Duct Smoke

Detector Accessories
Expand the versatility of the InnovairFlex™ line of duct
smoke detectors with System Sensor notification and test
accessories.

Available Accessories Duct smoke detector accessories add functionality to the duct
smoke detection system by allowing quick, convenient inspections
APA151 Piezo Annunciator
at eye level and effective audible and visible notification options. All
MHR Mini-Horn, Red System Sensor duct smoke detectors and accessories are UL listed.
MHW Mini-Horn, White
The APA151 piezo annunciator, which replaces the APA451 with a
RA100Z/RA100ZA Remote Annunciator new, improved look, provides an audible alarm signal, a red LED to
RTS151 Remote Test Station indicate alarm status, and a green LED to indicate power status. It is
intended for use with System Sensor 4-wire conventional duct smoke
RTS151KEY Remote Test Station with Key
detector applications without a system control panel, to comply with
RTS2 Multi-Signaling Accessory NFPA 90A.
AOS Add-On Strobe
The MHR and MHW SpectrAlert® Advance mini-horns feature
RTS2-AOS Multi-Signaling Accessory temporal or continuous tones at high and low volume settings.
Their small footprint allows mounting to single-gang back boxes for
applications where a small device is desired.

The RA100Z and RA100ZA remote annunciators are designed


for both conventional and intelligent applications. Their red LED
provides visual indication of an alarm condition.

The RTS151 and RTS151KEY remote test stations are automatic


fire detector accessories designed to test duct smoke detectors
from a convenient location. For 4-wire detectors, the RTS151KEY test
station features a multi-colored LED that alternates between steady
green and red. For 2-wire detectors, the LED illuminates red for
alarm.

The RTS2 and RTS2-AOS multi-signaling accessories are


designed to work with InnovairFlex 4-wire conventional duct smoke
detectors. These accessories include a key switch that can be used
to select one of two connected sensors to be tested, reset, or both
Agency Listings by a push button switch. They also enable sensitivity measurements
using the SENS-RDR sensitivity reader (sold separately). The AOS
(Add-On Strobe) is an optional accessory included with the RTS2-
AOS model.
7300-1653:0212
7300-1653:0211
S2522 3034401 7135-1653:0196 9080301
Specifications, Duct Smoke Detector Accessories
APA151 Piezo Annunciator RTS151 Remote Test Station
Voltage Regulated 24 VDC Power Requirements Alarm LED: 2.8 to 32 VDC, 12 mA max.
Operating Voltage 16 to 33 VDC Total Current: 105 mA max.
Maximum Alarm Current 30 mA Test Switch 10 VA @ 32 VDC
Temperature Range 0°C to 49°C (32°F to 120°F) Reset Switch 10 VA @ 32 VDC
Relative Humidity 10 to 93% non-condensing Alarm Response Time 40 seconds max.
Wire Gauge 12 to 18 AWG Temperature Range –10°C to 60°C (14°F to 140°F)
Dimensions 4.6˝ H × 2.9˝ W × .45˝ D Relative Humidity 95% non-condensing
MHR/MHW SpectrAlert® Advance Mini-Horns Wire Gauge 14 to 18 AWG
Voltage Regulated 12 DC or FWR (Full Wave Dimensions 4.8˝ H x 2.90˝ W x 1.4˝ D
Rectified) or Regulated 24 VDC or FWR RTS151KEY Remote Test Station with Key
Sounder Current Draw 22 mA RMS max. at 8 to 17.5 Volts DC Power Requirements Power LED (Green): 14 to 35 VDC,
29 mA RMS max. at 16 to 33 Volts DC 12 mA max.
Temperature Range 0°C to 49°C (32°F to 120°F) Alarm LED (Red): 2.8 to 32 VDC,
12 mA max.
Humidity Range 10 to 93% non-condensing
Total Current: 105 mA max.
Nominal Sounder 3 kHz
Alarm Response Time 40 seconds max.
Frequency
Temperature Range –10°C to 60°C (14°F to 140°F)
Wire Gauge 12 to 18 AWG
Relative Humidity 95% non-condensing
Dimensions 4.6˝ H × 2.9˝ W × 0.45˝ D
Wire Gauge 14 to 18 AWG
RA100Z/RA100ZA Remote Annunciator
Dimensions 4.6˝ H × 2.75˝ W × 1.8˝ D
Voltage Range Conventional System: 3.1 to 32 VDC
Intelligent System: 18 to 32 VDC RTS2 and RTS2-AOS Multi-signaling Accessory
Maximum Alarm Current 10 mA Voltage 20 to 29 VDC
Dimensions 4.6 ˝ H × 2.8˝ W × 1.3˝ D Power Requirements Standby: 3.0 mA max.
Trouble: 16.0 mA max.
Alarm without strobe: 30 mA max.
Alarm with strobe: 55 mA max.
Sounder 85 dBA at ten feet
Temperature Range –10°C to 60°C (14°F to 140°F)
Relative Humidity 95% non-condensing
Wire Gauge 14 to 22 AWG
Dimensions 4.8˝ W x 5.3˝ H x 1.6˝ D
For the very latest product specifications and listing information,
please visit the System Sensor Web site at www.systemsensor.com.

RTS151 UL S4011 RTS151KEY UL S2522 APA151 UL S4011 RTS2-AOS UL S2522

RA100Z UL S2522 MHW UL S4011 MHR UL S4011 AOS

3825 Ohio Avenue • St. Charles, IL 60174 ©2013 System Sensor.


Phone: 800-SENSOR2 • Fax: 630-377-6495 Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
www.systemsensor.com HVDS20202 • 8/13