic
5 7EB Phase A-B-C
6 7EC Phase A-C-B
7 Unused
8 Unused
9 Unused
Page 3
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Page 4
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Diagnostics
Step Action Result Comments
1. Plug the standby power cord into
a known good power supply and
turn the unit on.
2. Using a Fluke Meter, test the L1, The voltage should be between
L2, and L3 circuits at the input to 200 - 500 VAC between circuits.
the terminals where the Brown, If not, repair as necessary to
Blue and Black wires are supply the needed voltage to the
connected. unit.
3. Check the #8F and CH circuits to If this power is not present, check
the phase detect module. 12-24 the #8 circuit from the On/Off
VDC must be present from #8F to switch.
CH.
4. If correct power is present in the If power is not present replace Removal and replacement of the
test above then the ER circuit on the phase detect module. phase detect module is detailed
the interface board should have on a previous page.
12-24 VDC present.
6. If the unit is calling for operation If neither contactor is energized Removal and replacement of the
(LED 6 is on) one of the phase check for 12-24 VDC. If voltage is phase detect module is detailed
select contactors should be not present replace the phase on a previous page.
energized. detect module.
Page 5
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A48
A
Page 6
P41SA48A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A49A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units equipped with optional CargoWatch sensors
Purpose
To understand, use and diagnose the CargoWatch Data Logger
Description
The CargoWatch Datalogger is contained within the HMI Control Panel. This datalogger conforms to European
standard EN12830. The data logger supports up to 6 optional temperature sensors and 4 digital inputs. These
optional sensors are not the same as the temperature sensors used to control the unit. N
ote that the CargoWatch
data logger does not record unit sensors. Unit sensors and other unit operating data are recorded by the
ServiceWatch data logger.
Page 1
P41SA49A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A49A
Temperature Sensors
The sensors used for the CargoWatch data logger are RTD thermistor type sensors that differ from the sensors
used for unit control. These sensors are different than the unit temperature sensors. The Service Part number
for optional CargoWatch sensors is 41-5436. CargoWatch sensors can be identified by:
x N
o shrin k tubing over sensor barrel
x Shorter sensor barrel than unit sensors
x N
o sen sor grades
°F °C Ohms
-20°F -29°C 166,356
-10°F -23°C 115,757
0°F -18°C 86,501
10°F -12°C 61,737
20°F -7°C 47,070
30°F -1°C 34,374
32°F 0°C 32,650
40°F 4°C 26,688
50°F 10°C 19,904
60°F 16°C 15,002
70°F 21°C 11,944
80°F 27°C 9,166
90°F 32°C 7,402
100°F 38°C 5,775
Page 2
P41SA49A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A49A
The HMI Control Panel will update the SR-2 Controller and the ServiceWatch data logger with the correct time
and date each time the unit is turned on.
Downloads
To download the datalogger connect the download cable to the CargoWatch port on the unit. Downloads are
obtained using Wintrac4.6.
Printing Reports
Trip Reports and Delivery Reports can be directly printed. The printer must be connected to the printer port
connector located inside the unit control box. This port may be routed to the outside of the unit as required by the
individual user.
Programmable Features
The CargoWatch data logger programmable features are set from the Sensor Configuration Sub-menu in the
Guarded Access menu. The sensor features allow the logging interval to be set and the sensors and digital
inputs to be enabled, named, and tailored to customer requirements. The flowchart on the next page illustrates
the features and menu flow. See Section 3 of this manual for complete information on CargoWatch
programmable features.
Factory defaults have the Setpoint and CargoWatch Sensors 1 and 2 turned On. CargoWatch Sensors 3 through
6 and Digital Inputs 1 through 4 are turned Off.
Page 3
P41SA49A 05 February 2007
SR2 MENU OVERVIEW - GUARDED ACCESS - SENSOR CONFIG MENU
From Sensor (15 Min) (Log Sensor 1) (Log Sensor 2) (Log Sensor 3) (Log Sensor 4) (Log Sensor 5) (Log Sensor 6)
Config selection S Logging N Sensor N/B Sensor N/B Sensor N/B Sensor N/B Sensor N/B Sensor N/B
in Guarded Interval Config Config Config Config Config Config
Access Menu S S S S S
S
(Sensors 1 & 2 On, Sensor Sensor Sensor Sensor Sensor Sensor (Sensors 1 & 2 On,
Sensors 3-6 Off) Logging Logging Logging Logging Logging Logging Sensors 3-6 Off)
N/B N/B N/B N/B N/B N/B
Ind Sensor Ind Sensor Ind Sensor Ind Sensor Ind Sensor Ind Sensor
(Log Sensor X) (Log Sensor X)
#1: Name #2: Name #3: Name #4: Name #5: Name #6: Name
N/B N/B N/B N/B N/B N/B
Out-of-Range Out-of-Range Out-of-Range Out-of-Range Out-of-Range Out-of-Range
(On) (On)
Checking Checking Checking Checking Checking Checking
N/B N/B N/B N/B N/B N/B
Page 4
(-6.0°) Low Low Low Low Low Low (-6.0°)
(Off) Italian Option Italian Option Italian Option Italian Option Italian Option Italian Option (Off)
B B B B B B
Sensor Sensor Sensor Sensor Sensor Sensor
(Off) (Off)
Averaging Averaging Averaging Averaging Averaging Averaging
S S S S
(Digital 1 On, Door Open Door Open Door Open Door Open (Digital 1 On,
Digital 2-4 Off) Logging Logging Logging Logging Digital 2-4 Off)
B B B B
(Digital Input Digital Input Digital Input Digital Input Digital Input (Digital Input
#X Name) #1 #2 #3 #4 #X Name)
Section 6 – SR-2 and SR-2 M/T Service Procedure A49A
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To understand and use the ServiceWatch Data Logger
Description
The ServiceWatch Data Logger is contained within the SR-2 base controller.
To change the time and date with Wintrac the download cable must be connected to the CargoWarch port to
change the time and date in the HMI Control Panel. The HMI Control Panel will then update the base controller
and the ServiceWatch data logger when the unit is turned off and back on. Time and date can not be changed by
connecting directly to the ServiceWatch datalogger with Wintrac.
Downloads
Downloads are obtained using Wintrac 4.6
Page 1
P41SA50A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
4 Left click the Truck Icon in the of Wintrac will connect to the SR-2
the Wintrac menu bar. and display the Unit Serial
N
umb er, Trailer N
u mber, SR-2
Serial u
Nmbe r and SR-2
Software Revision.
Page 2
P41SA50A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
Page 3
P41SA50A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
8 Left click the Tool Menu and The Technician Level is enabled
select Enable Technician User and if a file is currently open the
Level. message shown below will
appear.
10 Left click the File Icon in the The Open Wintrac File Menu
upper left corner of the Wintrac appears.
menu bar.
Page 4
P41SA50A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
Page 5
P41SA50A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure A50A
Page 6
P41SA50A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure D01A
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To confirm the proper operation of the unit temperature sensors
Materials Required
x Fluke Digital Multimeter.
Operation
Both graded and ungraded sensors are used on SR-2 applications. Graded sensors are used to sense return air
and discharge air temperature. Ungraded sensors are used to sense coil and ambient air temperature. Both
graded and ungraded sensors are checked in the same manner.
Page 1
P41SD01A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure D01A
A “Soft Failure” is defined by erratic operation or sensor drift that exceeds acceptable tolerances, (sensor is out
of calibration). If this occurs the alarm code for the suspect sensor or sensors will be set along with Alarm Code
13. This indicates a potential problem that may not be immediately apparent, and that a hard failure as defined
above did not occur. Checking a ServiceWatch data logger download at Technician Level may indicate when
the soft failure occurred.
Page 2
P41SD01A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure D01A
Diagnostic Procedure
Step Action Result Comments
Note: Polarity must be
considered when connecting
temperature sensors. If the
sensors are connected
backwards, the display will show
dashes (----). Consult the
schematic diagram or wiring
diagram for the correct
connections.
3 If the sensor is a hard failure, turn This step can be omitted if the
the unit on. failure is a soft failure.
4 Using a high quality meter check The voltage from the This step can be omitted if the
the voltage at the sensor harness microprocessor must be from failure is a soft failure.
wires. 4.90 to 5.10 volts DC with the
sensor disconnected.
Page 3
P41SD01A 05 February 2007
Section 6 – SR-2 SPECTRUM Service Procedure D01A
6 If the voltage measured in Step 4 Test and repair the harness as This step can be omitted if the
above is incorrect, unplug the required. See Service Procedure failure is a soft failure.
sensor connector at the H04A for additional information.
microprocessor and check the
harness for shorts and open
wires.
7 If the harness passes inspection, If the microprocessor fails the test This step can be omitted if the
check the microprocessor as it must be replaced. failure is a soft failure.
shown in Service Procedure
A01A.
Page 4
P41SD01A 05 February 2007
Section 6 – SR-2 Service Procedure D03A
Where Used
All SR-2 SPECTRUM Multi-Temp units
Purpose
To confirm the proper operation of the suction or discharge pressure transducers
Materials Required
x Fluke Digital Multi-meter.
Additional Information
The Discharge Pressure Transducer, Suction Pressure Transducer and Coolant Level switch each have a
separate 5 Vdc power supply. A short circuit condition in one transducer or switch circuit should not affect the
others.
The maximum discharge pressure that can be displayed is 500 psig. If the sensed pressure is greater than 500
psig, the HMI Control Panel will display [- - - - ]instead of the discharge pressure.
The maximum suction pressure that can be displayed is 200 psig. If the sensed pressure is greater than 200
psig, the HMI Control Panel will display [- - - - ]instea d of the suction pressure. When the unit is off and the
refrigerant pressures have equalized, the system pressure can exceed 200 psig when ambient temperatures are
above 90°F (35°C). If this occurs the HMI Control Pa nel will display [- - - - ]. This is normal operation and no
cause for concern.
If the suction pressure transducer opens the display will read -10 PSIG. An alarm may not be generated
immediately but the unit will be forced to low speed due to low suction pressure.
Page 1
P41SD03A 05 February 2007
Section 6 – SR-2 Service Procedure D03A
The Discharge Pressure Transducer will have a “50 0” on the body of the part. The Suction Pressure Transducer
will have a 2
“ 00”on the body of the par t. They are not interchangeable.
Diagnostic Procedure
Step Action Result Comments
1. Turn the unit on.
2. Access the Gauge submenu in The display should show the Confirm reading with refrigeration
the Main or Maintenance Menu pressure reading for the gauges as necessary.
and display the suction pressure transducer. If the transducer
or discharge pressure. reading is obviously incorrect or
the display shows
[- - - - ], proceed a s shown
below.
3. Turn the unit off and disconnect
the suction or discharge pressure
transducer at the transducer plug.
Page 2
P41SD03A 05 February 2007
Section 6 – SR-2 Service Procedure D03A
Page 3
P41SD03A 05 February 2007
Section 6 – SR-2 Service Procedure D03A
Page 4
P41SD03A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F01A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To test the oil level switch for proper operation
Table of Contents
Checking and Replacing the Oil Level Switch........................................................................................................... 1
Where Used ........................................................................................................................................................... 1
Purpose.................................................................................................................................................................. 1
Table of Contents................................................................................................................................................... 1
Materials Required ................................................................................................................................................. 1
Operation ............................................................................................................................................................... 1
Diagnostic Procedure............................................................................................................................................. 2
Replacing the Switch – Screw In Applications....................................................................................................... 2
Materials Required
x Fluke Digital Multimeter.
Operation
The switch is open with the float up (indicating full oil level). The switch is closed with the float down (indicating
low oil level).
Page 1
P41SF01A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F01A
Diagnostic Procedure
Step Action Result Comments
1. Turn the unit off.
3. Use an ohmmeter to check With the oil above the "add " This check can be performed
switch continuity. mark, the switch should be open. while changing oil.
If the engine is 6 or more quarts
low the switch should be closed.
2. Disconnect the Deutsch connector at the The oil level switch is located on the top of
switch. the oil pan.
Page 2
P41SF01A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F05A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To test the oil pressure switch for proper operation
Materials Required
x Fluke Digital Multi-meter.
Page 1
P41SF05A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F05A
Diagnostic Procedure
Step Action Result Comments
1. Connect a multi-meter set for DC
Volts between the 20B wire at the
oil pressure shutdown switch and
chassis ground.
2. Turn the unit on and observe the The voltage with the unit on and
meter reading. the engine not running should be
0. If there is voltage present the
switch is defective.
3. Start the engine and observe the Battery voltage should be present
meter reading. when the engine is running. If
the voltage is low or is 0, proceed
to Step 4.
4. With the unit running, disconnect If the battery voltage is present Check the 20B circuit as required
the 20B wire from the switch. on the wire, the switch is to determine the cause.
Measure the voltage from the defective and should be replaced.
20B wire to chassis ground.
If the voltage on the 20B wire is
low or 0, there is a problem in the
20B circuit.
Page 2
P41SF05A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F07B
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units with magnetic coolant level sensors
Purpose
To confirm proper operation of the magnetic coolant level sensor
Materials Required
x Fluke Digital Multimeter.
Operation
A magnetic reed switch is used to determine the coolant level. This two wire switch is supplied with 5
+ V DC from
the microprocessor on the CLP wire (J
7 Pin 15). The switch outputs +
5 V DC on the CLS wire (J7 Pin 16) when
coolant level is above the sensor and less than 0 VDC when the coolant level is below the sensor.
The switch is housed in an isolated chamber within the coolant tank. A magnetic float is located in the engine
coolant adjacent to the switch chamber. The switch will open or close as the magnetic float falls or rises with the
coolant level. The switch can be changed without removing coolant from the radiator. Exercise care when
removing and installing the reed switch as the switch is enclosed in a glass shell.
Page 1
P41SF07B 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F07B
Diagnostic Procedure
Step Action Result Comments
1 Disconnect the switch and check +5 VDC sho uld be present
the voltage between the CLP wire between the CLP wire and
at the sensor harness connector chassis ground. If not, check the
and chassis ground for +5 VDC. harness and connectors as
required to determine the cause.
Page 2
P41SF07B 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F08A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To test the coolant temperature sensor for proper operation
Materials Required
x Fluke Digital Multi-meter.
Page 1
P41SF08A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F08A
Diagnostic Procedure
Step Action Result Comments
1. Note: Polarity must be
considered when connecting
temperature sensors. If the
sensors are connected
backwards, the display will show
dashes [- - - - ]. Consult the
schematic diagram or wiring
diagram for the correct
connections.
5. Access the Gauge menu and The display for the Engine If all the temperature sensors
display Coolant Temperature. Coolant Temperature sensor show dashes [- - - - ]without
should show dashes [- - - - ]. being disconnected, the
microprocessor is defective.
6. Using a high quality meter check The voltage must be from 4.90 to
the voltage at the sensor plug on 5.10 volts DC.
the harness.
Page 2
P41SF08A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F08A
9. If the base controller passes the Test and repair the harness as
test, the problem is in the wiring required.
harness.
Page 3
P41SF08A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F08A
Page 4
P41SF08A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F09A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To test and adjust the RP M sensor
Materials Required
x Fluke Digital Multimeter.
Operation
The RPM sensor rarely fails but may require adjustment for proper operation.
Page 1
P41SF09A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F09A
Diagnostic Procedure
Step Action Result Comments
1. Turn the unit off.
7. Access the Gauge menu and The display should show the
display Engine RPM. engine RPM.
Page 2
P41SF09A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F09A
10. Check the voltage across the The voltage in high speed should Set the meter to read AC volts.
sensor terminals with the FS1 read from 1.0 to 5.0 volts ac.
and FS2 wires removed.
12. Reattach the FS1 and FS2 wires Polarity is not important.
to the sensor.
Page 3
P41SF09A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure F09A
Page 4
P41SF09A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure H04A
Where Used
All SR-2 and SR-2 Spectrum Multi-Temp units
Purpose
To illustrate the correct procedures for checking harness continuity on equipment utilizing solid state devices
Materials Required
x Fluke Digital Multimeter.
Important Notes
x Do not use battery and light test tools to check continuity.
x Do not check to see if a circuit is energized by tapping a circuit wire to ground and watching for a spark.
Page 1
P41SH04A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure H04A
Diagnostic Procedure
Step Action Result Comments
1. Do not use battery and light test Using such devices may present
tools to check continuity. excessive voltage or current to
solid state devices. In many
cases the device will be damaged
or destroyed.
2. Use a high quality digital multi- Older analog (needle type meter
meter or an analog meter with movement) meters and some
high input impedance. inexpensive "mech anic tool box"
meters present a large load to the
circuit being tested. This can
significantly alter the meter
reading, especially when
measuring small voltages or
currents.
3. e
Nver tes t a circuit to see if it is This will damage solid state
energized by tapping the circuit components or blow a fuse.
wire to ground and watching for a
spark.
Page 2
P41SH04A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure H04A
6. Using jump ers as required, The meter must show a very low Be certain the ohmmeter battery
connect each end of the circuit to resistance (less than 1.0 ohm), is good and the meter zeros with
a high quality multimeter. indicating circuit continuity. If not, the leads held together to prevent
the circuit is open or has misleading results.
excessive resistance.
Troubleshoot the circuit to
determine the cause using the
wiring diagrams.
Page 3
P41SH04A 05 February 2007
Section 6 – SR-2 and SR-2 M/T Service Procedure H04A
Page 4
P41SH04A 05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-1
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-2
05 February 2007
Section 7 – SR-2 Multi-Temp Information
CAUTION: The software on a replacement controller should always be checked to be certain it is current
software.
7-3
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-4
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-5
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-6
05 February 2007
Section 7 – SR-2 Multi-Temp Information
Where Used: All SR-2 SPECTRUM Control Hardware for Multi-Temp Applications
x Interface Board Label The Interface Board label is located on the back surface (solder side) of the
interface board below the current shunts. It is necessary to remove the interface board from the base
controller to read this label.
x Base Controller/Interface Board Assembly Label The label for a factory Base Controller/Interface
Board Assembly is located on the front surface of the base controller J3 Sensor connector. It is visible
without removing the interface board from the base controller.
x The component serial number is part of each label. All 3 labels will have matching serial numbers on
factory assemblies.
x White Labels The labels on factory base controller/interface board assemblies that have been factory
loaded with Bxxx Single-Temp base controller software will have white labels on the base controller,
interface board and assembly.
x Interface Boards Only SR-2/C Interface Boards identified as Service Part #45-2148 can be used for
Multi-Temp applications. The serial number will end in 0T3. They can be identified as shown on the next
page.
7-7
05 February 2007
Section 7 – SR-2 Multi-Temp Information
x “0T3” Serial Number The serial numbers of SR-2/C Base Controllers (45-2147) and SR-2 Interface
Board Part Number 45-2148 end in “0T3” as shown below.
"0T3" Designator
Component Designator
The component designator is the letter preceding the serial number as shown above. On factory
installed SR-2/C Multi-Temp units the serial number on all three labels will be the same except for the
component designator letter. The component designator letters are as follows:
C = Base Controller. This label is located on the front surface of the base controller between the J1
and J2 connectors. It is necessary to remove the interface board from the base controller to read this
label.
I = Interface Board. This label is located on the bottom of the interface board below the current
shunts. It is necessary to remove the interface board from the base controller to read this label.
A = Assembly consisting of Base Controller and Interface Board. This label is located on the
base controller J3 Sensor Connector.
7-8
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-9
05 February 2007
Section 7 – SR-2 Multi-Temp Information
x “0T2” Serial Number The serial numbers of HMI-2 Control Panels end in “0T2” as shown below.
"0T2" Designator
7-10
05 February 2007
Section 7 – SR-2 Multi-Temp Information
Upgrade kit to upgrade original All original SR-2 Trailer Upgrade to 204-1196 204-1197
Diagnostic Tool (Service Part # Single Temp Diagnostic (Upgrade Kit)
204-1102) to current standards. Tools (Service Part #
204-1102).
7-11
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-12
05 February 2007
Section 7 – SR-2 Multi-Temp Information
WINTRAC REQUIREMENTS
Wintrac 4.6 or later is required for use with SR-2 SPECTRUM Multi-Temp applications.
Features Where Used Interchange With Service Parts
Number
Wintrac 4.6 Full Version SR-2 M/T Applications 204-1849
Wintrac 4.6 Upgrade Version SR-2 M/T Applications 204-1850
7-13
05 February 2007
Section 7 – SR-2 Multi-Temp Information
7-14
05 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Refrigeration Diagrams
TCI 3 Zone with 2 Single TLE Evaporators
TCI 3 Zone with Parallel and Single TLE Evaporators
05 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Page 2
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
x All Spectrum systems are capable maintaining any temperature in any zone and can also heat or cool in any
zone at any time. These systems include conventional host units as well as dual evaporator (DE) systems.
IMPORTANT: When operating in reduced reverse cycle heat or defrost the Condenser Inlet Solenoid
is not energized.
Page 3
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Page 4
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
The remote evaporators also include 12VDC electrical fans with electronic speed control and drain hose
heaters.
With the exception of the Zone 1 Liquid Line Solenoids these components are controlled by Smart FET
outputs that are part of the Expansion Module.
Page 5
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
MULTI-TEMP OPERATION
Warm
All Zones Cooling
Cold Cold Cool
When all zones are cooling, the host
unit condenser is used to eliminate Ambient
COOL COOL
the heat from all zones. This is
Conventional Cooling operation. Cool
Page 6
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigera
Page 7
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigera
NOTES:
NOTE 1
Reduced Reverse Cycle Heat is used to prevent excessive heating and to allow both the remote evaporator of the zone in heat
utilized by zones that are cooling.
If the setpoint in the heating zone is equal to or more than 20°F below the ambient temperature then the following valves a
x Condenser Inlet Solenoid
x Purge Valve
x Receiver Tank Pressure Solenoid
The zone is in Reduced Reverse Cycle Heat.
If the setpoint in the heating zone becomes less than 15°F below the ambient temperature then the following valves are en
x Condenser Inlet Solenoid
x Purge Valve (dependent on discharge pressure)
x Receiver Tank Pressure Solenoid (dependent on discharge pressure)
The zone is in Normal Reverse Cycle Heat.
NOTE 2
The fans in zones with fresh range setpoints will run in full speed if there are no more than 3 fans in a zone. If there are 4 or more
is reduced for power management.
The fans in zones with frozen range setpoints will run at a lower speed than fans in fresh zones with 4 or more fans.
If the Run Fans in Null feature is enabled and the unit is running then when a zone is in running null the zone fans will run for 3 min
minutes and then restart for 3 minutes. This maintains airflow in the zone and is normally used with fresh loads.
Page 8
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Summary
x When a zone is cooling the Liquid Line Solenoid (LLS) is energized (open).
x When a zone is heating, defrosting or in minimal heat the Liquid Line Solenoid (LLS) is energized (open) and
the Hot Gas Solenoid (HGS) is energized (open).
x When a zone is in reverse cycle heat the Liquid Line Solenoid (LLS) is energized (open), the Hot Gas
Solenoid (HGS) is energized (open) and the Suction Line Solenoid (SLS) is energized (closed).
Page 9
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Page 10
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Purge Valve & Receiver Tank Pressure High Speed Solenoid (Any Zone Heating)
Solenoids When any zone is in heat mode the microprocessor
When any zone is in heat or defrost mode with the will enable the unit to run in high speed heat if
Condenser Inlet Solenoid energized then the required until the discharge pressure exceeds 410
microprocessor will energize the Purge Valve and PSIG. At that time the unit will be forced to low
Receiver Tank Solenoid until the discharge pressure speed heat to prevent a shut down on high
exceeds 300 psig. At that time the unit will de- discharge pressure. When the discharge pressure
energize the solenoids. This controls the amount of drops below 390 PSIG the controller will enable the
refrigerant available when the unit is heating or unit to go back to high speed heat if required.
defrosting. When the discharge pressure drops
below 225 psig the microprocessor will again
energize the Purge Valve & Receiver Tank Pressure High Speed Solenoid (Any Zone Heating)
390 PSIG
de-energized for 55 seconds if the discharge
pressure is between 225 and 300 psig. Note that
this only applies to heat or reverse cycle heat, not to High Speed Solenoid - Any Zone Heating
300 PSIG
De-Energized
Energized
Page 11
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Increasing
Setpoint + Ambient
15°F Setpoint Temperature
Temperature
Page 12
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
R04A Liquid Line Solenoid and Liquid Return Check Valve Test
R06A Suction Line Check Valves and Condenser Inlet Check Valve Tests
R08A Condenser Inlet Solenoid, Receiver Tank Pressure Solenoid and Purge Check
Valve Test
Page 13
06 February 2007
Section 8 – SR-2 SPECTRUM Refrigeration Operation
Page 14
06 February 2007
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 2
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 3
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 4
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 5
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 6
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
Page 7
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R01A
NOTE: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 8
SR-2 SPECTRUM R01A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R02A
Purpose: To perform a low side pumpdown on an SR-2 SPECTRUM Multi-Temp refrigeration system to test
internal seals.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R02A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R02A
Page 2
SR-2 SPECTRUM R02A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R03
A
Title: O
HT G
AS SOLENOID TEST
Purpose: To test the Hot Gas Solenoid on an SR-2 SPECTRUM Multi-Temp refrigeration system.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R03A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R03
A
Page 2
SR-2 SPECTRUM R03A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R03
A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 3
SR-2 SPECTRUM R03A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R03
A
Page 4
SR-2 SPECTRUM R03A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R04A
Title: LIQUID LINE SOLENOID and LIQUID RETURN CHECK VALVE TEST
Purpose: To test the Liquid Line Solenoid on an SR-2 SPECTRUM Multi-Temp refrigeration system.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R04A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R04A
Page 2
SR-2 SPECTRUM R04A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R04A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 3
SR-2 SPECTRUM R04A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R04A
Page 4
SR-2 SPECTRUM R04A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R06A
Title: SUCTION LINE CHECK VALVES & CONDENSER INLET CHECK VALVES TESTS
Purpose: To test the Suction Line Check Valves and Condenser Inlet Check Valves on an SR-2 SPECTRUM
Multi-Temp refrigeration system.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R06A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R06A
Page 2
SR-2 SPECTRUM R06A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R06A
Page 3
SR-2 SPECTRUM R06A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R06A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 4
SR-2 SPECTRUM R06A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R07A
Purpose: To test the Purge Valve on an SR-2 SPECTRUM Multi-Temp refrigeration system.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R07A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R07A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 2
SR-2 SPECTRUM R07A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Purpose: To test the Condenser Inlet Solenoid, Receiver Pressure Tank Solenoid and Purge Check Valve on an
SR-2 SPECTRUM Multi-Temp refrigeration system.
Important: This test will require the removal of some refrigerant using a recovery machine
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Page 2
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Page 3
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Page 4
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 5
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R08A
Page 6
SR-2 SPECTRUM R08A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R09A
Purpose: To perform a service pumpdown on an SR-2 SPECTRUM Multi-Temp refrigeration system to allow
service of all low side components, compressor, discharge manifold, discharge vibrasorber, receiver tank
pressure solenoid, condenser inlet solenoid and purge check valve.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R09A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R09A
Page 2
SR-2 SPECTRUM R09A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R09A
Page 3
SR-2 SPECTRUM R09A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R09A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before releasing the unit for service or performing another Refrigeration Service Procedure.
Page 4
SR-2 SPECTRUM R09A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R10A
Purpose: To recover the refrigerant charge from an SR-2 SPECTRUM Multi-Temp refrigeration system.
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before performing another Refrigeration Service Procedure.
Page 1
SR-2 SPECTRUM R10A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R10A
Page 2
SR-2 SPECTRUM R10A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R10A
Page 3
SR-2 SPECTRUM R10A 02/05/07
SR-2 SPECTRUM Refrigeration Service Procedure R10A
Note: When finished with this Refrigeration Service Procedure return all service valves to the normal operating
positions before performing another Refrigeration Service Procedure.
Page 4
SR-2 SPECTRUM R10A 02/05/07
Section 9 – SR-2 SPECTRUM Drawings
01 February 2007
Section 9 – SR-2 SPECTRUM Drawings
01 February 2007
Section 9 – SR-2 SPECTRUM Drawings
You are invited to comment on this manual so it can be updated and improved to better meet
your needs. Any corrections or comments are welcome. Please complete the following
information:
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
__________________________________________________________________________
01 February 2007
Section 9 – SR-2 SPECTRUM Drawings
01 February 2007