This document summarizes test results for pre-insulated aluminium duct board. It lists 14 different tests measuring properties like thermal conductivity, reaction to fire, smoke opacity, smoke toxicity, fire propagation, surface flame spread, and board stiffness. The duct board passed all tests, meeting various European, UK, and international standards for fire safety, smoke emissions, and structural integrity for applications in buildings and railways.
This document summarizes test results for pre-insulated aluminium duct board. It lists 14 different tests measuring properties like thermal conductivity, reaction to fire, smoke opacity, smoke toxicity, fire propagation, surface flame spread, and board stiffness. The duct board passed all tests, meeting various European, UK, and international standards for fire safety, smoke emissions, and structural integrity for applications in buildings and railways.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1
Pre-Insulated Aluminium Duct Board
Type of test Standard Description Result Acceptance Language
Thermal EN 12667 Thermal performance of building l=0,024 Europe Conductivity: materials and products. W/m·K Determination of thermal resistance by means of guarded hot plate and heat flow meter methods. Products of high and medium thermal resistance. Spanish Reaction to EN 13501-1 Fire classification of construction B-s2,d0 Europe Fire: products and building elements. Classification using test data from reaction to fire test
Reaction to fire of the product English
EN 13501-1 Fire classification of construction B-s1,d0 Europe products and building elements. Classification using test data from reaction to fire test Reaction to fire of the product in end- use conditions with flanges English BS 476 Opinion of compliance with the Class 0 United CLASS 0 requirements for Class 0 according Kingdom & to BS 476 Part 6 & Part 7 Worldwide English BS 476, part Fire tests on building materials and I=6,3 United 6 structures. Method of test for fire Kingdom & propagation for products Worldwide English BS 476, part Fire tests on building materials and Class 1 United 7 structures. Method of test to Kingdom & determine the classification of the Worldwide surface spread of flame of products English ASTM E-84 Standard test method for surface Class A United burning characteristics of building Kingdom & materials Worldwide English Smoke ISO 5659-2 Plastics – Smoke generation. Part 2 VOF4=23 Worldwide opacity: Determination of optical density by a Ds(4)=19 single chamber method English Smoke ISO 5659-2 Plastics – Gas Analysis in the smoke CIT=0.0 Worldwide toxicity: box, using FTIR technicque. Determination of CIT, Convetional Index of Toxicity English Railway EN 45545-2 Railway applications - Fire protection R1 HL3 Europe applications on railway vehicles - Part 2: Requirements for fire behavior of materials and components English Board EN 13403 Ventilation for buildings. Non metallic Europe Stiffness ducts. Ductwork made from insulation ductboards. Determination of board stiffness in R3 Panel PIR-ALU 35 20mm airflow ducts Determination of board stiffness in R5 Panel PIR-ALU 45 20mm airflow ducts Determination of board stiffness in R3 Panel PIR-ALU 35 30mm airflow ducts